Metzger, Brian. From: Sent: To: Cc: Subject:

Similar documents
DRAFT NFPA 805 TRANSITION PILOT PLANT OBSERVATION GUIDANCE

REGULATORY GUIDE OFFICE OF NUCLEAR REGULATORY RESEARCH. REGULATORY GUIDE (Draft was issued as DG-1170, dated November 2006)

NUCLEAR REGULATORY COMMISSION. [Docket No ; NRC ] Exemption Requests for Special Nuclear Material License SNM-362,

Fire Protection Regulatory Approach for Nuclear Power Plants in Canada

July 29, 2002 EA

DRAFT REGULATORY GUIDE DG-1069 FIRE PROTECTION PROGRAM FOR NUCLEAR POWER PLANTS DURING DECOMMISSIONING AND PERMANENT SHUTDOWN

TetraTek, Inc. Regulatory. Compliance. Emergency Response. Nuclear Facility Compliance. Compliance. Fire Protection.

NRC REPORTING REQUIREMENTS IN PART 21

Exemption Request From The Requirements Of 10 CFR 50, Appendix R Section III.G.2 For Fire Area IX/Fire Zone 23A - Intake Structure Pump Room

ýj ".. I IIIIII1 IIII1 UID II11I III1I cc w/encls: Mr. Donald A. Reid

This copy courtesy ARS/MPI. This document is from a CD-ROM distributed courtesy of Appendix R Solutions. and Matrix Press, Inc. You may not alter,

December 4, Dear Mr. Stall:

Guidance for Post-fire Safe Shutdown Analysis

SAFETY EVALUATION REPORT FOR THE TANK FARMS FIRE HAZARDS ANALYSIS

Narrative Reports As Regulated by 780 CMR, Section 903.0

Westinghouse UK AP1000 GENERIC DESIGN ASSESSMENT Resolution Plan for GI-AP1000-IH-01 Internal Fire Safety Case Substantiation.

STATE FIRE MARSHAL S REQUIRED FIRE PROTECTION SYSTEMS NARRATIVE REPORT

January 30, 2002 INDIAN POINT NUCLEAR GENERATING UNIT NO. 3 - SUPPLEMENT TO SAFETY EVALUATION RE: LEAKAGE DETECTION SYSTEMS (TAC NO.

MEMORANDUM. Technical Committee on Mercantile and Business Occupancies. NFPA 101 Second Draft Technical Committee FINAL Ballot Results (A2017)

Executive Summary of Qualifications

Protection against Internal Hazards in the Design of Nuclear Power Plants

Protection against Internal Hazards in the Design of Nuclear Power Plants

FIRE PROBABILISTIC SAFETY ASSESSMENT FOR KUDANKULAM NPP IN INDIA. G.Tokmachev. Atomenergoproekt, Bakuninskaya 7, Moscow, Russia

Requirements for the protection of High-Piled Combustible Storage (HPCS) Effective Date: January 2011

[Docket No. FAA ; Product Identifier 2017-NE-02-AD; Amendment ; AD ]

December 5, 2016 V.C. SUMMER NUCLEAR STATION, UNIT 1 NRC TRIENNIAL FIRE PROTECTION INSPECTION REPORT /

M E M O R A N D U M. NFPA Technical Committee on Alternative Approaches to Life Safety. SUBJECT: NFPA 101A ROP TC Letter Ballot (A2012 Cycle)

U.S. Department of Energy Washington, DC

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

MEMORANDUM. NFPA Technical Committee on Fire Code (FCC-AAA) Subject: NFPA 1 Proposed Tentative Interim Amendment (TIA) No.1045


Airworthiness Directives; Kidde Aerospace Part Number (P/N) Hand-Held Halon Fire Extinguishers

August Process Industry Practices Electrical. PIP ELEHA01 Engineering Guide for Determining Electrical Area Classification

Regulatory Perspective for Fire Protection and Emergency Management at Nuclear Facilities in Canada

Options for addressing City of Edmonds Alternatives to Ecology s Required Changes addressing Edmonds Marsh Buffers and Setbacks.

