Prefco Series 5000 Damper Motor Replacement with Belimo FS Series Actuators

Similar documents
Replacement of Safe-Air Honeywell ML & MS Motors with Belimo FSNF120 Series

WARNING! Before replacing actuator, damper must be inspected and determined to be fully functional. See NFPA 80 & NFPA 105 below for recommendations.

Ruskin Honeywell ML & MS to Belimo Replacement Instructions

WARNING! Before replacing actuator, damper must be inspected and determined to be fully functional.

INSTRUCTION SHEET - Replacement of Ruskin Phillips P150 to Belimo FSNF or FSAF Actuator

Replacement of pneumatic actuators on Ruskin negator spring dampers with Belimo FSxx Series

Access door These are required for maintenance of fire and smoke dampers and duct smoke detectors.

Belimo Quality Oriented Safety in Buildings

1-300 Fire and/or Smoke Dampers to Inspect $ Fire and/or Smoke Dampers to Inspect $34.30

SECTION AIR DUCT ACCESSORIES

MANUAL RESET ALARM RELEASE

MANUAL RESET ALARM RELEASE

COMBINATION FIRE/SMOKE DAMPERS

Fire, Smoke and Control Dampers

Fire Smoke Damper Actuator Replacements SECTION COMMISSIONING OF HVAC

Firefly II Multi Voltage RELEASE DEVICES. Firefly II & IIB-MV INSTALLATION MANUAL

WHEN IT COMES TO FIRE / SMOKE DAMPERS, NAILOR S 1220 SERIES THE WALL PROVIDES THE ULTIMATE CLOSURE!

Life Safety Dampers Selection and Application Manual

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number:

RELEASE DEVICES RELEASE DEVICE-WPS MODELS A/B INSTALLATION MANUAL U.L. LISTED CANADIAN LISTED CSFM: :100 GENERAL DESCRIPTION:

RELEASE DEVICE CONTROLS

AIR DISTRIBUTION. C. Section Building Automation and Control System Guidelines. D. Section Fire Alarm System & Detection Systems

WHEN IT COMES TO FIRE / SMOKE DAMPERS, NAILOR S 1220 SERIES THE WALL PROVIDES THE ULTIMATE CLOSURE!

SERVICE MANUAL VC3ED FULL SIZE ELECTRIC CONVECTION OVEN - NOTICE -

INSTALLATION & MAINTENANCE CORNELL FIREGARD CHAIN & ES ECO #1515 REVISION # 0000 FIREGARD CRANK OPERATORS BY: RICKM DATE: 3/23/2011

SOLID STATE SECURITIES, INC. THE "SS90" SERIES RELEASE DEVICES MADE IN THE U.S.A. SS90-WPS MODEL A/B INSTALLATION MANUAL

FIREFLY II PLUS RELEASE DEVICES INSTALLATION MANUAL

MODEL B2 INSTALLATION MANUAL

SECTION (15820) - AIR DUCT ACCESSORIES

ANSUL ANSUL AUTOMAN II-C RELEASING DEVICE

FAN POWERED VAV TERMINALS

MADE IN THE U.S.A. MODELS A/B INSTALLATION MANUAL

THE "SS90" SERIES RELEASE DEVICES MADE IN THE U.S.A. MODELS A/B INSTALLATION MANUAL

AUTO RESET ALARM RELEASE BOX MODEL AR-C INSTRUCTION MANUAL

"SS90" SERIES CONTROLS MODEL C INSTALLATION MANUAL

Hand Chain (Model FCF) &

THE "SS90" SERIES RELEASE DEVICES MODEL B2 INSTALLATION MANUAL

YP7999A1000 ControLinks Fuel Air Ratio Control Panel

ENGINEERING SPECIFICATIONS FOR FM-200 CLEAN AGENT INDIRECT PRE-ENGINEERED FIRE SUPPRESSION SYSTEMS

15900 HVAC INSTRUMENTATION AND CONTROLS

SMOKE DAMPERS SMOKE DAMPERS

SMOKE DAMPERS AIRFOIL STAINLESS STEEL

INSTALLATION INSTRUCTIONS AND OPERATION MANUAL. FT-EPB Series. Single Motor

COMBINATION FIRE/SMOKE DAMPERS

MADE IN THE U.S.A. ADVANCE FIRE CONTROL MODEL LM21-AFC MANUAL RELEASE DEVICES TEST WEEKLY TO ASSURE PROPER OPERATION OF RELEASE DEVICE/CONTROL PANEL

WARNING. Installation Tip: Try out this unit before installing onto a fire door system. Test and learn the release INTRODUCTION

Powers Controls Low Temperature Detection Thermostat

ACSI AO ELECTRIC LATCH RETRACTION CONTROLLER INSTALLATION INSTRUCTIONS I.D. 1089, REV. F

SECTION KITCHEN HOOD AND DUCT FIRE SUPPRESSION SYSTEM

Updated: September 12, 2018 DIVISION INTEGRATED AUTOMATION. INTEGRATED AUTOMATION Page 1 of INTEGRATED AUTOMATION

KITCHEN HOOD AND DUCT FIRE SUPPRESSION SYSTEM

52 CEILING FAN READ AND SAVE THESE INSTRUCTIONS FAN RATING AC 120V.

Louvers & Dampers April Product Guide Specification SECTION COMBINATION FIRE SMOKE DAMPERS

Powers Controls ET 134 Low Temperature Detection Thermostat

A. AMERICAN ARCHITECTURAL MANUFACTURERS ASSOCIATION (AAMA) 101: Appendix Dissimilar Materials.

SERVICE PARTS/OPERATION for

COMBINATION FIRE/SMOKE DAMPERS

MODEL FPT-130 SINGLE POINT FREEZE PROTECTION HEAT TRACE CONTROL

B. Product Data: Provide manufacturers catalogue information. Indicate valve data and ratings.

A U TO S M O K E. Model AUTO SMOKE FIRE SHUT Flat Slats Fire Shut Rolling Doors

Reproduction or other use of this Manual, without the express written consent of Vulcan, is prohibited.

