A Generalized Correlation for Pressure Drop of Refrigerant R-134a through Helical Capillary Tubes

Similar documents
Pressure drop analysis of evaporator using refrigerants R-22, R-404A and R-407C

FABRICATION OF REFRIGERANT FLOW RATE WITH SPIRALLY COILED CAPILLARY TUBE

ANKUSH SHARMA & JAGDEV SINGH Department of Mechanical Engineering, Beant College of Engineering and Technology, Gurdaspur, Punjab, India

Performance of window air conditioner using alternative refrigerants with different configurations of capillary tube

An Experimental Study of a Simple Vapour Compression Refrigeration System with Varying Parameters

Experimental study on heat transfer characteristics of horizontal concentric tube using twisted wire brush inserts

Enhancement of COP in Vapour Compression Refrigeration System

Taguchi Method for Development of Mass Flow Rate Correlation using Hydrocarbon Refrigerant Mixture in Capillary Tube

Enhancement of COP by Using Spiral and Microchannel Condenser instead of conventional Condenser of VCR System

A STUDY OF THE FLOW OF REFRIGERANT THROUGH A CAPILLARY TUBE

Refrigeration Cycle And Compressor Performance For Various Low GWP Refrigerants

Research Article / Araştırma Makalesi EXPERIMENTAL INVESTIGATION OF R600A REFRIGERANT FLOW INSIDE ADIABATIC CAPILLARY TUBE

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger

Performance of an Improved Household Refrigerator/Freezer

Performance investigation of Air-conditioning system using ejector as expansion device

Performance Analysis of Electronic Expansion Valve in 1 TR Window Air Conditioner using Various Refrigerants

Pressure drop analysis of Condenser using refrigerants R-134a, R-407C

ASSESSMENT OF R430A REFRIGERANT AS A POSSIBLE SUBSTITUTE TO R134A REFRIGERANT IN LARGE CAPACITY FREEZER

Thermal Design of Condenser Using Ecofriendly Refrigerants R404A-R508B for Cascade Refrigeration System

HEFAT th International Conference on Heat Transfer, Fluid Mechanics and Thermodynamics Sun City, South Africa Paper number:pp1

EXPERIMENTAL VERIFICATION OF PERFORMANCE OF CAPILLARY TUBE USING VAPOUR COMPRESSION REFRIGERATION SYSTEM

INTERNATIONAL JOURNAL OF PURE AND APPLIED RESEARCH IN ENGINEERING AND TECHNOLOGY

Lesson 25 Analysis Of Complete Vapour Compression Refrigeration Systems

International Journal of Engineering Research (IJOER) [Vol-1, Issue-3, June- 2015]

Study of R-161 refrigerant as an Alternate Refrigerant to various other refrigerants

Performance Study of Triple Concentric Pipe Heat Exchanger

ijcrr Vol 04 issue 07 Category: Research Received on:06/02/12 Revised on:17/02/12 Accepted on:02/03/12

Enhancement of COP using Nanoadditives in Domestic Refrigerator

Design and Development of Water Cooled Condenser for Domestic Refrigerator

Numerical Studies On The Performance Of Methanol Based Air To Air Heat Pipe Heat Exchanger

Performance Comparison of Ejector Expansion Refrigeration Cycle with Throttled Expansion Cycle Using R-170 as Refrigerant

Numerical Study on Improvement of COP of Vapour Compression Refrigeration System

Effects of Non-Uniform Refrigerant and Air Flow Distributions on Finned- Tube Evaporator Performance

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger

ME 410 MECHANICAL ENGINEERING SYSTEMS LABORATORY MASS & ENERGY BALANCES IN PSYCHROMETRIC PROCESSES EXPERIMENT 3

Analysis of Constant Pressure and Constant Area Mixing Ejector Expansion Refrigeration System using R-1270 as Refrigerant

Performance Analysis of Li-Br Water Refrigeration System with Double Coil Anti-Swirl Shell and Coil Heat Exchangers

Experimental Study on the Performance of Twisted Capillary Tube


Experimental Study on Performance Parameters for Refrigerants R22, R410a and R404a at Various Air Outlet Temperatures

Experimental Analysis Of Vapour Compression Refrigeration System With Superheating By Using R-134a, R-12, R-717 Refrigerant

U.G. Student, Department of Mechanical Engineering, J D Engineering College, Nagpur, Maharashtra, India

