TERNARY ZEOTROPIC MIXTURE WITH CO 2 COMPONENT FOR R-22 HEAT PUMP APPLICATION

Similar documents
Study of R161 Refrigerant for Residential Airconditioning

Performance Study of a Water-to-Water Heat Pump Using Non-azeotropic Refrigerant Mixtures R407C

AN EXPERIMENTAL STUDY OF A REFRIGERATING PLANT WHEN REPLACING R22 WITH HFCs REFRIGERANTS

Available online at ScienceDirect. Energy Procedia 109 (2017 ) 56 63

COMPARATIVE PROPERTIES AND EFFICIENCY OF R-421A FOR RETROFIT USE TO REPLACE R-22

Performance of R-22, R-407C and R-410A at Constant Cooling Capacity in a 10

JJMIE Jordan Journal of Mechanical and Industrial Engineering

Study of R-161 refrigerant as an Alternate Refrigerant to various other refrigerants

NUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A

Low Global Warming Refrigerants For Commercial Refrigeration Systems

Low GWP Refrigerants for Air Conditioning Applications

NUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A

Keywords: Climate change; ozone depletion; Montreal protocol; eco-friendly refrigerant; hydrocarbon refrigerant; performance analysis.

SIMULATION OF POTENTIAL REFRIGERANTS FOR RETROFIT REPLACEMENT

CHAPTER 1 INTRODUCTION

A Theoretical investigation on HC Mixtures as Possible Alternatives to R134a in Vapor Compression Refrigeration

Drop-in Testing of Next-Generation R134a Alternates in a Commercial Bottle Cooler/Freezer

Refrigerants and lubricants

Comparative assessment for drop in replacement of R134a in domestic refrigerator.

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger

Refrigeration Cycle And Compressor Performance For Various Low GWP Refrigerants

Effects of Non-Uniform Refrigerant and Air Flow Distributions on Finned- Tube Evaporator Performance

Experimental Study on Compact Heat Pump System for Clothes Drying Using CO 2 as a Refrigerant. Abstract

R-407A R-448A R-449A

ASSESSMENT OF R430A REFRIGERANT AS A POSSIBLE SUBSTITUTE TO R134A REFRIGERANT IN LARGE CAPACITY FREEZER

Investigation of Evaporator Performance with and without Liquid Overfeeding

Role of Nano-technology for improving of thermal performances of vapour compression refrigeration system (VCRS): An Overview

STUDY ON THE CONTROL ALGORITHM OF THE HEAT PUMP SYSTEM FOR LOAD CHANGE

Experimental investigation on the performance of air conditioner using R32 Refrigerant

Performance Analysis of Electronic Expansion Valve in 1 TR Window Air Conditioner using Various Refrigerants

Modeling and Testing of an R-23/R-134a Mixed Refrigerant System for Low Temperature Refrigeration

TEST REPORT #14. System Drop-In Test of Refrigerant Blend ARM-42a in an Air-Cooled Screw Chiller

REPLACING HARMFUL CFC 12 BY ECO-FRIENDLY REFRIGERANT IN MILK CHILLER

Performance of CO2 Cycles with a Two-Stage Compressor

Why Hydrocarbons Save Energy

WORK STUDY ON LOW TEMPERATURE (CASCADE) REFRIGERATION SYSTEM

Air-Cooled Heat Exchanger Performance for R410A

Due to its low temperature glide about 1.5 approx. (75% less than R-407C and R-427A), it is suitable for a wide range of applications.

A Comparison Between Refrigerants Used In Air Conditioning

Australian Journal of Basic and Applied Sciences. Investigation of New Eco Friendly Refrigerant Mixture Alternative to R134a in Domestic Refrigerator

CHAPTER 1 INTRODUCTION

Performance Measurement of R32 Vapor Injection Heat Pump System

THE USE OF HYDROCARBONS PROPANE AND ISOBUTANE IN REFRIGERATION SYSTEMS

Design of Divided Condensers for Desiccant Wheel-Assisted Separate Sensible and Latent Cooling AC Systems

Performance Evaluation of Eco- Friendly Alternate Refrigerants for VCRS

The Potential of HFC-134a and HFC-152a to Replace CFC-12 in Medium Temperature Heat Pump Applications

HCFC-22 replacement with drop-in and retrofit HFC refrigerants in a two-stage refrigeration plant for low temperature