SECTION INSPECTION AND TESTING OF WORK

Fire Sprinklers Working Group Final Report

Technical Paper. Functional Safety Update IEC Edition 2 Standards Update

Fire Protection at Shearon Harris: Other than being unsafe and illegal, no problems at all

CAN/ULC-S1001, INTEGRATED SYSTEMS TESTING OF FIRE PROTECTION & LIFE SAFETY SYSTEMS Simon Crosby, LEL, CET, CFPS October 21, 2015

December 4, 2003 SUBJECT: QUAD CITIES NUCLEAR POWER STATION, UNITS 1 AND 2 NRC INSPECTION REPORT / ; / (DRS)

Dispute over the requirement for fire door signage to hotel suites at 124 Devon Street West, New Plymouth

1.3 REFERENCE STANDARDS

Cable Selection and Detailed Circuit Analysis on Plant under Construction

M E M O R A N D U M. NFPA Technical Committee on Building Services and Fire Protection Equipment

Public Input No. 1-NFPA [ Global Input ] Additional Proposed Changes. Statement of Problem and Substantiation for Public Input

British Columbia Building Code 2006 Division B Part 3 Fire Protection, Occupant Safety and Accessibility Section 3.2 Building Fire Safety

Standard PRC Transmission Relay Loadability

Major Changes Nova Scotia Building Code 2011 Construction and Maintenance Regulatory Change Industry Briefing

Soot Mitigation Strategies

CAN/ULC S Integrated Systems Testing of Fire Protection and Life Safety Systems and Fire Protection Commissioning

The North American Electric Reliability Corporation ( NERC ) hereby submits

UNIVERSITY OF ROCHESTER ENVIRONMENTAL HEALTH & SAFETY

Rancho Cucamonga Fire Protection District Prevention Bureau Standard

Highway Oriented Commercial Development Criteria


International Fire Code 2006 Requirements for Construction Plan Reviews of Commercial and Multi-Family Structures

Report on First Revision June 2014 NFPA 5000

INTERNATIONAL STANDARD

December 26, 2006 SUBJECT: CALLAWAY PLANT - NRC TRIENNIAL FIRE PROTECTION INSPECTION REPORT / AND EXERCISE OF ENFORCEMENT DISCRETION

CAN/ULC-S1001, INTEGRATED SYSTEMS TEST OF FIRE PROTECTION AND LIFE SAFETY SYSTEMS

SECTION AUTOMATIC TRANSFER SWITCHES

M E M O R A N D U M. NFPA 5000 A2011 ROP Letter Ballot

Table EXIT ACCESS TRAVEL DISTANCE a OCCUPANCY SYSTEM SYSTEM. A, E, F-1, I-1, M, b,d R, S-1. B c. F-2, S-2, U c

Major Changes to the 2010 National Construction Codes Contractor s Breakfast January 2014

CHAPTER 61G15-32 RESPONSIBILITY RULES OF PROFESSIONAL ENGINEERS CONCERNING THE DESIGN OF FIRE PROTECTION SYSTEMS

CAN/ULC-S INTEGRATED SYSTEMS TESTING OF FIRE PROTECTION AND LIFE SAFETY SYSTEMS

ABSTRACT. State adoption is not required, See Paragraph V. Directorate of Compliance Programs. 200 Constitution Avenue, NW Washington, DC 20210

UC Irvine Environmental Health & Safety TITLE: FIRE WATCH AND OUT OF SERVICE NOTIFICATION

Agency for Health Care Administration

Options for Developing a Compliant PLC-based BMS

Engineering Standard. Saudi Aramco DeskTop Standards

rpsa FIRE PROTECTION ENGINEERS

NFPA 101 Life Safety Code Culture change 2012

FIRE SAFETY INSPECTION REPORT REDPOINT JACKETS LTD, DHAKA, BANGLADESH

Management Practices: Fire Protection Impairments November 2015

November 17, Sent Via Electronic and Regular Mail

[Docket No. FAA ; Directorate Identifier 2012-NM-176-AD] Airworthiness Directives; DASSAULT AVIATION Airplanes

Second Revision No. 3-NFPA [ Section No. 2.3 ]

South Carolina Department of Labor, Licensing and Regulation Division of Labor Office of Occupational Safety and Health Columbia, South Carolina 29211

International Water Mist Conference, Istanbul October 22-23, 2014 The background and development of the guidelines in IMO Resolution A.