International Journal of Engineering & Technology Sciences Volume 03, Issue 01, Pages 55-64, 2015

Role of Nano-technology for improving of thermal performances of vapour compression refrigeration system (VCRS): An Overview

Effects of Flash and Vapor Injection on the Air-to- Air Heat Pump System

Improvement Of Energy Efficiency Ratio Of Refrigerant Compressor

Subscripts 1-4 States of the given system Comp Compressor Cond Condenser E Evaporator vol Volumetric G Gas L Liquid

STUDY ON THE CONTROL ALGORITHM OF THE HEAT PUMP SYSTEM FOR LOAD CHANGE

[Jhansi, 5(10): October 2018] ISSN DOI /zenodo Impact Factor

Heat Transfer Analysis of Vapor Compression System Using Nano Cuo-R134a

Control Method Of Circulating Refrigerant Amount For Heat Pump System

Compression of Fins pipe and simple Heat pipe Using CFD

PERFORMANCE OF VCRS SYSTEM WITH HEAT EXCHANGER AND PHASE CHANGE MATERIAL

"COP Enhancement Of Domestic Refrigerator By Sub cooling And Superheating Using Shell &Tube Type Heat Exchanger"

An Experimental Investigation Of Oil Retention Characteristics In CO2 Air-Conditioning Systems

Virtual Refrigerant Pressure Sensors for Use in Monitoring and Fault Diagnosis of Vapor- Compression Equipment

Institute of Aeronautical Engineering (Autonomous) Dundigal, Hyderabad B.Tech (III II SEM) MECHANICAL ENGINEERING

Experimental study of Hydrocarbon Refrigerant Mixture R290/R600a as an alternative to Refrigerant R134a used in a Domestic Refrigerator

Effect of Modification in Refrigerant Passage of an Automotive Air Conditioning Compressor

MAL-DISTRIBUTION MODEL OF HEAT EXCHANGERS IN MICRO CHANNEL EVAPORATOR

PERFORMANCE OF DEEP FREEZER BY USING HYDROCARBON BLENDS AS REFRIGERANTS

IJESRT. Scientific Journal Impact Factor: (ISRA), Impact Factor: 1.852

EXPERIMENTAL INVESTIGATIONS ON AUTOMOBILE AIR CONDITIONERS WORKING WITH R134a AND R290/R600a AS AN ALTERNATIVE

Improving and Comparing the Coefficient of Performance of Domestic Refgirator by using Refrigerants R134a and R600a

Performance Evaluation of VCRS with Nested Helical Shaped Condenser by Using R134a as Refrigerant

Effects of evaporator load on vapour compression refrigeration system using ecofriendly hydrocarbon refrigerants with sub cooling

International Journal of Informative & Futuristic Research ISSN (Online):

WASTE HEAT RECOVERY FROM DOMESTIC REFRIGERATOR Soma A. Biswas 1, Sandeep M. Joshi 2 1,2 Pillai College of Engineering

ME 410 MECHA ICAL E GI EERI G SYSTEMS LABORATORY

Performance Study of a Water-to-Water Heat Pump Using Non-azeotropic Refrigerant Mixtures R407C

[Vali*, 5(2): February, 2016] ISSN: (I2OR), Publication Impact Factor: 3.785

Performance Characteristics and Optimization of a Dual-Loop Cycle for a Domestic Refrigerator- Freezer

Experimental Investigation of Two Phase Closed Thermosyphon Using Propylene Glycol As A Working Fluid

Capillary Tube and Thermostatic Expansion Valve Comparative Analysis in Water Chiller Air Conditioning

Experimental Investigation of a Hybrid Evacuated Tube Solar Collector

Numerical Simulation of Window Air Conditioner

WORK STUDY ON LOW TEMPERATURE (CASCADE) REFRIGERATION SYSTEM

DEEPAK PALIWAL, S.P.S.RAJPUT

Optimization of Capillary Tube Parameters in Vapour Compression System using Environmentally Friendly Refrigerant R1234yf

Waghmare Tushar Ramrao, D.S.Nakate

EVALUATION OF REFRIGERANT R290 AS A REPLACEMENT TO R22

EXPERIMENTAL INVESTIGATION OF WATER COOLER SYSTEM BY USING ECO-FRIENDLY REFRIGERANT (R-134a)

