INSTALLATION INSTRUTIONS LOW VOLTAGE ONTROL IRUIT WIRING W**A W**AD WA*S* MODELS W**L WL*S* Bard Manufacturing ompany, Inc. Bryan, Ohio 506 Since 9...Moving ahead just as planned. Manual : 00-58 Supersedes: NEW File: Volume III Tab 6 Date: -09- * Page of
ontents Installation Instructions Wiring Low Voltage Wiring... Operating Voltage Range... Low Voltage onnection... Tables Table Diagram to Use w/unit & Vents... Table Operating Voltage Range... Table Wall Thermostat... Table Humidity ontrols... Table 5 O ontroller... Table 6 Thermostat Wire Size... Figures Figure Basic A/ with Optional Electric Heat No. Economizer or Vent Packages... 5 Figure Opt. MFAD, RV or ERV Vent. Pkg. w/ Programmable T-Stat... 6 Figure Opt. MFAD, RV or ERV Vent. Pkg. w/ Non-Programmable T-Stat... 7 Figure A/ with Economizer... 8 Figure 5 A/ w/dehumidification Sequence & No Vent Pkg... 9 Figure 6 A/ w/dehumidification Sequence & No Vent Pkg. Using Sep. ontrols... 0 Figure 7 A/ w/dehumidification Sequence w/vent Pkg. Using ombination ontroller... Figure 8 A/ w/dehumidification Sequence w/vent. Pkg. Using Non-Prog. T-Stat & Separate. Humidity ontroller... Figure 9 A/ w/dehumidification Sequence & Economizer... Figure 0 A/ w/dehumidification Sequence & Economizer w/ombination Temperature. & Humidity ontrol... Figure A/ w/s000 Wiring Diagram... 5 Figure -Stage A/ with Optional Electric Heat.. No Economizer or Vent Pkgs... 6 Figure -Stage A/ Opt. MFAD or ERV Vent. Pkg.. w/non-programmable T-Stat... 7 Figure -Stage A/ Opt. MFAD or ERV Vent. Pkg.. w/programmable T-Stat... 8 Figure 5 -Stage A/ with Economizer... 9 Figure 6 -Stage A/ w/opt. RVMP Low Voltage.. Wiring... 0 Figure 7 -Stage A/ w/opt. Elec. Heat w/... EONWM* Style Economizer... Figure 8 -Stage A/ w/opt. Elec. Heat w/... EONWM* Style Economizer... Page of
TABLE DIAGRAM TO USE WITH UNIT AND VENTS Vent None RV, ERV, MFAD RVMP EIFM EONWM* S000A* Vent ode X R,M,V,P E T,W Thermostat Programmable Programmable ALL Programmable ALL ALL System Type Model No Yes No Yes All No Yes All All Air onditioner W**A, W**L N/A 7 Air onditioner w/dehumidification Sequence -Stage Air onditioner W**A*D W**L*D WA*S* WL*S* 6 5 8 7 N/A 9 0 N/A 6 5 5 8 WIRING LOW VOLTAGE WIRING All 0/08V, phase and phase units are equipped with dual primary voltage transformers. All equipment leaves the factory wired on 0V tap. For 08V operation, reconnect from 0V to 08V tap. The acceptable operating voltage range for the 0V and 08V taps are: An 8 gauge copper, color-coded thermostat cable is recommended. The connection points are shown in this Manual. See Table below. TABLE OPERATING VOLTAGE RANGE TAP RANGE 0V 5 6 08V 0 87 NOTE: The voltage should be