[Docket No. FAA ; Directorate Identifier 2004-CE-25-AD; Amendment ; AD ]

Chapter 4 - Preparation of Stormwater Site Plans

Fire Risks of Loviisa NPP During Shutdown States

September 22, Dear General Gioconda:

A. Product Data: Include rated capacities, furnished specialties and accessories.

CONTENTS. B. System Design and Performance Requirements

SOCIETY OF FIRE PROTECTION ENGINEERS POSITION STATEMENT P THE ENGINEER AND THE TECHNICIAN DESIGNING FIRE PROTECTION SYSTEMS.

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

Bold items are particular to the City of Euless

At its meeting of August 7-9, 2012, the Standards Council considered the above referenced matter.

FIRE & LIFE SAFTEY STANDARD

NEW YORK CITY FIRE DEPARTMENT. Notice of Public Hearing and Opportunity to Comment on Proposed Rule

Addendum # 2 Wicomico County Circuit Court Second Floor Renovations Date of Addendum: 2/6/2017

Changes in NFPA

September 30, Dear Fire Suppression System Contractor/Designer:

Information Bulletin

DIRECTIVE NO: D-B

July 16, 2001 PRAIRIE ISLAND NUCLEAR GENERATING PLANT NRC INSPECTION REPORT NO /01-05(DRS); /01-05(DRS) Dear Mr.

CONSENT CALENDAR CITY PLANNING COMMISSION AGENDA ITEM NO: A.1, A.2 STAFF: LARRY LARSEN

Transcription:

Metzger, Brian From: Sent: To: Cc: Subject: Sullivan, Kenneth [ks@bnl.gov],(j\ L' Friday, October 02, 2009 9:00 AM Metzger, Brian Vi'cN.Z- Frumkin, Daniel; Higgins, James C RE: RAIs Hi Brian! Have moved on to Oyster Creek Phase 2 submittal - After I complete this - Plan is to do IP2, IP3, and then Wolf Creek last - This is certainly not cast in concrete - let me know if you would like me to alter it. Note that for licensee's that IP) I am preparing a separate Task 1, there will be a total have more than one submittal (i.e., OC and RAI for each, So although there are only three licensee's, in of five RAIs Admittedly, I spent more time than anticipated on OC Ph 1 but still all five RAIs by the agreed upon date (10/30) on track for submittal of Received internal (BNL) review comments on OC Ph I RAI this am - as soon as I receive your comments I will develop the "final" version and submit it to you and Dan (with cc to Bernie Grenier). Didn't consider the need for this additional review step (staff review of draft RAI) when we were developing the SOW - but I appreciate having staff comments on the draft version before issuing the final. Have a great weekend Ken ----- Original Message ----- From: Metzger, Brian rmailto:brian.metzger(@nrc.govl, - Sent: Thursday, October 01, 2009 4:49 PM To: Sullivan, Kenneth Subject: RAIs Ken, Dan provided me your draft RAIs for Oyster Creek and we will review them as soon as possible but I was wondering which request you were going to be reviewing next. I am revising some schedules and just wanted to know where to "slot" the requests that we have you working on. Please let me know if you have any questions. Regards, Brian Metzger Fire Protection Engineer, NRR/DRA/AFPB, Phone: 301-415-3972 Location: 0-10G13 Mail Stop: 0-10C15 ^ -7 1

