SFC-200 SERIES LED FIRE ALARM PANEL

Similar documents
FA-300 Series. LED Fire Alarm Control Panel. User Guide. FA-300 SERIES Fire Alarm Control Panel. FA-300 SERIES Fire Alarm Control Panel

CONVENTIONAL FIRE ALARM CONTROL PANELS. SFC-200 Series Fire Alarm Control Panels MEA. Features. Description

INSTALLATION & OPERATION GUIDE

CONVENTIONAL FIRE ALARM CONTROL UNITS. MR-2300 SERIES Fire Alarm Control Units MEA

FX-350/351 Series. Analog/Addressable Fire Alarm Control Panel. User Guide

INTELLIGENT FIRE ALARM CONTROL PANEL

MMX TM. Intelligent Fire Alarm Network. User Guide

RAX-LCD-LITE. Remote Annunciator. Installation and Operation Manual

To operate the 5207 you can use either the built-in touchpad or the Model 5230 Remote Annunciator.

FX Intelligent Analog Fire Alarm Control Panel. Installation and Operation Manual

User Operation Manual

OPERATOR S MANUAL MR-2100/2200. Fire Alarm Control Unit. Revision 0 Document #: LT-2002

RAM-3500-LCD. Remote Annunciator. Installation and Operation Manual

Conventional Releasing Control Panel

SFC-200 SERIES LCD FIRE ALARM PANEL

AFP-300/400 OPERATORS MANUAL INTELLIGENT FIRE DETECTION AND ALARM SYSTEM SOFTWARE VERSION 2.2 REVISION AUS 3

IDS S E C U R I T Y IDS816. User Manual. MANUAL NO A ISSUED November 2004 VERSION 1.00

Contents. Glossary

Specification/ Data Sheet

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel

MR-2602 Two Zone Fire Alarm Control Panel

Operator s Manual Part: InfoAlarm Product: 4100U, 4100ES Rev. B

IDS816 User Manual H Issued January 2009

Installation Manual CFP-105. Fire Alarm Control Panel. Version 1.0

Installation, Operating and Maintenance Manual

Data Sheet Fire Safety & Security Products. System Overview. Initiating Circuits SXL-EX FACP 7906

INTELLIGENT FIRE TECHNOLOGY. Twinflex and Multipoint V3. User Guide (TO BE RETAINED BY USER) Issue 3

ZX1e ZX2e ZX5e. Document No Issue 01 user manual

NETWORK FIRE ALARM CONTROL PANEL. Features

FA-1000 SERIES. Microprocessor-Based Fire Alarm Control Panel. Installation and Operation Manual

IDS S E C U R I T Y IDS816. User Manual MANUAL NO B ISSUED DEC 2004 VERSION 2.00

ID2000. operating manual

3200 NON-ADDRESSABLE FIRE ALARM CONTROL PANEL

INTELLIGENT FIRE ALARM CONTROL UNITS. MMX NDS Intelligent Network Fire Alarm Control Unit. Features. Description

IDS S E C U R I T Y IDS816. User Manual MANUAL NO C ISSUED APRIL 2005 VERSION 2.00

Conventional Fire Alarm System 2014 V1.2

PAT E N T System 88. COMPLIES WITH Singapore Standard : SS CP10 : 2005 British Standard : BS EN54-2 : 1998 BS EN54-4 : 1998 REV.00

Destiny Destiny Owners Manual

RANGER 8600 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL

CSP-204 CSP-208 CSP-104 CSP-108

Operating Instructions MXL Multi-Line Keyboard/Display Panel

D8024, D9024, D10024 Analog Fire Alarm Control Panels Programming Guide

INTELLIGENT FIRE ALARM CONTROL UNITS. MMX NDS Intelligent Network Fire Alarm Control Unit. Features. Description

Installation and user manual for the FX range of fire panels. 1, 2, 4 and 8 zone panels

DESTINY OWNER S MANUAL

Contents. Glossary Introduction to the IDS Notes Understanding the Keypad Indicators Operation of the Keypad...