measured at the field power connection point in the unit and while the unit is operating at full load (maximum amperage operating condition). Low Voltage onnection These units use a -volt A low voltage circuit. The R terminal is the hot terminal and the terminal is grounded. G terminal is the fan input. Y terminal is the compressor input for cooling -Stage units only or -Stage units with EONWM* Pink Wire is nd Stage cooling -Stage units only with EONWM* Y terminal is the st Stage compressor input for cooling -Stage units only No EONWM* Y terminal is the nd Stage compressor input for cooling -Stage units only No EONWM* W terminal is the st stage electric heat. W terminal is the nd stage heat (if equipped). A terminal is the ventilation input. This terminal energizes any factory installed ventilation option. D terminal is the dehumidification input. If installed, this terminal energizes any factory installed dehumidification option. LOW VOLTAGE ONNETIONS FOR DD ONTROL -Stage Units -Stage Units -Stage Units w/eonwm* Fan Only Energize G Energize G Energize G st Stage ooling Mode Energize Y, G Energize Y, G Energize G, Y nd Stage ooling Mode Energize Y, Y, G Energize G, Y, Pink st Stage Heating Energize W Energize W Energize W nd Stage Heating Energize W, W Energize W, W Energize W, W (if employed) Ventilation Energize G, A Energize G, A Energize G, A Dehumidification Energize D Energize D Energize D (if employed) Page of
TABLE WALL THERMOSTAT Part Number 80-057 (TH0D00) 80-058 (TH50D5) 80-060 (0-5) Predominate Features stage ool, stage Heat Electronic Non-Programmable Auto or Manual changeover stage ool, stage Heat Electronic Non-Programmable HP or onventional Auto or Manual changeover stage ool; stage Heat Programmable/Non-Programmable Electronic HP or onventional Auto or Manual changeover Dehumidification Output Part Number 80-08 (H600A0) 80-07 (H00-0--0) TABLE HUMIDITY ONTROLS Predominate Features SPDT switching, pilot duty 50VA @ V Humidity range 0-80% RH Electronic dehumidstat SPST closes-on-rise Humidity range 0-90% with adjustable stops Part Number 80-067 TABLE 5 O ONTROLLER Predominate Features Normally Open SPST relay closes-on-rise V dual wave length sensor. Default setting 950ppm, adjustable to 0-000ppm Default off setting 000ppm, adjustable to 0-00 ppm can be calibrated Transformer VA TABLE 6 THERMOSTAT WIRE SIZE FLA 55. Wire Gauge 0 gauge 8 gauge 6 gauge gauge gauge Maximum Distance In Feet 5 60 00 60 50 Page of
FIGURE BASI A/ with OPTIONAL ELETRI HEAT NO EONOMIZER or VENTILATION PAKAGES Page 5 of
Page 6 of FIGURE OPTIONAL MFAD, RV or ERV VENTILATION PAKAGES with PROGRAMMABLE THERMOSTAT (REOMMENDED)