SPECIFICATION DELETED SECTION CENTRIFUGAL HVAC FANS

Construction Standards Page Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA

SPX SERIES PACKAGED AIR CONDITIONING/HEAT PUMP UNITS INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS

MANUAL RESET ALARM RELEASE BOX

Guide Spec Summary. Option List. Date: 05/21/2001. EarthWise VAV Terminal Units Full Spec. Prepared by: Phone Number: Prepared for:

INSTRUCTION MANUAL. AlarmGard Chain Operator (Model FCA) AlarmGard Crank Operator (Model FKA)

SECTION (15900) - INSTRUMENTATION AND CONTROL FOR HVAC

Model 17A00 Expansion Enclosure

INSTALLATION INSTRUCTION BOOKLET FOR SMOKE DAMPERS

DETEX ARCHITECTURAL SPECIFICATIONS, June 2012 AO19 SERIES HEAVY DUTY LOW-ENERGY ELECTRIC SWING DOOR OPERATOR

! WARNING. Replacement Head Mechanism INSTRUCTION MANUAL MM-413F

Easy installation in both new construction and retrofit. READ AND SAVE THESE INSTRUCTIONS Installer: leave this guide with homeowner.

UHIR Series. Horizontal or Vertical Mounting Industrial / Commercial Electric Unit Heater. Owner s Manual

SERVICE AND INSTALLATION MANUAL MODELS HDO(H) OIL FOR YOUR SAFETY

Installation Instructions

The Extraordinaire OWNER S MANUAL. Orbital Ceiling Fan. Model No. OF110** READ AND SAVE THESE INSTRUCTIONS. Net Weight 14.5 lbs. or 6.59 kg.

Fire Alarm Acceptance Testing & On-Going Maintenance with The Joint Comm. Standards / Reporting. Prepared Especially for : OSFM TEC 2016

RV Products Division INSTALLATION INSTRUCTIONS FOR SERIES PACKAGE AIR CONDITIONER

TRUSTY PRODUCTS, INC.

FIRE & SMOKE DAMPERS. Meeting tomorrow's requirements for fire and smoke protection today.

Single Point Freeze Protection Heat Trace Control TRACON MODEL FPT 130 Installation and Operation Manual

52 Lacey LED. Instruction Manual. 6 Speed DC Wall Control System

3MAVR60XX Series Fan. Owner s Guide and Installation Manual. UL Model NO. : 3MAVR60XX

T4031A,B,P; T6031A,B Refrigeration Temperature Controllers

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 11/06/2018

Installation Instructions Part No , Part No Part No

Pipe Freeze Protection Control SCFP-CO-F130 Installation and Operation Manual

INSTRUMENTATION AND CONTROL DEVICES FOR HVAC

ELECTRONIC FIREPLACE DAMPER

Viking Installation Guide

1. SAFETY RULES WARNING WARNING. 8. Avoid placing objects in the path of the blades.

TABLE OF CONTENTS GENERAL... 2 A. DEFINITIONS DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2

COMBINATION FIRE/SMOKE DAMPERS

UP (run) position for normal operation of the damper. For details on the use of the Test/Run switch, see Troubleshooting Procedure.

5COM52XXD Series Fan. Owner s Guide and Installation Manual. UL Model NO. : 5COM52XXD

Maintenance 5-1. Good maintenance is essential for cleaning results, and long economical life of the washer.

LED. 60 StarkkTM. Instruction Manual. A Kichler Select ceiling fan

ELECTRONIC FIREPLACE DAMPER

Fire, Smoke, and Combination Fire Smoke Dampers

Transcription:

WARNING! Before replacing actuator, damper must be inspected and determined to be fully functional. See NFPA 80 & NFPA 105 below. Prefco Series 5000 Damper Motor Replacement with Belimo FS Series Actuators Contents UL... 2 Code and Standard Issues... 2 NFPA 80 (Fire) & NFPA 105 (Smoke)... 3 Local Code Approval... 4 Cross Reference... 4 Prefco McCabe Link... 8 Prefco or PHL 5800, MB2, MB3, EM2X, & others... 9 Cable-pully applications... 11 Prefco Series 5000 Dampers... 13 Mounting... 14 Replacement Instructions Series 5000 and 5100 Dampers... 15 Linkage mounting... 20 Miscellaneous parts... 22 Wiring... 24 Auxiliary Switches... 27 Blade Position Indication Switches... 28 Building Official / Fire Marshal Notification Form... 29 Contacts: Chris Sheehan 203 749-3112 Larry Felker 775 355-2461 (775 250-4160 Cell) Mike Knipple 203 749-3170 Laure Pomianowski 775 355-2466 800 543-9038 WARNING! Installer must be trained and experienced with repair of fire and smoke dampers and actuators. www.belimo.us/firesmoke Prefco Series 5000 Replacement with Belimo FS Series Actuators March 2018 1