FireNET FN-LCD-S Serial Annunciator Installation and Operation Manual

NETWORK FIRE ALARM CONTROL PANEL. Features S7010 S :111

NetworX Series NX-1500E LED Keypad

FIRE FIRE. 4100U Fire Alarm. Operator's Manual. Technical Manuals Online! -

CATALOG NUMBER. Features. Description

Control/Communicator Installation Manual

USER MANUAL COMBINED FIRE & EXTINGUISHING CONTROL PANEL COMPLIES WITH BS EN PART 1 & EN54 PARTS 2 & 4

TECHNICAL DATA. Humidity: 85% Relative Humidity (non-condensing) at 90 F (32 C) maximum.

RAM-216. Remote Multiplex Annunciator Panel. Wiring & Installation Manual COMMON TROUBLE A.C. ON SIGNAL SILENCED BUZZER SILENCE SIGNAL SILENCE

Functional Performance Test

MPC-6000 / MPC-7000 / RND-2

IDS800 USER MANUAL. Summary of Operation. + [ ] 2 IDS800 USER MANUAL NO K ISSUED APR 2003 VER 1.44

Installation and user manual for the CF5000, MF5000 and FXP5000 range of fire panels

Saffire User & Installation Manual. IMPORTANT This manual should be left with the panel after installation.

Testing the System. Battery Test. Dialer Test. Fire Drill Test (Code + [#] + 69) One-Man Fire Walk-Test (Code + [#] + 68)

NetworX NX-8V2. LED Keypad User Manual

RAPID RESPONSE Model RCP-1 Residential Control Panel 1 or 1-1/2 Inch (DN25 or DN40), 175 psi (12,1 bar) General Description.

Project No Belleville Fire Hall/Headquarters and Emergency Operations Centre Section Belleville, Ontario Page 1 of 10

DESTINY 6100 SERIES SECURITY SYSTEM OWNER S MANUAL V1 12/01

FX Fire Alarm Control Panel. Installation and Operation Manual

Using Your. Security System With LED Keypad S5030, S5031, S5032

RANGER 7600 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL

RAPID RESPONSE Model RCP-1 Residential Control Panel 1 or 1-1/2 Inch (DN25 or DN40), 175 psi (12,1 bar) General Description

DS9400 Series. Release Notes for Firmware V2.07. Fire Alarm Control Panel

U ser's Guide PC6010

Summit 3208GLD USER MANUAL. Electronics Line

Fire Command Keypad. XR5 User s Guide

ZM2 OPERATING AND MAINTENANCE INSTRUCTIONS

ABORT Light flashes during an abort delay time; is on during or after an alarm report to the central station. EMERGENCY ACTIVATION KEYS

FA-101U Fire Alarm Control Panel

Intelligent Security & Fire Ltd

Sigma. K1000 Series 1, 2, 4 & 6 Zone Fire Control Panels. Operation and Maintenance Manual. Man-1048 Issue 05 October 2009

L900 series USER MANUAL

Solution 880 Operators Manual. Issue 1.00

Panel Functions & Indicators - Key to Icons General & Zone Fire LEDs ACCEPT SOUNDERS START/ STOP RESET BUZZER MUTE KEYSWITCH DELAY ON/OFF ITEM SELECT

SFC-500 SERIES FIRE ALARM PANEL

ESP TECHNOLOGIES LIMITED

FMR Installation Instructions. Addressable Fire System Controller

TrueAlarm Fire Alarm Systems

FX-350/351/353 SERIES

Alarm Control Panel WIC-16Z4P WIC-5Z2P. User Instructions

FireSeeker Fire Alarm Control Panel Model FS-100 Installation, Operation, and Maintenance Manual

NETWORX TM. User manual NX-4

FX-3500RCU. Fire Alarm Control Panel. Installation and Operation Manual

Section 9 System Operation

FireSeeker Fire Alarm Control Panel Model FS-250 Installation, Operation and Maintenance Manual

SECURITY SYSTEM NOTES

MIR2. System Operations Manual. P/N Rev 1.5 OCT98

Noby-448 User Operating Manual & Log Book Page 1 of 12. Fire Control Panel. User Operating Manual & Log Book

