FABRICATION OF REFRIGERANT FLOW RATE WITH SPIRALLY COILED CAPILLARY TUBE

Similar documents
ANKUSH SHARMA & JAGDEV SINGH Department of Mechanical Engineering, Beant College of Engineering and Technology, Gurdaspur, Punjab, India

A Generalized Correlation for Pressure Drop of Refrigerant R-134a through Helical Capillary Tubes

Role of Nano-technology for improving of thermal performances of vapour compression refrigeration system (VCRS): An Overview

NUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A

NUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A

Improving and Comparing the Coefficient of Performance of Domestic Refgirator by using Refrigerants R134a and R600a

Assessment of LPG as a possible alternative to R-12 in domestic refrigerators

An Experimental Study of a Simple Vapour Compression Refrigeration System with Varying Parameters

Performance Analysis of Electronic Expansion Valve in 1 TR Window Air Conditioner using Various Refrigerants

ASSESSMENT OF R430A REFRIGERANT AS A POSSIBLE SUBSTITUTE TO R134A REFRIGERANT IN LARGE CAPACITY FREEZER

Thermal Design of Condenser Using Ecofriendly Refrigerants R404A-R508B for Cascade Refrigeration System

EVALUATION OF REFRIGERANT R290 AS A REPLACEMENT TO R22

Performance of window air conditioner using alternative refrigerants with different configurations of capillary tube

AN EXPERIMENTAL STUDY OF A REFRIGERATING PLANT WHEN REPLACING R22 WITH HFCs REFRIGERANTS

Experimental study of Hydrocarbon Refrigerant Mixture R290/R600a as an alternative to Refrigerant R134a used in a Domestic Refrigerator

Enhancement of COP by Using Spiral and Microchannel Condenser instead of conventional Condenser of VCR System

CHAPTER 1 INTRODUCTION

Volume 4, Issue 1 (2016) ISSN International Journal of Advance Research and Innovation

DEEPAK PALIWAL, S.P.S.RAJPUT

Research Article / Araştırma Makalesi EXPERIMENTAL INVESTIGATION OF R600A REFRIGERANT FLOW INSIDE ADIABATIC CAPILLARY TUBE

PERFORMANCE OF DEEP FREEZER BY USING HYDROCARBON BLENDS AS REFRIGERANTS

Experimental Study on the Performance of Twisted Capillary Tube

LPG Refrigerator. October 2017 IJIRT Volume 4 Issue 5 ISSN:

Performance Analysis of Li-Br Water Refrigeration System with Double Coil Anti-Swirl Shell and Coil Heat Exchangers

Experimental Study on Performance Parameters for Refrigerants R22, R410a and R404a at Various Air Outlet Temperatures

Experimental Evaluation of Refrigerant Mixtures as Substitutes for HFC134a

Study of R-161 refrigerant as an Alternate Refrigerant to various other refrigerants

Enhancement of COP in Vapour Compression Refrigeration System

Comparative assessment for drop in replacement of R134a in domestic refrigerator.

International Journal of Informative & Futuristic Research ISSN (Online):

Subscripts 1-4 States of the given system Comp Compressor Cond Condenser E Evaporator vol Volumetric G Gas L Liquid

Design of LPG Refrigeration System

Department of MCE, Islamic University of Technology 2. Abstract

Comparative Performance Analysis of Domestic Refrigerator using R12, R134a and R600a Refrigerants

Performance Evaluation of Eco- Friendly Alternate Refrigerants for VCRS

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger

A STUDY OF THE FLOW OF REFRIGERANT THROUGH A CAPILLARY TUBE

Thermodynamic study of R134a in Vapour Compression Refrigeration System in Summer Climate

Numerical Study on Improvement of COP of Vapour Compression Refrigeration System

Performance Evaluation of VCRS with Nested Helical Shaped Condenser by Using R134a as Refrigerant

Taguchi Method for Development of Mass Flow Rate Correlation using Hydrocarbon Refrigerant Mixture in Capillary Tube

Oyelami S., Bolaji B. O.