FIGURE OPTIONAL MFAD, RV or ERV VENTILATION PAKAGES with NON-PROGRAMMABLE THERMOSTAT Page 7 of
Page 8 of FIGURE A/ with EIFM
FIGURE 5 A/ with DEHUMIDIFIATION SEQUENE & NO VENTILATION PAKAGE USING 80-060 OMBINATION TEMPERATURE and HUMIDITY ONTROLLER Page 9 of
Page 0 of FIGURE 6 A/ with DEHUMIDIFIATION SEQUENE & NO VENTILATION PAKAGE USING SEPARATE TEMPERATURE and HUMIDITY ONTROLS
FIGURE 7 A/ with DEHUMIDIFIATION SEQUENE with VENTILATION PAKAGE USING 80-060 OMBINATION TEMPERATURE & HUMIDITY ONTROLLER and 80-067 O ONTROLLER Page of
Page of FIGURE 8 A/ with DEHUMIDIFIATION SEQUENE with VENTILATION PAKAGE USING NON-PROGRAMMABLE THERMOSTAT and SEPARATE HUMIDITY ONTROLLER
FIGURE 9 A/ with DEHUMIDIFIATION SEQUENE & EIFM with 80-058 THERMOSTAT and 80-08 or 80-07 HUMIDISTAT Page of
FIGURE 0 A/ with DEHUMIDIFIATION SEQUENE & EIFM with 80-060 OMBINATION TEMPERATURE and HUMIDITY ONTROL LOW VOLTAGE WIRING Page of
FIGURE AIR ONDITIONER WITH S000 DO NOT ONNET "L" UNTIL AFTER 80-060 ONTROLLER IS ONFIGURED TO S000 = YES TEMPERATURE/HUMIDITY ONTROLLER BARD P/N 80-060 THERMOSTAT TH50D5 BARD P/N 80-058 NOTE: MUST BE ONFIGURED FOR HEAT/OOL R G Y W/E W Y L YO/D G Y W W Y R R BLUE RED YELLOW 6 5 80-08 H600A0 HUMIDITY ONTROLLER 80-07 H00-0--0 DEHUMIDSTAT IF OPTIONAL VENT PAKAGE IS INSTALLED, THE "G" WIRE MUST BE ONNETED TO ASSURE ONTINUOUS BLOWER DURING OUPIED PERIODS WHEN VENT SYSTEM IS "ON". THE "G" WIRE MUST ALSO BE ONNETED FOR PRE-PURGE OPERATION (SEE STEP, FUNTION SWITH SETTINGS). BARD VENTILATION PAKAGE (OPTIONAL) NOTE: IF FATORY INSTALLED DISONNET AND TAPE RED AND ORANGE WIRES R O A BK WERV OR RV BR/W R G Y W W N NO N VENT HVA FAN Y PWR N D UNIT V TERMINALS HUMIDITY ONTROLLER ONNETIONS USED ONLY FOR OPTIONAL DEHUMIDIFIATION IRUIT THAT MUST BE FATORY INSTALLED IN AIR ONDITIONER FATORY JUMPER - SEE SEARH TIME DETAIL ON PAGE OPTIONAL LIGHTING ONTROL LIGHTING ONTROL RELAY NORMALLY LOSED ONTATS MANUAL SWITH FIELD SUPPLIED LIGHTS REMOTE MOTION DETETOR (OPTIONAL) NORMALLY OPEN ONTATS AREA OUP. NO N REM - + - + - + PWR PREOND DOOR NO N HVA MAN. OVERIDE ( HRS) S000A ENERGY MONITOR NEEDED WHEN STAGES OF ELETRI HEAT ARE REQUIRED. REQUIRED FOR STAGE OOLING UNITS OR UNITS WITH EONOMIZERS. JUMPER IS FATORY INSTALLED. LIGHTING ONTROL IRUIT IS OPTIONAL AND FIELD SUPPLIED. LIGHTING ONTROL RELAY REQUIRES NORMALLY LOSED ONTATS AND MUST BE SIZED AORDING TO ONTROLLED LOAD. REOMMENDED SWITH SETTINGS SHOWN BELOW FUNTION SWITHES LEARN PRE P MODE RATE SEARH-TIME N/ STAGE AUX DEMAND DEMAND TEMPERATURE SWITHES 90 8 8 78 68 65 6 58 5 8 09-57 Page 5 of