UL In the Marking & Application Guide, Dampers for Fire Barrier and Smoke Applications & Ceiling Dampers April 2013 by Underwriters Laboratories Inc., page 6 they state: DAMPER ACTUATORS field mounting or substitution of actuators is not covered within the scope of the UL certification of the product. However, this does not necessarily preclude replacement of actuators in the field. Like any appliance, field servicing of these products is not covered under the scope of the UL certification and factory follow-up service program. As with any part of the damper, it is expected that replacement of actuators in the field be done in accordance with the damper manufacturer s normal field servicing program. Code and Standard Issues In general, the administrative section of codes state that all mechanical and electrical systems must be kept in working order and an individual section may state that all life safety devices and systems must be operable. NFPA 80 (Fire) & NFPA 105 (Smoke) require periodic testing and repair of dampers as soon as possible after any deficiency is uncovered. Chapter 7 IBC & IFC "Containment Dampers Commissioning End of first year Every 4 years except in hospitals every 6 years Chapter 9 IFC "Smoke Control System Dampers Dedicated Non-dedicated Commissioning Commissioning Semi-annually Annually Chapter 9 IBC & IFC Fire detection & Smoke control systems Dedicated Non-dedicated Weekly self-test Not required Fire & smoke dampers are appliances and field replacement of components is required when failure of any component occurs. The Authority Having Jurisdiction (local Fire Marshal and/or Building Official) must be consulted if any blade or auxiliary switches are employed and are connected to the fire alarm system or to a Fire Fighters Smoke Control System (FSCS) panel. Retesting is required. A permit and inspection may be required since connections to an alarm system have been touched. Prefco Series 5000 Replacement with Belimo FS Series Actuators March 2018 2

NFPA 80 (Fire) & NFPA 105 (Smoke) NFPA requires damper inspection and repair of dampers. See www.nfpa.org. for Standards. See NFPA 80 & NFPA 105 for details. The damper cleaning and examination check list here is based on them. Damper installation shall meet code requirements. Fire stopping and drywall integrity shall be confirmed. Damper blades shall be in plane of wall. Duct shall be fall away with no fasteners connected to damper sleeve. a. Dampers and ducts shall be cleaned of all foreign debris and dust build-up. b. All exposed moving parts of the damper shall be dry lubricated as required by the manufacturer. Do not use oil as it draws dirt. c. Damper shall be examined without defective old motor or new actuator to determine: i. The damper shall fully close from the open position. ii. Damper shall fully open from the closed position. iii. There are no obstructions to the operation of the damper. The damper shall not be blocked from closure in any way due to rusted, bent, misaligned, or damaged frame or blades. The damper shall not have defective hinges, side &/or blade seals, or other moving parts. The damper frame shall not be penetrated by any foreign objects that would affect operation. d. If the damper is equipped with a fusible link, the link shall be removed for testing to ensure full closure and lock-in-place if so equipped. If the link is damaged or painted, it shall be replaced with a link of the same size, temperature, and load rating. e. The fusible link shall be reinstalled after testing is complete. After installation and wiring of new actuator it shall be tested. a. The checklist may be customized using material here and in NFPA Standards. Multiple geometric configurations of springs, fusible link, thermal sensor(s), and actuation are possible. Confirm with AHJ if any additional requirements exist. b. Electric thermal sensors, if present, must be tested and replaced if defective. c. The test shall be conducted with normal HVAC airflow. d. When equipped with smoke detection activation, the smoke detector shall be activated and damper operation observed. Test voltage input to actuators and repair as necessary if voltage is not correct. Old breakers often deliver below 115V and failed actuators may be due to power supply problems. A record of all repairs must be kept and made available to AHJ. For the Air Movement and Control Association damper maintainance manual go to: http://www.amca.org/publications/damper_maintenance.aspx Prefco Series 5000 Replacement with Belimo FS Series Actuators March 2018 3

Local Code Approval While it is not detailed in codes, the following rules should be followed for selecting Belimo actuators for replacement: Check the technical specifications to ensure an equal or better actuator is used. Temperature the replacement actuator shall have been UL555S tested at the same or better temperature as the original actuator. 250 F or 350 F are standard. (Code is 250 F. However, in engineered smoke control systems the consulting engineer may have required 350 F. Tunnels and some other applications require higher temperatures.) Time the replacement actuator shall drive open and spring closed at a speed equal or faster than presently required by codes. (<75 seconds is UL 555S and most codes. Las Vegas is 60 seconds. Consult the AHJ with any questions.) Torque replacement actuator shall have equal or greater torque than the failed actuator. Voltage replacement actuator shall have the same voltage rating as the original. Amperage the replacement actuator(s) shall not draw more amperage than the original(s) and cause the total connected amp draw on a circuit breaker to be greater than allowed by electrical code. (This is not a problem as Belimo actuators draw very low current.) Final Testing actuated damper and associated devices shall be tested for proper operation. See Acceptance testing details below. (Mnemonic device: TTT-VAT) WARNING! Note that where any fire alarm wiring is touched, the fire department must be informed. WARNING! In all cases, installation must comply with any and all local electrical and life safety codes. Operation of the system after installation must be performed to verify proper damper cycling. Final checkout requires verifying correct function. Prefco Series 5000 Replacement with Belimo FS Series Actuators March 2018 4