EVALUATION OF REFRIGERANT R290 AS A REPLACEMENT TO R22

Refrigerant Glide and Effect on Performances Declaration

Study of Performance of Binary Mixture of R134a and R161 as a Substitution of R134a in a Domestic Refrigerator

POTENTIAL OF NON - AZEOTROPIC REFRIGERANT MIXTURE AS WORKING REFRIGERANT IN HOT WATER HEAT PUMPS. FJ Smit and JP Meyer

Chapter 2. Alternatives to HCFCs and their Characteristics

Subscripts 1-4 States of the given system Comp Compressor Cond Condenser E Evaporator vol Volumetric G Gas L Liquid

Efficiency of Non-Azeotropic Refrigerant Cycle

Assessment of LPG as a possible alternative to R-12 in domestic refrigerators

Control Method Of Circulating Refrigerant Amount For Heat Pump System

Experimental Study on Performance Parameters for Refrigerants R22, R410a and R404a at Various Air Outlet Temperatures

Behavior of R410A Low GWP Alternative Refrigerants DR-55, DR-5A, and R32 in the Components of a 4-RT RTU

Theoretical and Experimental Analysis of the Superheating in Heat Pump Compressors. * Corresponding Author ABSTRACT 1.

Experimental Investigate on the Performance of High Temperature Heat Pump Using Scroll Compressor

Effect of evaporator temperature on vapor compression refrigeration system

Replacement Refrigerants for Water Chillers

A COMPARATIVE STUDY FOR RETROFITTING OF R-12 VAPOUR COMPRESSION REFRIGERATION SYSTEM BY ECO- FRIENDLY REFRIGERANTS R-134A, R-413A, R-423A

Lower GWP Refrigerants Compared to R404A for Economizer Style Compressors

Effect of magnetic field on the performance of new refrigerant mixtures

IR-REVERSIBILITY ANALYSIS OF A SPLIT TYPE AIRCONDITIONER USING R600a AS REFRIGERANT

Performance Characteristics and Optimization of a Dual-Loop Cycle for a Domestic Refrigerator- Freezer

RS-70 is suitable as a direct replacement for R-22 in low, medium and high temperatures in a great number of applications:

EXPERIMENTAL INVESTIGATIONS ON AUTOMOBILE AIR CONDITIONERS WORKING WITH R134a AND R290/R600a AS AN ALTERNATIVE

*Corresponding author;

4th International Conference on Sensors, Measurement and Intelligent Materials (ICSMIM 2015)

International Research Journal of Engineering and Technology (IRJET) e-issn: Volume: 04 Issue: 05 May p-issn:

IJISET - International Journal of Innovative Science, Engineering & Technology, Vol. 2 Issue 12, December

TEST REPORT #43. System Drop-in Tests of Refrigerants L-41-1, L-41-2, and R-32 in Water-to- Water Heat Pump

R-404A Alternative with Low Compressor Discharge Temperature

Main Anthropogenic Sources of Greenhouse Gases Refrigerants

Experimental Investigation Of A New Low- Approach Evaporator With Reduced Refrigerant Charge

IJESRT. (I2OR), Publication Impact Factor: (ISRA), Journal Impact Factor: 2.114

PRACTICAL EXPERIENCE WITH AN ALTERNATIVE TO R-22 BASED ON R-32lR /R a. R E Low, B E Gilbert, T W Dekleva.

DROP-IN EVALUATION OF REFRIGERANT 1234YF IN A RESIDENTIAL INTEGRAL HEAT PUMP WATER HEATER

Performance Comparison of Hydronic Secondary Loop Heat Pump and Conventional Air-Source Heat Pump ABSTRACT 1. INTRODUCTION

HEFAT th International Conference on Heat Transfer, Fluid Mechanics and Thermodynamics Sun City, South Africa Paper number:pp1

Performance Comparison of Ejector Expansion Refrigeration Cycle with Throttled Expansion Cycle Using R-170 as Refrigerant

Department of MCE, Islamic University of Technology 2. Abstract

Thermodynamic study of R134a in Vapour Compression Refrigeration System in Summer Climate

Performance Evaluation of R290 as Substitution to R22 & Mixture of Them in Vapour Compression Refrigeration System

Performance Investigation of Refrigerant Vapor- Injection Technique for Residential Heat Pump Systems

Refrigerant Mass and Oil Migration During Start-up Transient

Comparison of CFC-114 and HFC-236ea Performance in Shipboard Vapor Compression Systems

