SIMULATION OF POTENTIAL REFRIGERANTS FOR RETROFIT REPLACEMENT

Similar documents
EVALUATION OF REFRIGERANT R290 AS A REPLACEMENT TO R22

THEORETICAL INVESTIGATION OF THE PERFORMANCE OF SOME ENVIRONMENT-FRIENDLY REFRIGERANTS IN A SUB-COOLING HEAT EXCHANGER REFRIGERATION SYSTEM

Available online at ScienceDirect. Energy Procedia 109 (2017 ) 56 63

Study of R161 Refrigerant for Residential Airconditioning

A Theoretical investigation on HC Mixtures as Possible Alternatives to R134a in Vapor Compression Refrigeration

NUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A

NUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A

Subscripts 1-4 States of the given system Comp Compressor Cond Condenser E Evaporator vol Volumetric G Gas L Liquid

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger

Low GWP Refrigerants for Air Conditioning Applications

International Journal of Advance Engineering and Research Development

Australian Journal of Basic and Applied Sciences. Investigation of New Eco Friendly Refrigerant Mixture Alternative to R134a in Domestic Refrigerator

Thermal Design of Condenser Using Ecofriendly Refrigerants R404A-R508B for Cascade Refrigeration System

ASSESSMENT OF R430A REFRIGERANT AS A POSSIBLE SUBSTITUTE TO R134A REFRIGERANT IN LARGE CAPACITY FREEZER

Performance Study of a Water-to-Water Heat Pump Using Non-azeotropic Refrigerant Mixtures R407C

Role of Nano-technology for improving of thermal performances of vapour compression refrigeration system (VCRS): An Overview

Environment Protection Engineering

International Research Journal of Engineering and Technology (IRJET) e-issn: Volume: 04 Issue: 05 May p-issn:

Thermodynamic Analysis of Cascade Refrigeration System Using R12-R13, R290-R23 and R404A-R23

Implementation and testing of a model for the calculation of equilibrium between components of a refrigeration installation

Part load performance analysis of vapour compression refrigeration system with hydrocarbon refrigerants

Control Method Of Circulating Refrigerant Amount For Heat Pump System

A Comparison Between Refrigerants Used In Air Conditioning

Performance Evaluation of Eco- Friendly Alternate Refrigerants for VCRS

AN EXPERIMENTAL STUDY OF A REFRIGERATING PLANT WHEN REPLACING R22 WITH HFCs REFRIGERANTS

TERNARY ZEOTROPIC MIXTURE WITH CO 2 COMPONENT FOR R-22 HEAT PUMP APPLICATION

JJMIE Jordan Journal of Mechanical and Industrial Engineering

Oyelami S., Bolaji B. O.

Performance and exergy analysis of vapour compression refrigeration system using various alternative of R134a.

REPLACING HARMFUL CFC 12 BY ECO-FRIENDLY REFRIGERANT IN MILK CHILLER

Keywords: Climate change; ozone depletion; Montreal protocol; eco-friendly refrigerant; hydrocarbon refrigerant; performance analysis.

Volume 6, Issue 3(2018) ISSN International Journal of Advance Research and Innovation

Comparative assessment for drop in replacement of R134a in domestic refrigerator.

η second law = Second law efficiency

Refrigerant Glide and Effect on Performances Declaration

Experimental investigation on the performance of air conditioner using R32 Refrigerant

Evaluation of HCFC Alternative Refrigerants

POTENTIAL OF NON - AZEOTROPIC REFRIGERANT MIXTURE AS WORKING REFRIGERANT IN HOT WATER HEAT PUMPS. FJ Smit and JP Meyer

IJISET - International Journal of Innovative Science, Engineering & Technology, Vol. 2 Issue 12, December

Study of Performance of Binary Mixture of R134a and R161 as a Substitution of R134a in a Domestic Refrigerator