Energy Sciences and Technology Department BROQKHZ EN Building 130 P.O. Box 5000 NAT ION-AL LABORATORY Upton, NY 11973-5000 Phone 631 344-7915 kscbnl.qov managed by Brookhaven Science Associates for the U.S. Department of Energy www.bnl.qov Mr. Daniel Frumkin U.S. Nuclear Regulatory Commission Office of Nuclear Reactor Regulation Division of Risk Assessment, Fire Protection Branch (NRR/DRA / AFPB) Washington, DC 20555-0001 October 13, 2009 Reference: JCN No. J-4242, Task Order No. 1, Exelon Generation Company, Oyster Creek Nuclear Generating Station TAC No. ME0756. Dear Mr. Frumkin By letter to the Nuclear Regulatory Commission (NRC) dated March 3, 2009, Exelon Generation Company, LLC (the licensee), submitted a Request for Exemption from Title 10 of the Code of Federal Regulations, Part 50, Section IlI.G, "Fire Protection of Safe Shutdown Capability," for Oyster Creek Nuclear Generating station. In accordance with the scope of work described in Task 1 of Project J-4242, I have reviewed the request submitted by the licensee and identified a need for additional information, as set forth in the Enclosure. It should be noted that the RAIs described in this report resulted from a review of the technical merits of the March 3,. 2009 submittal. As a result, the review was limited to an assessment of the feasibility of the OMAs and adequacy of defense-in-depth provided for fire areas which credit the performance of OMAs as a means of achieving and maintaining hot shutdown conditions. A determination of the validity of prior staff approval of the requested OMAs is considered to be the purview of the NRC staff and, therefore, beyond the scope of this review. In performing this review, it was assumed that the all of the requested OMAs were previously approved by the staff and are appropriately documented in the SERs referenced by the licensee in its submittal. If you have any questions, please contact me at the phone number or e-mail address indicated above. Sincerely, Kenneth Sullivan, Systems Engineering and Safety Analysis Group cc: B. Grenier, NRC D. Diamond J. Higgins Project File J4242., Task 1

Enclosure

REQUEST FOR ADDITIONAL INFORMATION REGARDING REQUEST FOR EXEMPTION FROM 10 CFR 50 APPENDIX R. SECTION III.G OYSTER CREEK NUCLEAR GENERATING STATION DOCKET NO. 50-219 Background By letter to the Nuclear Regulatory Commission (NRC) dated March 3, 2009 (Agencywide Documents Access and Management System (ADAMS) Accession No. ML090630132), Exelon Generation Company, LLC (the licensee), submitted a Request for Exemption from Title 10 of the Code of Federal Regulations, Part 50, Section IIl.G, "Fire Protection of Safe Shutdown Capability," for Oyster Creek Nuclear Generating Station (OCNGS). The NRC staff has reviewed the request for exemption the licensee provided in the March 3, 2009 submittal. As described in Regulatory Issue Summary 2006-10, "Regulatory Expectations with Appendix R Paragraph III.G.2 Operator Manual Actions," for plants licensed before January 1, 1979, an approved exemption is required for all operator manual actions (OMAs) used to achieve compliance with 10 CFR Part 50, Appendix R Section III.G.2, even those that were accepted in a previously-issued NRC SER. Accordingly, the licensee is requesting that the NRC approve an exemption request to allow the use of manual actions for demonstrating compliance with Section III.G.2 of Appendix R, which, it asserts were previously approved in Fire Protection Safety Evaluation Reports (SER) dated March 24, 1986 and June 25,1990. The specific manual actions related to this request are listed in Attachment 2 of the licensee's March 3, 2009 submittal. The requests for additional information (RAIs) described below resulted from a review performed by Brookhaven National Laboratory of the technical merits of the March 3, 2009 submittal. As a result, the review was limited to an assessment of the feasibility of the OMAs and adequacy of defense-in-depth provided for fire areas which credit the performance of OMAs as a means of achieving and maintaining hot shutdown conditions. A determination of the validity of prior staff approval of the requested OMAs is considered to be the purview of the NRC staff and, therefore, beyond the scope of this review. In performing this review, it was assumed that the all of the requested OMAs were previously approved by the staff and are appropriately documented in the SERs referenced by the licensee in its submittal. To verify the feasibility of the OMAs and adequacy of defense-in-depth provided for fire areas crediting the performance of an OMA to achieve and/or maintain hot shutdown conditions, a response to the following RAIs is requested: 1

