FUNCTIONAL DESCRIPTION DIS01

Similar documents
FUNCTIONAL DESCRIPTION AIS01

FUNCTIONAL DESCRIPTION FLOW01

Functional Description AIS01 - Analog Input Signal Version 5.2-0

Functional Description Flow01 - Temp & Press Compensation Flow Version 5.2-0

Procidia iware AlarmWorX32. AlarmWorX32 Viewer January 2010

Multistate Alarm. Introduction

COCB_ Circuit Breaker (2 state inputs/ 2 control inputs)

Instruction manual MTL process alarm equipment. October 2016 CSM 725B rev 2 MTL RTK 725B. Configuration Software Manual

Alarms Updated 03/26/2018

Avigilon Control Center System Integration Guide

725B Configuration Software Manual

Avigilon Control Center System Integration Guide

Compact Product Suite Compact HMI 6.0 Overview ABB

Laptop / PC Programming Manual

System 800xA Operations

Manual# User s Manual. 200E Series. DCU 210E/208E Diesel Engine Control Unit RP 210E Remote Panel

2017/11/16 P a g e 1

Yokogawa DX Ethernet Driver Help Kepware Technologies

DeltaV Operate. Product Data Sheet DeltaV Operate December 2006 Page 1. Introduction. Benefits

LineGuard 2300 Program User Manual (FloBoss 107)

M3092 Programmer. User s Manual. M3096B-33 E Copyright 2017 SELCO

ECO N DATE DESCRIPTION OF CHANGE CHG

IndigoVision. GAI-Tronics Integration Module. Administrator's Guide

Ademco Vista Alarm Panel

Experion PKS Operator Course EXP01R201 06/2004 Rev 01

System Galaxy Quick Guide

FCD-wire Contents. List of Figures

Introduction. Introduction

Milestone SMI Intrepid II Perimeter Module 1.1 User s Manual

Replaceable LED modules. Sleep or unattended mode. Auto-silence and auto-acknowledge

VAC PLC. System Description

Manual# User s Manual. 200 Series. DCU 210/208 Diesel Engine Control Unit RP 210 Remote Panel

HERCULES 6 GRAPHICS SYSTEM

Oracle Communications Performance Intelligence Center

1 Application Note Bosch Security Sys Sy tems m Bosch Security Systems Smart Safety Link -

MEVO3_ Three-Phase Voltage Measurement

Synergis Master Controller 2.2 Integration Guide for Assa Abloy IP Locks

FIRECLASS Networking. Addressable Fire Alarm Control Panels From Software version 21. Product Application and Design Information FC-A-FCNET-A

Alarms for the Cisco ISA 3000

Weekly Testing of Dedicated Smoke Control Dampers - Metasys System Extended Architecture

Architectural and Engineering Specification for a Security Management System. StarNet 2

FlameGard 5 UV/IR HART

How to Configure the Alarm Action Outgoing Cell Call MultiLogger Application Note #14


[ [ ADMIN PANEL USER GUIDE

Bosch TCU Integration Module Administrator's Guide

Monitor Alarms and Events

Added password for IP setup page : Password must be in IP format!

Paradox Integration Module Settings Guide

Configuration and Operation Manual for the Unipos

Avigilon Control Center System Integration Guide

Running IGSS as an Operator, Part One

Honeywell Control Panels FOR RESIDENTIAL AND COMMERCIAL INSTALLATIONS. Feature Charts

WeatherLink for Alarm Output Addendum

Alarm Coordination Connected Components Building Block. Quick Start

WorkstationST* Alarm Viewer

Alarm Monitoring and Management

RAy SNMP. Application notes.

Fire System Objects. Introduction Page *3. Engineering *17. Data Base Generation *43

Smart Combiners Installation Guide. For Obvius A89DC-08 sensor modules

CBI-064. User Manual. Caddx to KNX-BUS Interface

Synergis Master Controller 2.2 Integration Guide for Assa Abloy Aperio- Enabled Locks

Compact HMI Overview

RADview-EMS/TDM. Element Management System for TDM Applications Optimux RAD Data Communications Publication 07/04

Universal Monitoring System. Model IMEC8A. User Manual Version 1.10 Software version 2.3.1

CAN bus-based I/O module, CIO relays Mounting Terminals and wiring Commissioning, using the utility software

Avigilon Control Center 5 System Integration Guide

MicroTech Series 200 Centrifugal Chiller

User Manual Doc.Ref : JA-KNX-UM. JA-KNX Jablotron KNX Interface ELAUSYS JA-KNX. KNX Interface for Jablotron alarm system.