DESIGN AND DEVELOPMENT OF ECO-FRIENDLY REFRIGERATION SYSTEM

A Theoretical investigation on HC Mixtures as Possible Alternatives to R134a in Vapor Compression Refrigeration

EXPERIMENTAL INVESTIGATIONS ON AUTOMOBILE AIR CONDITIONERS WORKING WITH R134a AND R290/R600a AS AN ALTERNATIVE

ISSN: [Sachuthananthan * et al., 5(10): October, 2016] Impact Factor: 4.116

Paper No. : 04 Paper Title : Unit Operations in Food processing Module 11 : Principles of Refrigeration

International Journal of Advance Engineering and Research Development

TRANSCRITICAL CO 2 SYSTEM

Effects of evaporator load on vapour compression refrigeration system using ecofriendly hydrocarbon refrigerants with sub cooling

Experimental study on heat transfer characteristics of horizontal concentric tube using twisted wire brush inserts

Australian Journal of Basic and Applied Sciences. Investigation of New Eco Friendly Refrigerant Mixture Alternative to R134a in Domestic Refrigerator

HFCs or the Old Refrigerants - what is the best Choice?

EXPERIMENTAL INVESTIGATION OF WATER COOLER SYSTEM BY USING ECO-FRIENDLY REFRIGERANT (R-134a)

Study of Behavior of Refrigerant Mixtures in Domestic Refrigerator- Practical Research

Main Anthropogenic Sources of Greenhouse Gases Refrigerants

U.G. Student, Department of Mechanical Engineering, J D Engineering College, Nagpur, Maharashtra, India

Thermodynamic Analysis of Cascade Refrigeration System Using R12-R13, R290-R23 and R404A-R23

An experimental study of the effect of evaporator temperature on the compressor work of a simple vapour compression refrigeration system

ENSC 388. Assignment #6

EXPERIMENTAL INVESTIGATIONS ON AL 2 O 3 NANO REFRIGERANT WITH DIFFUSER AT CONDENSER INLET IN A VCR SYSTEM

Available online at ScienceDirect. Energy Procedia 109 (2017 ) 56 63

JJMIE Jordan Journal of Mechanical and Industrial Engineering

Study of Performance of Binary Mixture of R134a and R161 as a Substitution of R134a in a Domestic Refrigerator

Thermodynamics I. Refrigeration and Heat Pump Cycles

Feasibility Study of Condensation Heat Exchanger with Helical Tubes for a Passive Auxiliary Feedwater System

Chapter 10. Refrigeration and Heat Pump Systems

ISSN Electronic International Interdisciplinary Research Journal (EIIRJ) Bi-monthly Reviewed Journal Mar- April 2015

International Journal of Research in Engineering and Innovation Vol-1, Issue-5 (2017), 68-72

Volume 6, Issue 3(2018) ISSN International Journal of Advance Research and Innovation

A Review Paper on Comparative Study of Household- Refrigerator with Alternative Low Global Warming Potential Refrigerants

International Journal of Engineering Research (IJOER) [Vol-1, Issue-3, June- 2015]

Thermodynamics II Chapter 5 Refrigeration

Refrigeration Cycles MOHAMMAD FAISAL HAIDER. Bangladesh University of Engineering and Technology

A COMPARATIVE STUDY FOR RETROFITTING OF R-12 VAPOUR COMPRESSION REFRIGERATION SYSTEM BY ECO- FRIENDLY REFRIGERANTS R-134A, R-413A, R-423A

REPLACING HARMFUL CFC 12 BY ECO-FRIENDLY REFRIGERANT IN MILK CHILLER

A Review on Analysis of Vapour Compression Refrigeration System Using Matrix Heat Exchanger

IJISET - International Journal of Innovative Science, Engineering & Technology, Vol. 2 Issue 12, December

Use of fourth generation ecofriendly refrigerants in two and three cascade refrigeration systems for reducing global warming and ozone depletion