INTERNATIONAL JOURNAL OF PURE AND APPLIED RESEARCH IN ENGINEERING AND TECHNOLOGY

Experimental Evaluation of Refrigerant Mixtures as Substitutes for HFC134a

Development of Energy Efficient R-134a Automotive Air Conditioning System Using Internal Heat Exchanger

A Review on Analysis of Vapour Compression Refrigeration System Using Matrix Heat Exchanger

Global Journal of Engineering Science and Research Management

Performance analysis of a vapour compression refrigeration system with a diffuser for theeco-friendly refrigerants R-134a, R-600a and R-152a

Design & Fabrication of Hybrid Cooler

Comparative Study of Transcritical CO 2 Cycle with and Without Suction Line Heat Exchanger at High Ambienttemperature

NUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A

CFD Analysis of temperature dissipation from a hollow metallic pipe through circular fins using Ansys 14.5

2. HEAT EXCHANGERS MESA

Performance Investigation of Refrigerant Vapor- Injection Technique for Residential Heat Pump Systems

Design, Manufacturing of Chilled Water System for Process Cooling Application

Volume 6, Issue 3(2018) ISSN International Journal of Advance Research and Innovation

(Refer Slide Time: 00:00:40 min)

AN EXPERIMENTAL STUDY OF A REFRIGERATING PLANT WHEN REPLACING R22 WITH HFCs REFRIGERANTS

Performance Comparison of Hydronic Secondary Loop Heat Pump and Conventional Air-Source Heat Pump ABSTRACT 1. INTRODUCTION

Analysis of Coefficient of Performance & Heat Transfer Coefficient on Sterling Cycle Refrigeration system.

Transcription:

ISSN 2395-1621 A Generalized Correlation for Pressure Drop of Refrigerant R-134a through Helical Capillary Tubes #1 N. Dhekale, #2 Dr. P. A. Patil 1 amardhekale@gmail.com #12 Research Laboratory, Department of Mechanical engineering, JSPMs JSCOE, Pune, 411028, India. ABSTRACT A capillary tube is a common expansion device used in small sized refrigeration and airconditioning systems. The objective of this study is to present test results and to develop a dimensionless correlation on the basis of the experimental data of helical capillary tube for R134a. A generalized correlation for Pressure drop of refrigerant through helical capillary tubes is developed by implementing Buckingham Pi theorem and regression analysis. Several capillary tubes with different length and inner diameter were selected as test sections. Mass flow rate and Pressure drop through capillary tube was measured for several inlet pressures for each capillary tube. The generalized correlation yields good agreement with the present experimental data for R134a. The Predicted results and experimental data within relative deviations ranging from ±5% for 93% of experimental reading. Keywords Capillary tube, Refrigerant pressure drop, Mass flow rate, R134a, Expansion device, Compressor Calorimeter test rig ARTICLE INFO Article History Received :18 th November 2015 Received in revised form : 19 th November 2015 Accepted : 21 st November, 2015 Published online : 22 nd November 2015 I. INTRODUCTION Every refrigeration system requires a pressure reducing device to meter refrigerant flow from high pressure side to low pressure side as per the load requirements. The capillary tubes especially popular in smaller vapor compression systems such as household refrigerators, freezers and room air conditioners. The capillary operates on the principle that liquid passes through it much more readily than vapors; as a result, it is practical metering device. It is a length of drawn copper tubing with small inner diameter. Generally, inner diameters are from 0.5 mm to 1.8 mm and length up to 6 meter can be used. Due to the simplicity, low cost, zero maintenance and requirement of a low starting torque motor to run the compressor, capillary tubes are widely used in vapor compression systems. When a capillary tube is sized to permit the desired refrigerant flow, the liquid refrigerant seals its inlet. If the system becomes unbalanced some uncondensed refrigerant enters the capillary tube. This vapor reduces the mass flow of refrigerant considerably, which increases condenser pressure and causes sub-cooling at condenser outlet means at capillary tube inlet. The result is increases refrigerant mass flow rate through capillary tube. If properly sized for the application, the capillary tube compensates automatically for load and systems variations and gives acceptable performance over a limited range of operating conditions. Walf et al. 1995 [1] had developed generalized correlation for prediction of mass flow through adiabatic straight capillary tube for refrigerants R-134a, R-22 and R-410A. In this method the Buckingham π theorem and regression was applied to the physical factor and fluid factors that affect capillary tube flow rate. Khan et al. [2] carried out experimental study on performance of spirally coiled and straight capillary tube for R-134a refrigerant. He found that the effect of coiling reduces mass flow through capillary by 10% to 15% than straight capillary tube. It is considered that pressure drop of coiled tube was increased due to an existence of secondary flow generated by centrifugal force. Further, generalized correlation was developed for spirally coiled capillary tubes. Mittal et al. [3] experimentally investigated performance of helically coiled capillary tube for R-407C refrigerant which is alternate refrigerant for HCFC R-22. The mass flow rate through coiled capillary with coil diameter of 60 mm, 100 mm and 140 mm was reduced by an average of 10%, 7% and 5% respectively than 2015, IERJ All Rights Reserved Page 1