Meridian wiredhart. HART Field Device Specification Goldmine Rd. Monroe, NC USA

Lesson 10: Configuring Events IGSS. Interactive Graphical SCADA System. Lesson 10: Configuring Events 1

Security Management System - Configuring Video Analytics

Installation Instructions. Fire Command Center/Fire Alarm Annunciators D1256/D1257

Weekly Testing of Dedicated Stairwell Pressurization Fans- Metasys System Extended Architecture Code No. LIT

RESET + Password Enter (During Auto Speed Procedure) Maintenance Timeout or after TEST + RESET + DISABLE (No Need for Device to Initialize)

Dryer Controller M720

ION Meter Alerts TECHNICAL NOTE NOVEMBER In This Document

FlameGard 5 MSIR HART

Tebis application software

Manage Alarms. Before You Begin. NTP-E57 Document Existing Provisioning CHAPTER

Manage Alarms. Before You Begin CHAPTER

Single Story Enclosed Shopping Mall Smoke Control with FSCS Override - Metasys System Extended Architecture

Using ANM Mobile CHAPTER

Security Management System Configuring TCP-IP MODBUS Inputs

SEC 3500 OI- StatCast RS232 Gas Status Text Broadcast Configuration Manual

DX-9100/9120 Weekly Testing of Dedicated Stairwell Pressurization Fans

DATA SHEET BENEFITS CURRENT CHALLENGES SSM INFOTECH S X-FORCE AMS - THE IDEAL SOLUTION

Technical Publications. FactoryTalk Alarms and Events System Configuration Guide

Reference Manual. Common Alarm Block (P_Alarm) Version 3.1

Halton SAFE / 7.14 user guide and installation instructions

Alarm Gateway Object for Wonderware Application Server User Guide Ver 1.x Rev 1.4 PR 00185

Metasys Integrator Cleaver-Brooks Application

Alarm User Guide IGSS Version 12.0

GV2 Series Control Panels

FI6000 INSTRUCTION MANUAL. Thank you for choosing another quality product from Amperes Electronics. Fire Alarm Interface

User Manual. Dryer Controller M720

Simplex Panel Interface Guide

BeneVision Central Monitoring System. Quick Reference Guide

Monitoring Operator Guide. Access Control Manager Software Version

Control Panel Type ABS CP 116/216 COMLI/Modbus - Version 1.25

Transcription:

We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. ABB FUNCTIONAL DESCRIPTION DIS01 Digital Input Signal Prep. / 10-11-30 Function Description No. of p. Appr. PA/R/ Bengt Persson Approved DIS01 Functional Description 19 Resp. dept. Functional Descr DIS01RevI.doc; TECHN_DOC_STAND_P.DOT; 2010-11-29 16:15 ABB AB 3AST 001 596D003 en I 1

Contents 1 General... 4 2 Configuration... 4 3 Function Block DIS01... 5 4 DIS01 Datatypes... 6 4.1 DIS01_InPar... 6 4.2 DIS01_OutPar... 6 4.3 DIS01_Opr... 6 5 Function... 7 5.1 Basic Properties... 7 5.2 Control Modes and Updating... 7 5.2.1 E1... 7 5.2.2 Manual... 7 5.2.3 Manual Forced... 7 5.3 Filtering... 8 5.4 Error handling... 8 5.5 IO Status... 8 5.6 Alarm Functions... 8 5.6.1 Alarm Blocking... 8 5.6.2 Event handling... 9 5.7 Process connections... 9 5.8 Interaction Window... 9 5.8.1 DIS01 Interaction Window... 9 5.8.2 General Parameters... 9 5.8.3 Orders and Events Block... 10 5.8.4 Alarm & Event... 10 5.8.5 Texts... 11 6 Operator Functions... 12 6.1 Presentation... 12 6.1.1 Display Elements... 12 6.1.2 Time-logged Properties... 13 6.2 Faceplate(Dialog)... 14 6.3 Alarm and Event Handling... 16 6.3.1 General... 16 6.3.2 Alarm and Event Message... 16 6.4 Faceplate tabs... 16 6.4.1 Alarm and Event Blocking... 16 6.4.2 Order Blocking... 17 6.4.3 Status... 17 6.4.4 Info... 18 ABB AB 3AST 001 596D003 en I 2

