A-8-01 Typical questions and answers on the boiler specifications on tender and boiler contract documents

Similar documents
Bryan Flexible Water Tube. Ultra-High Efficiency Condensing Hot Water Boilers. 3,000,000 BTUH Natural Gas Fired

HORIZONTAL FIRE TUBE BOILERS Piping (HVAC) Pumping Equipment (HVAC).

SECTION HEATING BOILERS

SECTION WATER-TUBE BOILERS

PART 0 A/E INSTRUCTIONS 0.01 DESIGN REQUIREMENTS

.2 Section Waste Management and Disposal..4 Section Vibration Isolation and Seismic Control Measures.

Revitalize Building Mechanical Systems (4619)

C. Shop Drawings: For boilers, boiler trim, and accessories. Include plans, elevations, sections, details, and attachments to other work.

BuildingName The Description of the Project P DOCUMENTS

Indirect gas-fired air heater

SAMPLE SPECIFICATION FOR RIELLO ARRAY MODULATING BOILER

A. Section Common Motor Requirements for HVAC Equipment: Fan motors.

Suggested Specification: Benchmark 1.5 Low NOx Gas-Fired Hydronic Boiler(s)

Engineering Bulletin. Gas Heat. for M-Series and T-Series Climate Changer Air Handlers CLCH-PRB010-EN. March 2004

AFUE up to 83.9% Heating Input 50,000 to 299,000 Btuh

LATTNER BOILER COMPANY 9.5 HP Low-NOx Installation and Start-Up Checklist for Dry Cleaners

Power Flame Incorporated

Project Name: Location: Engineer: Contractor: I. GENERAL

150 BHP, 3 Pass High-Pressure Fire Tube Boiler mounted in a 53 Trailer

WATER HEATERS / BOILERS GSB8-E. Gas-Fired Steam Boiler PRODUCT SPECIFICATIONS. AFUE up to 82.7% Heating Input 75,000 to 299,000 Btuh GSB E

Model CB-LE. Packaged Boiler HP. Operation, Service, and Parts Manual /09. and Model CB Ohio Special HP

AFUE up to 85.2% Heating Input 105,000 to 245,000 Btuh

FUEL-FIRED VERTICAL TUBELESS BOILERS

GSB8. CONSERVATOR Gas-Fired Steam Boiler. AFUE up to 82.7% Heating Input 75,000 to 299,000 Btuh GSB S MODEL NUMBER IDENTIFICATION FEATURES

WATER HEATERS / BOILERS GWB8-E. Gas-Fired Hot Water Boiler PRODUCT SPECIFICATIONS. AFUE up to 83.9% Heating Input 50,000 to 299,000 Btuh

LGB Gas fired boiler

Hubbell NX500 High Efficiency Gas Condensing Water Heater

FLEXCORE SERIES MASTERSPEC

mith Mills 4500A Smith Mills 4500A 4500A-3R OIL, GAS OR COMBINATION GAS/OIL COMMERCIAL BOILER/BURNER CAST IRON

Internet Version for Reference Only INDUCED DRAFT COMMERCIAL WATER HEATERS SUPPLEMENT INSTRUCTIONS TO PART #

Section B1. Flexible Watertube Boilers TABLE OF CONTENTS

Power Flame Incorporated

Steam Fundamentals. (in heating & processing applications)

Internal ridged board 1" x 1.5 foil face installation shall be installed on roof, walls and base of casing.

Lattner Boiler Company Model HRT Steam Boilers with Forced Draft Burners

Lattner Boiler Company Scotch Marine Steam & Hot Water Boilers

SPECIFICATION DIVISION 23 SECTION DESCRIPTION DIVISION 23 HEATING, VENTILATING AND AIR CONDITIONING (HVAC) SECTION FIRE TUBE BOILERS (STEAM)

RBI MASTERSPEC. A. This Section includes gas-fired, non-condensing finned copper water tube water heaters for heating hot water.