QS1 Technical Reference Manual P/N REV 05 REB 14FEB13

Version 1.03 January-2002 USER S MANUAL

Operating instructions SENTRI4 Control panel based Fire detection and alarm system

MODUL-R FIRE ALARM CONTROL PANELS. MR-2900/MR-2920 Addressable Fire Alarm Control Panels MEA. Features. Description

How to Use Your Sentrol Security System

Transcription:

SFC-200 SERIES LED FIRE ALARM PANEL USER GUIDE LT-953SUM

SFC-200 Series LED Version User Guide Contents Contents... i Introduction... 1 About this Manual... 1 Technical Support... 1 Main Display... 2 The Buzzer and LED Indicators... 3 Common LED Indicators... 3 Alarm Circuit Indicators... 5 Supervisory Circuit Indicators... 5 Monitor Circuit Indicators... 5 Trouble-only Circuit Indicators... 6 Signal Circuit Indicators... 7 Main Display Buttons... 7 Circuit (Zone) Disconnect Buttons... 8 Glossary... 9 i

SFC-200 Series LED Version User Guide Introduction About this Manual This user s guide provides information on the main indicators and controls of the SFC-200 Fire Alarm Control Panel. Specifically, with this manual you will learn about what the LEDs indicate and what the buttons on the main display do. Refer to the Glossary on page 9 for an explanation of commonly used terms in this manual. Technical Support For all technical support inquiries, please contact Summit s Technical Support Department between 8 A.M. and 5 P.M. (EDT) Monday through Friday, excluding holidays. Local Phone: 905-695-3549 Toll-Free Phone: 1-866-SUMMIT-0 (1-866-786-6480) Local Fax: 905-660-4113 Toll-Free Fax: 1-888-660-4113 1

Main Display Main Display Refer to the diagram below for the LED indicators and control buttons locations. WALK TEST A.C. ON REMOTE TROUBLE COMMON ALARM CPU FAIL COMMON SUPV GROUND FAULT COMMON TROUBLE BATTERY TROUBLE SIGNAL SILENCE SYSTEM RESET FIRE DRILL AUX ACK LAMP TEST GENERAL ALARM BUZZER SILENCE ZONE-1 ZONE-2 ZONE-3 ZONE-4 ZONE-5 ZONE-6 ZONE-7 ZONE-8 ZONE-9 ZONE-10 ABORT MANUAL RELEASE NAC-1 NAC-2 RELEASE CIRCUIT-1 RELEASE CIRCUIT-2 The main display panel on the main fire alarm control board consists of: 18 common LED indicators (top half of display) Eight common buttons (top half of display) Up to 12 Initiating circuit alarm LEDs and 12 initiating circuit trouble LED indicators Four indicating circuit LEDs (labeled NAC- Notifying Appliance Circuit) Up to sixteen disconnect buttons (12 for initiating circuit & four for indicating circuits) LED indicators may be amber, red, or green, and may illuminate continuously (steady), or at one of two flash rates: Fast flash (supervisory): 120 flashes per minute Trouble flash (trouble): 20 flashes per minute Paper labels for buttons and indicators Each display is supplied with laser printable labels. These labels slide into the plastic label templates on the panel. 2