straight capillary. He also found that increase in degree of sub-cooling from 5ºC to 10ºC results in increase of mass flow rate by 15% for 1.52 mm inner diameter tube. Further, he found effect of sub-cooling on mass flow rate was more on larger inner diameter of capillary tubes due to increase in liquid length. S. Kim et al. [4] experimentally studied the performance of capillary tube for HCFC R-22, HFC R-407C and R-410A. The mass flow rates of R-407C were greater by 4.0%, and those of R-410A were greater by 23% as an average, than those of R22. Choi et al. [5] has experimentally investigated performance of capillary tube for R-22, R-290 and R-407C refrigerant and developed generalized correlation. The flow characteristics of refrigerants through straight capillary tubes have been studied extensively in the past six decades, both experimentally and numerically. Experimental studies on helically coiled capillary tubes are very limited. Actually, in all practical applications, the capillary tubes are helically coiled to make it compact in size. Further, the practical capillary sizing problem is to determine required length at given pressure drop, mass flow rate, inner diameter and given operating conditions. However in most of the generalized correlations pressure drop term were not found and mostly focused on determination of mass flow rate through capillary tube. Therefore, considering practical sizing problem of capillary, the experimental investigation has been undertaken to study the flow of R-134a through helically coiled capillary tube at various inner diameter, length and operating conditions. The generalized correlation is developed using 68 experimental readings with different diameter, length and operating conditions. A pressure drop term also included in dimension analysis in the point of view of practical sizing of capillary. II. Fig. 1 Schematic diagram of experimental setup EXPERIMENTAL SET-UP AND PROCEDURE The schematic diagram of experimental set-up is shown in Fig. 1. The test-section was a copper capillary tube, in which the refrigerant expands from high pressure side to low pressure side. The helically coiled tube test-section in the experimental set-up was put in horizontal position. Suitable isolation valves are installed for easy replacement of test pieces. The low pressure refrigerant coming out from capillary tube entered the evaporator consisting of a copper coil submerged in a glycol tank. An electric heater was fitted in the evaporator tank to provide a heat load to the evaporator. The heating load was varied through a Solid state rely and PID controller. An agitator was also fitted in the tank to maintain the uniform bulk temperature of glycol. The refrigerant vapors emerging from the evaporator were sent to suction port of compressor after assurance of achieving desired suction superheat of refrigerant. The hermetically sealed compressor was run by means of single phase electrical supply. The high pressure superheated vapors emerging from the compressor entered the oil separator. The oil free vapors from separator were condensed in the water cooled condenser. The desired condensing pressure/temperature was achieved by varying mass flow rate through condenser by using three way proportionate control valve and PID controller. The cooling tower was used to reject heat in to the atmospheric. The provision of on-off of cooling tower fan was made to control the cooling tower water temperature. To vary the degree of sub-cooling, a pre-heater followed the sub-cooler was installed. In the pre-heater, liquid refrigerant heating was done by electrical heater and controlled by Solid state relay and PID controller. The high pressure saturated liquid from the pre-heater was made to flow through sub-cooler to control the degree of sub-cool. The same arrangement like condenser cooling water circuit was made to achieve desired sub-cooling in sub-cooler heat exchanger. The cold water from cooling tower flows through sub-cooler and then flows through condenser. The sub-cooled liquid refrigerant collected in a receiver to ensure a continuous supply of refrigerant to the capillary tube. The unwanted solid particles and moisture in refrigerant were removed through a filter-drier. A hand operated expansion valve was also provided in parallel to the capillary tube. A centrifugal pump was used to circulate cooling water through the subcooler and condenser. The mass flow rate of high pressure liquid refrigerant was measured by magnetic mass flow meter having an accuracy of ±0.25% of indicated value. A sight glass was also provided to visualize the state of refrigerant entering into the capillary tube. A number of hand shutoff valves were provided in between the major components of the experimental set-up. Therefore, in case of leakage or any repair, the damaged component was retrieved with ease. The temperature at different locations of the set-up and the test section was measured by means of T- type thermocouples with an accuracy of ±0.2. The pressure of the refrigerant was measured by pressure transducers having an accuracy of ±0.25%. The pressure at capillary tube inlet was adjusted from 915 kpa to 1350 kpa. The degree of sub-cooling and degree of superheating was maintained constant throughout the experimentation to 3ºC and 5ºC respectively. The capillary inner diameters, 1.52 mm, 1.63 mm and 1.78 mm, and coil diameter 50 mm were selected for this study. All the test data were collected under steady state conditions. At the start up, the system typically takes about 1 h to reach the steady state and thereafter, it takes only 15 min for any subsequent setting. III. RESULT AND DISCUSSION The test results on the performance of various capillary tubes are presented for various geometric and operating 2015, IERJ All Rights Reserved Page 2