Theoretical performance evaluation of R134a and its low GWP Hydrocarbon alternatives in Domestic Refrigerator

International Journal of Advance Engineering and Research Development

Volume 6, Issue 3(2018) ISSN International Journal of Advance Research and Innovation

Effects of evaporator load on vapour compression refrigeration system using ecofriendly hydrocarbon refrigerants with sub cooling

2016 Annual Conference

Life-Cycle Energy Costs and Greenhouse Gas Emissions for Gas Turbine Power

THEORETICAL INVESTIGATION OF THE PERFORMANCE OF SOME ENVIRONMENT-FRIENDLY REFRIGERANTS IN A SUB-COOLING HEAT EXCHANGER REFRIGERATION SYSTEM

Framtidens köldmedier

Performance Assessment of Three Eco-Friendly Hydro-Fluorocarbon and Hydrocarbon Refrigerant Mixtures as R22 Alternatives in Refrigeration Systems

The Circulation Composition Characteristic of the Zeotropic Mixture R1234ze(E)/R32 in a Heat Pump Cycle

Experimental Investigation on the Performance of Ground-source Heat Pump with the Refrigerant R410A

Transcription:

TERNARY ZEOTROPIC MIXTURE WITH CO 2 COMPONENT FOR R-22 HEAT PUMP APPLICATION Kazimierz MACZEK Jaros aw MÜLLER Kazimierz WOJTAS TECHNICAL UNIVERSITY of CRACOW Institute of Thermal Engineering and Air Protection ul. Warszawska 24, 31-155 Kraków, POLAND ABSTRACT Piotr A. DOMANSKI NATIONAL INSTITUTE of STANDARD and TECHNOLOGY Building Environment Division Gaithersburg, MD 899, USA The paper presents results of a simulation and laboratory study of the performance of a zeotropic mixture R- 744/32/134a in a water-heating heat pump. The goal of the research was to obtain operating parameters comparable to a system charged with R-22. The performance of R-22 served as a reference for the ternary mixture studied. A semi-theoretical simulation model was used first to examine the influence of R-744 properties on the mixture performance and to determine the optimum mixture composition. The formulated mixture, R-744/32/134a (7/31/62) was then tested in a laboratory. The experimental apparatus consisted of a counter-flow condenser and evaporator. The primary measurement of capacity was performed on the heat-transfer fluid side. Compressor power was obtained form speed and torque measurements on the open compressor s shaft. Compared with the performance of R-22, the COP of R-744/32/134a was better by 9.5% at a 21% increase in volumetric capacity. 1. INTRODUCTION The objective of this research project was to demonstrate a successful operation of a high efficiency heat pump employing a zeotropic mixture with a zero ozone-depletion and a small greenhouse warming potentials (ODP and GWP, respectively). The project addresses the technical challenges resulting from international agreements regulating the use of ozonedepleting substances. The signatory countries of the Montreal Protocol agreed to phase out production of chlorine-containing refrigerants with deadlines depending on the ODP of the fluids [1]. A search for a proper substitute has to consider factors such as capacity, efficiency, flammability, oil/refrigerant solubility, toxicity, etc. [2, 3]. This study investigated possible R-22 alternatives with the goal of achieving a comparable system capacity and 10% improvement in Coefficient of Performance (COP). The tests were performed in COCH (Refrigerating Machinery Research Center in Cracow, Poland). Nomenclature COP - Coefficient of Performance M - torque [N m] n - compressor RPM P comp - compressor power [kw] p - pressure [kpa] Q vol - volumetric heating capacity [kj/m 3 ]