FIGURE -STAGE A/ with OPTIONAL ELETRI HEAT NO EONOMIZER or VENTILATION PAKAGES LOW VOLTAGE WIRING Thermostat Part #80-060 R G Y Y W/E W O/B YO/D Y A L ELETRONI PROGRAMMABLE TH5005 Part #80-058 R R G Y Y W W STAGE OOL STAGE HEAT THERMOSTAT UNIT V TERMINAL BLOK R Rt G Y Y W W Y E F D A 5 REMOVE JUMPER FOR STAGE ELETRI HEAT ON UNITS WITH 5 OR MORE KW FATORY INSTALLED JUMPER HANGE "SYSTEM TYPE". SET UP FUNTION, FROM 5 ( HEAT/ OOL HEAT PUMP) TO 6 ( HEAT/ OOL ONVENTIONAL). HANGE MODEL ONFIGURATION FROM HEAT PUMP TO HEAT/OOL MIS-8 5 FATORY INSTALLED JUMPER. FOR IMMEDIATE EMERGENY SHUTDOWN OF ALL HVA OPERATION, REMOVE JUMPER AND ONNET NORMALLY LOSED (N) ONTAT TO R AND Rt TERMINALS. Page 6 of
FIGURE -STAGE A/ with OPTIONAL MFAD OR ERV VENTILATION PAKAGES with NON-PROGRAMMABLE THERMOSTAT LOW VOLTAGE WIRING OPTIONAL 80-067 O ONTROLLER 5 80-058 (TH50D5) Rc R G Y W W Y 5 6 STAGE OOL STAGE HEAT THERMOSTAT UNIT V TERMINAL BLOK Rt R G Y W W Y Y E F D A RED BLAK 7 ERV ORANGE 6 BROWN/WHITE MFAD OPTIONAL VENT PAKAGES RED REMOVE JUMPER FOR STAGE ELETRI HEAT ON UNITS WITH 5 OR MORE KW OPTIONAL VENT OPTION SUGGESTED HOOK UP MIS-9 FATORY INSTALLED JUMPER ADD JUMPER IF OPTIONAL O ONTROLLER IS NOT USED, VENT WILL RUN WHILE BLOWER IS ENERGIZED. DO NOT INSTALL JUMPER IF OPTIONAL O ONTROLLER INSTALLED, AND SEE NOTE 6. 5 HANGE "SYSTEM TYPE", SET UP FUNTION, FROM 5 ( HEAT/ OOL HEAT PUMP) TO 6 ( HEAT / OOL ONVENTIONAL). 6 7 ONNET ORANGE WIRE TO "G" ONLY IF OPTIONAL O ONTROLLER IS INSTALLED. FATORY INSTALLED JUMPER. FOR IMMEDIATE EMERGENY SHUTDOWN OF ALL HVA OPERATION, REMOVE JUMPER AND ONNET NORMALLY LOSED (N) ONTAT TO R AND Rt TERMINALS. Page 7 of
FIGURE -STAGE A/ with OPTIONAL MFAD OR ERV VENTILATION PAKAGES with PROGRAMMABLE THERMOSTAT (REOMMENDED) LOW VOLTAGE WIRING THERMOSTAT Part #80-060 R G Y Y W/E W YO/D O/B L A ELETRONI PROGRAMMABLE OPTIONAL 80-067 O ONTROLLER 5 6 UNIT V TERMINAL BLOK Rt R G Y Y W W Y E F D A BLAK 5 ERV MFAD ORANGE OPTIONAL VENT PAKAGES BROWN/WHITE RED REMOVE JUMPER FOR STAGE ELETRI HEAT ON UNITS WITH 5 OR MORE KW MIS-50 DO NOT ONNET "A" FROM 80-060 IF OPTIONAL O ONTROLLER IS USED 5 ONNET ORANGE WIRE TO "G" ONLY IF OPTIONAL O ONTROLLER IS USED HANGE MODEL ONFIGURATION FROM HEAT PUMP TO HEAT/OOL. MUST BE ONFIGURED TO PROGRAMMABLE AND FAN SET TO PROGRAMMED FAN FOR THE "A" OUTPUT TO FUNTION DURING SHEDULED OUPIED PERIODS. FATORY INSTALLED JUMPER. FOR IMMEDIATE EMERGENY SHUTDOWN OF ALL HVA OPERATION, REMOVE JUMPER AND ONNET NORMALLY LOSED (N) ONTAT TO R AND Rt TERMINALS. Page 8 of
FIGURE 5 -STAGE A/ with EIFM Thermostat Part #80-060 OPTIONAL EONOMIZER LOW VOLTAGE WIRING G Y R W/E W Y YO/D O/B L A ELETRONI PROGRAMMABLE UNIT V TERMINAL BLOK BLAK G ORANGE Y YELLOW Rt R W W Y PINK Y PURPLE E BLUE F BLAK D A EONOMIZER WIRING HARNESS MIS-5 REMOVE JUMPER FOR STAGE ELETRI HEAT ON UNITS WITH 5 OR MORE KW HANGE MODEL ONFIGURATION FROM HEAT PUMP TO HEAT/OOL, AND MUST BE ONFIGURED FOR EONOMIZER FOR YO/D OUTPUT TO BE ATIVE AS FIRST STAGE OOLING. FATORY INSTALLED JUMPER. FOR IMMEDIATE EMERGENY SHUTDOWN OF ALL HVA OPERATION, REMOVE JUMPER AND ONNET NORMALLY LOSED (N) ONTAT TO R AND Rt TERMINALS. Page 9 of