Requests for Additional Information RAI-01 Circumstances for Review Section 2.0 of Attachment 1 cites the basis for the exemption request as modifications needed to achieve compliance with Section 111.G.2 of Appendix R, represent an unwarranted burden because they are not necessary to meet the underlying purpose of the rule. Provide the following relevant details to support this position: " A technical justification of how the proposed arrangement achieves the underlying purpose of the rule. " The specific requirements of III.G.2 that are not met for each of the requested exemptions, for example, a lack of fire barriers, spatial separation, automatic suppression, etc. " A summary of the plant specific features that compensate for this lack of IIl.G.2-required features for each of the requested exemptions. For example, note any enhanced defense-in-depth measures such as a lack of ignition sources and/or combustibles, more robust and/or supplemental detection and suppression systems and the availability of the requested manual action(s). * A technical explanation that justifies how the proposed methods will result in a level of protection that is commensurate with that intended by III.G.2. The response should demonstrate that defense-in-depth is provided such that operators are able to safely and reliably achieve and maintain hot shut down capability from the control room. Note that it is the Nuclear Regulatory Commission (NRC) staffs position that operator manual actions alone, regardless of their feasibility and reliability, do not meet the underlying purpose of the rule without specific consideration of the overall concept of defense-in-depth that is being applied in a particular fire area. RAI-02 Ensuring That One of the Redundant Trains Is Free of Fire Damage Section IV-A of Attachment 1 identifies 34 fire areas/zones that are not in compliance with Appendix R, Section III.G.2 because hot shut down OMAs would be required to align redundant train systems to achieve safe shutdown. Section IV- C also states that the Fire Support Procedure (FSP) makes provision for a worst-case fire affecting all of the fire zones Section III.G.2 of Appendix R provides three options for ensuring that one of the redundant trains of equipment remains free of fire damage. The use of Operator Manual Actions (OMAs), in lieu of the three options provided in III.G.2, is not explicitly included as a means of 2

demonstrating compliance with Section III.G.2. Thus, systems and equipment that are not provided with a level of fire protection commensurate with Section III.G.2 must be assumed to be lost or damaged as a result of fire. Confirm whether all redundant equipment located within a particular fire area, that is not provided with fire protection features specified in Section III.G.2 is assumed lost or damaged during a fire event and also confirm the time at which this equipment is assumed to be lost or damaged. RAI-03 Other Evaluations Fire areas may have other exemptions or engineering evaluations that affect fire protection systems or safe shutdown capabilities. Provide a discussion of any other exemptions or evaluations that impact this request in any way and a justification for why such impact should be considered acceptable. RAI-04 Fire Protection System and Fire Barrier Design Criteria Attachment 1 notes that several areas are equipped with various fire detection and suppression systems. However, the request does not state whether the systems have been designed and installed in accordance with applicable design standards or requirements. For example: Attachment 1 states that the Fire Zones DG-FA-15 and OB-FZ-6A are separated from other plant areas by rated fire barriers. For areas such as these which credit fire barriers for providing separation from other plant areas, state what the fire rating is for the barriers as well as any penetrations and whether they are designed and installed in accordance with a particular standard or listing. Also, Attachment 1 states that areas such as, Fire Zone OB-FZ- 6A, are equipped with smoke detectors and that an enhancement is being made to OB-FZ-8B to install area-wide smoke detection. For areas such as these that rely on smoke detectors, state whether the detectors have been installed and maintained in accordance with a particular design standard or basis, e.g. National Fire Protection Association 72: National Fire Alarm Code, 1985 Edition. Where fire protection features such as detection and suppression systems and fire rated assemblies are installed, describe the technical basis for such installations including the applicable codes, standards and listings. In addition, provide a technical justification for any deviations from codes, standards and listings by independent testing laboratories in the fire areas that could impact this evaluation. Lastly, provide a technical justification for any nonrated fire protection assemblies. Additionally, Section B.(5) of Attachment 1 states that a water curtain located in openings between the 23' to 51' elevations and 51' to 75' elevations will provide reasonable assurance of 3