PERFORMANCE OF A VERY LOW TEMPERATURE REFRIGERATION SYSTEM OPERATING WITH NATURAL FLUIDS

A Comparison Between Refrigerants Used In Air Conditioning

Design and Fabrication of Liquefied Petroleum Gas Refrigeration System and Comparison with Domestic Refrigerator

THEORETICAL INVESTIGATION OF THE PERFORMANCE OF SOME ENVIRONMENT-FRIENDLY REFRIGERANTS IN A SUB-COOLING HEAT EXCHANGER REFRIGERATION SYSTEM

Study of Adiabatic Capillary Tube in Carbon Dioxide Refrigeration System

MECHANICAL ENGINEERING ME.2017 FUNDAMENTAL OF REFRIGERATION AND AIR CONDITIONING. Sample Questions and Answers

EXPERIMENTAL INVESTIGATION OF A REFRIGERATOR BY USING ALTERNATIVE ECO FRIENDLY REFRIGERANTS (R600A & HC MIXTURE)

Pressure drop analysis of evaporator using refrigerants R-22, R-404A and R-407C

Part load performance analysis of vapour compression refrigeration system with hydrocarbon refrigerants

International Journal of Research in Engineering and Innovation Vol-2, Issue-2 (2018),

Design & Fabrication of Hybrid Cooler

International Journal of Engineering & Technology Sciences Volume 03, Issue 01, Pages 55-64, 2015

Evaluation of Vapour Compression Refrigeration System Using Different Refrigerants

Effect of magnetic field on the performance of new refrigerant mixtures

REFRIGERATION CYCLE Principles of Mechanical Refrigeration Level 2: Cycle Analysis

INTERNATIONAL JOURNAL OF PURE AND APPLIED RESEARCH IN ENGINEERING AND TECHNOLOGY

Technology Application of Environmental Friendly Refrigeration (Green Refrigeration) on Cold Storage for Fishery Industry

A Review of Hydroflorocarbons (HFC S) Refrigerants as an Alternative to R134a Refrigerant

Due to its low temperature glide about 1.5 approx. (75% less than R-407C and R-427A), it is suitable for a wide range of applications.

Design Procedure for a Liquid Dessicant and Evaporative Cooling Assisted 100% Outdoor Air System

Analysis of Coefficient of Performance & Heat Transfer Coefficient on Sterling Cycle Refrigeration system.

Transcription:

FABRICATION OF REFRIGERANT FLOW RATE WITH SPIRALLY COILED CAPILLARY TUBE PRESENTED BY J.SARAVANA PERUMAL 1 Saravananjsp005@gmail.com D.SATHEESH 2 Satheeshd123@gmail.com Contact no: 9789080381 DEPARTMENT OF MECHANICAL ENGINEERING ADHIPARASAKTHI ENGINEERING COLLEGE MELMARUVATHUR 603319 16

ABSTRACT: This paper represents an experimental investigation about effect of simple and twisted spirally coiled adiabatic capillary tube on the refrigerant flow rate. Several capillary tubes with different inner diameters, lengths and pitches are taken as test sections. An eco-friendly refrigerant; The effect of various geometric parameters like capillary tube diameter, length and coil pitch for different capillary tube inlet subcoolings on the mass flow rate of R-134a through the spiral capillary tube geometry has been investigated. It has been established that the coil pitch significantly influences the mass flow rate of R-134a through the adiabatic spiral capillary tube. The effect of providing pressure taps on the capillary tube surface has a negligible effect on the mass flow rate through the capillary tube. Mass flow rate for different capillary tubes are measured for different degrees of sub cooling with constant inlet pressure of capillary. For comparison, the experiments have also been conducted for straight capillary tube and it has been observed that the mass flow rates in spiral coiled capillary tube are less than those in a straight one where as in twisted spiral coiled capillary tube, refrigerant flow rate is further reduced. KEYWORDS: Spiral Capillary Tube, LPG, Vapour Compression Refrigeration System. INTRODUCTION: The basic vapour compression or mechanical refrigeration cycle relies mainly on process of evaporation by absorbing large amounts of heat and releasing the same through condensation with the circulation of fluid called refrigerant. This heat which must be gained or lost during the change of state is called latent heat of vaporisation. In general, latent heat of vaporisation is more than the specific heat that is the heat lost or gained during a one degree change in temperature. Thus, there in general only two pressures are in principal, within the refrigeration system, which are relative to the evaporating and condensing temperatures which depends on the refrigerant used the temperature of the space to be cooled and the type of application. This difference in pressure is mainly achieved by installing a throttle device either manual or automatic The functions of the such throttling devices is to regulate the flow of high pressure liquid refrigerant from the condenser to a low pressure liquid refrigerant into the evaporator and to 17