Cross Reference For greater detail see www.belimo.us/firesmoke RETROFIT or download from https://www.belimo.us/mam/americas/technical_documents/pdfweb/fire_and_smoke_doc/fire_smoke_competitive_replacement_data_reference.pdf Honeywell Voltage Control Torque Aux Replacement ML4105A1000 120 VAC On/Off 30 FSLF120 US * ML4105B1009 120 VAC On/Off 30 FSLF120 US * ML4105C1008 230 VAC On/Off 30 FSLF230 US * ML4105D1007 230 VAC On/Off 30 FSLF230 US * ML4115A1009 120 VAC On/Off 30 FSLF120 US * ML4115A1017 120 VAC On/Off 30 FSLF120 US * ML4115B1008 120 VAC On/Off 30 FSLF120 US * ML4115B1016 120 VAC On/Off 30 FSLF120 US * ML4115C1007 230 VAC On/Off 30 FSLF230 US * ML4115C1015 230 VAC On/Off 30 FSLF230 US * ML4115D1006 230 VAC On/Off 30 FSLF230 US * ML4115D1014 230 VAC On/Off 30 FSLF230 US * ML4115H1002 120 VAC On/Off 30 FSLF120 US * ML4115J1019 120 VAC On/Off 30 FSLF120 US * ML4202F1000 120 VAC On/Off 20 FSLF120 US * ML4202F1000 120VAC On/Off 20 FSLF120 US * ML4302F1008 120 VAC On/Off 20 FSLF120 US * ML8105A1006 24 VAC On/Off 30 FSLF24 US * ML8105B1005 24 VAC On/Off 30 FSLF24 US * ML8115A1005 24 VAC On/Off 30 FSLF24 US * ML8115A1013 24 VAC On/Off 30 FSLF24 US * ML8115B1004 24 VAC On/Off 30 FSLF24 US * ML8115B1012 24 VAC On/Off 30 FSLF24 US * ML8115H 24 VAC On/Off 30 FSLF24 US * ML8115J 24 VAC On/Off 30 FSLF24 US * ML8202 24 VAC On/Off 20 FSLF24 US * ML8302 24 VAC On/Off 20 FSLF24 US * MS4104F1010 120 VAC On/Off 30 FSLF120 US * MS4104F1210 120 VAC On/Off 30 2 FSLF120-S US * MS4109F1010 120 VAC On/Off 80 FSNF120 US MS4109F1210 120 VAC On/Off 80 2 FSNF120-S MS4120F1006 120 VAC On/Off 175 FSAFA120 MS4120F1204 120 VAC On/Off 175 2 FSAF120A-S MS4209F1007 120 VAC On/Off 80 FSNF120 US MS4309F1005 120 VAC On/Off 80 FSNF120 US Prefco Series 5000 Replacement with Belimo FS Series Actuators March 2018 5

MS4604F1010 230 VAC On/Off 30 FSLF230 * MS4604F1210 230 VAC On/Off 30 2 FSLF230-S * MS4609F1010 230 VAC On/Off 80 FSNF230 MS4609F1210 230 VAC On/Off 80 2 FSNF230-S MS4620F1005 230 VAC On/Off 175 FSAF230A MS4620F1203 230 VAC On/Off 175 2 FSAF230A-S MS4709F1014 230 VAC On/Off 80 FSNF230 US MS4809F1012 230 VAC On/Off 80 FSNF230 US MS7520A2015 24 VAC 2-10V, 4-20mA 175 FSAFB24-SR US MS8104F1010 24 VAC On/Off 30 FSLF24 * MS8104F1210 24 VAC On/Off 30 FSLF24 * MS8109F1010 24 VAC On/Off 80 FSNF24 MS8109F1210 24 VAC On/Off 80 2 FSNF24-S MS8120F1002 24 VAC On/Off 175 FSAF24A MS8120F1200 24 VAC On/Off 175 2 FSAF24A-S MS8209F1003 24 VAC On/Off 80 FSNF24 US MS8309F1001 24 VAC On/Off 80 FSNF24 US S20230-F 230 VAC On/Off 175 FSAF230A S20230-F-SW2 230 VAC On/Off 175 2 FSAF230A-S S2024-F 24 VAC On/Off 175 FSAF24A S2024-F-SW2 24 VAC On/Off 175 2 FSAF24A-S SPH2 Aux Switch ** 32003532-002 Aux Switch ** * Use FSNF series if damper is > 4 sq.ft. ** Use -S model of proper voltage. Nominal sq.ft. per UL555S testing. Temp Actuator <4 350 F FSLF 36 w x 24 h also. <12 350 F FSNF Multisections also. <16 250 F FSNF Multisections also. <18 350 F FSAF*A Multisections also. The FSTF series actuators were introduced in 2013. They are 18 in-lb and designed for under 1.5 sq.ft. of fire and smoke damper. Use on larger dampers only when replacing an existing FSTF on a fire and smoke damper. The FSLF is recommended for small dampers. Belimo actuators pass UL555S at the same damper sizes as the Honeywell. NOTE. Although an actuator may operate a larger sized damper use the UL listed sizing. Call for assistance. Prefco Series 5000 Replacement with Belimo FS Series Actuators March 2018 6

