Effect of Height Difference on The Performance of Two-phase Thermosyphon Loop Used in Airconditioning

Similar documents
Performance Investigation of Refrigerant Vapor- Injection Technique for Residential Heat Pump Systems

Experimental Study on Match for Indoor and Outdoor Heat Exchanger of Residential Airconditioner

An Experimental Investigation Of Oil Retention Characteristics In CO2 Air-Conditioning Systems

Experimental Research On Gas Injection High Temperature Heat Pump With An Economizer

Control Method Of Circulating Refrigerant Amount For Heat Pump System

Thermal Performance of a Loop Thermosyphon

Purdue e-pubs. Purdue University

Mini Vapour Cycle System For High Density Electronic Cooling Applications

Effects of Flash and Vapor Injection on the Air-to- Air Heat Pump System

Performance of R-22, R-407C and R-410A at Constant Cooling Capacity in a 10

Study of R161 Refrigerant for Residential Airconditioning

Feasibility of Controlling Heat and Enthalpy Wheel Effectiveness to Achieve Optimal Closed DOAS Operation

Experimental Investigation of Closed Loop Oscillating Heat Pipe as the Condenser for Vapor Compression Refrigeration

Performance of CO2 Cycles with a Two-Stage Compressor

Effect of the Use Pattern on Performance of Heat Pump Water Heater

SIMULATION ANALYSIS ON THE FRESH AIR HANDLING UNIT WITH LIQUID DESICCANT TOTAL HEAT RECOVERY

R32 Compressor for Air conditioning and Refrigeration applications in China

Hunting Phenomena Of Automotive Air Conditioning Systems With Variable Displacement Compressor

Performance Characteristics of Air-Conditioner Under Tropical Ambient Condition

Experimental Study of Fouling Performance of Air Conditioning System with Microchannel Heat Exchanger

Experimental Investigation on Condensation Performance of Fin-and-Flat-Tube Heat Exchanger

Enhancement of Round Tube and Flat Tube- Louver Fin Heat Exchanger Performance Using Deluge Water Cooling

Design of Divided Condensers for Desiccant Wheel-Assisted Separate Sensible and Latent Cooling AC Systems

Development of a Novel Structure Rotary Compressor for Separate Sensible and Latent Cooling Air-Conditioning System

Numerical Study on the Design of Microchannel Evaporators for Ejector Refrigeration Cycles

Visualization of Evaporatively Cooled Heat Exchanger Wetted Fin Area

Comparison of Performance of a Residential Air- Conditioning System Using Microchannel and Finand-Tube

Performance Characteristics and Optimization of a Dual-Loop Cycle for a Domestic Refrigerator- Freezer

Experimental Research and CFD Simulation on Microchannel Evaporator Header to Improve Heat Exchanger Efficiency

Drop-in Testing of Next-Generation R134a Alternates in a Commercial Bottle Cooler/Freezer

Two-Phase Evaporation Pressure Drop Experimental Results for Low Refrigerant Mass Flux

Experimental Study About An Amount Of Oil Charge On Electric Driven Scroll Compressor For Electric Vehicle

EFFECT OF PAG OIL CIRCULATION RATE ON THE HEAT TRANSFER PERFORMANCE OF AIR-COOLED HEAT EXCHANGER IN CARBON DIOXIDE HEAT PUMP SYSTEM

Heat Transfer Analysis of Vapor Compression System Using Nano Cuo-R134a

Air-Cooled Thermosyphon for Press-Pack Stack of Semiconductors

Design and Research of the Digital VRV Multi- Connected Units With Three Pipes Type Heat Recovery System

Experimental Study on the Performance of Twisted Capillary Tube

Development of Performance Test Facility of Positive Displacement CO2 Refrigerant Compressor

Experimental Investigation on the Performance of Ground-source Heat Pump with the Refrigerant R410A

Performance Characteristics of a Refrigerator- Freezer with Parallel Evaporators using a Linear Compressor

Enhancement of the Separate Sensible and Latent Cooling Air-Conditioning Systems

Design and Research of the Commercial Digital VRV Multi-Connected Units With Sub-Cooled Ice Storage System

Air-Cooled Heat Exchanger Performance for R410A

Experimental Study on the Performance and Oil Return Characteristics of Multi-Split Air- Conditioning System for Medium Size Building