Q - heating capacity [kw] RPM - compressor speed - revolutions per minute T glide - refrigerant temperature difference [K] T in - water inlet temperature [ o C] T out - water outlet temperature [ o C] T - water temperature difference [K] V - water volumetric flow rate [l/min] HTF - heat-transfer fluid 2. DESCRIPTION OF TEST FACILITY The test facility, shown in Figure 1, was designed and constructed to allow on-line comparison of an R-22 heat pump with a heat pump charged with an alternative refrigerant. The rig consisted of two identical heat pump systems connected to the same heat-sink and heatsource loops for maintaining operating conditions. The compressors had a nominal refrigeration capacity of 11.5 kw (for R-22) and were equipped with electric motors of a nominal electric power of 7.5 kw. The evaporators and condensers had a tube-in-tube counterflow configuration to facilitate temperature glide matching between the refrigerant and HTFs. Both heat exchanger types consisted of ten sections made with 2.5m long copper tubes; however, other tube dimensions were different. For the evaporators, the external tube was 42mm x 1.5mm (external diameter x wall thickness) and internal pipe was 28mm x 1.5mm. For the condensers, the external tube was 35mm x 1.5mm and the internal tube was 22mm x 1mm. Water was used as the heat-transfer fluid (HTF). All heat exchangers were properly insulated. The following control and safety devices were installed to ensure proper and reliable operation of the experimental rig: - electronic expansion valve to control vapor superheat at the evaporator outlet at different operating conditions - electrically-heated thermostatic water tanks equipped with power control and mixing pumps for stabilizing temperature of the water supplied to the evaporators and condensers - frequency transducers for controlling each compressor s speed - all required safety devices for each compressor - safety temperature sensors at the water outlet of each heat exchanger to guard against water freezing in the evaporator and excessively high temperature in the condenser. The control system was designed to allow both manual and microprocessor control of the experimental rig. The data acquisition system was based on a personal computer with PC-add on cards and multiplexers installed. The system collected data from: - 106 temperature measurement points (thermocouples) - 10 pressure measurement points (pressure transducers) - 4 water flow measurement points (two turbines and two electromagnetic meters) - 2 liquid refrigerant mass flow measurement points - 2 compressor power inlet measurement points (watt-hour meters) - 1 torque meter for torque and RPM reading.

In addition to measurements recorded on the data acquisition system, refrigerant and water temperatures along condenser and evaporator were displayed on separate displays located on the test rig. Water inlet and outlet temperatures were simultaneously measured by a data log system working independently of the basic data acquisition system. PUMP FLOWMETER FLOWMETER PUMP WATER TANK ELECTRIC REHEAT PUMP HX CHILLED WATER POOL EV CONDENSER EV CONDENSER HEAT DEMAND EXP. VALVE EVAPORATOR EXP. VALVE COMPRESSOR EVAPORATOR COMPRESSOR PUMP WATER TANK PUMP HX FLOWMETER FLOWMETER ELECTRIC REHEAT EV - ELECTROMAGNETIC VALVE Fig. 1. A schematic layout of test facility 3. TEST PROCEDURE Cycle simulations using a semi-theoretical model, CYCLE-11 [4], preceded laboratory tests. The goal of these simulations was to derive an optimum mixture (i.e., mixture components and their mass fractions) for use in the laboratory test program. Eight fluids were considered as possible mixture components: R-123, R-124, R-152a, R-134a, R-290, R-32, R-125, and R-744 [5, 6, 7]. A mixture of R-744, R-32 and R-134a showed the most promising results and, consequently, was prepared for testing. The tests included R-22 and R-32/134a as a reference. Table 1 shows selected properties of the tested fluids obtained from REFPROP [8].

Table 1. Selected properties of the tested fluids Refrigerant Mass Fraction (%) Molar Mass [g/mol] T (1) glide [K] Q vol (2) [kj/m 3 ] Liquid (3) Thermal Conductivity [W/(m K)] Liquid (3) Viscosity [µp] R-22 100 86.47 0 40.4 0.09671 2194 R-32/134a 29/71 79.79 6.7 3843.1 0.1129 2290 R-744/32/134a 7/31/62 73.39 17.1 4869.6 0.1178 2157 (1) T dew point - T bubble point at saturation pressure corresponding to T dew point = 0 o C (2) Calculated for average T evaporator = 2.5 o C and T condenser = 52.5 o C (3) Saturated liquid at pressure corresponding to Tdew point = 0 o C Table 2. Complete range of operating conditions (HTF temperatures) Evaporator Condenser T in [ o C] T [K] T in [ o C] T [K] where: 35 15 40 15 10 45 15 35 15 40 15 15 45 15 T in - water inlet temperature T - water temperature change in the heat exchanger The complete project involved an extensive test program shown in Table 2 in terms of operating temperatures of the HTFs. This paper focuses on the results obtained for the waterheating applications, which is indicated in Table 2 by the entries made in a bold font. As shown in the table, the tests were performed at the specified temperatures of water at the inlet and outlet of the condenser and the evaporator. The water temperatures were controlled within ±0.2 K. Refrigerant superheat at the evaporator outlet and subcooling at the condenser outlet were set to