Comparative Study of Transcritical CO 2 Cycle with and Without Suction Line Heat Exchanger at High Ambienttemperature

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger

A COMPARATIVE STUDY FOR RETROFITTING OF R-12 VAPOUR COMPRESSION REFRIGERATION SYSTEM BY ECO- FRIENDLY REFRIGERANTS R-134A, R-413A, R-423A

Energy Performance of Eco-friendly R152a and R600a Refrigerants as Alternative to R134a in Vapour Compression Refrigeration System

CHAPTER 1 INTRODUCTION

Low Global Warming Refrigerants For Commercial Refrigeration Systems

Performance of CO2 Cycles with a Two-Stage Compressor

Study of R-161 refrigerant as an Alternate Refrigerant to various other refrigerants

Effects of evaporator load on vapour compression refrigeration system using ecofriendly hydrocarbon refrigerants with sub cooling

Numerical Studies On The Performance Of Methanol Based Air To Air Heat Pipe Heat Exchanger

Experimental Study on Performance Parameters for Refrigerants R22, R410a and R404a at Various Air Outlet Temperatures

EXPERIMENTAL INVESTIGATIONS ON AUTOMOBILE AIR CONDITIONERS WORKING WITH R134a AND R290/R600a AS AN ALTERNATIVE

WORK STUDY ON LOW TEMPERATURE (CASCADE) REFRIGERATION SYSTEM

Volume 4, Issue 1 (2016) ISSN International Journal of Advance Research and Innovation

Performance Evaluation of Vapour Compression System with R22 and Environment-Friendly Refrigerant

Theoretical analysis of low GWP mixture R600a/ R1234ze as a possible alternative to R600a in domestic refrigerators

Improving and Comparing the Coefficient of Performance of Domestic Refgirator by using Refrigerants R134a and R600a

Due to its low temperature glide about 1.5 approx. (75% less than R-407C and R-427A), it is suitable for a wide range of applications.

ISSN: [Sachuthananthan * et al., 5(10): October, 2016] Impact Factor: 4.116

Behavior of R410A Low GWP Alternative Refrigerants DR-55, DR-5A, and R32 in the Components of a 4-RT RTU

Performance Evaluation of R290 as Substitution to R22 & Mixture of Them in Vapour Compression Refrigeration System

Performance Assessment of Three Eco-Friendly Hydro-Fluorocarbon and Hydrocarbon Refrigerant Mixtures as R22 Alternatives in Refrigeration Systems

CHAPTER 1 INTRODUCTION

Comparative Exergy Analysis of Vapor Compression Refrigeration System Using Alternative Refrigerants

Thermodynamic analysis of the performance of a vapour compression refrigeration system, working with R290 and R600a mixtures

Lower GWP Refrigerants Compared to R404A for Economizer Style Compressors

Performance Evaluation of R290 as Substitution to R22 & Mixture of Them in Vapour Compression Refrigeration System

"COP Enhancement Of Domestic Refrigerator By Sub cooling And Superheating Using Shell &Tube Type Heat Exchanger"

Design of Divided Condensers for Desiccant Wheel-Assisted Separate Sensible and Latent Cooling AC Systems

Performance Measurement of R32 Vapor Injection Heat Pump System

Experimental Study on Compact Heat Pump System for Clothes Drying Using CO 2 as a Refrigerant. Abstract

An Experiment of Heat Exchanger Produces Hot Water Using Waste Heat Recovery from Air Conditioning

Experimental Research On Gas Injection High Temperature Heat Pump With An Economizer

IR-REVERSIBILITY ANALYSIS OF A SPLIT TYPE AIRCONDITIONER USING R600a AS REFRIGERANT

Thermodynamic study of R134a in Vapour Compression Refrigeration System in Summer Climate

Effect of capillary diameter on the power consumption of VCRS using different refrigerants

Scientific Journal of Maritime Research 31 (2017) Faculty of Maritime Studies Rijeka, 2017

Alternatives in the AC & Chiller Sectors. Sukumar Devotta and Lambert Kuijpers OORG Refrigeration

Performance characteristics of low global warming potential R134a alternative refrigerants in ejector-expansion refrigeration system

Performance Comparison of Ejector Expansion Refrigeration Cycle with Throttled Expansion Cycle Using R-170 as Refrigerant

The analysis proceeded by adopting the ASHRAE guideline for conventional HVAC chiller applications. This guideline is summarized in Table II.