Experimental Investigation Of A New Low- Approach Evaporator With Reduced Refrigerant Charge

Performance Comparisons Of A Unitary Split System Using Microchannel and Fin-Tube Outdoor Coils, Part I: Cooling Tests

CHAPTER 2 EXPERIMENTAL APPARATUS AND PROCEDURES

Experimental Investigate on the Performance of High Temperature Heat Pump Using Scroll Compressor

A study of Transient Performance of A Cascade Heat Pump System

The Innovative Green Technology for Refrigerators Development of Innovative Linear Compressor

Performance Analysis of a Miniature-Scale Vapor Compression System for Electronics Cooling: Bread Board Setup

The Effect of the Ventilation and the Control Mode on the Performance of a VRV System in Cooling and Heating Modes

Investigation of Evaporator Performance with and without Liquid Overfeeding

Experimental Investigation of a New High Temperature Heat Pump Using Water as Refrigerant for Industrial Heat Recovery

STUDY ON THE CONTROL ALGORITHM OF THE HEAT PUMP SYSTEM FOR LOAD CHANGE

Oil Return Measurements In A Unitary Split System Air Conditioner Using Different Refrigerant Mixtures

Experimental and Numerical Study on the Performance of R410A Liquid Recirculation Cycles with and without Ejectors

Experimental Analysis of a Stirling Refrigerator Employing Jet-Impingement Heat Exchanger and Nanofluids

Experimental Study on the Thermal Behavior of a Domestic Refrigeration Compressor during Transient Operation in a Small Capacity Cooling System

Research Article / Araştırma Makalesi EXPERIMENTAL INVESTIGATION OF R600A REFRIGERANT FLOW INSIDE ADIABATIC CAPILLARY TUBE

Noise Reduction Technology With Porous Metal for Refrigerant Two-Phase Flow Through the Expansion Valve

Efficiency of Non-Azeotropic Refrigerant Cycle

Performance Evaluation of a Plug-In Refrigeration System Running Under the Simultaneous Control of Compressor Speed and Expansion Valve Opening

Low Global Warming Refrigerants For Commercial Refrigeration Systems

Performance Measurement of R32 Vapor Injection Heat Pump System

Low GWP Refrigerants for Air Conditioning Applications

Effects of Oil on atranscritical Carbon Dioxide Air Conditioning Systems some experiences -

Improving Heating Performance of a MPS Heat Pump System With Consideration of Compressor Heating Effects in Heat Exchanger Design

Heat Transfer Characteristics and Heat Exchanger Performances for R407C Using Herringbone Heat Transfer Tube

Development and Performance Measurements of a Small Compressor for Transcritical CO2 Applications

Refrigerant Mass and Oil Migration During Start-up Transient

Effects of Frost Formation on the External Heat Transfer Coefficient of a Counter-Crossflow Display Case Air Coil

Performance of the Variable Refrigerant Volume Air-Conditioning System. with Heat Recovery

Performance Evaluation of Heat pump System using R32 and HFO-mixed Refrigerant in High Ambient Temperature.

Operation of a Two-Phase Reverse Loop Thermosyphon

Analysis of Oil Pumping in the Hermetic Reciprocating Compressor for Household Refrigerators

Full and Partial Load Performances of RAC and CAC Heat Pump using R-32

A study of high efficiency CO2 refrigerant VRF air conditioning system adopting multi-stage compression cycle

Performance Study of a Water-to-Water Heat Pump Using Non-azeotropic Refrigerant Mixtures R407C

The Development Of High Efficiency Air Conditioner With Two Compressors Of Different Capacities

Reduction Of Energy Consumption in Airconditioning Systems employing direct evaporative pre-cooling of Condenser air

Numerical Simulation of a New Cooling System for Commercial Aircrafts

Developing Two-Phase Flow Distribution in Horizontal Headers With Downward Minichannel-Branches

Experimental investigation of Hybrid Nanofluid on wickless heat pipe heat exchanger thermal performance

Evaluation and Optimization of System Performance using HFO-mix Refrigerants for VRF and Mini-split Air-Conditioner

Exploring the Performance Characteristics of CO2 Cycles in a Breadboard-Type Test Facility