1 General DIS01 is a functional unit for digital input signals in Control IT, to be operated from Operate IT, Operator Station. DIS01 normally performs a complete function independently. DIS01 has the following functions and properties: Different control modes set by operator or by control logic. Alarm and event handling of important control signals. 2 Configuration DIS01 comprises a function block type for control and logic functions in Control IT, a faceplate and an object display in Operate IT for operator functions and control parameters. HSI P A R A M E T E R S Control mode logic HSI INTERFACE VDU Op. Panel Local Signal processing DIAGN. - alarms (fault, warning) - events - loggers I/O INTERFACE PROCESS OBJECT Figure 1. The Structure of the Functional Unit ABB AB 3AST 001 5XXD001 en I 4

3 Function Block DIS01 FUNCTION OF INPUT TERMINALS DIS01 FUNCTION OF OUTPUT TERMINALS Signal from I/O-board ------------ IOSignal ------------ Object name Name Value Value Object description Description IO_Value I/O value Enable object Enable Err Error Signal inverted Inverted Err_Type Error type Hardware address, for SOE I/O SignalID Man Man mode Block alarm AL_P_Blk E1 E1 mode Acknowledge alarm AlarmAck Forced Channel is forced In Parameter InPar Disturb Alarm Figure 3-1. Function Block Type, Complete symbol Event name EventName OutPar Out Parameter Opr Operator order Table 3-1 below illustrates the default properties of each terminal of the DIS01 function block. Name Data Type Attributes Direction FD Initial Port value Description IOSignal BoolIO in_out yes Signal from I/O-board(s) Name string coldretain in yes 'DIS01' Object name Description string coldretain in yes 'Descr' Object description Enable bool coldretain in yes true Enable object Inverted bool coldretain in yes false Signal inverted SignalID string coldretain in yes Hardware address, for SOE I/O AL_P_Blk bool retain in yes Block alarm AlarmAck bool retain in yes Acknowledge alarm InPar DIS01_InPar by_ref in yes In Parameter EventName string coldretain in yes ' DIS01_' Event name Value bool retain out yes Value IO_Value bool retain out yes I/O value Err bool retain out yes Error Err_Type string[20] retain out yes Error type Man bool retain out yes Man mode E1 bool retain out yes E1 mode Forced bool retain out yes Channel is forced Disturb bool retain out yes Alarm OutPar DIS01_OutPar by_ref out yes Out Parameter Opr DIS01_Opr by_ref out yes Operator order Table 3-1. Terminal properties. ABB AB 3AST 001 5XXD001 en I 5

4 DIS01 Datatypes 4.1 DIS01_InPar Name Data Type Attributes Initial ISP value value Description Class dint coldretain 500 AE class Severity dint coldretain 1000 AE severity InitMode dint coldretain 7 Init mode (5 = Man ; 7 = E1) ManBlk bool coldretain false Block operator order Man mode E1Blk bool coldretain false Block operator order E1 mode AlcBlkEvBlk bool coldretain true Block event for AlcBlk AEConfigStatus dint coldretain 0 AE configuration for Disturbance NormPos bool coldretain false Normal position AlarmDelay time coldretain 0s Alarm delay AlarmText string coldretain 'Alarm' Alarm text 4.2 DIS01_OutPar Name Data Type Attributes Initial ISP value value Description AlarmBlk bool retain Alarm blocked Mode dint retain Active mode NormalMode bool retain Normal mode (Active mode = Init mode) Status AlarmInd retain Alarm indication for Status HWStatus HwStatus retain Hardware status SubStatus dint retain Hardware substatus IOStatus dint retain Hardware I/O status quality 4.3 DIS01_Opr Name Data Type Attributes Initial ISP value value Description BlockAlarm bool retain Operator block alarms Man bool retain Operator order Manual mode E1 bool retain Operator order E1 mode Ord_On bool retain Operator order ON command Ord_Off bool retain Operator order OFF command ABB AB 3AST 001 596D003 en I 6