Theoretical performance evaluation of R134a and its low GWP Hydrocarbon alternatives in Domestic Refrigerator

Chapter 10. Refrigeration and Heat Pump Systems

Experimental Investigate on the Performance of High Temperature Heat Pump Using Scroll Compressor

Dynamic Simulation of Liquid Chillers

A Review of Hydroflorocarbons (HFC S) Refrigerants as an Alternative to R134a Refrigerant

Theoretical and Experimental Analysis of the Superheating in Heat Pump Compressors. * Corresponding Author ABSTRACT 1.

Technology Application of Environmental Friendly Refrigeration (Green Refrigeration) on Cold Storage for Fishery Industry

A RECENT REVIEW OF REFRIGERANT R-1234YF AND R-1234ZE (E)

Experimental study of Hydrocarbon Refrigerant Mixture R290/R600a as an alternative to Refrigerant R134a used in a Domestic Refrigerator

RS-70 is suitable as a direct replacement for R-22 in low, medium and high temperatures in a great number of applications:

Figure 1: Overview of CO 2 evaporator types

Low GWP Refrigerants for Air Conditioning and Chiller Applications

Design, Manufacturing of Chilled Water System for Process Cooling Application

Performance Analysis of Electronic Expansion Valve in 1 TR Window Air Conditioner using Various Refrigerants

ADVANCES in NATURAL and APPLIED SCIENCES

HCFC-22 replacement with drop-in and retrofit HFC refrigerants in a two-stage refrigeration plant for low temperature

Performance of an Improved Household Refrigerator/Freezer

Experimental Analysis Of Vapour Compression Refrigeration System With Superheating By Using R-134a, R-12, R-717 Refrigerant

International Journal of Research in Engineering and Innovation Vol-2, Issue-2 (2018),

Transcription:

SIMULATION OF POTENTIAL REFRIGERANTS FOR RETROFIT REPLACEMENT R. Prapainop 1* and K. O. Suen 2 1 Department of Mechanical Engineering, Kasetsart University, Si Racha Campus, Chonburi, Thailand 2 Department of Mechanical Engineering, University College London, London, United Kingdom *E-Mail: sfengrcp@src.ku.ac.th ABSTRACT This paper shows two approaches of refrigerant comparison for retrofit replacement. One is the screening based on refrigerant thermo-physical properties and cycle performance analysis, another method is the full simulation. The impact of component sizes on the refrigerant temperatures and performance is included in the full simulation while it is ignored in the former analysis. The methods are exemplified by comparing some common refrigerants, including R32, R410A, R125, R1270, R22, R407C, R290, R134a, R600a and R600. Keywords: refrigerant, screening, full simulation, retrofit, replacement. Nomenclature A area [m 2 ] c p isobaric specific heat [kj kg 1 K 1 ] C heat capacity = mass flow rate isobaric specific heat [kw K 1 ], COP coefficient of performance (= Q cool / Wcom ) [---] GWP global warming potential h specific enthalpy [kj kg 1 ] HCFC hydro chlorofluorocarbon HX heat exchanger HTC heat transfer coefficient [W m 2 K 1 ] HTF heat transfer fluid L length [m] m& mass flow rate [kg s 1 ] NBP normal boiling point [ C] NTU number of transfer unit [---] ODP ozone depleting potential [---] P pressure [kpa] Q capacity [kw] SC degree of sub-cooling [ C or K] SH degree of superheating (for evaporator), or degree of de-superheating (for condenser) [ C or K] T temperature [ C or K] V & sw compressor swept volume rate [m 3 /s] VRC volumetric refrigerating capacity or effect (= hrefrig ν suc ) [kj/m 3 ] W compressor work [kw] the difference h enthalpy difference [kj kg 1 ] h refrig refrigerating effect [kj kg 1 ] T w the difference between inlet and outlet HTF temperatures of the entire heat exchanger [ C] Greek symbols ε effectiveness η efficiency [%] ρ density [kg m 3 ] ν specific volume [m 3 kg 1 ] Subscripts act actual c, cond condenser or condensation or conduction cool cooling com compressor dew dew (saturated vapour state) dis discharge e, evap evaporator, evaporation exv expansion valve in inlet isen isentropic min minimum out outlet r refrigerant SC sub-cooling SH superheating suc suction vol volumetric w water or heat transfer fluid INTRODUCTION Among available refrigerants, R-22 has been widely used for many years. It possesses many desirable physical and thermodynamic properties and can be employed in a wide range of applications and temperatures with good system performance. It is also safe in terms of toxicity and flammability. Nevertheless, in response to Montreal Protocol [1], R22, as the last remaining ozone depleting HCFC, will face the eventual phase-out in probably less than 5 to 10 years time [1]. Many alternative refrigerants have been developed to replace R22 as well as many of those already phased out. The choice of alternative refrigerants is vast and it is not always easy to make the appropriate decision, though many of the new refrigerants are expected to deliver the same or even better energy performance than those being phased out. Several scenarios of refrigerant substitution can be adopted; these are drop-in, retrofit, and new systems. Drop-in - where the old refrigerant is taken out and the system charged with the alternative refrigerant and 1146