SFC-200 Series LED Version User Guide The Buzzer and LED Indicators Common LED Indicators Buzzer The buzzer sounds if there is a fire alarm, a supervisory alarm, or a trouble in the fire alarm system. It turns off if the condition causing the buzzer to sound goes away or if the Buzzer Silence Button is pressed. AC On LED A.C. ON The green AC On LED illuminates steadily as long as the main power is above minimum level. The indicator turns off when the level falls below the minimum level and the panel switches to standby (battery) power. Common Alarm LED COMMON ALARM The red Common Alarm LED will illuminate steadily whenever there is a fire alarm. If the panel is set for two stage operation, pressing the red General Alarm button will also turn on the Common Alarm indicator. This indicator will remain on until the system is reset. Common Supervisory LED Common Trouble LED Remote Trouble LED REMOTE TROUBLE COMMON SUPV COMMON TROUBLE The amber Common Supervisory LED illuminates at the fast flash rate when there is a supervisory alarm in the fire alarm system. For non-latching supervisory alarms, the Supervisory LED will turn off when the condition causing the alarm goes away. For latching supervisory alarms, this LED remains on until the panel is reset. The amber Common Trouble LED flashes at the trouble flash rate when the panel detects any trouble condition. For non-latching trouble conditions, the Common Trouble LED will turns off when the condition causing the alarm goes away. For latching trouble conditions, this LED remains on until the panel is reset. The amber Remote Trouble LED flashes at the trouble flash rate if the panel detects a trouble at the City Tie or UDACT module, communication trouble with a remote annunciator, or a local trouble at a remote annunciator. Fire Drill LED FIRE DRILL The amber Fire Drill LED illuminates steadily after you press the Fire Drill button. This LED remains on until you press the Fire Drill button again. Acknowledge LED ACK If the panel is configured as a two-stage system, the amber Acknowledge LED flashes at the fast flash rate while the Auto General Alarm timer is timing out. The Acknowledge indicator illuminates steadily when the General Alarm timer is cancelled by the pressing of the Acknowledge or Signal Silence buttons. If the Auto General Alarm timer times out and puts the panel into general alarm, this LED turns off. 3

The Buzzer and LED Indicators General Alarm LED GENERAL ALARM Walk Test LED WALK TEST If the panel is configured as a two-stage system, the red General Alarm LED illuminates steadily when the General Alarm button is pushed, a General Alarm Initiating circuit is activated, or the Auto General Alarm timer times out. Once the General Alarm LED has turned on, it will stay active until the panel is reset. The amber Walk Test indicator illuminates steadily to indicate that the panel is in walk test mode. If the panel is left in this mode for over an hour with no operator activity, the panel will return to normal and the Walk Test indicator will turn OFF. CPU Fail LED CPU FAIL The CPU Fail LED flashes amber at the trouble flash rate to indicate a microprocessor failure on the main board. Auxiliary Disconnect LED Signal Silence LED SIGNAL SILENCE AUX The amber Auxiliary Disconnect LED flashes at the trouble rate when the Auxiliary Disconnect button is pressed. It turns off when the Auxiliary Disconnect button is pressed a second time. When on, the Auxiliary Disconnect LED signifies that auxiliary alarm relay and relay adder modules (if disconnect is enabled) are not activated. If installed and enabled, the city tie module and the smart relay annunciator relays are also inactive. The Signal Silence indicator flashes amber at the trouble rate when indicating circuits are silenced either by the Signal Silence button or by the Auto Signal Silence timer. It turns off when the signals are re-sounded by a subsequent alarm or when the panel is reset. Battery Trouble LED BATTERY TROUBLE The amber Battery Trouble LED flashes at the trouble rate when the battery is either low or disconnected. Ground Fault LED GROUND FAULT The amber Ground Fault LED flashes at the trouble rate when the ground fault detector detects a ground fault on any field wiring. It turns off when the ground fault is cleared. System Reset LED SYSTEM RESET The amber System Reset LED illuminates for a short time when the System Reset button is pressed. 4

SFC-200 Series LED Version User Guide Alarm Circuit Indicators This operation applies to Initiating Circuits configured as Verified Alarm, Non-Verified Alarm, Water flow Alarm, Sprinkler Alarm, or General Alarm Circuits. The following table summarizes the indications at different events: Event Circuit Trouble LED Configuration Open circuit or (Style D)/(Class A) trouble Disconnected Circuit in Alarm Circuit in Alarm Pre-alarm Active circuit reconnected OFF Steady (red) Fast flash rate (red) OFF Verified Alarm Non-Verified Alarm Water Flow Alarm Sprinkler Alarm General Alarm Verified Alarm Sprinkler Alarm Water flow Alarm Supervisory Circuit Indicators This operation applies to initiating circuits configured as latching or non-latching supervisory circuits. The following table summarizes the indications in response to different events: Event Circuit Trouble LED Configuration Open circuit or (Style D)/(Class A) trouble Disconnected Circuit in Alarm OFF Latching Sup. Non-Latching Sup. Circuit in Alarm Steady Latching Sup. Active circuit reconnected Fast flash rate Non-Latching Sup. Monitor Circuit Indicators This operation applies to initiating circuits configured as monitor circuits. The following table summarizes the indications in response to different events: Event Circuit Trouble LED Configuration Open circuit or (Style D)/(Class A) trouble Disconnected Circuit Active Circuit Active Active circuit reconnected OFF Steady Fast flash rate Monitor Monitor 5