Performance Evaluation and Design Optimization of Refrigerated Display Cabinets Through Fluid Dynamic Analysis

Experimental and Numerical Study on a Dryexpansion Shell-and-Tube Evaporator Used in Wastewater Source Heat Pump (WWSHP)

Performance Evaluation of the Energy Efficiency of Crank-Driven Compressor and Linear Compressor for a Household Refrigerator

FROSTING BEHAVIOR OF FIN-TUBE HEAT EXCHANGER ACCORDING TO REFRIGERANT FLOW TYPE

PERFORMANCE OF DEEP FREEZER BY USING HYDROCARBON BLENDS AS REFRIGERANTS

Sub-Critical Operation of the CO2 Expander/ Compressor

Experimental Performance of Solar Collector cum Regenerator for Coupling with a Liquid Desiccant Cooling System

Application of two hybrid control methods of expansion valves and vapor injected compression to heat pumps

4th International Conference on Sensors, Measurement and Intelligent Materials (ICSMIM 2015)

Evaluation The Effect Of Washing On The Heat Transfer Capacity And Air-Side Flow Resistance Of Air Cooled Condensers

Compressor Capacity Control

Passive cooling of telecommunication outdoor cabinets for mobile base station

The Design Of A New Generation Of Twin Screw Refrigeration Compressors

Energy Transfer Based Test Method Development and Evaluation of Horizontal Air Flow Re- Circulatory Air Curtain Efficiencies

Transcription:

Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2014 Effect of Height Difference on The Performance of Two-phase Thermosyphon Loop Used in Airconditioning System Penglei Zhang Tsinghua University, China, People's Republic of, zpl11@mails.tsinghua.edu.cn Xianting Li Tsinghua University, China, People's Republic of Sheng Shang Tsinghua University, China, People's Republic of Wenxing Shi Tsinghua University, China, People's Republic of Baolong Wang Tsinghua University, China, People's Republic of ollow this and additional works at: http://docs.lib.purdue.edu/iracc Zhang, Penglei; Li, Xianting; Shang, Sheng; Shi, Wenxing; and Wang, Baolong, "Effect of Height Difference on The Performance of Two-phase Thermosyphon Loop Used in Air-conditioning System" (2014). International Refrigeration and Air Conditioning Conference. Paper 1517. http://docs.lib.purdue.edu/iracc/1517 This document has been made available through Purdue e-pubs, a service of the Purdue University Libraries. Please contact epubs@purdue.edu for additional information. Complete proceedings may be acquired in print and on CD-ROM directly from the Ray W. Herrick Laboratories at https://engineering.purdue.edu/ Herrick/Events/orderlit.html

2519, Page 1 Effect of Height Difference on the Performance of Two-phase Thermosyphon Loop Used in Air-conditioning System Penglei ZHANG, Xianting LI, Sheng SHANG, Wenxing SHI, Baolong WANG* Department of Building Science, Tsinghua University, Beijing, 100084, P.R. China Telephone: +86-10-62786571 ax: +86-10-62773461, E-mail: wangbl@tsinghua.edu.cn * Corresponding author: Baolong WANG ABSTRACT: Two-phase thermosyphon loops (TPTLs) are widely used in air-conditioning field for heat recovery and free cooling utilization in recent years. The height difference between the condenser and the evaporator is always considered as the driven force of thermosyphon. However, experiments show the cooling capacity of the TPTLs is not linearly improved with the increase of the height difference. So, the influence mechanism of height difference on the performance of TPTLs is not clear and needs more deep investigation. In this study, a visual experimental setup is established, and the effect of height difference and circulation resistance on the performance of TPTL is investigated. The results shows that with the increase of the height difference, the liquid head rises continuously until remain stable approximately. Therefore, the liquid head is less than the height difference in some cases, which means that the downcomer is partially liquid filled. Consequently, with the increase of height difference, the circulation flow rate and thermal performance firstly increases then remains constant, rather than continuous increase in the traditional understandings. 1. INTRODUCTION Two-phase thermosyphon loops (TPTLs) are highly effective devices for spontaneously transferring heat through a relatively long distance. Therefore, TPTLs are extensively used in various fields, such as cooling of electronic components(garrity et al., 2007; Khodabandeh, 2005), light water reactors(nayak et al., 2006; Rao et al., 2006), etc., owing to their simplicity, flexibility, high heat transfer efficiency, and passive nature. Recently, the TPTL has also been found to be an effective way to recover heat or utilizing free energy in air-conditioning systems for energy saving. or example, Liu (Liu et al., 2006) used TPTL heat exchanger to recover heat from exhaust air or waste water for free; Tu (Tu et al., 2011) developed a TPTL heat exchanger for telecommunication base stations to eliminate the heat rejection spontaneously in cold seasons; Han (Han et al., 2012) integrated the TPTL with vapor compression into one device. The integrated air-conditioner was used in the spaces with large heat rejection, and showed significant energy-saving effect. As a whole, TPTL shows bright prospects in the field of air-conditioning.