occasionally with some minor adjustments to the control settings, retrofit - where the old refrigerant is replaced with an alternative refrigerant often accompanied by oil and material changes due to compatibility issues, and new system - replacement of old systems with new ones designed specifically for the alternative refrigerant [2]. The objective of this paper is to demonstrate the differences of the outcome from the cycle analysis and the simulation technique for retrofit refrigerant comparison; their limitations are also discussed. The methods are exemplified by comparing some common refrigerants, e.g. R32, R410A, R125, R1270, R22, R407C, R290, R134a, R600a and R600 for the cycle analysis. For the full simulation, R417A, 422D, R427A are included as they are recommended as retrofit choices by refrigerant companies while excluding R600 since its properties are rather similar to R600a. Screening based on thermo-physical properties and cycle performance analysis Many factors need to be considered when deciding upon whether certain alternatives can be suitably used as replacement refrigerants [3], [4], [5]. Apart from assessing the environmental factors, i.e., ODP and GWP, as well as the safety and material compatibility issues, the preliminary screening of potential replacements for given application temperatures can be based on the T crit and NBP of the refrigerants. Further evaluation can employ cycle analysis, examining factors such as P cond, T dis, COP and VRC, and matching them with the corresponding values of the replaced refrigerant for the specified T r,dew,evap, T r,dew, cond, η isen, SH evap and SC cond. In general, the replacement refrigerants should have an appropriate T crit and NBP for a given application temperature [6], i.e., the refrigerant should have T crit that is higher than T r,dew,cond and NBP that is lower than T r,dew,evap. In addition, to replace refrigerant in an existing system, the VRC should be close to provide similar capacity [7], and P cond for a given ambient temperature should be no more than that of the original refrigerant. In addition, a higher COP is preferred [7], [8]. Results and discussions of cycle analysis Table-1 shows the refrigerant properties and calculated cycle operation parameters at specified conditions for initial screening purpose (ordered from high to low VRC) [9]. As explained in McLinden and Didion [6], T crit should be a trade-off between COP and capacity. R125 has a very low T crit resulting in a poor COP, though it offers a much higher capacity than R22 due to its larger ρ suc value despite having a much lower h refrig than R22. Table-1. Refrigerant properties and performance calculated at given conditions [9]. Refrigerant GWP T crit NBP ρ suc h refrig VRC P cond T dis COP ( C) ( C) kg/m 3 kj/kg kj/m 3 kpa ( C) --- R32 550 78.1-51.7 22.5 257 5790 2478 89.8 4.08 R410A 2000 70.4* -52.7* 31.1 171 5325 2419 71.7 4.01 R125 3400 66.0-48.1 43.0 91 3908 2008 52.7 3.81 R1270 20 92.4-47.7 12.6 297 3745 1652 64 4.19 R22 1700 96.1-40.8 21.8 166 3615 1534 75.7 4.26 R407C 1700 86.0* -43.7* 20.3 171 3464 1541 66.9 4.17 R290 20 96.7-42.1 10.6 292 3095 1370 58.2 4.22 R134a 1300 101.1-26.1 14.9 155 2310 1017 59.1 4.29 R600a 20 134.7-11.7 4.4 281 1234 531 52.3 4.38 R600 20 152.0-0.6 2.9 311 893 379 50.9 4.45 Note: 1) All refrigerants shown have zero ODP except R22 which has ODP = 0.034 [5]. 2) All properties are obtained from REFPROP7.0 except GWP are from [5]. 3) * NBP of mixtures are approximated from their compositions. 4) Conditions for cycle analysis are T r,dew,evap = 1.67 C, SH evap = 5 C, T r,dew,cond, = 40 C, SC cond = 5 C, η isen = 70%. On the other hand, R600 though has a higher T crit, it is considered not a suitable retrofit choice for R22 system as it has a much lower VRC due to its very low suction density, and hence a lower capacity. Also from NBP point of view, R600 is not suitable retrofit replacement for sub-zero application temperatures, and so is R600a. P cond of R410A and R32 are very much higher (by about 60%) than that of R22, suggesting it is not suitable for retrofitting R22 systems, constrained by the system pressure limit. R134a has a far too low VRC (36% lower than R22) suggesting it is unsuitable for retrofit unless the compressor size or speed is increased. R407C can be used in retrofit, supported by the experimental work of Greco et al., [10], with both its VRC and COP slightly less, and P cond a little higher, than that of R22. In addition, T dis is another factor relating to the 1147