The Buzzer and LED Indicators Trouble-only Circuit Indicators This operation applies to initiating circuits configured as Trouble-Only Circuits. The following table summarizes the indications in response to different events: Event Circuit Trouble LED Configuration Open circuit or (Style D)/(Class A) trouble Disconnected Short Circuit Trouble Only Signal Circuit Indicators This operation applies to indicating circuits of any type. The Circuit Trouble Indicator flashes amber at the Trouble Rate to indicate short-circuit or open-circuit trouble, or if the circuit is Disconnected. Event Circuit Trouble LED Configuration Open Circuit Disconnected Short Circuit Signal 6

SFC-200 Series LED Version User Guide Main Display Buttons System Reset Button SIGNAL SILENCE The System Reset button resets the fire alarm control panel and all circuits. Signal Silence Button SIGNAL SILENCE Fire Drill Button FIRE DRILL Acknowledge Button ACK Pressing the Signal Silence button when the panel is in alarm deactivates any silenceable signal devices in the fire alarm system. Non-Silenceable signal devices are unaffected. If you press the Signal Silence button a second time, or if there is a subsequent alarm, the signals will re-sound. If the panel has been configured with a Signal Silence Inhibit timer, this button will not work until the timer times out. This button also does not work if you have pressed the Fire Drill button.in a two stage system, if the Auto General Alarm timer has timed out, this button also performs the same function as the Acknowledge button. Pressing the Fire Drill button will simulate a fire alarm by activating the fire alarm signals without transmitting an alarm to the central station. To cancel the fire drill, press the button again. If the fire alarm system goes into a real alarm while you are performing a fire drill, this button will not turn off the signals or activate any programmed relays. If the panel is not configured for two-stage operation, this button is not active. If the panel is configured for two-stage operation, pressing the Acknowledge button while the Auto General Alarm timer is timing (there is an alarm in the panel, but it is still in the first stage), the timer is cancelled and the amber Acknowledge LED illuminates steadily. General Alarm Button (or Info button for single stage system) GENERAL ALARM If the panel is not configured for two-stage operation, this button is not active. If the panel is configured for two-stage operation, pressing the General Alarm button immediately sends the panel into second stage general alarm. It will also re-activate the signals if they have been silenced during general alarm. The general alarm condition remains active until the panel is reset. Auxiliary Disconnect Button AUX Pressing the Auxiliary Disconnect button activates the auxiliary disconnect function. Pressing the button again de-activates this function. Lamp Test Button LAMP TEST Buzzer Silence Button BUZZER SILENCE Pressing and holding the Lamp Test button causes all front panel LEDs to illuminate and sounds the buzzer. Use this button to test that all LEDs in the main display are working. If you hold the Lamp Test button for more than ten seconds, the Trouble LED will illuminate. Pressing the Buzzer Silence button while the buzzer is sounding silences the buzzer. The buzzer will resound if there is a subsequent event. Pressing the button when the buzzer is not sounding has no effect. 7