Barber Colman-Siebe Invensys Siebe/Barber Coleman Power Torque Aux Switches Belimo Notes MA220 120 VAC 30 FSLF120 US 1, 2, 4 MA221 240 VAC 30 FSLF230 US 1, 2, 4 MA223 24 VAC 30 FSLF24 US 1, 2, 4 MA230 120 VAC 50 FSNF120 US 1, 2, 3 MA231 240 VAC 50 FSNF230 US 1, 2, 3 MA233 24 VAC 50 FSNF24 US 1, 2, 3 MA240 120 VAC 50 5,6 MA250 120 VAC 50 FSNF120 US 1, 2, 3, 4 MA251 230 VAC 50 FSNF230 US 1, 2, 3, 4 MA253 24 VAC 50 FSNF24 US 1, 2, 3, 4 MA-318 24 VAC 60 FSNF24 US 1, 3 MA-318-500 24 VAC 60 1 FSNF24 -S US 1, 3 MA-418 120 VAC 60 FSNF120 US 1, 3 MA-418-500 120 VAC 60 1 FSNF120-S US 1, 3 Direct couple the Belimo where shaft is available. 1 Some were direct coupled.. FSTF <1.5 sq.ft. FSLF <4 2 sq.ft. 3 FSNF <12 sq.ft. FSAF*A <18 sq.ft. 4 For Pottorff with shaft spring see: https://www.belimo.us/mam/americas/technical_documents/pdfweb/fire_and_smoke_doc/pottorff-ma2xx_to_belimo.pdf 5 Motor was not 90 degree and pulley and cable were usually used. Some geometric changes are necessary to simplify. 6 Provide photos. Motor, linkage, blades, fusible link, McCabe Link, Typically direct couple to damper shaft if available. Otherwise, investigation necessary. Prefco Series 5000 Replacement with Belimo FS Series Actuators March 2018 7

Prefco McCabe Link McCabe Link dampers are covered in detail in a separate document. See www.belimo.us/firesmoke or http://www.belimo.us/cms/sh/firesmoke/retrofit.php Siemens Make & Model Power Belimo Replacement GGD121 24 FSAF24 FSNF24 GGD221 120 FSAF120 FSNF120 GGD321 230 FSAF230 FSNF230 GND12x.1x 24V FSLF24 GND22x.1x 120V FSLF120 GND32x.1x 230V FSLF230 Electronic Fuse Link (24 Vac) ASK79.165 165 F (74 C) ASK79.212 212 F (100 F) ASK79.250 250 F (121 C) ASK79.350 350 F (177 C) BAE165 US None. Call if needed. None. Call if needed. None. Call if needed. Optional Two Auxiliary Switches Fixed 5 and 85 Prefco Series 5000 Replacement with Belimo FS Series Actuators March 2018 8

Prefco or PHL 5800, MB2, MB3, EM2X, & others In all cases disconnect external motor spring without compromising fusible link and internal spring ability to close the blades. These are quite old and changes may have been made over the years. Investigate operation. Confirm voltage. Check fusible links or McCabe Link. Verify damper functions after replacement by testing damper open and spring closed. Use of FSLF is recommended for dampers less than 4 sq.ft. For linkage applications all FSTF & FSNF parts can be used. FSTF if less than 1.5 sq.ft. FSLF from 1.5 to 4 sq.ft. FSNF up to 10 sq.ft. Use -S models if auxiliary switches are required. 5800EMB2XPO FSLF120 5800EMB2XPC FSLF120 5800EMB1 FSLF120 5800EMB1 - Outside the duct, top mount, power open 5800EMB7 FSLF120 5800EMB7 - Inside the duct, bottom mount, power closed 5800EMB10 FSLF120 5800EMB10 - Outside the duct, bottom mount, power closed 5800EMB5 FSLF120 5800EMB5 - Inside the duct, top mount, power open 5800EMB8 FSLF24 5800EMB9 FSLF120 While direct coupling is preferable, some applications require linkages. See Linkages below for an example of a FSTF linkaged to a Prefco internally. Model Voltage Notes 2430 120VAC 2553A 120VAC 1 2585 120VAC 2 2659 120VAC 3 2724 120VAC 4 2781 24/120 VAC 5 2814A-SQ 120VAC 6 2814-SQ 120VAC 7 2920 120VAC 8 2985 120VAC 9 2986 120VAC 10 3158 120VAC 11 3159 120VAC 12 5983 120VAC 13 6247 120VAC 14 MZRHM 120VAC 15 TB2000/1 120VAC 16 All 120V, FSLF120 Nailor 5953 5949 M12, MZRHM 6247 5186 Prefco Series 5000 Replacement with Belimo FS Series Actuators March 2018 9