system reliability in terms of oil and refrigerant degradation [11], and heat transfer loss, thus a low T dis is preferred. Compared with R22, R1270 and R290 both have lower discharge temperatures, and putting aside the flammability issues, they could be considered as potential alternatives. As already pointed out, VRC is indeed the product of suction density and specific refrigerating effect. Therefore, though R1270 has a much lower suction density than R22, it also has a much higher h refrig, resulting in a rather similar VRC and capacity as R22. In summary, as suggested by many researchers T crit, VRC, P cond and COP at given temperatures (T r,dew,evap and T r,dew,cond ) can be used to screen for retrofit replacement. In initial screening, T r,dew,evap, T r,dew,cond, and η isen are normally specified the same for all refrigerants being compared. However, in retrofit these parameters are likely to be different and they must be evaluated properly. The numerical approach implemented in this study, so called the full simulation, is shown in the following section. The comparison of refrigerant performance for a given system using a full simulation Full simulation method The term full simulation adopted in this study refers to dividing the heat exchangers into small elements and grouping the elements into either single-phase or twophase zone. For the evaporator, there are two-phase evaporation and single-phase superheating zones; for the condenser there are two-phase condensation, and singlephase sub-cooling and de-superheating zones. NTUeffectiveness method is applied for both the heat exchanger sizing and the capacity rating calculation. The system model for the full simulation consists of an evaporator, a condenser, a compressor and an expansion valve. The system characteristics and numerical procedure are described below. Heat exchanger A tube-in-tube counter-flow HX is employed for both the evaporator and the condenser. Refrigerant is in the inner tube, while the water, as the HTF, is in the annulus. A conventional numerical approach using element-by-element NTU-effectiveness [12] is adopted. Heat balance equations in an evaporator are shown as in Equations (1) to (3). For refrigerant side: Q evap = m& h (1) r r For heat transfer between the refrigerant and the HTF: ( T T ) Q evap Cmin w, in r, in = ε (2) For heat transfer fluid side: Q m& c T (3) evap = w p, w w Similarly, these three heat balance equations also apply to the condenser heat rejection, using the corresponding properties and parameters in the condenser. The methodology of Breber et al. (1980) (cited in [13]) is chosen for the two-phase flow regime prediction in the HXs, from which appropriate HTC correlations were chosen. Gungor and Winterton (1987) and Cavallini and Zecchin (1974) (cited in [13]) correlations are used, respectively for evaporation and condensation HTC. Compressor An open-typed reciprocating compressor is employed. It is characterised by using its isentropic and volumetric efficiencies to determine work input and mass flow rate, [14], respectively as in Equations (4) and (5). W m h r isen act = & (4) η isen m& = ρ V& η (5) r suc sw vol Expansion valve The expansion process is modelled as an isenthalpic process and the degree of superheat at the evaporator outlet is assumed fixed at all times [14] as in Equations (6) and (7), respectively. h exv in hexv, out, = (6) SH evap = constant (7) Assumptions The assumptions adopted in the full simulation are as following. a) Pressure drops in the system are ignored. b) The SH evap and SC cond are kept constant for all refrigerants. c) The refrigerant charge quantity is always enough to provide the specified SC cond. d) The inlet temperature and mass flow rate of HTF through the HXs are kept constant before and after the retrofit. e) Isentropic and volumetric efficiencies are specified the same for all refrigerants. Though, these parameters can influence the ranking of refrigerant performance comparison [9]. Results and discussions of the full simulation The design conditions are shown in Table-2. The system performance relative to R22 and refrigerant conditions for different refrigerants are shown respectively in Figure-1 and Table-3. The system was originally sized for R22 at a cooling capacity (Q cool or Q evap ) of 8 kw (COP = 4.26) at the design conditions (shown in Table-2), providing an A evap = 1.10 m 2, A cond = 0.85 m 2 and a compressor swept flow rate = 0.002454 m 3 /s (or 8.83 m 3 /h). It is noted that A cond is smaller than A evap due to smaller T w and higher HTF mass flow rate in the condenser. Refrigerant safety issues and pressure limit are 1148

not considered, and the compressor motor rating is assumed sufficient to cope with additional power requirement, if needed. In Figure-1, the refrigerants are ordered from low (on the left) to high cooling capacity and in Table-3, they are ordered from low to high evaporating temperatures. Table-2. Design conditions for component sizing. Q cool (kw) 8 T w,in,evap ( C) 12.2 T r,dew,evap ( C) 1.7 T w,evap ( C) 5.5 T r,dew,cond ( C) 40 T w,in,cond ( C) 29 SH evap ( C) 5 T w,cond ( C) 3 SC cond ( C) 5 inner tube diameter (mm) 17 η isen (%) 70 outer (annulus) tube diameter (mm) 34 η vol (%) 90 1.60 1.40 1.20 1.00 0.80 0.60 Qevap ratio COP ratio 0.40 R600a R134a R417A R290 R422D R427A R22 R407C R1270 R125 R410A R32 Figure-1. The ratios of cooling capacity and COP of different refrigerants in retrofit system normalised to those of R22 [9]. The results clearly show that when retrofit an existing R22 system to another refrigerant, both Q cool and COP change together with the refrigerant temperatures. Refrigerants that provide too low Q cool such as R600a and R134a are not suitable for retrofit, unless the compressor is changed (to a larger size or a higher speed). Refrigerants with too high Q cool such as R410A and R32 are not appropriate either, because much more additional work input is required to drive the much higher capacity and the existing motor may have insufficient power rating. Therefore, the refrigerants that provide within ±10% of the baseline capacity in this figure may be considered as potential candidates for retrofit. 1149