maintain a pressure differential between the high and low pressure sides of the refrigeration system which allows the refrigerant to vaporize under the desired low pressure in the evaporator. In capillary, the fall in pressure of the refrigerant takes place not due to the orifice but due to the small opening. It depends on the diameter of the capillary and the length of the capillary. Smaller is the diameter and more is the length of the capillary more is the drop in pressure of the refrigerant as it passes through it. Although the device lacks active function (mechanical or electrical) to actively adjust to any sudden change in the load conditions, it is still in use as a result of its simplicity, low cost and requirement of low compressor starting torque. Capillary length ranges from 400 to 6200 mm thus; capillary tubes are normally folded in various configurations, so as to reduce the required. The flow characteristics of refrigerants through capillary tubes have been studied extensively in past six decades, both experimentally and numerically, most of these studies mainly focused on straight capillary tubes. However in practical applications, if this length is to be kept straight in any installation, a lot of space would be required. As a result, the capillary tubes are normally folded in various configurations, so as to reduce the required space. Since the capillary tube is to be folded in order to reduce the required space, there is the need to study the effect of capillary tube geometry on the performance of refrigeration systems. At the same time, changing cross section of the capillary at certain nodes like twists can also significantly affect the flow through it. Moreover, with the advent of new ecofriendly refrigerants, the studies on coiled capillary tubes with alternative refrigerants become all more important to select appropriate sized capillary tubes for specific applications. Some of the investigations made in earlier decades regarding capillary tubes suggested some of the interesting effects and applications. The effect of coiling on the refrigerant mass flow rate of the refrigerant has been discussed by a few investigators. Kuehl and Goldschmidt (1990) have conducted experiments on the flow of R-22 through adiabatic capillary tubes of straight and coiled geometries. They have concluded that because of the coiling of capillary tube, the refrigerant mass flow rate was reduced by not more than 5%. Kim et al. (2002) have studied the flow of R-22 and its alternatives, 18

viz., R-407C and R-410A through the straight and helically coiled adiabatic capillary tubes. In addition, a numerical model using Mori and Nakayama friction factor correlation Mori and Nakayama, was also proposed. It was concluded that for the mean coil diameter beyond 300 mm, the change in mass flow rate was insignificant. It was also observed that the refrigerant mass flow rate through a helical capillary tube with coil diameter of 40 mm was approximately 10% less than that of the straight capillary tube. Further, Zhou and Zhang confirmed the hysteresis in refrigerant mass flow rate with increasing and decreasing inlet subcooling in an adiabatic helical capillary tube. The hysteresis effect was more prominent in helical capillary tube than that in straight tube due to the disturbance generated from the secondary flows caused by the centrifugal force. It was also found that in the coiled capillary tube the refrigerant flashed earlier with decreased coil diameter as reduction in coil diameter caused the pressure drop to increase However, for validation of the numerical model with the experimental data, the increasing subcooling data should be taken into account due to their consistency and reproducibility. Deodhar have conducted an experimental and numerical investigation on R-134a refrigerant through straight and helically coiled capillary tube. Experiments carried out on helically coiled capillary tubes indicate an increase in resistance to the flow due to coiling. Mass flow rate through a capillary tube of capillary tube of coil diameter of 20 mm is lower by about 9 to 19 percent than that through the straight capillary tube. Park et al. (2007) studied the flow of R-22 and its alternatives, R-407C and R-600, through coiled adiabatic capillary. It been has revealed a slightly higher drop in mass flow rates of the coiled capillary tubes compared to those in straight capillary tubes as reported.. The model for spiral capillary tube is compared with the model for straight capillary tube operating under similar conditions. It has been found that because of coiling the length of the capillary tube is reduced considerably for a given set of conditions. Khan et al. (2008a) investigated the effect of the coiling on the mass flow rate of R-134a in helical capillary tube by varying the coil pitch in the range 20-60 mm for the coil diameter of 140 mm. They observed that the coiling of capillary tube reduces the mass flow rate by 5-15 percent 19