AFUE 95% Heating Input 50,000 to 200,000 Btuh

Fuel-Fired Vertical Tubeless Boilers

LGB COMMERCIAL GAS BOILER. Versatile combustion control systems. Made with Weil-McLain quality COMMERCIAL GAS BOILER APPLICATIONS INCLUDE:

SERIES 19A. mith PRESSURIZED WET BASE

Direct Fired Heater Model AD Specification

GP COMBUSTION EQUIPMENT INC 100 Sheldon Dr., Units 16/17 Cambridge, Ontario N1R 7S7. Model C Forced Draft Burners. Natural Gas or Propane MODEL C10

GENERAL BASIC INSTALLATION INSTRUCTIONS DIRECT FIRED HOT WATER BOILERS PARKER BOILER CO.

mith Mills Smith Mills 6500A 6500A-4 OIL OR GAS CAST IRON BOILER/BURNER CAST IRON

Trinity Tft High Efficiency Gas Condensing Boiler & Water Heater

University of Houston Master Construction Specifications Insert Project Name SECTION DOMESTIC WATER HEATERS PART 1 - GENERAL

Trinity Lx400 High Efficiency Gas Condensing Boiler & Water Heater

Trinity Lx200 High Efficiency Gas Condensing Boiler & Water Heater

UTICA BOILER. SSV Submittal. Project Name: Project Location: Contractor:

C1210ES Tankless Water Heater

SECTION HEATING BOILER FEEDWATER EQUIPMENT

C1050ES Tankless Water Heater

CSD-1 COMMERCIAL BOILER CONTROLS

Indirect Gas-Fired Make-Up Air

Suggested Specifications Prestige Excellence 110

UNFIRED STEAM GENERATORS STANDARD EQUIPMENT

SECTION FUEL-FIRED DOMESTIC WATER HEATERS

User s Information Manual

Burner Comparisons. Typical Competitor s Burner

DIVISION FINNED WATER-TUBE WATER HEATERS

INVITATION FOR BID. May 17, Purchase Natural Gas Hot Water Boiler MAWSS Purchasing Department

SECTION SAMPLE SPECIFICATION FOR BOILER CONTROLLER CONVERSION KIT

Design and Construction Standards SECTION PLUMBING EQUIPMENT

Type CG Series Forced Draft Gas Burner

Date: Project #: Engineer: Prepared By: Bid Date:

Williams & Davis Boilers

Bosch Greentherm T9800 SE 199 Gas Tankless Water Heater

SAMPLE SPECIFICATIONS

EGH Series 5. Control Supplement. EGH-105 to EGH-125 Natural gas CSD-1 control system

KN2/4 SERIES MASTER SPECIFICATION

LOW NOx, HIGH EFFICIENCY, HOT WATER SUPPLY AND HYDRONIC HEATING BOILERS

VCLEARFIRE. High-Efficiency, Commercial Steam Boiler Horsepower

GAS/LOW NOx SERIES. High or Low Pressure Steam Boiler. The most versatile industrial steam boiler in the world

KN-SERIES MASTER SPECIFICATION

Rental Boiler Specifications (Nebraska Boiler)

Power Flame Incorporated

SECTION PLUMBING EQUIPMENT

Bryan Water-Pak Indirect Systems 360,000 BTU to 4,500,000 BTU Inputs 199 to 3,533 Gallons Storage Capacity

DIVISION WALL-HUNG STAINLESS STEEL HEATING BOILERS

SERVICE AND INSTALLATION MANUAL MODELS HDO(H) OIL FOR YOUR SAFETY

RBI MASTERSPEC. A. This Section includes gas-fired, non-condensing finned copper water tube boilers for heating hot water.

DIVISION FINNED WATER-TUBE WATER HEATERS

**************************************************************************

ClearFire. Startup Guide. Model CFH. Horizontal Steam Boiler

User s Information Manual Models: 45, ,000 Btu/hr

SUPER HIGH EFFICIENCY WATER HEATERS SUPPLEMENT TO INSTRUCTION MANUAL P/N (Replaces pg. 2 in instruction manual.) CONGRATULATIONS!

SECTION PLUMBING EQUIPMENT

Conversion Instructions Logano G234X. Gas boiler. Please read carefully before installing and servicing. Gas boiler

Figure 10 or Figure 6

BURNHAM COMMERCIAL 27 February 2008 MPC Multiple Pass Commercial Boiler Suggested Specifications

DIVISION FIRE-TUBE STAINLESS STEEL HEATING BOILERS

MODEL CEW OHIO SPECIAL

FSB Series II Gas-Fired Hot Water Induced Draft Boilers

Solution builder. in energy management.

