BS 476: Part 3: External Fire Exposure Roof Test. WF Report Number: Date: 13 th October Test Sponsor: Tapco Europe Limited

Similar documents
BS 476: Part 3: External Fire Exposure Roof Test. WF Report Number: Date: 28 th April Test Sponsor: Tapco Europe Limited

BS EN : Measurements Of Smoke Density Of Electric Cables. WF Report Number. Date: 17 th November Test Sponsor:

BS EN :2004. Test On Electric And Optical Fibre Cables Under Fire Conditions. WF Report Number. Date: 14 th November 2008.

BS EN ISO : Fire Tests For Determination Of The Burning Behaviour of Floorings. WF Report Number. Date: 16 th November 2009.

BS EN ISO 1716: Determination Of The Heat Of Combustion For Building Products

BS EN ISO : 2010

IMO Resolution MSC 61 (67) 1996; Annex 1, Part 2. Smoke & Toxicity Test. WF Report Number: Date: 13 th August Test Sponsor:

BS 6387: 1994 Specification for performance requirements for cables required to maintain circuit integrity under fire conditions.

BS EN : 2001 & IEC :2000

BS EN ISO : 2010

BS EN :2004. Test On Electric And Optical Fibre Cables Under Fire Conditions. WF Report Number. Date: 14 th November 2008.

Method of test defined in IEC for determining the circuit integrity performance of a cable under fire conditions.

BS EN ISO : 2010

IEC Method of test defined in IEC / -21 for determining the circuit integrity of electric cables under fire conditions

BS 476: Part 6: 1989+A1:2009

BS 476: Part 6: 1989+A1:2009

Ad-hoc IEC Ad-hoc investigation to determine the fire performance of a cable junction box, using the principles of IEC

Ad-hoc IEC Ad-hoc investigation to determine the fire performance of a cable junction box, using the principles of IEC

NF X : Parts 1, 2, 3, 4 & 5

Review Fire Test Report

Title: Fire resistance test utilising the general principles of BS 476: Part 20: 1987 on four specimens of Uninsulated Air Valves.

BS EN 13823: A Report To: Contra Vision. Document Reference: Date: 25 th November Issue No.: 1

IMO Resolution MSC 61(67): Annex 1: Part 2

WARRES No Page 1 of 27. Fire Resistance Test Generally In Accordance With BS 476: Part 22: 1987, Clause 5, on an Insulated Fabric Barrier

BS EN 13823: A Report To: Durabuild Technologies Pvt. Limited. Document Reference: Date: 22 nd February Issue No.

EN : A Report To: Poliuretanos S.A. Document Reference: (Issue 2), (Issue 2) & (Issue 4) Date: 13 th February 2015

Roof Ventilators and Terminals: Fire Performance. CI/SfB (37.9) Uniclass L529 May 2012

Title: Indicative fire test. WF Report No: /A. Prepared for: Hoody Speaker Hoods Ltd

BS 476: Part 7: 1997 on K-Flex IN Clad Foil. Prepared for: L'Isolante K-Flex Srl Via Leonardo da Vinci, RONCELLO (MB) Italy

Title: The Air Leakage Performance of Timber Doorsets fitted with NOR710 Smoke Seals in Accordance with BS 476: Part 31, Section 31.

Title: WF Assessment Report No B. Prepared for: CHEMOLLI S.A.S. di Eros Chemolli & C. Via Fitta, Arco (TN), Italy

25 th November Title:

The Fire Resistance Performance Of Timber Or Mineral Composite Based Insulated Doorsets When Fitted With D & E Architectural Hardware Spring Hinges

CERTIFICATE OF APPROVAL No CF 5236 EMVER PAINTS INDUSTRIES LLC

Fire Test Reports for Interpon D Powder Coatings

CERTIFICATE OF APPROVAL No ME 5085

Forbo Flooring Attn. Mr. A. Tijhof Postbus AA Krommenie. Report. Sponsor : Contractor, manufacturer : Forbo Flooring. Lot. No. : 66869/3877.

Test Report No: ICL/H17/7967

ASSESSMENT REVIEW. Review of Assessment Report WFRA C91415

Test Report: ICL/CR15/11/087

BCTC CARPET TECHNICAL CENTRE

Test Report: ICL/H18/9039 Rev 1

CERTIFICATE OF APPROVAL No CF 5635 P3 SRL

Classification of reaction to fire performance in accordance with BS EN : A1: 2009 on Sandwich Panel, WP 50.