extinguishing any postulated fire. Where the erection of physical barriers between redundant shutdown systems is precluded, the staff has accepted, in concept, the use of an automatic fire suppression system which discharges a "water curtain" across the boundary areas separating the redundant systems. A water curtain may aid in the extinguishment of fires. However, as discussed in Generic Letter (GL) 83-33, the design objective of a "water curtain" is to reduce the spread of hot gases and products of combustion between adjoining areas, not fire extinguishment. Provide a technical basis to support your reliance on water curtains for fire extinguishment. RAI-05 Time and Sequence Assumptions Attachment 1 states that the shutdown methodology incorporates both "symptom based" and "prompt" (prescriptive) OMAs. For each of the 34 OMAs contained in this request, identify the type of action being performed (prompt or symptom based) and provide a discussion of the required time verses the observed and/or calculated completion time. The response should describe the methodology and all assumptions used to determine each time. For "symptom based" OMAs, provide a justification to support the time assumed to be available to perform the actions, including confirmation that there is adequate time for the operators to diagnose the need for the actions, travel to action location(s), perform the actions, and confirm the expected response before an undesired consequence occurs. For OMAs identified as "Prompt Actions, " provide a justification for: (a) selecting 45 minutes for classifying OMAs as "Prompt Actions" and (b) clarification and justification of when this 45 minute time period is assumed to start. The request also lacks a detailed description of the series of events that may occur prior to initiating the OMA procedures. Specifically, the request does not describe the conditions that must be satisfied in order for operators to enter the procedure (i.e., procedure entry conditions). In addition the request does not describe whether the procedures are initiated immediately upon activation of the smoke detection system, upon confirmation of fires of a certain size or type or upon some other fire confirmation criteria. Describe the circumstances and criteria needed to enter the OMA procedure. In addition, describe the amount of time, and the technical basis, that has been assumed for detection and assessment of a postulated fire as well as the expected plant response to a postulated fire. Additionally, provide either: (1) an analysis and/or technical justification that demonstrates that the detection capability is sufficient to provide notification of a postulated event coincident to or before damage to the redundant trains of equipment occurs; or (2) provide an analysis and/or technical justification for scenarios where the redundant components are damaged before a fire has been confirmed. 4

RAI-06 Ignition Sources and Combustible Fuel Load Attachment 1 uses terms such as "low" or "moderate" to describe the combustible fuel loading in the fire areas included in the request. Provide critical details and/or assumptions regarding the fire hazards for each fire area included in the request. This information may include, but is not limited to: * The number, type and location of potential ignition sources, * The number and types of equipment that may exhibit high energy arcing faults, and the relationship between this equipment and any secondary combustibles, * The quantity of cables and other secondary combustibles and their relationship to potential ignition sources, The cable type, e.g., thermoplastic or thermoset. If thermoplastic cables are used, provide a discussion of self-ignited cable fires, * Ratings for cables, e.g., IEEE-383, etc. If not rated, justify why fire spread would be assumed to be slow, * Controls on hot work and transient combustibles in the area, and the proximity of secondary combustibles that could be impacted by a transient fire, and * Dimensions of the rooms including ceiling heights. RAI-07 Fire Zone Proximity and Access Attachment 1 states that the performance of certain OMAs may require the use of a SCBA. The submittal includes a discussion of circumstances and features that may preclude the need for SCBAs. However, the submittal does not definitively state whether operators are procedurally directed to don SCBAs or if the time needed to don the SCBAs was included in the analysis of time available to perform line. For example, Section B(6) states that for a fire in OB-FZ-8C actions 17 and 18 may require the use of SCBAs for either traveling to the "C" or "D" 4160V Switchgear Rooms, or if C02 is present in the area. However, the discussion then provides your rationale for why operators would not be expected to need SCBAs to perform these actions. As a result, it is not clear if the discussion of the use of SCBAs is intended to portray environmental conditions operators may be reasonably expected to encounter or if the request is seeking staff approval of the rationale provided so the need for SCBAs may be eliminated. 5