as compared to those of straight capillary tube operating under similar conditions. it also examined the flow characteristics of R- 134a in spiral capillary tube having coil pitch of 20, 40 and 60 mm. They concluded that the mass flow rate in spiral capillary tube is 5-15 percent less than that in straight capillary tube. They also developed a nondimensional correlation to predict the mass flow rate of R-134a in spiral capillary tube. Mittal et al. (2009) proposed a homogenous model for the adiabatic flow of the refrigerant through the spiral capillary tube and the effect of pitch of the spiral on the mass flow rate of refrigerant. A comparison of the flow characteristics of refrigerant R22 and its alternatives. investigates the inlet pressure fluctuations for the coiled adiabatic capillary tubes. It has been found that pressure fluctuation for coiled capillary tubes is much more prominent than for straight ones. With growing environmental hazards, one of the serious threats to the environment is the stratospheric ozone layer depletion. The stratospheric ozone layer plays a beneficial role by absorbing most of the biologically damaging ultraviolet sunlight called UV-B coming towards the Earth. Ozone also plays a key role in the temperature regulation of the Earth s Atmosphere. The ozone depleting compounds (i.e., CFCs and HCFCs) contain reactive gaseous atoms of chlorine or bromine. Although, the CFC and HCFC molecules are heavier than the molecules of air, the atmospheric air-circulation takes these compounds to the stratosphere over a period of time. Thus, in the present environmentally conscious age, it has been pointed out that production, leakage, disposal, etc. of CFCs and HCFCs refrigerants has an adverse effect on our environment by contributing towards ozone layer depletion and green- house effect Thus, due to slow improvement of efficiency and concern for the environment, efforts are now being directed to develop eco-friendly alternative refrigeration systems.. LPG is ozone-safe blend of three hydrocarbons (30% propane, 55% n-butane, 15% iso butane) and exhibits properties similar to that of R12 and there is not any single study reported in literature suggesting the study of flow of LPG through coiled capillary tube. Therefore, in order to strengthen the work of LPG as refrigerant, the present study has been done by different operating conditions and different geometrical parameters of capillary tube. 20

Figure 1: Schematic Diagram of Experimental Setup EXPERIMENTAL SETUP: The experimental facility as shown below consists of a simple vapour compression refrigeration system charged with LPG as a refrigerant. The evaporator and condenser are shell and tube type adiabatic heat exchangers. Refrigerant flows through copper tubes of inside diameter as ¼ inch throughout the condenser, evaporator and connecting lines. All connecting tubes of refrigerant are well insulated by polyurethane cellular foam. Water can flow through the insulated shell of each of the evaporator and condenser and there is an arrangement for control and measurement of water flow rate through 21