UL Test Methods for Determining the Combustibility Characteristics of Plastics Used in Semiconductor Tool Construction. General Information

Test on extruded rigid PVC profile for concrete formwork at 50 kw/m² irradiance in

Loss Prevention Standard

The Train Now Arriving At... Harmonised Fire Safety For European Rolling Stock

Analysis Report

TFI Report Classification

ISO 5657 INTERNATIONAL STANDARD. Reaction to fire tests Ignitability of building products using a radiant heat source

PRODUCT PERFORMANCE TEST REPORT. Report No.: D Test Date: May 29, Rendered to: Natural Light Energy Systems Phoenix, Arizona

Test Report No. AJHG FB Date: FEB.17, 2015 Page 1 of 13

Test Report No. AJD Date: JUN.09, 2013 Page 1 of 6

REACTION TO FIRE CLASSIFICATION REPORT No. RA ACCORDING TO THE EUROPEAN STANDARD NF EN A1:2013

Test report. NanoPhos coating system EPR and EEN. Name of client: NanoPhos SA. Date: Pages: 5 Encl.: 1 Ref: BP / KTO

CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN :2007+A1:2009

Guide to interpreting Markings for Single Axis Fire Doors Hinges

Report Number BTC 15450A

FTSG RESOLUTIONS. This document of FTSG resolutions was issued by the Company Secretary 20 July 2012.

CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN :2007+A1:2009

Report on the Fire Testing of a Roofing System with a Synthetic Underlayment in Accordance with ASTM E a. Trinity ERD Columbia, SC

Contact person Date Reference Page Richard Johansson P (2) Fire Research

Tech Notes. TESTING PROTOCOL Fire Retardant Gel Coats. INTERPLASTIC CORPORATION Thermoset Resins Divison ISSUE 5

FIRE TESTING OF LOW SLOPE ROOF ASSEMBLIES AN INTERNATIONAL REVIEW

CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN :2007+A1:2009

Are Your Kitchen Hood Filters Compliant?

CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN :2007+A1:2009

Classification of reaction to fire performance in accordance with EN : A1: 2009 on Superfoil SFNC. Prepared for:

Abrasion Resistance of Fluoropolymer and polyester Coatings

REACTION TO FIRE CLASSIFICATION REPORT No. RA ACCORDING TO THE EUROPEAN STANDARD NF EN A1:2013

PERFORMANCE TEST REPORT. Rendered to: Metal Building Manufacturers Association Cleveland, Ohio

CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN :2007+A1:2009

REACTION TO FIRE CLASSIFICATION REPORT No. RA ACCORDING TO THE EUROPEAN STANDARD NF EN A1:2013

1.0 INTRODUCTION 2.0 CLASSIFICATION CRITERIA

RENDERED TO. Laminam S.P.A. Via Ghiarola Nuova Fiorano Modenese Italy

FUNDERMAX GMBH FIRE TEST REPORT

Additional reaction to fire classification report No H

Australian/New Zealand Standard

TEST REPORT. NFPA 253 / ASTM E648-14c Standard Test Method for Critical Radiant Flux of Floor-Covering Systems Using a Radiant Heat Energy Source

DRAFT COMBINED POSTAL BALLOT/ AUSTRALIAN / NEW ZEALAND STANDARD FOR COMMENT

ISO INTERNATIONAL STANDARD. Reaction to fire tests for floorings Part 1: Determination of the burning behaviour using a radiant heat source

ISO INTERNATIONAL STANDARD. Protective gloves for firefighters Laboratory test methods and performance requirements

CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN :2007+A1:2009

TFI Report Reaction to fire test

PERFORMANCE TEST REPORT. Rendered to: VELUX America, Inc. PRODUCT: SUN TUNNEL Acrylic Dome

M E M O R A N D U M. Diane Matthews, Administrator, Technical Projects. NFPA 101 First Draft Letter Ballot (A2014)

Timber in construction Eurocode 5 Span tables and guidelines

Report VNLF Test Report

SLIP RESISTANCE TESTING OF ENDURO-MESH PANEL

Schedule of Accreditation issued by United Kingdom Accreditation Service 2 Pine Trees, Chertsey Lane, Staines-upon-Thames, TW18 3HR, UK

Guidance Note. 3. Fire Propagation and flame Flame Spread in in Powder Coatings. Abrasion Resistance of Fluoropolymer and polyester Coatings

P.O. Box NL-2665 ZN Bleiswijk Brandpuntlaan Zuid 16 - NL-2665 NZ Bleiswijk The Netherlands

Testing coated fabrics

SOUTH AFRICAN NATIONAL STANDARD

Overhead Line Insulators

TEST REPORT. Report No.: E Test Date: May 6, Rendered to: FUNDERMAX GMBH A-9300 St. Veit an der Glan, Austria