5 Function 5.1 Basic Properties The DIS01 functional unit is designed for a standard digital input signal. DIS01 has the following basic functions: Control Modes and Updating Filtering Error Handling Alarm and event handling. Operator Functions 5.2 Control Modes and Updating The digital signal is read at intervals determined by the controllers task scan-time. You should set scan time to the requirements of your system. The control modes can individually be blocked for operator access. 5.2.1 E1 E1 is the initial control mode of the DIS01, where the value is obtained from the I/Omodule at input terminal :IOSignal. The control mode E1 can be commanded from the operator s station. The control mode E1is activated by: By clicking on the E1 button on the operator s faceplate. E1 is indicated on the object display and Faceplate. 5.2.2 Manual In this mode the operator directly sets the output value from the operator station. The control mode MAN is activated by: Clicking on the Man button on the operator s faceplate activates the control mode MAN. Man is indicated on the object display and on the Faceplate. 5.2.3 Manual Forced Manual Forced is a control mode, where the operator blocks the I/O-module input and can write directly to the I/O-module input variable. Enabling the Forced check box in the I/O Hardware section of the controller activates the control mode FORCED. Examples of use: During a plant stop I/O conditions could prevent opening of e.g. a valve. ManFd enables the operator to still use the I/O for value testing etc. ABB AB 3AST 001 5XXD001 en I 7

5.3 Filtering A filter time is set directly on the I/O module, which can be used to remove noise. The value may be 2ms, 4ms, 8ms or 16ms. 5.4 Error handling The control function of a DI signal indicates errors via Err and Err_Type. Different types of errors can occur, that are caused by the system. This occurs if the I/O-module function is determined non-functional. Typical causes of this type of error are: Missing or faulty hardware Incorrectly installed hardware or software Error in the bus communication. Errors in the DI-module are copied to the error handling function of the DIS01 and the error flag Err is set to 1 and the type of error can be read at terminal Err_Type. The Err and Err_Type terminals of the DIS01 function block can be connected to programs where the desired function may be built. 5.5 IO Status The status of the connected IO devices can be indicated of the faceplate of the DIS01 object on tab Status. 5.6 Alarm Functions The following alarms are monitored in the function block: OPC Status. Input I/O Signal if changing state from the normal position. When an alarm state is activated, an alarm, which must be acknowledged, is transmitted to the operator station (and printer, if provided). The Alarm is also available as an output on the disturbance terminal of the Function Block. The inverted input terminal of the function block can be used to invert the presentation of the signal. The time stamping of the alarm is done when the function block is executed. With SOE I/O-units e.g. DI830 the time stamping is done in the hardware unit. To transfer this time stamp to the FB, the hardware address of the I/O-channel is entered in terminal SignalID. 5.6.1 Alarm Blocking The Alarm Block function disables the alarm supervision of the input value. The alarm and event handling function makes it possible to block alarms from the operator s station or from the function block. By blocking alarms, the printer and operator s stations updating of the Alarm list are blocked. ABB AB 3AST 001 596D003 en I 8

5.6.2 Event handling Event are generated for status change on the signals defined in interaction window in chapter 4.9.4 The layout of the event is described in chapter 6.3. All Operator Events are reported by Audit Trail Functionality and not included in the FunctionBlock. The individual text string for each event is stored in the Alarm and Event Translator aspect. This text can be NLS handled. 5.7 Process connections The DIS01 is connected to the process via the following terminals. IOSignal Connection for input value e.g. a pressure switch. 5.8 Interaction Window The interaction window is available in the Control IT Control Builder. The interaction window is an engineering aid used to simplify configuration and blocking of signals not available on the faceplates. Changes to values in the Interaction window are only available in Online mode in Control IT. 5.8.1 DIS01 Interaction Window Interaction window overview. Name and description are shown. The buttons are links to sub-windows. Figure 4-1 Main Interaction Window. 5.8.2 General Parameters Class defines the process section or area in which alarms are grouped. By utilizing class the alarms can be filtered. Valid values are user defined. A suggestion would be to use mill area numbers as class values. Severity defines the alarm priority. Valid values are 1 1000 where 1 is the lowest priority. ABB AB 3AST 001 5XXD001 en I 9

Figure 4-2 General Parameters. 5.8.3 Orders and Events Block Manual Mode blocks the possibility to enter input signal from faceplate. E1 Mode blocks the possibility to enter input signal from application program. The Alarm Ctrl Blk controls the sending of an Event when the Input parameter AL_P_Blk is activated. If Event Block is set to 1 no Event is send. Init Mode define the mode of the object when is cold started Figure 4-3 Orders and Events. 5.8.4 Alarm & Event Alarm handling, Normal position and alarm delay time is entered in this window. For Alarm Treatment config the following values are valid 0 No Alarm or Event are generated 1 Alarm and Event are generated 2 Event is generated Alarm text is defining the text that will be presented in the message field in the alarm list. Figure 4-4 Alarm ABB AB 3AST 001 596D003 en I 10