2519, Page 2 A typical TPTL consists of an evaporator, a riser (gas tube), a condenser, and a downcomer (liquid tube). The condenser is higher than the evaporator by a certain height difference. The TPTL is powered by the gravity, which means the liquid head, caused by the height difference and density difference of the liquid in the downcomer and the vapor or vapor/liquid mixture in the riser, is the key factor affecting the circulation flow rate and energy performance of TPTLs. In the traditional ideas, the liquid head is considered to be equal to the height difference between the condenser and the evaporator based on the underlying assumption: the downcomer is fully liquid filled (Garrity et al., 2007; Haider et al., 2002; Imura et al., 1989; Khodabandeh, 2005). According to that, the TPTL will perform better with a larger height difference, since driving force becomes larger. The conclusion is correct in the cases with large temperature difference and heat flux, such as in the field of cooling of electronic and light water reactors. However, when the TPTL is used in air-conditioning system, which has quite small temperature difference and small heat flux, the behavior of TPTL is different. The preliminary research indicated the heat transfer rate does not always increase with the increase of the height (Lee et al., 2009). What happened to the TPTL in air conditioning application? Is the common sense of the downcomer fully filled correct? Does the liquid head always keep consistent with the height difference? These are the fundamental questions that required answers before using TPTLs in air conditioner field. In this study, a visual experimental plant is established, the behavior of the liquid head in the downcomer is observed and the effect of height difference and circulation resistance on the performance of TPTL is investigated experimentally. 2. EXPERIMENTAL SETUPS igure 1 shows the visual experimental plant of TPTL heat exchanger. The TPTL is a water-to-water type heat exchanger, and consists of an evaporator, a condenser, a riser, and a downcomer. A high-temperature water tank and a low-temperature water tank are set to create required temperature conditions. The evaporator is a double-pipe heat exchanger with three parallel pipes, and made of copper. The refrigerant flows in the inner pipe with a diameter of 12 mm, and the water flows in the outer pipe with a diameter of 16 mm. A transparent pipe is set in parallel with the evaporator to observe the liquid level before experiments. A ball valve is set at the outlet of the evaporator to change the circulation resistance in the experiment. The condenser uses the similar structure as the evaporator. The condenser is fixed on a lifter, which falls or rises to change the height difference between condenser and evaporator from 0 m to 1.5 m. The outer surfaces of the evaporator and the condenser are in good thermal insulation, and the heat loss can be neglected. In order to observe the flow pattern and liquid level in the riser and downcomer, a transparent pipe, made of PU, is selected to act as the riser and downcomer. The detailed specifications of the TPTL are presented in the Table 1.

2519, Page 3 T Condenser ΔP Differential pressure gauge Water flowmeter Pump Low temperature water tank T T P P Pressure Transducer Downcomer Riser Ball valve T T Evaporator Water flowmeter Pump Coriolis Mass lowmeter High temperature water tank igure 1: Schematic diagram of the experimental setup Items Evaporator Condenser Riser Downcomer Height difference Refrigerant Table 1: Specifications of the TPTL heat exchanger Specifications 3 parallel double pipes; Pipe length: 0.45 m Diameter of inner pipe: 12 mm; Diameter of outer pipe: 16 mm; 3 parallel double pipes; Pipe length: 0.45 m Diameter of inner pipe: 12 mm; Diameter of outer pipe: 16 mm; Length: 2.0 m; Inner diameter: 12 mm Length: 2.0 m; Inner diameter: 12 mm 0-1.5 m R134a To monitor heat transfer performance of the TPTL, a couple of thermocouples and a water flowmeter are set to measure the inlet/outlet water temperature and flow rate of water. A Coriolis mass flowmeter with relatively small circulation resistance is selected to measure the flow rate of refrigerant. A differential pressure transducer is used to measure the pressure difference along the riser. In order to monitor the thermodynamic state in the downcomer, a thermocouple and a pressure transducer are used to measure the temperature and pressure of the refrigerant at the outlet of condenser. The detailed information of the transducers are presented in Table 2.