ISO INTERNATIONAL STANDARD

EU DECLARATION OF CONFORMITY (Doc) issued in accordance with the MARINE EQUIPMENT DIRECTIVE (MED) and EU/US MRA

CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN :2007+A1:2009

Transcription:

BS 476: Part 3: 2004 External Fire Exposure Roof Test WF Report Number: 158117 Date: 13 th October 2006 Test Sponsor: Tapco Europe Limited 0249

Page 2 of 9 Warringtonfire Test Report No 158117 BS 476: Part 3: 2004 External Fire Exposure Roof Test Sponsored By Tapco Europe Limited Unit 32, Tokenspire Business Park, Hull Road Woodmansey East Yorkshire HU17 OTB

Page 3 of 9 CONTENTS PAGE NO. TEST DETAILS... 4 DESCRIPTION OF TEST SPECIMENS... 5 TEST RESULTS... 6 SIGNATORIES... 7 Table 1... 8

Page 4 of 9 Test Details Purpose of test Scope of test To determine the performance of specimens of a roof construction when they are subjected to the conditions of the test specified in BS 476: Part 3: 2004, "British Standard Specification for Fire Tests on Building Materials and Structures - External Fire Exposure Roof Tests". The test was performed in accordance with the test procedures specified in BS 476: Part 3: 2004 and this report should be read in conjunction with that British Standard. The tests are designed to enable measurement of: a) capacity of a representative section of a roof to resist penetration by fire when the external surface is exposed to radiation and flame; and b) distance of the spread of flame on the outer surface of the roof covering under certain conditions. Roofs are graded according to the angle at which they are tested, the time for which they resist penetration by fire and the distance of superficial spread of flame on their external surface. Fire test study group Instruction to test Provision of test specimens The test specimens are tested at an angle of 45 o to the horizontal (sloping position) unless the roof construction is used at an angle of less than 10 o to the horizontal, in which case the specimens are tested horizontally (flat position). Certain aspects of some fire test specifications are open to different interpretations. The Fire Test Study Group and EGOLF have identified a number of such areas and have agreed Resolutions which define common agreement of interpretations between fire test laboratories which are members of the Groups. Where such Resolutions are applicable to this test they have been followed. The test was conducted on the 12 th October 2006 at the request of Tapco Europe Limited, the sponsor of the test. The specimens were supplied by the sponsor of the test. Warringtonfire was not involved in any selection or sampling procedure. Conditioning of specimens Orientation of specimens The specimens were received on the 21 st September 2006. Prior to testing the specimens were conditioned to equilibrium in an atmosphere having a temperature of 23 ±2 C and a relative humidity of 45 to 55%. The specimens were tested in the sloping position.

Page 5 of 9 Description of Test Specimens The description of the specimens given below has been prepared from information provided by the sponsor of the test. All values quoted are nominal, unless tolerances are given. General description Plastic based roofing tile with an underlay mechanically fixed to a batten and rafter system. Product reference Inspire Slate Composition details Polypropylene, Limestone, Pigment Blend, UV Absorber and Additives. The sponsor was unable to provide any further information in relation to the composition of the roofing tiles Plastic Tiles Name of manufacturer Inspire Slate (Test Face) Tile size 288mm x 438mm Weight per unit area 4.76kg/m² Thickness Tapers from a thickness of 7mm at the top of the tile to 3.5mm at the bottom edge. Colour Grey Flame retardant details See Note 1 Below General description Roofing Underlayment Product reference Layfast SBS TU-35 Composition details Asphalt, Fiberglass, Rubber, Sand, Granules. The sponsor was unable to provide any further information in relation to the composition of the Underlay underlay. Name of manufacturer MB Technology Weight per unit area 1.81kg/m² Thickness 1.1mm Colour Black Flame retardant details See Note 2 Below Brief description of manufacturing process See Note 2 Below Mounting and fixing details The specimens were fixed to a 50mm x 50mm wooden frame with 30mm x 30mm wooden battens with ¾ clout nails. Note 1 : The sponsor of the test has confirmed that no flame retardant additives were utilised in the production of the product / component. Note 2 : The sponsor was unable to provide this information.