In addition to clarifying the discussions presented in Attachment 1 regarding the use of SCBAs, for each fire area / zone included in the request, provide a technical justification that demonstrates that a fire in the fire area of fire origin would not impact the performance of the OMA. The response should address effects of fire such as heat, smoke, ventilation and any other fire effects that could have an impact on the OMAs. RAI-08 Fire Scenarios Attachment 1 Section A, Fire Area / Zone Descriptions and Attachment 2, Appendix R III.G.2 Manual Operator Actions, identify the OMAs needed in each fire area / zone, but do not describe the fire scenarios that have been considered for the postulated events. For example, in the event of fire in Fire Zones TB-FA-26, TB-FZ-1 1 B, TB-FZ-1 1 C, TB-FZ-1 1 D, TB-FZ-1 1 E, OMAs may be required to isolate damaged cables and reestablish control locally for 4160V Switchgear 1 D. However, no information is provided to describe the separation between the redundant train cables. It is also not clear where the cables are located relative to floor, walls and other trains or whether any spatial separation exists between the two trains. For each OMA included in this request, describe the in situ and transient fire hazards (ignition potential and combustibles) in the fire area that have the potential to affect the redundant trains. Provide a description of the proximity of the redundant train equipment to in situ hazards and the spatial relationship between the redundant trains in the fire area such that if they are damaged, manual actions would be necessary. Note, that this question is distinct from the RAI addressing Ignition Sources and Combustible Loading, which is generally focused on the combustibles in an area, whereas, this RAI addresses the specific relationship between ignition sources and combustibles and the redundant trains. RAI-09 Fire Area of Origin Re-entry The March 3, 2009, request states that operators are required to re-enter certain fire areas, including RB-FZ-1 E and RB-FZ-1 F to perform an action following a fire event. Since the request also indicates that all unprotected equipment located in a fire affected area / zone is assumed lost or damaged as a result of the fire, additional clarification is needed to confirm the accessibility, availability and operability of the credited equipment. Provide a tabular cross reference between all fire areas / zones that credit operator re-entry to perform OMAs and the equipment to be operated. For each piece of equipment and /or component, provide a justification of why the assumption that all equipment located in the fire area of origin is lost during a fire does not apply. Additionally, provide critical details and/or assumptions of the analysis which demonstrate that the required safe shut down equipment and/or component located within the area is maintained free of fire damage and remains operable following the fire event. 6

p RAI-10 Feedwater Regulating Valve Leakage Rate The description of OMA Item No. 15 provided in Attachment 1 states that the action is needed to stop the pumps at the switchgear since air leakage may cause the feedwater regulating valves to drift back open. Based on an assumed "minor" leakage rate, the analysis further states that there will be 180 minutes to perform this action. Quantify the assumed "minor" leakage rate and provide a technical justification to support its application for determining the time available to perform the OMA and describe how the potentially adverse effects of fire on valve leakage rate were considered. RAI-11 Diagnostic Instrumentation Several sections of Attachment 1 state that the need for an operator to perform a required OMA can be "readily diagnosed from the Control Room due to the numerous indications and symptoms available." In addition, for Fire Area OB-FZ-8C Attachment 1 states that any delay in the entry into the appropriate FSP or delay in suppression of the fire would not significantly affect the performance of the operator actions, since the EOPs would direct the same actions to be performed, based on system status (emphasis added). The staff has defined diagnostic instrumentation in it's response to Question 5.3.9 of Generic Letter 86-10, as follows: "Diagnostic instrumentation is instrumentation, beyond that previously identified in Attachment I to I&E Information Notice 84-09, that is needed to assure proper actuation and functioning of safe shutdown equipment and support equipment (e.g., flow rate, pump discharge pressure). Therefore, it may not be sufficient to protect only the instrumentation needed to show conformance to IN 84-09 and GL 81-12. Diagnostic instrumentation beyond that needed to detect and diagnose the location of the fire, may not be required if the OMA is taken immediately in response to fire and has been properly integrated into fire response procedures. However, appropriate diagnostic indications are necessary if the fire response procedures direct operator actions in response to observed changes in plant conditions or other unexpected symptoms of fire damage. For each OMA that relies on control room indications to detect the need for the action, provide information which demonstrates that suitable diagnostic instrumentation has been identified and that the credited indications are: (a) known to remain unaffected by a postulated fire, (b) identified in the safe shutdown equipment list and fire response procedures, (c) capable of promptly identifying the need for the action without forcing operators to enter complex diagnosis procedures and (d) that the action, once completed, has achieved its objective. 7

--. 4 RAI -12 Hot Shutdown Repairs Operator manual actions (OMAs) are defined as actions performed by operators to manipulate components and equipment from outside the MCR to achieve and maintain postfire hot shutdown, but do not include "repairs." Provide confirmation that the OMAs described in your March 3, 2009 submittal meet this definition. RAI-13 Operator Re-entry Time Attachment 1 states that the assessment of OMAs in fire-affected areas assumes that the area can be reentered within 90 minutes. Provide a technical justification to support this assumption including why a 90 minute period of time is suitable for all fire areas / zones requiring re-entry. 8