5 K ± 0.2 K. The test program included six compressor speeds from 1000 RPM to 1500 RPM at a 100 RPM step (see Table 3). Although initial tests were performed using both compressors, the final tests (reported here) used the compressor equipped with the torque meter. This eliminated the influence of changing electric motor efficiency with the load, and allowed the compressor power to be obtained from torque and RPM readings provided by the torque meter. The reported system capacities are the water-side capacities obtained from measurements of a water mass flow rate and water temperature difference between condenser inlet and outlet. The mineral oil supplied with the compressor was used during R-22 tests. This oil was replaced with a polyolester oil for experiments with the binary and ternary mixture. No hardware changes were made between different tests except a filter-dryer. The mixture composition was measured by means of gas chromatograph. The samples were taken simultaneously from the liquid line and the compressor discharge line. The measurements were repeated several times for each mixture tested. Table 4 presents relative uncertainties of the basic measurements and the compounded uncertainties for capacity, compressor power and COP. Table 3. Operating conditions for tests with different compressor speed evaporator T in /T out [ o C] condenser T in /T out [ o C] superheat [K] subcooling [K] compressor speed [RPM] /5 35/50 5 5 1000-1500 (step 100) Table 4. Relative uncertainties (%) of the measurements (approx. 95% confidence level) T V M n p P comp Q COP 1.6 0.5 0.2 0.2 0.13 1.2 1.7 2.1 4. RESULTS The obtained test data for the water heating application provided the basis for comparison of the refrigerants using two methods: drop-in evaluation and constant-capacity evaluation. Drop-in Comparison The tests were run at 1500 compressor RPM to perform a drop-in comparison. In these tests refrigerant charge and the opening of the expansion valve were adjusted to obtain the same evaporator superheat and condenser subcooling (5 K). Table 5 presents the obtained heating capacity and COP. The mixtures performed better than R-22, both in terms of capacity and COP. The capacity increase over that of R-22 was 2.9% for R-32/134a and 18.6% for R-744/32/134a. For COP, the increases were 3.9% and 2.5% for the binary and ternary mixture, respectively. The significant 18.6% increase in capacity achieved by the R-744/32/134a mixture is related to its higher evaporator pressure (Table 6). While pressures for R-22 and R-32/134a were similar, 496 kpa and 498 kpa in the evaporator and 1959 kpa and 99 kpa in the condenser, those for the R-744/32/134a mixture were higher, 571 kpa and 2680 kpa in the evaporator and the condenser, respectively. Pressure drops in both evaporator and condenser were small for all the fluids (approximately 15- kpa).

Table 5. mixture R-32/134a (29/71) Heating capacities and COPs for tests with 1500 compressor RPM Q Q COP R 22 COP COPR 22 100% 100% Q COP Q [kw] R 22 R 22 [%] [%] 17.7 2.9 3.801 3.9 R-744/32/134a (7/31/62).4 18.6 3.750 2.5 Table 6. Refrigerant pressures at different compressor speeds Fluid Compressor speed [RPM] Evaporator outlet [kpa] Condenser inlet [kpa] R-22 1500 496 1959 R-32/134a 1500 498 99 R-744/32/134a 1500 571 2680 R-32/134a 1448 498 95 R-744/32/134a 1185 585 2514 Constant-Capacity Comparison Since R-22 showed a lower heating capacity than the two mixtures studied, the R-22 heating capacity at 1500 compressor RPM was selected as a target capacity for the constant-capacity comparison. This allowed the use of the test data of R-22 at 1500 compressor RPM directly. To obtain the mixtures COPs for the same capacity level, the mixtures measured data were correlated as a function of compressor speed, and used these correlations for calculating performance at the compressor speeds that resulted in the capacity match. Figures 3 and 4 show this process graphically for R-744/32/134a, for which the capacity match with Q R-22 occurred at 1185 RPM. In these figures, the solid lines were generated by linear fits to the test data. For comparison, the figures include simulated performance, dotted lines predicted by CYCLE-11. The solid and dotted lines do not overlap; however, they show a similar trend validating CYCLE-11 as a useful support tool for a laboratory effort. Table 7 shows compressor speeds and COPs for the mixtures for the constant-capacity comparison. The 1448 RPM indicated for R-32/134a means a 3.5% reduction of the required compressor displacement. The additional benefit measured for R32/134a is its COP that exceeded that for R-22 by 5.2%. For the R-744/32/134a mixture, the reduction of RPM was more considerable, down to 1185 RPM, which corresponds to a 21% reduction of the