Page 6 of 9 Test Results Results of test The test results relate only to the behaviour of the test specimens of the construction under the particular conditions of test, they are not intended to be the sole criterion for assessing the potential fire hazard of the construction in use. The test results relate only to the specimens of the roof construction which were tested. Small differences in the composition or thickness of the construction may significantly affect the results of the test and may therefore invalidate the test results. Care should be taken to ensure that any construction which is supplied or used is fully represented by the specimens which were tested. The results of the tests on each of the specimens are given in Table 1. In Accordance With The Designations Defined In BS 476: Part 3: 2004 The Test Specimens Are In Category EXT.S.AC. Validity The specification and interpretation of fire test methods are the subject of ongoing development and refinement. Changes in associated legislation may also occur. For these reasons it is recommended that the relevance of test reports over five years old should be considered by the user. The laboratory that issued the report will be able to offer, on behalf of the legal owner, a review of the procedures adopted for a particular test to ensure that they are consistent with current practices, and if required may endorse the test report. This report may only be reproduced in full. Extracts or abridgements shall not be published without permission of warringtonfire

Page 7 of 9 Signatories Responsible Officer A Myler* Approved I Moore * Laboratory Supervisor Head of Department P E Lythgoe * * For and on behalf of warringtonfire. Report Issued: 13 th October 2006 This version of the report has been produced from a.pdf format electronic file that has been provided by Warringtonfire to the sponsor of the report and must only be reproduced in full. Extracts or abridgements of reports must not be published without permission of Warringtonfire. The original signed paper version of this report, which includes signatures in blue ink, is the sole authentic version. Only original paper versions of this report bear authentic signatures of the responsible Warringtonfire staff.

Page 8 of 9 Table 1 PRELIMINARY IGNITION TEST WITH BURNING Specimen No: BRANDS (STAGE 1) 1 Room Temperature at Start of Test ( C) 16 Time to Fire Penetration (if applicable) (min:sec) N/A Duration of Flaming after Withdrawal of the Test Flame (if applicable) (min:sec) 1:11 Maximum Flame Spread Distance (if applicable) (mm) N/A SPREAD OF FLAME TEST WITH BURNING BRANDS Specimen No: AND SUPPLEMENTARY RADIANT HEAT (STAGE 2) 2 3 4 Room Temperature at Start of Test ( C) 29 28 29 Duration of Flaming after Withdrawal of the Test Flame (if applicable) (min:sec) 79:08 88:12 78:26 Maximum Flame Spread Distance (if applicable) (mm) 580 630 590 Other observations: In the case of each specimen, ignition occurred upon application of the pilot flame during the third minute of the test. In the case of each specimen, flaming remained upon removal of the pilot flame during the fourth minute of the test and began to spread down over the specimen surface from the fifth minute of the test. PENETRATION TEST WITH BURNING BRANDS, WIND Specimen No: AND SUPPLEMENTARY RADIANT HEAT (STAGE 3) 5 6 7 Room Temperature at Start of Test ( C) 30 30 30 Time to Fire Penetration (if applicable) (min:sec) N/A N/A N/A Other observations: In the case of each specimen, ignition occurred upon application of the pilot flame during the sixth minute of the test. In the case of each specimen, flaming remained upon removal of the pilot flame at six minutes and continued to the end of the test duration. In the case of each specimen fire penetration did not occur.

Page 9 of 9 Classification Of Specimens The following is reproduced from Clause 4 of BS 476: Part 3: 2004. 4 Classification 4.1 Roof system Roof systems shall be designated by the letters EXT.F or EXT.S to indicate whether the test results apply to a flat (horizontal) or an inclined roof system, respectively 4.2 Fire Resistance of roof system 4.2.1 Coding system Roof systems subject to conditions of external fire shall be classified according to both the time of penetration and the distance of spread of flame along their external surface. Each category designation shall consist of two letters, e.g. AA, AC, BB, these being determined as specified in 4.22 and 4.23 4.2.2 Fire penetration (first letter) A. Those specimens that have not been penetrated within one hour B. Those specimens that are penetrated in not less than 30 min. C. Those specimens that are penetrated in less than 30 min. D. Those specimens that are penetrated in the preliminary flame test 4.2.3 Spread of flame (second letter) A. Those specimens on which there is no spread of flame B. Those specimens on which there is not more than 533mm spread of flame C. Those specimens on which there is more than 533mm spread of flame D. Those specimens that continue to burn for five minutes after withdrawal of the test flame or spread more than 381mm across the region of burning in the preliminary test. 4.2.4 Suffix X Attention shall be drawn to dripping from the underside of the specimen, any mechanical failure, and any development of holes, by adding a suffix X to the designation to denote that one or more of these took place during the test. EXAMPLE 1 EXT.F.AA is a flat roofing system with one hour fire penetration resistance on which there was no spread of flame. EXAMPLE 2 EXT.S.CCX is an inclined roofing system with less than 30 min fire penetration resistance, on which the spread of flame exceeded 533mm and further deterioration took place.

Bodycote warringtonfire Testing Holmesfield Road Warrington Cheshire WA1 2DS United Kingdom Tel: +44 (0) 1925 655 116 Fax: +44 (0) 1925 655 419 Email: Info@warringtonfire.net Website: www.warringtonfire.net