2519, Page 4 Table 2: Specifications of transducers Items Range Uncertainty Type Thermocouple -10-50 o C <0.1 o C T type Pressure transducer 0-2.5 MPa <0.2% UNIK 5000 Differential pressure transducer 0-50 kpa <0.2% UNIK 5000 Coriolis mass flowmeter (for refrigerant) 0-1000 kg/h <0.05% MASS 6000 lowmeter (for water) 0-10 m 3 /h <0.1 m 3 /h LXSR-E During the test, each measuring point lasts 20 minutes after the operation condition keep steady. All the signals from the transducers (thermocouples, pressure transducer, flow meters) are transferred to a data acquisition unit, then analyzed in a computer. The uncertainties of the measurement instruments are presented in Table 2. The method to calculate the heat transfer rate Q e in the evaporator and its uncertainty are given in Eq. (1) and Eq. (2). Q c V ( t t ) (1) e P in out 2 2 2 e V in out 2 e ( in out ) Q t t Q V t t 3. RESULTS AND DISCUSSION (2) 3.1 Partially Liquid-illed Phenomenon in the Downcomer As mentioned before, most of the researchers believe that the downcomer is full of liquid. rom our experiments, it is found that in some cases, the downcomer does be fully liquid filled; but in some cases, the downcomer is partially liquid filled rather than fully liquid filled. At that time, the lower part of the downcomer is full of liquid while the upper part is only surrounded by a hollow liquid film, shown in igure 2. In that case, the temperature and pressure of the refrigerant are measured, and the measured temperature keeps consistent with the saturation temperature corresponding to the measured pressure, shown in igure 3, which means that it is just the saturation state. Liquid film Liquid column igure 2: Partially liquid-filled phenomenon observed in experiments

Saturation temperature ( o C) 2519, Page 5 30 25 20 15 10 5 0 0 5 10 15 20 25 30 Measured temperature ( o C) igure 3: The measured temperature and the saturation temperature corresponding to the measured pressure at the outlet of condenser when the downcomer is partially liquid filled rom the measurement, it can be concluded that there are two possible scenarios for downcomer: fully liquid filled (igure 4(b)) and partially liquid filled (igure 4(a)). In the fully liquid-filled case, the liquid head is equal to the height difference. When the downcomer is partially liquid filled, there is a static saturation gas column, surrounded by a layer of liquid film in the upper part of the downcomer. In the static gas column, the pressure remains constant, corresponding to the saturation temperature. The liquid film flows down along the inner wall, and it does not provide the driving force. In the lower part of the downcomer, there is a liquid column full of liquid, which provides the driving force for circulation. And previous experiments also show that the downcomer is more likely to be partially liquid filled, when the refrigerant charge and temperature difference (or heat flux) is relatively small, which may be the reason why the phenomenon are not found in the field of cooling of electronic and light water reactors, where large refrigerant charge is need to avoid dryout in the evaporator.

2519, Page 6 Condenser Condenser Riser Evaporator Static saturation gas column Downcomer Liquid film Liquid column Riser Evaporator Downcomer Liquid column (a) Partially liquid-filled case igure 4: Two possible cases for the downcomer (b)ully liquid-filled case 3.2 Effect of Height Difference and Circulation Resistance on the flow and heat transfer performance of TPTL In this study, effect of height difference and circulation resistance on the performance of TPTL have been studied experimentally. The height difference between the condenser and the evaporator ranges from 0 m to 1.5 m. There are three different openings of the ball valve at the outlet of the evaporator, 25%, 50%, 100%, on behalf of different circulation resistance. The inlet water temperature of the evaporator keeps 35 o C, and the inlet water temperature of condenser keeps 5 o C. There are 0.48 kg refrigerant in the system, and the static liquid level is 0.9 m before experiment, the refrigerant charge is selected by the optimization of refrigerant charge based on heat transfer performance. 900 800 700 Heat transfer rate (W) 600 500 400 300 200 100 0 0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 Height difference (m) Exp: Valve opening 100% Exp: Valve opening 50% Exp: Valve opening 25% igure 5: Heat transfer rate as a function of height difference between the condenser and evaporator