each. Hand operated valves and connectors are provided before and after the capillary tube to facilitate its replacement. The temperature of refrigerant at various points is measured with PT-100 (strongly insulated along length of tubes by means of polyurethane cellular foam). Pressure of refrigerant is measured and indicated by separate dial gauges at four points before and after each of the evaporator and condenser. Mass flow rate of refrigerant liquid after condenser is indicated by a glass tube Rotameter fitted in the refrigerant line after condenser. A digital wattmeter gives the instant value of power consumption of compressor and also the total energy consumed during whole trial. PROCEDURE: Spirally coiled capillary tubes as Test sections used in the experimental investigation are used by keeping pitch as area of interest. Three capillary coil diameters i.e., 1.12 mm, 1.40 mm and 1.52 mm are used and three different pitch of the spiral geometry are used. Lengths of capillary tubes used in the experiment are 2.9 m, 3.7 m, and 4.5 m. Different pitches of the spiral shaped are taken as solid, 1 cm, 2cm. The capillaries are provided with twists at 15cm apart along the length to produce twisted test sections of capillaries. This makes total 72 test sections including both simple capillary and twisted type capillary. The pressure at capillary inlet test section is adjusted to 760 KPa. The sub cooling at inlet of capillary are randomly set in the range 1 o C to12 o C. REFRIGERANT USED : A refrigerant is a substance or mixture, usually a fluid, used in a heat pump and refrigeration cycle. Many working fluids have been used for such purposes. where more than 90% of refrigerators are manufactured using R 600a as refrigerant. Because of the availability of isobutane all over the world.it has been discussed widely for CFC replacement. Isobutane R 600a is a possible refrigerant for this application, with good energy efficiency, But with a very different characteristic in several points. The first large difference between R 600a and R 134a or R 12, is found in the pressure level. Thisleads to operating pressures being very much lower than previously common. Evaporators of household refrigerators will thus operate below normal atmospheric pressure. 22

CAPACITY OF THE PLANT: The low pressure level is connected to a relatively high critical temperature. This gives a good cooling capacity even at high condensing temperature. R 600a has roughly 50 % of R 12 or 55 % of R 134a volumetric capacity at 55 C condensing. Temperature of the plant increase Because of this the necessary compressor swept volume will be up to 2 times the swept volume used for R 12. Refrigerant R 600a is mostly used with mineral compressor oils, so material compatibility is almost identical to R 12 situation from oil side. The main disadvantage discussed in connection with R 600a use is the risk based in its flammability. behaviour depends on capillary tube length, capillary tube diameter, capillary tube inlet pressure, degree of sub cooling, cross section of capillary tube and nature of refrigerant. The cumulative effect of coil pitch, capillary tube diameter, inlet sub cooling, twisted nodes and capillary tube length on the refrigerant mass flow rate has been arranged in tabular orientations as shown: EFFECT OF CAPILLARY TUBE LENGTH AND SHAPE OF CAPILLARY ON MASS FLOW RATE: RESULT AND DISCUSSIONS: The refrigerant mass flow rate in capillary tubes and its thermo-fluid-dynamic 23

The length of the capillary tube has a significant impact on the mass flow rate of the refrigerant across cycle. It can be found that when the length of the capillary of a particular diameter is increased, mass flow rate decreases, refer fig., 1.1 at a constant inlet pressure and sub cooling rate. Also, when straight capillary tube is shaped spirally, the mass flow rate of the system falls which can be futher reduced by providing locational twists across the length of the capillary tube. This is mainly caused due to increase in frictional resistance across the capillary length. For the capillary diameter 1.12mm and length 2.9 m of simple straight capillary, the mass flow rate is decreased by 4.3%, 8.6 % and 15.13%, when these are turned into spiral shape of pitches 2mm, 1mm and 0mm respectively. Similarly, for length 3.7m a fall of 2.43%, 7.14% and 14.28% in mass flow rate is recorded. To verify the behaviour of mass flow rate, another capillary length 4.5m, is subjected to similar operating parameters and an overall decrease of 2.83%, 5.67% and 11.34% was found, this shows the effect of spiral geometry of capillary. This is mainly due to action of centrifugal force acting along the spiral shape of the capillary. For the capillary diameter of 1.40mm and length 2.9m straight capillary and spiral capillaries of pitches 2mm,1mm and 0mm, the mass flow rate decreased by 2.57%, 2.82% and 4.41% respectively. Similarly, for capillary of length 3.7m and diameter 1.40mm, the mass flow rate is reduced by 1.54%, 3.045% and 4.76%, when compared to straight capillary respectively. For the capillary tube of length 4.5m, mass flow rate is reduced by 4.56%, 5.08% respectively, when the straight capillary is turned into spiral shape. When capillary tube of 1.52mm is taken of different lengths and diameter are 24