Table-3. Replacement refrigerant dew point temperatures and evaporator outlet water temperatures [9]. T r,dew,evap ( C) T r,dew,cond ( C) T w,evap,out ( C) R32-1.2 41.2 4.3 R410A -0.5 40.6 4.8 R125 1.4 39.2 6.2 R22 (baseline) 1.7 40.0 6.7 R1270 1.7 39.0 6.5 R290 2.7 38.6 7.3 R422D 3.5 40.4 7.0 R407C 3.9 42.3 6.7 R427A 4.0 41.9 6.8 R417A 4.1 40.3 7.4 R134a 4.1 37.9 8.3 R600a 6.2 36.2 9.9 The difference of Q cool in Figure-1 can be explained by their differences in VRC and refrigerant temperatures. Since the VRC varies with refrigerant temperatures, the results can be used to illustrate it is not appropriate to use the VRC at the same temperatures to evaluate the retrofit capacity. The retrofit capacity obtained for R290 is 10% smaller than R22 (Figure-1), though at the same temperatures (as previously seen in Table-1), the VRC of R290 is 14% smaller than R22. Likewise, the retrofit capacity of R407C is about 1% higher than R22 (Figure-1), despite at the same refrigerant temperature, VRC of R407C is in fact 4% lower than R22 (Table-1). The increase of capacities for R290 and R407C compared to those at fixed refrigerant temperatures is attributed to the fact that both refrigerants experience an increase in T r,dew,evap (Table-3) following a retrofit. The HTF outlet temperature from the evaporator (shown in the last column of Table 3) can be regarded as the reciprocal to the cooling capacities obtained, i.e. the higher cooling capacity, the lower HTF outlet temperature. This implies that the desired HTF temperature cannot be attained when the capacity does not match with the original one; either too low or too high HTF temperature could be experienced. Experimental results from published literature were used to assure the simulation trends are correctly predicted. Review paper of Granryd [15] indicates that when retrofit R22 systems to R290, a lower cooling capacity and an improved COP than R22 were observed; same trends were obtained by the current simulation. Park et al., [16] compared R290 and R1270 with R22 experimentally in the same system at the approximately the same refrigerant temperatures. It was found that COP of R290 and R1270 are higher and lower (though slightly), respectively than that of R22; and cooling capacities for R290 and R1270 are lower and higher, respectively than that of R22. These again in general agree well with the simulation except that the simulation only predicts a marginally higher COP for R1270 than R22. The experimental results of Devotta et al., [17] showed that both cooling capacity and COP of R407C are lower than that of R22. However, the current simulation gives a slightly higher cooling capacity for R407C than R22. Inaccuracy in the simulation, the use of a different reference condition/temperature and assumption of having the compressor efficiency fixed could easily result in these small discrepancies. The retrofit temperatures predicted by the simulation also agree well with published experimental and other simulated results. A higher T r,dew,evap of R290 compared to R22 obtained in a drop-in simulation of Domanski and Didion [18] and Devotta et al., [19] supports the current prediction. A higher T r,dew,evap for R407C was also observed by Devotta et al., [17]. A lower predicted T r,dew,cond of R290 also agrees well with Hammad and Tarawnah [20]. To summarize, in general the full simulation results agree well with the experimental results. Nevertheless, it is worth to emphasize that in this simulation, the compressor efficiencies are assumed the same for all refrigerants, which are unlikely to happen in practice. In addition, pressure drops are not considered in the simulation, while they are inherently included in the experimental results. Hence, some discrepancies are expected. CONCLUSIONS a) T crit, VRC, P cond and COP at given temperatures (T r,dew,evap and T r,dew,cond ) can be used to screen for retrofit replacement. In initial screening, T r,dew,evap, T r,dew,cond, and η isen are normally specified the same for 1150