1 Square shaft inserted into damper sleeve with special crankarm. If a smoke damper, replacement may be possible and requires a new shaft and other linkage parts. If a combination fire and smoke damper, Belimo may not be capable of being used. See Air Balance with MP2553. 2 Typically these were linkaged using a crank arm on the square motor shaft and the spring was on the round shaft. Remove all linkage parts and direct couple to damper shaft. 3 Safe-Air / Imperial. Typically linkaged. There was an internal spring and fusible link for the fire function. 4 Except in rare occasions where space constraints exist, simply remove all linkage parts and direct couple on damper shaft. Use old motor as a mounting platform for anti-rotation strap 5 Usually on a Negator Spring damper. For pneumatic, the FSLF120 will usually work. For electric, the Ruskin kit FSLF120/MP must be ordered from a Ruskin rep. 6 10 in-lb. "A" model = CW rotation; plain = CCW. Check voltage. FSLF replaces both in most cases. Use FSTF when linkages necessary 7 10 in-lb. "A" model = CW rotation; plain = CCW. Check voltage. FSLF replaces both in most cases. Use FSTF when linkages necessary. 8 Inside clamp mounting or a shaft extension required. 9 See Greenheck Installation Instructions. Typically these were linkaged using a crank arm on the square shaft and the spring was on the round shaft. Remove all linkage parts and direct couple to damper shaft. 10 See Greenheck Installation Instructions. Typically these were linkaged using a crank arm on the square shaft and the spring was on the round shaft. Remove all linkage parts and direct couple to damper shaft 11 Some were direct coupled to the damper shaft with an external spring. Some were linkaged using a crank arm on the square motor shaft and the spring was on the round shaft. Remove all linkage parts and direct couple. 12 Some were direct coupled to the damper shaft with an external spring. Some were linkaged using a crank arm on the square motor shaft and the spring was on the round shaft. Remove all linkage parts and direct couple. 13 https://www.belimo.us/mam/americas/technical_documents/pdfweb/fire_and_smoke_doc/nailor_multiproducts_to_belimo_fs_instructions.pdf 14 Nailor. Remove linkage parts and mount to damper shaft. FSLF for dampers < 4 sq.ft. and FSNF for dameprs > 4 sq.ft. 15 Nailor. Remove linkage parts and mount to damper shaft. FSLF for dampers < 4 sq.ft. and FSNF for dameprs > 4 sq.ft. 16 Typically these were linkaged using a crank arm on the square motor shaft and the spring was on the round shaft. Remove spring and all linkage parts and direct couple to damper shaft. Prefco Series 5000 Replacement with Belimo FS Series Actuators March 2018 10

(TYPICAL) Most Multiproducts motors 5800 and EM2X and the like are covered in other installation documents at www.belimo.us/firesmoke or http://www.belimo.us/cms/sh/firesmoke/retrofit.php Cable-pully applications www.belimo.us/firesmoke or Installation Instructions for Retrofit Applications Prefco_Internal_Pulley- Cable_Multiproducts_to_Belimo _FS_Actuator Use of the FSTF and linkage is shown for replacement on dampers less than 2 sq. ft. Larger dampers require the FSNF and linkage. Prefco Series 5000 Replacement with Belimo FS Series Actuators March 2018 11

USE CAUTION! WARNING! Springs on old dampers may be under high torsion and may cause serious injury! If any external springs are present, exercise caution wear face and hand protection. Call Belimo for information about other actuators or applications. Digital photographs aid in identification to ensure accuracy. Prefco was purchased by Metal Industries and has since been sold to Johnson Tech in Taiwan. http://www.prefco-hvac.com/ Technical support is available at 800-437-6653. Notes: Prefco Series 5000 Replacement with Belimo FS Series Actuators March 2018 12

Prefco Series 5000 Dampers MODEL 5020-1 - RESETTABLE COMBINATION AIR/SMOKE/FIRE DAMPER WITH McCabe link. The operation of the actuator open (or closed) resets the temperature link if the duct temperature drops below its setpoint. MODEL 5020 FUSIBLE LINK OPERATED AIR/SMOKE/FIRE DAMPER This incorporates the standard one time fusible link to respond to a rise in duct temperature. It is reopenable only up to the chosen link-disconnect temperature. MODEL 5010 - ELECTRICALLY SIGNALABLE COMBINATION AIR/SMOKE/FIRE DAMPER Similar to the 5020-1 above. It incorporates an electrically energized heating element laminated directly to the bimetallic McCabe link on the damper s operator. This (or an elevated temperature condition) releases the damper blades and physically disconnects them from the actuator drive shaft. Therefore, an actuator is only needed for automatic reset/reopen. MODELS 5150/5151 - AIR/SMOKE/BALANCING DAMPERS Smoke rated only. The extended shaft extends outside the duct. Direct coupling is the preferred method. Crank arm linkage is possible where space or other constraints exist. The McCabe link mechanism operates independently of the actuator. McCabe Link After mounting and wiring of the actuator, it is necessary to test all operations. Prefco Series 5000 Replacement with Belimo FS Series Actuators March 2018 13

Thermal Sensor Flex Conduit Knee Lock Jackshaft Coupler Shaft Existing Motor Sleeve Above shows typical Model 5050/5150 damper with a Honeywell motor Below shows Belimo mounted to jackshaft with the damper sleeve removed. Mounting Prefco Series 5000 Replacement with Belimo FS Series Actuators March 2018 14

Replacement Instructions Series 5000 and 5100 Dampers Belimo FSNF shown Replacement Instructions Thermal Sensor Version 1. Disconnect incoming power and wiring to thermal sensor at actuator. Tag all wires. (Sensor may be inside the damper sleeve and only accessible from inside. 2. Remove old actuator and mounting bracket 3. Close damper. Mount Belimo actuator. Check that actuator springs in closed direction. 4. Reconnect wiring per original drawing. Typical wiring shown below. 5. Restore incoming power. 6. Test all functions. a. Power sensor and actuator. Press reset if necessary. b. Open smoke detector or relay contacts. Actuator springs damper fully closed. c. Reclose contacts. Actuator drives damper open. d. Trip thermal sensor. Actuator springs damper fully closed. e. Press manual reset. Actuator drives damper open. See Fire Marshal form for testing. Prefco Series 5000 Replacement with Belimo FS Series Actuators March 2018 15