moulded into spiral shape from straight, significant reduction in mass flow rate is found as compared to straight capillary. For, capillary length 4.5m in such a capillary, mass flow rate reduces to 1.91%, 2.83% and 2.85% respectively, when straight capillary is turned into spiral capillary of 2mm pitch, 1mm pitch and zero pitch respectively. A similar approach was taken for twisted straight capillary tube having same diameters and lengths as shown in fig., 1.2. A decrease of 11.4% and 14.5% was recorded on increasing the length from 2.9m to 3.7m and 4.5m respectively for capillary diameter 1.12mm. For a capillary tube diameter of 1.40mm, decrease of 11.3% and 8.46% is found respectively. In case of capillary size 1.52mm, 10.48% and 3.52% fall in mass flow rate is recorded when increasing the length from 2.9m to 3.7m and 4.5m respectively. Also, the mass flow rate decreases further when the straight capillary with twist is moulded into spiral shape as discussed above in case of capillaries without twisted nodes. A comparison is shown in fig. 1.3 with straight capillary of dia. 1.52mm without any twist and with twist. It has been found that the effect of twists has a greater influence on mass flow rate as compared to simple capillary tube. While increasing the length from 2.9m to 3.7m, mass flow rate decreases to 8.61% in case of simple straight capillary tube which is further more reduced to 13.80% when the same capillary is provided twisted nodes across the length of capillary. Similarly, when the same capillary is turned into spiral shape, an overall reduction of 19.4% is found when twisted capillary is further turned to spiral shape. A similar approach was taken for twisted straight capillary tube having same diameters and lengths as shown in fig., 1.2. A decrease of 11.4% and 14.5% was recorded on increasing the length from 2.9m to 3.7m and 4.5m respectively for capillary 25

diameter 1.12mm. For a capillary tube diameter of 1.40mm, decrease of 11.3% and 8.46% is found respectively. In case of capillary size 1.52mm, 10.48% and 3.52% fall in mass flow rate is recorded when increasing the length from 2.9m to 3.7m and 4.5m respectively. Also, the mass flow rate decreases further when the straight capillary with twist is moulded into spiral shape as discussed above in case of capillaries without twisted nodes. diameters, mass flow rate decreases. Smaller is the capillary tube diameter more is the percentage decrease in mass flow rate. Therefore, for a given compressor capacity, length of the capillary can be optimised so as to save the material of the capillary and a more compact unit. A comparison is shown in fig. 1.3 with straight capillary of dia. 1.52mm without any twist and with twist. It has been found that the effect of twists has a greater influence on mass flow rate as compared to simple capillary tube. While increasing the length from 2.9m to 3.7m, mass flow rate decreases to 8.61% in case of simple straight capillary tube which is further more reduced to 13.80% when the same capillary is provided twisted nodes across the length of capillary. Similarly, when the same capillary is turned into spiral shape, an overall reduction of 19.4% is found when twisted capillary is further turned to spiral shape. It has been concluded from above graphical representations that with increase in length of capillary tubes irrespective of internal Also, compressor capacity can be lowered for a particular length of capillary tube in order to minimize the power required to drive the unit. Further, use of locational twisted capillary tube can further decrease mass flow rate through the refrigeration 26

system and can be applied for more material and power savings as suggested earlier as shown in fig., 1.3. on smallest capillary tube diameter i.e. EFFECT OF RADIAL PITCH ON MASS FLOW RATE THROUGH THE CAPILLARY TUBE: The spiral shaped capillary tube has a significant effect on the mass flow rate when compared with straight capillary test section. So, the effect of radial pitch on the spiral geometry derives interest towards next area of investigation in this experiment. Different test sections of spiral geometry are fabricated and the radial pitch is taken as zero, 1cm and 2cm cm respectively. The length of the capillaries is taken as 4.5m, 3.7m and 2.9m. It has been observed from experimental investigation that mass flow rate through spiral capillary tube rises on increasing the radial pitch as shown in fig., 2.1. The effect of pitch is found maximum 1.12mm and goes on decreasing when larger capillary diameters are taken as 1.40mm and 1.52mm in this experiment. Thus, pitch of the spiral geometry can be significantly adjusted so as to decrease the mass flow rate through the cycle providing the same pressure difference across the capillary. Thus, a smaller compressor unit is to be implied for spiral geometries having lower radial pitch resulting to be more energy efficient. 27