conditions. The generalized correlation is developed based on extensive experimental readings. A. Pressure Drop through Capillary Tube: Fig. 2 shows variation of pressure drop with capillary inlet pressure. Pressure drop curve of all six capillary tube samples are plotted. The pressure difference across capillary tube increases as the capillary inlet pressure increases due to higher frictional resistance offered by capillary at higher inlet pressure. For capillary tube of 1.625 mm diameter and 1.59 meter length, the pressure difference across capillary increases by 26.7% and 48.5% after increasing inlet pressure from 9.2 bar to 11.53 bar and 13.53 bar respectively. The Fig. 2 also indicates that pressure difference across capillary decreases as capillary inner diameter increases and pressure drop increases as length of capillary increases. Fig. 2 Variation of Pressure drop with inlet pressure for different capillary Fig. 3 shows variation of mass flow with capillary inlet pressure for all six capillary samples. The refrigerant mass flow rate increases as the capillary inlet pressure increases due to higher driving force at the inlet of capillary tube at higher capillary inlet pressure. For capillary tube of 1.625 mm diameter and 1.59 meter length, the mass flow rate increases by 19% and 31% after increasing inlet pressure from 9.2 bar to 11.53 bar and 13.53 bar respectively. The Fig. 3 also indicates that mass flow increases as capillary inner diameter increases and mass flow decreases as length of capillary increases. Fig. 4 shows that variation of pressure drop with capillary inlet diameter and constant capillary length of 1.49 meter. The refrigerant pressure drop decreases as the capillary inner diameter increases due to lower frictional resistance. For capillary tube inlet pressure 9.7 bar corresponding to 42ºC condensing pressure, the pressure drop decreases by 6.85% and 24.33% after increasing the inner diameter 1.524 mm to 1.625 mm and 1.778 mm respectively. Fig. 3 Variation of Mass flow rate with inlet pressure for different capillary Fig. 4 Variation of pressure drop with inner diameter at constant length Fig. 5 shows variation of pressure drop with capillary tube length at constant inner diameter 1.625 mm. The refrigerant pressure drop increases as the capillary length increases due to higher frictional resistance. For capillary tube inlet pressure 9.15 bar corresponding to 40ºC condensing pressure, the pressure drop increases by 7.12% and 9.7% after increasing the capillary length from 1.39 meter to 1.49 meter and 1.59 meter respectively. From Fig. 3 and Fig. 4, we can conclude that inner diameter has significant effect on pressure drop through capillary than capillary tube length. In trial and error method for optimization of capillary tube, it is always advisable to alter capillary tube length than diameter to smooth increment or decrement in pressure drop. Fig. 5 Variation of mass flow with capillary length for constant inner diameter From above Fig.2 to Fig.5, we can say the refrigerant pressure drop and mass flow rate in adiabatic capillary tube depends upon capillary tube diameter, length, coil diameter and pressure at capillary inlet. Other parameters like liquid specific volume, vapor specific volume, liquid and vapor viscosity and latent heat of vaporization also have influence on the mass flow of the refrigerant. Hence these parameters are taken into consideration while preparing generalized correlation for prediction of mass flow rate and pressure drop across the capillary tube. A. Development of Generalized Correlation: P= ƒ ( V f, Vg, m, L, D, g, h fg, P s, P d, µ f, µ g ) The non dimensional π-groups represented in table-1 have been derived from Buckingham-π theorem. The equation-1 is developed using Buckingham-π theorem and multiple linear regression. The refrigerant properties are obtained from REFPROP. 2015, IERJ All Rights Reserved Page 3