5.8.5 Texts ABB AB 3AST 001 5XXD001 en I 11

6 Operator Functions The Operator functions are divided in principle into 3 parts: Presentation (Display elements, Time logged properties) Faceplate (Dialog) Alarm and Event handling 6.1 Presentation 6.1.1 Display Elements Display elements, which can be used for different display types, are available for use in the functional unit DIS01. The display elements show the status and the controls of the process with different degrees of detail and are intended for the following displays: Object display Process display Examples of different display elements, which could be used, are given in the following sections. 6.1.1.1 Object Display Figure 5-1 Object Display. ABB AB 3AST 001 596D003 en I 12

6.1.1.2 Process Display Figure 5-2 Process Display Elements. 6.1.2 Time-logged Properties Digital values stored can be presented graphically in the form of traces on the display screen. Such a display, a Trend display, can consist of 1-4 traces as standard. All properties for the object DIS01 are available to be logged on the trend curves. Figure 5-3 Trend Curve ABB AB 3AST 001 5XXD001 en I 13

Figure 5-4 Extended Faceplate (T Curve 6.2 Faceplate(Dialog) The display screen is supplemented with a mouse and keyboard for operator communication with the functional unit/object. By using Operate IT Operator Station the operator can view and control the process through faceplates. The dialogue consists of buttons, indicators and graphic presentations within a Faceplate. A faceplate has three levels of dialogue, which are presented by the following three runtime views: Reduced Faceplate, where the size and contents typically have been optimized to cover most of the normal process operator actions. Minimum dialogue. This is the default view. Faceplate, which typically covers all normal process operator actions. This view is disabled as default. Extended Faceplate, with functions and information intended for the process engineer or the advanced operator. Maximum dialogue. The figures 5-5 to 5-7 below and overleaf illustrate the various presentations of the faceplate. ABB AB 3AST 001 596D003 en I 14

Figure 5-5 Reduced Faceplate. Figure 5-6 Faceplate. Figure 5-7 Extended Faceplate ABB AB 3AST 001 5XXD001 en I 15

6.3 Alarm and Event Handling 6.3.1 General This section contains a description of all alarms and events in the functional unit DIS01. When an input value fails or changes state an alarm and an event is generated and can be viewed on the Operate IT Operator Station. The alarms are indicated in the faceplate, object display and in the alarm and event list. The alarm limits for DIS01 can be controlled individually. Figure 5-8 Alarm List 6.3.2 Alarm and Event Message The following alarm texts are generated by the functional unit DIS01. The Message Description text is hard coded and can not be changed. The Condition text are stored in the Alarm and Event Translator aspect and can be NLS handled. Object Name Object Description Condition Message Description <Name> <Description> Status Alarm The following event texts are generated. The Message Description text are stored in the Alarm and Event Translator aspect and can be NLS handled. SourceName ObjectDescription Condition Message Description <Name> <Description> Alarm P Blk <Name> <Description> Acknowledge Alarm 6.4 Faceplate tabs 6.4.1 Alarm and Event Blocking By using the extended faceplate it is possible for the process engineer to block alarm. ABB AB 3AST 001 596D003 en I 16

Figure 5-9 Extended Faceplate (Block) 6.4.2 Order Blocking By using the extended faceplate it is possible for the process engineer to limit the operator access to different control modes. Figure 5-10 Extended Faceplate (Max Dialog) 6.4.3 Status The Status tab of the extended faceplate is showing the type of device and it s status for the measured value. The faceplate elements in the extended faceplate below illustrate this. ABB AB 3AST 001 5XXD001 en I 17

Figure 5-11 Extended Faceplate (Status) 6.4.4 Info Figure 5-12 Extended Faceplate (Info) ABB AB 3AST 001 596D003 en I 18

REVISION Rev. Page (P) Chapt. (C) Description Date Dept./Init. A Version 2.0 03-02-10/MP B Orderblock added 031106/MP C 5, 6 Initialization 04-04-14/FM D Rev 3.1/2 050223/MP E 4,5 Event handling is added. Update of Faceplate and Interaction 050324/BP window elements F 4, 5 Faceplate 05-08-26/MP G 3 Rev 4.0/5 070510/BP H Rev 5.0-1 081230/BP I Update Rev 5.1/0 101102/BP ABB AB 3AST 001 5XXD001 en I 19