all refrigerants compared. However, in retrofit those parameters are likely to be different. b) Compared with conventional cycle analysis which can only be performed under fixed temperatures, the full simulation can generate the retrofit temperatures so the results provide a more realistic representation of the practical situation. c) In retrofit, the same original performance and/or capacity may not be attained due to the use of the existing heat exchangers and compressor, unless the two refrigerants have very similar properties. REFERENCES [1] UNEP. 2006. Handbook for the Montreal Protocol on Substances that Deplete the Ozone layer. [2] Overview of new and alternative refrigerants. MPROG: BNCR35. [3] W. L. Kopko. 1990. Beyond CFCs: Extending the search for new refrigerants. International Journal of Refrigeration. 13: 79-85. [4] S. Devotta. 1995. Alternative heat pump working fluids to CFCs. Heat recovery systems and CHP. 15: 273-279. [5] J. M. Calm and G. C. Hourahan. 2001. Refrigerant data summary. Engineered systems. 18: 74-88. [6] M. O. McLinden and D. A. Didion. 1987. Quest for alternatives. ASHRAE Journal. 29: 32-42. [7] B. Saleh and M. Wendland. 2006. Screening of pure fluids as alternative refrigerants. International Journal of Refrigeration. 29: 260-269. [8] J. M. Calm and P. A. Domanski. 2004. R22 Replacement status. ASHRAE Journal. August, pp. 29-39. [12] M. W. Browne and P. K. Bansal. 2001. An elemental NTU-e model for vapour-compression liquid chillers. International Journal of Refrigeration. 24: 612-627. [13] P. J. Marto. 1998. Condensation. In: Handbook of heat transfer. 3 Ed. W. M. Rohsenow, J. P. Hartnett, and Y. I. Cho, (Eds.). McGraw-Hill. [14] J. M. Corberan, J. Gonzalvez, J. Urchueguia and A. M. Lendoiro. 2000. Simulation of an air-to-water reversible heat pump. In: International Refrigeration Conference, Purdue University. pp. 529-536. [15] E. Granryd. 2001. Hydrocarbons as refrigerants: an overview. International Journal of Refrigeration. 24: 15-24. [16] K.-J. Park, T. Seo and D. Jung. 2007. Performance of alternative refrigerants for residential air-conditioning applications. Applied Energy. 84: 985-991. [17] S. Devotta, A. S. Padalkar and N. K. Sane. 2005. Performance assessment of HCFC-22 window air conditioner retrofitted with R-407C. Applied Thermal Engineering. 25: 2937-2949. [18] P. A. Domanski and D. A. Didion. 1993. Thermodynamic evaluation of R22 alternative refrigerants and refrigerant mixtures. ASHRAE Transactions. 99: 636-648. [19] S. Devotta, A. S. Padalkar and N. K. Sane. 2005. Performance assessment of HC-290 as a drop-in substitute to HCFC-22 in a window air conditioner. International Journal of Refrigeration. 28: 594-604. [20] M. Hammad and R. Tarawnah. 2000. Hydrocarbon refrigerants performance in an air conditioning unit. In: 4 th IIR-Gustav Lorentzen Conference on Natural Working Fluids Purdue University. [9] R. Prapainop. 2010. Development of an assessment method for refrigerant performance comparison. In Mechanical Engineering. vol. Ph.D. London: University College London. [10] A. Greco, R. Mastrullo and A. Palombo. 1997. R407C as an alternative to R22 in vapour compression plant: an experimental study. International Journal of Energy Research. 21: 1087-1098. [11] K.-J. Park, Y.-B. Shim and D. Jung. 2009. Experimental performance of R432A to replace R22 in residential air-conditioners and heat pumps. Applied Thermal Engineering. 29: 597-600. 1151