Internal mount Internally mounted actuators are prevented from rotating by a stud or screw on a bracket. Do not jam the stud hard into the U-slot of the actuator. Let actuator have slight up and down movement. To replace actuator remove jackshaft and slide actuator off. Reverse process to put new actuator on jackshaft. Knee-lock adjustment Prefco Series 5000 Replacement with Belimo FS Series Actuators March 2018 16

Best to mount the Belimo anti-rotation strap perpendicular to the actuator to allow for movement on nonconcentric shaft. Two screws hold the antirotation strap. Two nuts secure cold-weld clamp onto shaft. FSAF mounts the same. Side view Damper Axel shaft or Jackshaft Mounting holes for different actuators anti-rotation Actuator Mounting Bracket Bracket can be attached to other brackets, damper sleeve, or frame FSLF mounted on damper shaft with a plate extended for the anti-rotation strap. Anti-rotation strap 11695 LF - P Bend strap at perforations to adjust for necessary height. The heavier duty 11414 AF- P may be ordered when needed. Prefco Series 5000 Replacement with Belimo FS Series Actuators March 2018 17

Distance at top must be the same as at bottom Actuator must be perpendicular to the damper shaft. Figure 1 Allow any non-concentric shaft motion to be taken up by mounting stud in middle of U-slot Actuator should be parallel to the plane of the damper frame and sleeve. Note how the pin of the antirotation strap is mounted in middle of actuator U-slot. Figure 2 This is acceptable as long as mechanically solid. As long as it is mechanically solid, the anti-rotation strap may be bent to fit height. Figure 3 - Prefco Series 5000 Replacement with Belimo FS Series Actuators March 2018 18

WARNING! Actuator anti-rotation strap may not be screwed to the duct. It must attach to either the sleeve or to the mounting bracket. The duct must be able to fall away from the damper in case of ceiling collapse in a fire. Short shaft mounting For short shaft mounting, the ZG-LMSA-1/2-5 can be used. Alternately, the clamp can be installed between the actuator and sheet metal. Clamp Depending on the geometry, any number of mounting arrangements are correct. The most common is shown at left. Alternately, the anti-rotation strap can be attached to any Belimo linkage, an electrical J-box cover plate, or to a pieced of U-channel. It is important to remember that the ducts are fall-away. The actuator mounting cannot interfere with the ability of the duct to fall from the damper. The damper must continue to protect the wall. See Belimo Mounting Methods Guide for more mounting drawings at www.belimo.us in the documentation tab. Prefco Series 5000 Replacement with Belimo FS Series Actuators March 2018 19

Small dampers Mounting The Belimo Anti-rotation strap may be attached to the HW bracket or to the sleeve. Duct must be able to fall away; do not attach so that this is prevented. A 4 x 4 or larger electrical plate will serve as an antirotation mounting plate if old actuator is hung over free air. Anti-rotation strap can be attached to bracket, 4 x 4 plate, or sheet metal bracket. See Belimo Mounting Methods Guide for more at www.belimo.com/documentation. FSTF Best solution for small dampers where the HW bracket has been hung out into the air is to use an FSTF actuator Prefco Series 5000 Replacement with Belimo FS Series Actuators March 2018 20

Code violation damage to drywall The Belimo may be direct coupled by using sheet metal to fill the defective drywall covering. Verify with Building Official or Fire Marshal before replacement. Prefco Series 5000 Replacement with Belimo FS Series Actuators March 2018 21

Linkage mounting WARNING! Read Data Sheet provided in box with each actuator for specific wiring details. Possible alternate arrangements for damper clip. (FSNF, FSAF actuators shown.) Belimo linkage kits: https://www.belimo.com/pim/mam /americas/technical_documents/d ata_sheets/man-airacc/mechanical_accessories.pdf Mounting Methods Guide: https://www.belimo.us/mam/americ as/technical_documents/pdfweb/guides/mounting_methods.pdf Miscellaneous parts Prefco Series 5000 Replacement with Belimo FS Series Actuators March 2018 22

Should they be needed, Belimo carries a range of parts. Ball joints and 5/16 rods are available from most distributors. Where the crank arm on the jackshaft is broken or not of the type needed, the KH12 fits over the shaft without removing it. Zinc plated steel. Slot is for the KG10A ball joint. V-bolt fits ¾ to 1 (20 to 25mm) shafts. KH8 KH-6. Zinc plated steel. For shafts 3/8 to 11/16 Uses KG6 ball joint. Slot width 1/4 KH-8. Zinc plated steel. For shafts 3/8 to 11/16 Uses KG8 (90 degree) or KG10A ball joint. Slot width 21/64 KG8 3/8 KG6, KG10A ¼ SH8 (not shown see picture page 9). Push-rod for KG6 & KG8 ball joints. 5/16 36 long Use SH10 3/8 rods for GMB and dual FSAF or FSNF linkages. 5/16 can bend under heavy loads. ZG-DC1 ZG-DC2 Damper blade clip and ball joints for blades typically 3.5 in width. Typically the actuator or rod to shaft is in front of blade. Damper blade clip and ball joints typically used for 6 wide blade control dampers. Typically the ctuator or rod to shaft is above or below the damper. Prefco Series 5000 Replacement with Belimo FS Series Actuators March 2018 23

Wiring J-box 165 F Thermodisc Anti- rotation strap FSLF FSNF ½ threaded connector Chase nipple 2 x 4 blank cover Existing flex connector and incoming power wires Prefco Series 5000 Replacement with Belimo FS Series Actuators March 2018 24