Industrial Space Heating Direct Gas-Fired Heating. Greenheat 50/50 Recirculation

Tray ST5. Tray Type Deaerator Pressurized.005 cc/liter. industrialsteam.com

Utica Boilers MAC Submittal

Distributed By: M&M Control Service, Inc Building Technologies

Transcription:

Boiler specifications A-8-01 Typical questions and answers on the boiler specifications on tender and boiler contract documents Burner General: Q. Burner and burner safeguards shall comply with the CGA Gas codes. A. Our boiler controller (flame safety and water level control) comply with UL and c-ul. Q. Burner control devices and control sequence shall comply with the requirements of Factory Mutual. A. Yes. Request on PO. Q. The turndown ratio for the burner shall be at least 4:1 A. No, our turn down ratio is usually 2:1 for EX and depends on model for LX. Refer to A-1 for details. Oil burner: Q. Oil burners shall be: - pressure atomizing forced draft type. A. yes Q. Oil burners shall be complete with -Built-in blower to supply combustion air, complete with motor, silencer and damper A. yes except the silencer(need details of what they need). Silencer is optional. Q. -with stainless steel flame retention diffuser A. Yes Q. - Oil pump complete with integral relief valve A. oil pump has internal recirculation or external return to the tank (depends on model) Q. -Oil filter A. yes, it comes as standard Q. - Pressure gauge A. yes, gauge is standard on the pressure side of the pump. Q. -High voltage ignition transformer A. yes only for EX(H)(W)-100. Other models have gas pilot as ignition means. Q. - Flame observation port A. yes, it comes as standard. Q. - Easy access to nozzles and electrodes A. yes, we can say that. Q. - Fuel and air modulating controls for maximum burner efficiency throughout operating range A. No, our burner is off-low-high step fire control. Q. -Oil atomizer utilizing air blower A. No, our oil atomizer uses the oil pressure itself to spray the oil, and mixes with air supplied by the blower. 1 / 5

Q. - electric oil heater to heat fuel oil from - 48 C to 0 C A. No, our burner is designed for #2 fuel oil, which does not need the heater for proper combustion. In cold region or season, the oil supplier usually provides #2 oil arranged for use in cold conditions. Gas burner Q.the burner shall be complete with gas train including -lubricated type manual shut off cock on the gas train A. No, our gas train has ball type manual shut off valve. Q. -automatic gas vent valve A. automatic gas vent is not standard for boilers 200BHP and below. 250 and 300BHP boilers have that, but it is not required by code we comply with. Q. -Main gas safety shutoff valves A. Yes, we have two safety shutoff valves (both UL listed as safety shutoff valve) Q. -high and low gas pressure switches A. Yes, our boiler has both high and low gas pressure switches as standard. Q. -Main manual gas shutoff and leakage test cocks A. Main manual gas shutoff valve is standard, and leakage test cocks are optional as CDS-1 option. Q. -gas pressure regulators A. Standard. Except for LX50-07 which has the gas regulating function integrated in the valve. Q. -Air safety switch A. Air pressure switch is standard Q. -Electronic annunciating combustion safety control with UV sensor. A. Our BL combustion safety control includes display and lamps for status and errors. Q. -Automatic gas valve A. main and pilot gas valves are automatic Q. -Adjustable cam gas metering valves. A. No, we can monitor gas flow using gas orifice differential pressure. Pilot burner Q. -gas pressure regulators A. Standard Q. -Pilot solenoid valve and shutoff cock A. Yes, the pilot gas train has 2 safety shutoff valves and manual shutoff cock. Q. -gas pilot assembly and ignition transformer A. Yes, but except EX(H)(W)100-O. for 100BHP oil burner, the burner is spark direct ignition. 2 / 5