2519, Page 7 igure 5 presents the heat transfer rate as a function of height difference between the condenser and the evaporator. As shown in igure 5, on the whole, the heat transfer rate rises with the increase of height difference. But for the loop with lower circulation resistance (Valve opening 100% and 75%), with the increase of height difference, the heat transfer rate first increases sharply, then increases slowly, finally remains constant. While for the loop with higher circulation resistance (Valve opening 25%), with the increase of height difference the heat transfer rate increases continuously. Moreover, the TPTL performs worse with larger circulation resistance. The reasons for these behaviors can be found in igure 6 and igure 7. 1.6 Liquid column height in the downcomer(m) 1.4 1.2 1.0 0.8 0.6 0.4 0.2 Exp: Valve opening 100% Exp: Valve opening 50% Exp: Valve opening 25% Liquid column height 0.0 0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 Height difference (m) igure 6: Liquid column height in the downcomer as a function of height difference between the condenser and evaporator igure 6 shows the liquid column height in the downcomer as a function of height difference and circulation resistance. As shown in igure 6, when the height difference is relatively small, the liquid column height keeps consistent with the height difference between the condenser and evaporator, which means the downcomer is fully liquid filled, and the condenser outlet is subcooled; but when the height difference continues to increases, the liquid column height cannot keep up with the increase of height difference, which means the downcomer turns to be partially liquid filled at that time. Additionally, the loop with lower circulation resistance (larger opening of the valve) has lower liquid column in the downcomer, and the downcomer turns to be partially liquid filled at smaller height difference, which means the loop with lower circulation resistance are more likely to be partially liquid filled than that with larger circulation resistance. It can be explained like that, TPTL is a natural circulation driven by the liquid head, and the pressure drop in the cycle always equals to the liquid head caused by the density difference of the liquid in the downcomer and the vapor or vapor/liquid mixture in the riser, therefore the loop with larger circulation resistance requires higher liquid head (liquid column height) to drive the circulation. In summary, the height difference and circulation resistance

2519, Page 8 jointly influence the behavior of the liquid head, and the liquid head always keeps balance with the pressure drop resulting from height difference and circulation resistance, which shows good self-regulation of TPTLs. 14 Exp: Valve opening 100% Exp: Valve opening 50% Exp: Valve opening 25% 12 Mass flow rate (kg/h) 10 8 6 4 2 Not measured be calculated 0 0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 Height difference (m) igure 7: Refrigerant mass flow rate as a function of height difference between the condenser and evaporator igure 7 shows the refrigerant mass flow rate as a function of height difference between the condenser and the evaporator. The refrigerant mass flow rate shares the similar behavior with the heat transfer rate (shown in igure 5). When the downcomer is fully liquid filled, with the increase of height difference, the refrigerant mass flow rate and the heat transfer rate increase sharply, since the liquid head increases sharply (shown in igure 6). But when the downcomer turns to be partially liquid filled, with the increase of height difference,the refrigerant mass flow rate and the heat transfer rate rise slowly even remain constant, since the liquid head risers slowly even keeps constant (shown in igure 6). It should be noteworthy that there are some points (hollow points in the dashed rectangle) cannot be measured in the experiments, and they are calculated by the ratio of heat transfer rate and latent heat of vaporization. Because in these cases, the horizontal liquid tube (connecting the Coriolis mass flowmeter and the evaporator) turns to be partially liquid filled (just like a brook) rather than fully liquid filled, and the Coriolis mass flowmeter does not work at that time.