π1= ƒ (π2, π3, π4, π5, π6) π1 = 1.0002 π2 1.0745 π3 0.6115 π4 0.3418 π5 0.659 π6-2.6202 - (1) Fig. 6 Comparison of predicted pressure drop with measured pressure drop data with this study Table-1 Non dimensional π-groups π Group Correlation Consideration π1 Mass flow rate and pressure drop π2 π3 π4 π5 π6 Specific volume Tube geometry Heat of vaporization Pressure ratio Viscosity All the points are inside the 10% deviation line. The generalized correlation yields good agreement with the present experimental data. The Predicted results and experimental data within relative deviations ranging from ±5% for 93% of experimental reading. IV. CONCLUSION The following conclusions can be drawn from the present study: 1. For a given capillary, the pressure drop is function of mass flow rate, capillary length, inlet pressure and coil diameter. 2. In proposed correlation, capillary length can be determined at given pressure drop across capillary tube, mass flow rate and operating conditions. 3. Non-dimensional correlations to predict the refrigerant pressure drop through helical capillary tube have been proposed. The developed correlation for pressure drop yield good agreement with the measured data of present study with deviations of ±5 percent for 93 percent of experimental reading. NOMENCLATURE dc Capillary tube internal diameter, m L Capillary tube length, m m Mass flow rate, kg/sec Pd Discharge pressure, Pa Ps Suction pressure, Pa Vg Specific volume of vapor, m3/kg Vf Specific volume of liquid, m3/kg μg Dynamic viscosity of vapor, pa-s μf Dynamic viscosity of liquid, pa-s g Gravitational acceleration, m/sec2 ΔP pressure difference across capillary, pa μ Dimensionless parameter group ACKNOLEDGEMENT Thanks to Dr P. A. Patil for his valuable guidance in this experimental work and also thanks to Jayawantrao Sawant College of Engineering for providing Compressor Calorimeter test rig for experimentation. REFERENCES Fig. 7 Deviation in predicted mass flow rate from measured data for different mass flow rate The proposed correlations for helical capillary tubes have been verified by comparing the measured mass flow rates with those predicted by the proposed correlations in Fig. 6 for all experimental reading. Fig.7 shows deviation in predicted mass flow rate from measured mass flow rate at different mass flows of experimental data. [1] ASHRAE Handbook Refrigeration, 2006. American Society of Heating, Refrigerating and Air-Conditioning Engineer Inc. (Chapter 44, Refrigerant- Control device, pg. 26 / 33) [2] Mohd. Kaleem Khan, Ravi Kumar, Pradeep K. Sahoo, An experimental study of the flow of R-134a inside an adiabatic spirally coiled capillary tube, International Journal of Refrigeration 31 (2008) 970-978 [3] M.K. Mittal, Ravi Kumar, Akhilesh Gupta, An experimental study of the flow of R-407C in an adiabatic helical capillary tube, International Journal of Refrigeration 33 (2010) 840-847 [4] S. G. Kim, M. S. Kim1, S. T. Ro, Experimental investigation of the performance of R22, R407C and R410A 2015, IERJ All Rights Reserved Page 4

in several capillary tubes for air-conditioners, International Journal of Refrigeration 25 (2002) 521 531 [5] Jongmin Choi, Yongchan Kim, Ho Young Kim, A generalized correlation for refrigerant mass flow rate through adiabatic capillary tubes, International Journal of Refrigeration 26 (2003) 881 888 [6] Fl_avio Augusto Sanzovo Fiorelli, Alex Alberto Silva Huerta, Ota vio de Mattos Silvares, Experimental analysis of refrigerant mixtures flow through adiabatic capillary tubes, Experimental Thermal and Fluid Science 26 (2002) 499 512 [7] C. P. Arrora, Expansion Valves, Chapter 8 in book Refrigeration and Air Conditioning Mc Graw-Hill. [8] Ramgopal M. NPTEL tutorial on refrigeration and air conditioning, lesson 24, IIT Kharagpur. 2015, IERJ All Rights Reserved Page 5