Also, on capillary having locational twists the mass flow rate is lesser through the capillary as compared to the normal spiral capillary tube. At the same time mass flow rate of the locational twisted capillary tube also increases on increasing the radial pitch of the spiral capillary. For a capillary of dia. 1.12mm, with locational twists, mass flow rate increases to 2.2% and 5.6% for an increase in pitch from 0 to 1cm and 2cm, which are less in percentage rise as compared to non twisted capillary tube as shown in fig., 2.2. On increasing the radial pitch of spiral capillary of dia.1.12mm and length 4.5m from 0cm to 1 cm, the mass flow rate across the capillary is found to be increased by 9% which further increases to 11.2% if radial pitch is increased to 2cm. Similarly, for spiral capillary tube of length 4.5m and dia. 1.40mm, the mass flow rate increases by 5.1% and 6.8% respectively for radial pitches 1cm and 2cm respectively. For a capillary tube of dia. 1.52mm and length 4.5m, spirally shaped, effect of increasing radial pitch to 1cm and 2 cm is investigated to be 2.8% and 5.4% respectively. EFFECT OF CAPILLARY DIAMETER ON MASS FLOW RATE : It has been observed that with the increase in capillary diameter, mass flow rate of the refrigerant also increases. This is mainly due to the lesser contact of the capillary walls with the refrigerant flow as the passage area increases. The above fig.3.1 shows that mass flow rate through the cycle increases when diameter of capillary is increased. For the capillaries of length 4.5m in this experimental work, mass flow rate increases to 35.68% when the diameter of the capillary is increased from 1.12mm to 1.40mm. If the capillary diameter is raised 28

to 1.52mm, the mass flow rate is enhanced by 47%. For capillary of length 3.7m, the mass flow rate is enhanced by 39% and 49%, when the diameter of the capillary is increased from 1.12mm to 1.40mm and 1.52mm respectively. It has been observed that effect of diameter is more prominent in the smaller capillary lengths. While increasing the same diameter proportions, a 39% and 51% increase in mass flow rate is accompanied with the capillaries of length 2.9m. CONCLUSIONS: 2. The refrigerant flow rate across the capillary can be increased up to 52% by increasing the capillary diameter from 1.12mm to 1.52mm using different lengths with LPG as working fluid. REFERENCES: 1. Bolstad, M.M., Jordan, R.C., 1948. Theory and use of the capillary tube expansion device. Refrigerating Engineering, 519-523. The whole experiment is concluded as: 2. Dean, W.R., 1927. Note on the motion of fluid in a curved pipe. Phil. Mag. 4, 208-223. 1. While using LPG as a refrigerant; mass flow rate across capillaries of different lengths and diameters can be decreased up to 12% by turning the straight capillary into spiral shape having radial pitch ranging from zero to 2cm. This mass flow rate is further reduced up to 18% by providing the locational twists (15cm apart) along the length of capillary. 3. Khan, M.K., Sahoo, P.K., Kumar, R., 2008a. Experimental study of the flow of R-134a through a adiabatic helical coiled capillary tube. HVAC&R Res. 14(5), 749-762. 4 Khan, M.K., Sahoo, P.K., Kumar, R., 2008b. An experimental study of the flow of R-134a inside inside an adiabatic spirally coiled capillary tube. International Journal of Refrigeration 29

31(6), 970-978. 5. Kuehl, S.J., Goldschmidt, V.W., (1990). Steady flows of R-22 through capillary tubes: test data. ASHRAE Trans. 719-728. 6. Milkol, E.P., 1963. Adiabatic single and two-phase flow in small bore tubes. ASHRAE Journal, 75-86. 30