Circuit (Zone) Disconnect Buttons Circuit (Zone) Disconnect Buttons Circuit (zone) disconnect buttons are provided for all initiating and indicating circuits on the fire alarm control panel. These buttons are located beside their respective indicating LEDs. Pressing a circuit disconnect button disconnects that circuit from the system and turns on its trouble indicator. While a circuit is disconnected, the panel will ignore all changes in the status (alarms and troubles) of that circuit. Circuit disconnect buttons are toggle switches; therefore, pressing an activated button a second time will reconnect the circuit. Disconnecting an active latching initiating circuit such as alarms, water-flow alarm, sprinkler alarm, general alarm, and latching supervisory does not affect its status until the panel is reset. Disconnecting active non-latching initiating circuits including non-latching supervisory and trouble-only causes them to behave as if the alarm situation has disappeared. Disconnecting an active indicating circuit immediately deactivates the circuit. When an initiating circuit disconnect button is pressed a second time, the panel checks the state of the circuit. If the circuit is active and will cause a false alarm, the Status LED flashes for ten seconds at the fast flash rate (red for alarm or amber for supervisory) without processing the input. If the circuit is not re-disconnected by then, it will be processed as a new input. 8

SFC-200 Series LED Version User Guide Glossary Alarm Condition Circuits Fast Flash Rate General Alarm Timer Indicating Circuit Initiating Circuit Occurs when devices such as detectors, pull stations, or sprinklers are activated. In a single stage system, this condition will activate all signalling devices throughout the building. In a two stage system, this condition will activate an alert signal and the General Alarm timer. Refers to an actual electrical interface and can be classified as initiating (detection), indicating (signal), or relay. The terms circuit and zone are often used interchangeably in the fire alarm industry. 120 flashes per minute is the rate at which an LED will flash to indicate a supervisory alarm. In a two stage system, the general alarm timer begins timing when the panel is in the alert stage. When the general alarm timer times out, the system will go into a general alarm, where all signals in the building will sound. A circuit in a fire alarm system that is connected to audible or visual signalling devices. A circuit in a fire alarm system that is connected to detectors, pull stations, or sprinkler flow switches. Latching Circuit A circuit that, when activated, will cause a condition on the panel that cannot be cleared until the panel is reset. LED Monitor Condition Non-latching Circuit Non- Silenceable Circuit Relay Circuit Remote Annunciator Single Stage System Silenceable Circuit The light-emitting diodes (LEDs) of the SFC-200 ar colored either amber, red, or green. When lit, LEDs provide information regarding the status of the panel. Occurs when dampers open or close, when supply and return fans are running, etc. A circuit that, when activated, will cause a condition on the panel that will be cleared once the circuit is deactivated. This term is used to describe supervisory and trouble circuits. A signal circuit that cannot be silenced by pressing the Signal Silence button. A circuit in a fire alarm system that connects relay devices (e.g. fan damper relays, etc). A device that visually indicates, either by LCD or LEDs, the floor or zone where the alarm originated. A type of fire alarm system that immediately sounds all the signals throughout the building when an alarm is detected in any part of the system. A signal circuit that can be silenced by pressing the Signal Silence button. 9

Glossary Supervisory Condition Trouble Condition Trouble Flash Rate Two Stage System Walk Test Zones Occurs when the system detects open circuits, short circuits, and grounds. A supervisory condition is one that would interfere with the operation of the fire alarm system. Occurs when an abnormal condition such as a problem in the wiring, battery or power circuits exists in the fire alarm system. 20 flashes per minute is the rate at which an LED will flash to indicate a trouble condition. A type of fire alarm system that causes an alert signal to sound when an alarm is detected in any part of the system. An alert signal advises designated persons of a fire emergency. If the alert signal is not acknowledged within five minutes of its initiation, an alarm signal will automatically sound throughout the building. A test performed by a technician to ensure that each detection device is connected to the panel and working properly. A fire alarm protected area that consists of at least one circuit. The terms circuit and zone are often used interchangeably in the fire alarm industry. 10

THE PEAK OF PROTECTION Canada 25 Interchange Way Vaughan, ON L4K 5W3 Tel: 905-695-3549 Fax: 905-660-4113 U.S.A. 60 Industrial Parkway PMB 278 Cheektowaga, NY 14227 Tel: 1-866-SUMMIT-0 Fax: 1-888-660-4113 Summit 2006 Printed in Canada Subject to change without prior notice www.summit-st.net