2519, Page 9 Liquid level in the evaporator (m) 0.5 0.4 0.3 0.2 0.1 P Liquid level ΔP Exp: Valve opening 100% Exp: Valve opening 50% Exp: Valve opening 25% 0.0 0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 Height difference (m) igure 8: Liquid level in the evaporator as a function of height difference between the condenser and evaporator To present the distribution of refrigerant at different height difference, liquid level in the evaporator (observed in the transparent pipe in parallel with the evaporator) is plotted in igure 8. Corresponding to the points which can not be measured in igure 7, the liquid level in the evaporator stays at 0 m approximately, which indicates that there are nearly little refrigerant for boiling in the evaporator at that time, that is also the reason for worse performance with smaller height difference. As shown in igure 8, when the height difference is small, especially for the loop with larger circulation resistance, the liquid level in the evaporator is very low and much refrigerant stays in the condenser, since the liquid head is not sufficient to drive the refrigerant to the evaporator, therefore the TPTL performs badly. With the increase of height difference, the liquid level in the evaporator rises, which means the boiling region gets larger, so the TPTL performs better. 4. CONCLUSIONS To find out the effect of height difference on the performance of TPTL, a visual experimental setup is established, a water-to-water type TPTL with the height difference from 0 to 1.5 m is investigated experimentally. The following conclusions can be drawn: 1) The downcomer can be partially liquid filled rather than always fully liquid filled, and the condenser outlet is just saturated when the downcomer is partially liquid filled; 2) With the increase of height difference, the heat transfer rate and circulation flow rate first increases sharply, then increases slowly, finally remains constant, since the downcomer turns to be partially liquid filled, and the liquid head stops rapid rise; 3) The loop with larger circulation resistance shows worse heat transfer performance and is more likely to be fully liquid filled. NOMENCLATURE The nomenclature should be located at the end of the text using the following format: c P specific heat (kj/(kg oc))

2519, Page 10 V volumetric flow rate (m 3 /s) Q heat transfer rate (kw) t temperature ( o C) ρ density (kg/m 3 ) Subscript e in evaporator inlet out outlet ACKNOWLEGE This study is supported by the National Natural Science oundation of China (Grant No. 51176084) and National Science oundation for Distinguished Young Scholars of China (Grant No. 51125030). REERENCES Garrity, P.T., Klausner, J.., Mei, R., 2007, A flow boiling microchannel evaporator plate for fuel cell thermal management. Heat Transfer Engineering, vol. 28, no, 10: p. 877-884. Haider, S., Joshi, Y.K., Nakayama, W., 2002, A natural circulation model of the closed loop, two-phase thermosyphon for electronics cooling. Journal of heat transfer, vol. 124, no, 5: p. 881. Han, L., Shi, W., Wang, B., Zhang, P., Li, X., 2012, Development of an integrated air conditioner with thermosyphon and the application in mobile phone base station. International Journal of Refrigeration. vol. 36, no, 1: p. 58-69. Imura, H., Saito, Y., ujimoto, H., 1989, low and Heat transfer Characteristics in a Closed-Type Two-Phase Loop Thermosyphon. Transactions of the Japan Society of Refrigerating and Air Conditioning Engineers, vol. 6: p. 173-182. Khodabandeh, R., 2005, Pressure drop in riser and evaporator in an advanced two-phase thermosyphon loop. International Journal of Refrigeration, vol. 28, no, 5: p. 725-734. Lee, S., Kang, H., Kim, Y., 2009, Performance optimization of a hybrid cooler combining vapor compression and natural circulation cycles. International Journal of Refrigeration, vol. 32, no, 5: p. 800-808. Liu, D., Tang, G.-., Zhao,.-Y., Wang, H.-Q., 2006, Modeling and experimental investigation of looped separate heat pipe as waste heat recovery facility. Applied thermal engineering, vol. 26, no, 17: p. 2433-2441. Nayak, A., Lathouwers, D., Hagen, T., Schrauwen,., Molenaar, P., Rogers, A., 2006, A numerical study of boiling flow instability of a reactor thermosyphon system. Applied thermal engineering, vol. 26, no, 5: p. 644-653. Rao, N., Sekhar, C.C., Maiti, B., Das, P., 2006, Steady-state performance of a two-phase natural circulation loop. International communications in heat and mass transfer, vol. 33, no, 8: p. 1042-1052. Tu, R., Liu, X.-H., Li, Z., Jiang, Y., 2011, Energy performance analysis on telecommunication base station. Energy and Buildings, vol. 43, no, 2: p. 315-325.