compressor displacement required to match the capacity of R-22. The COP of R-744/32/134a was the highest of the fluids tested, exceeding that of R-22 by 9.5%. The high COP of R- 744/32/134a was achieved because of several factors. The glide-matching of the HTF and zeotropic mixtures was probably the most influential one. Figure 2 presents the glides of the HTF and refrigerant along heat exchanger sections. Other favorable factors were good transport properties and low molar heat capacity. The latter promotes good COP in the basic refrigeration cycle. Although no flammability tests were performed, it may be expected that the R- 744/32/134a mixture is not flammable. This speculation is based on the fact that the R-32/134a (30/70) mixture is marginally flammable, and bracketing the flammable component, R-32, by non-flammable R-744 and R-134a may render this ternary mixture to be safer. Table 7. Compressor speeds and COPs for constant-capacity evaluation COP COPR RPM COP mixture R-32/134a (29/71) R-744/32/134a (7/31/62) R 22 [%] 1448 5.2 1185 9.5 22 100%

100 90 80 water R-744/32/134a C] Temperature [ 70 60 50 40 30 1 2 3 4 5 6 7 8 9 10 11 Fig. 2. Temperature glide along condenser sections for R-744/32/134a and water

25 15 correlated capacity simulated capacity measured capacity (Q-QR22)*100/QR22 [%] 10 5 0-5 -10-15 1000 1100 1185 10 1300 1400 1500 Com pressor speed [RPM] Fig. 3. Heating capacity of R-744/32/134a at different compressor speeds referenced to heating capacity of R-22 at 1500 compressor RPM 18 16 simulated COP correlated COP measured COP (COP-COP_R22)*100/COP_R22 [%] 14 12 10 9.53 8 6 4 2 0 1000 1100 1185 10 1300 1400 1500 C o m p resso r sp eed [R P M ] Fig. 4. COP of R-744/32/134a at different compressor speeds referenced to COP of R-22 at 1500 compressor RPM

5. CONCLUSIONS 1. Employing CO 2 as a third component to binary mixture R-32/134a caused an increase of system heating capacity and an increase of COP. 2. Ternary mixture R-744/32/134a (7/31/62) is applicable as "drop-in" replacement of R-22 only for low temperature heat pumps because of its excessive condensing pressure. 3. The mixture R-744/32/134a (7/31/62) seems to be very promising as an R-22 substitute in newly designed refrigerating/heat pumping systems. The experimental COP increase in comparison with R-22 reached almost 10% for a system using counter-flow heat exchangers. 6. REFERENCES [1] Bivens D.B. and D.A. Didion - "The Role of Refrigerant Mixtures as Alternative CFCs", Proceedings of ASHRAE's 1989 CFC Technology Conference, 1989 [2] Kruse H. - "European Research Concerning CFC and HCFC Substitution", Int. Journal of Refrigeration, vol.17, no. 3, 1994 [3] Nakatani K., Ikoma R.K. and I.Yosida, "Development of High Temperature Heat Pump Using Alternative Mixtures', Proceedings of ASHRAE - Purdue CFC Conference, July 1990, Purdue University, U.S.A. [4] Doma ski P.A., Mc Linden M.O. "A simplified cycle simulation model for the performance rating of refrigerants and refrigerant mixtures" - Int. Journal of Refrigeration, 1992, vol. 15, no. 2 [5] Garofano A. Fabbertti V. - "Theoretical comparison on refrigerant cycle for air conditioning system operating with R22, R134a blends and relative experimental tests" - 'CFC's The Day After", II Conf. B1/2, E1/2, Padova, Italy, 1994 [6] Hesse U, Kruse H - "Alternatives for CFC's and HCFC's based on CO 2 " - IIR Commission B1/2, Ghent, Belgium, 1993 [7] Lorentzen G. - "Large Heat Pumps Using CO 2 Refrigerant" - IIR Commission B1/2, Ghent, Belgium, 1993 [8] Huber M., Gallagher J., McLinden M., Morrison G., NIST Thermodynamic Properties of Refrigerants and Refrigerant Mixtures Database (REFPROP), Version 5.0, National Institute of Standards and Technology, Gaithersburg, MD USA, 1996 7. ACKNOWLEDGMENTS This project was sponsored by the Polish-American Maria Sklodowska-Curie II Joint Found. The authors also want to thank Dr. D.Bivens (Du Pont) and Mr. B. Gilbert (ICI) for providing refrigerants for the project.