WARNING! Disconnect and lock out power before starting to disconnect old motor. There are three wiring schemes that describe all applications. While the geometry of the wire runs may vary, the connections are straightforward. TYPICAL FIRE - SMOKE COMBINATION DAMPER WIRING Electric thermal disc Smoke Detector or Relay from area smoke detection system HOT 120 or 24 VAC TYPICAL SENSOR TEMPERATURE 165 F N or COM To alarm system BELIMO FSxx ACTUATOR Regardless of the wiring routes used, this drawing shows the wiring necessary for a UL555S damper and actuator. Use it as a basis for any of the other wiring schematics. Note that the alarm connections are not touched when replacing an actuator. This is a major concern for Fire Marshals. Fusible link DAMPER ACTUATOR WIRING McCabe TM link DAMPER ACTUATOR WIRING Smoke Detector or Relay from area smoke detection system HOT 120 or 24 VAC N or COM BELIMO FSxx ACTUATOR The wiring below is commonly connected to alarm or smoke control electronic modules in modern systems. The functional sequence is the same. Prefco Series 5000 Replacement with Belimo FS Series Actuators March 2018 25

TYPICAL REOPENABLE DAMPER with FSCS Belimo Auxiliary Switches for position indication to FSCS FIRE FIGHTERS CONTROL PANEL Smoke detector or relay contacts TYPICAL SENSOR TEMPERATURES 165 F 350 F BELIMO FSLF or FSNF ACTUATOR N or COM A HOT 120 or 24 VAC HOA O H To alarm system -S models have two SPST (FSLF) or two SPDT (FSNF) auxiliary switches. See FSLF or FSNF data sheet for wiring numbers and/or color coding.. FSNF C NO NC C NO NC Com NO Com NC FSLF Damper Open or Closed Damper Open or Closed The auxiliary switches are used to provide status indication to the fire fighters smoke control panel. Typically there are two or three status lights or leds. This wiring is the responsibility of the fire alarm company. If it is touched, they must retest to verify proper operation. WARNING! Damper must be free to move from open to closed without undue stress. Damper and duct must be clean and free of all debris. Test damper and controls per Fire Marshal s checklist below. Fire alarm company may need to be present to verify proper status indication at FSCS panel. Prefco Series 5000 Replacement with Belimo FS Series Actuators March 2018 26

Auxiliary Switches Damper blade switch assembly Externally mounted auxiliary switches Where the original switches for signaling position to a Fire Fighters Smoke Control Panel or to local indicator lights must be replaced or are inoperative the Belimo S model actuators may be used or a S2A-F may be installed. Belimo S2A-F. FSLF (mid 2014ff), FSNF, and FSAF actuators can use the add on switch package. -S models H 165 F H C C Internal switches S1 S2 Contact closed if Contact closes if damper closed damper open Manual reset Switch cable Some models are SPDT. Check data sheets. Closed Hot Open Prefco Series 5000 Replacement with Belimo FS Series Actuators March 2018 27

Blade Position Indication Switches Dampers under 10 in height do not use a full 90º of rotation. If using the Belimo S actuator and installed as noted on U-10 dampers above, only the full open switch would be functional. Use of Prefco blade indicator switches is recommended in that case. On larger than 10 dampers, the Belimo FSxx -S models provide auxiliary switches that can replace existing switches as well as the actuator. See Belimo data sheets for information. WARNING! Read Data Sheet provided in box with each actuator for specific wiring details. Colors of wires and switch configurations vary. Prefco Series 5000 Replacement with Belimo FS Series Actuators March 2018 28

Building Official / Fire Marshal Notification Form Retain this portion of checklist at premises for Fire Marshal inspection. See local AHJ or Fire Marshal for other information and requirements regarding conformance with NFPA 80 & NFPA 105. Test Checklist (Smoke dampers do not have sensors. Only steps a & b apply.) 1. Single Sensor Combination Damper a. Open smoke detector or relay wire or contact to cut power. Damper springs closed. b. Reconnect power. Damper drives open. c. Open thermal sensor using heat gun. Damper springs closed. d. Press thermal sensor manual reset. Damper drives open. Repeat 3 times to ensure operation. This imitates UL555S test. 2. Reopenable Two Sensor Fire-Smoke Combination Damper (Since this system involves the Firefighters Smoke Control System, inform fire department or alarm company.) With FSCS switch in Auto position: a. Disconnect power from smoke detector or relay contacts. Actuator springs damper closed. b. Reconnect power. Actuator drives damper open. c. Trip thermal sensor. Actuator springs damper fully closed. d. Press manual reset. Actuator drives damper open. Test FSCS switch functions: a. Move FSCS switch to Off position. Actuator springs damper fully closed. b. Move FSCS switch to Hand position. Actuator drives damper open. c. Trip secondary (higher temperature) thermal sensor. Actuator springs damper fully closed. d. Press manual reset of secondary sensor. Actuator drives damper open. Move FSCS switch back to Auto position: a. Actuator springs damper closed if Primary sensor is still open. b. Actuator stays open if Primary sensor has re-closed. When completed, ensure sensors are reset and smoke detector is in normal state and FSCS switch is in Auto. Damper is normally Open; check sequence of operation. Damper Numbers or Location Identifying Numbers.. Date - -.. Contractor. Service Technician (Print).. Service Technician (Signed).. Phone Number ( ) Notes....... Prefco Series 5000 Replacement with Belimo FS Series Actuators March 2018 29