Boiler Q. Boiler pressure vessel shall conform to ASME section. A. Our boiler pressure vessel has S stamp = ASME section or H stamp = ASME Section IV. Q. ASHRAE/IESNA 90.1 Compliance: Water-tube boilers shall have minimum efficiency according to Table 10-8. A. Our boiler efficiency conform to such minimum efficiency requirement. Q. Design, documentation, fabrication and testing shall comply with ASTM, ANSI, CGA, ULC standards and TSSA requirements. A. CGA / CSA = boilers are no longer labeled with these approvals because they are equivalent to UL/c-UL, ULC = boilers will be either labeled UL and c-ul, and not ULC. Q. boiler water tubes shall be made of ASME SA-106-B. A. Now, main models uses SA-178-A, and some still uses SA- 106-B. Q. Boiler should include the following trim: -NEMA 250 type 1 control box A. Our boiler is a packaged boiler including the boiler control panel, and the entire boiler is UL listed. In this case, the NEMA control box is generally not required. Our control box is following the strict rules in the UL codes. Q. -Steam pressure gauge with 6 dial: A. We do have one pressure gauge but 4. And also pressure display on the controller. Q. -Pressure control operator.(modulating) A. Yes, we have BL(or XJ-1) pressure control as well as the backup pressure control switch from Honeywell as standard. However, it is not modulating as itself. Q. -Pressure high limit safety control. A. Yes, we have high limit safety switch as standard. Q. -Water gauge glass A. No, our boiler type is exempt from gauge glass requirement in the ASME code. Q. -Low-Water Cutoff Switch: Manual reset type. External column mounted float type. A. We have the low water cutoff as standard (code requirement) = manual reset, external column mounted, but electrode type (not float type) Q. -Auxiliary low water cutoff A. Yes, we have it as standard = auto reset. Q. -feed pump control A. Yes, we have it as standard included in the BL(or XJ-1). Q. -ASME safety valve(s) A. Yes, we have 1 or 2 (quantity depends on ASME requirement and design) safety valve(s) on the boiler pressure vessel as standard. Q. -Auxiliary contacts for start/stop and alarm indication A. we can supply some dry contacts for monitoring purpose Q. -Alarm Bell: Factory mounted on control panel with silence switch. 3 / 5

A. yes Q. -Provide electronic programming relay, feedwater pump and blower motor starter control switches, control circuit transformer and alarm bell. A. all included. Q. -selector switch to permit only low fire. A. not included for BL boilers. Low fire hold only in the test mode. Q. Jacket: Sheet metal, with screw-fastened closures and baked-enamel protective finish. A. Our boiler is installed with painted sheet metal casings. (not baked paint) Q. Mounting base to secure boiler to concrete base A. Yes Q. Two bottom blow valves (one slow and one quick opening, or two slow opening) A. standard boiler includes one quick or slow opening valve. One additional slow opening valve is optional. Economizer Q. Provide an economizer for each of the steam boilers. The economizers shall be gas to liquid heat exchangers, designed to utilize heat in the boiler flue gasses to preheat boiler feedwater. A. Yes. Q. Tube material shall be SA-178-A boiler tube A. economizer water tubes are all SA-106-B boiler tube. Tube size is 1 SCH40. Q. Provide economizer with safety valve. A. on boilers for US market, the economizer is made under ASME section 1 and it is part of the boiler. The safety valve on the main pressure vessel protects the economizer from excessive pressure. On some boilers for Canadian market, the economizer is made under ASME section 8, and considered as a separate pressure vessel. In this case, the economizer is equipped with a pressure relief valve. Q. Provide economizer with automatic soot blower A. Our boiler is intended for fuel gas and #2 oil and the deposit of soot is relatively small. That is why we do not need the soot blower. In case of economizer cleaning, we can open the box and clean the vessels easily for EX models. Q. Provide additional feed water controls as required to ensure proper economizer operation. A. Economizer feed water control is combined with the boiler water control (feed water to the boiler = feed water to the economizer). With BL control, we have one additional control to prevent the water to boil in the economizer. 4 / 5

Ancillary Q. Boiler shall use propane as a backup fuel. A. Propane backup fuel is optional only for some LX models. Q. Barometric Damper: Galvanized-steel assembly with flue-gas thermometer having a minimum 90 mm diameter dial. A. Barometric damper is not supplied by our factory. Consult chimney installer when required. Q. Silencer to reduce the noise to 80dB or below A. Air inlet silencer is optional. It can reduce the noise from 85dB to 80dB. Revision Record: Rev. Date Content of change Related docs Revised by 00 May 2009 New content T.F. 01 Apr. 2011 Amendments to section Boiler K.S. 5 / 5