FIGURE 6 -STAGE A/ with OPTIONAL RVMP LOW VOLTAGE WIRING OPTIONAL RVMP LOW VOLTAGE WIRING Thermostat Part #80-060 R G Y Y W/E W A TH5005 Part #80-058 R R G Y Y W W UNIT V TERMINAL BLOK R Rt G Y Y W W Y E F D A RVMP BROWN/ WHITE BLAK ORANGE BLUE YELLOW BROWN PURPLE BLAK ONTROL BOARD ASSEMBLY INSTALL JUMPER WHEN USING THERMOSTAT PART #80-058 FATORY INSTALLED JUMPER HANGE MODEL ONFIGURATION FROM HEAT PUMP TO HEAT/OOL. MUST BE ONFIGURED TO PROGRAMMABLE AND FAN SET TO PROGRAMMED FAN FOR THE "A" OUTPUT TO FUNTION DURING SHEDULED OUPIED PERIODS. MIS-5 FATORY INSTALLED JUMPER. FOR IMMEDIATE EMERGENY SHUTDOWN OF ALL HVA OPERATION, REMOVE JUMPER AND ONNET NORMALLY LOSED (N) ONTAT TO R AND Rt TERMINALS. Page 0 of
FIGURE 7 -STAGE A/ with OPTIONAL ELETRI HEAT WITH EONWM STYLE EONOMIZER Low Voltage Wiring Diagram 80-058 (TH50D5) G R R Y Y W W 5 Thermostat part #80-060 G R Y YO/D Y W/E W A L O/B A/ UNIT V TERMINALS G Rt R Y Y Y W W A D E F 7 6 BLAK RED YELLOW PURPLE PINK BLUE TAPE WIRE END YELLOW/RED Economizer Wiring Harness ORANGE BROWN/WHITE YELLOW/WHITE MIS-5 5 6 7 Factory installed jumper. Remove for -stage operation on units with 5 or more kw. Must be energized to enable minimum position. NOTE: Economizer ontrol Default Setting is 0V (00%). Depending upon application may require setting to lower value. Factory Jumper Installed. hange "system type", set up function, from 5 ( heat/ cool heat pump) to 6 ( heat/ cool conventional). hange model configuration from heat pump to heat/cool, and must be configured for economizer for YO/D output to be active as first stage cooling. Older units may not have Y and Y connections on v terminal block. If not present wire nuts must be used. Factory installed jumper. For immediate emergency shutdown of all HVA operation, remove jumper and connect normally closed (N) contact to R and Rt terminals. Page of
FIGURE 8 -STAGE A/ with OPTIONAL ELETRI HEAT WITH EONWM STYLE EONOMIZER Low Voltage Wiring Diagram 80-058 (TH50D5) G R R Y Y W W 5 Thermostat part #80-060 G R Y YO/D Y W/E W A L O/B A/ UNIT V TERMINALS G Rt R Y Y Y W W A D E F 6 BLAK RED YELLOW PURPLE ORANGE BLUE TAPE WIRE END YELLOW/RED Economizer Wiring Harness PINK BROWN/WHITE YELLOW/WHITE MIS-5 Factory installed jumper. Remove for -stage operation on units with 5 or more kw. 5 6 Must be energized to enable minimum position. NOTE: Economizer ontrol Default Setting is 0V (00%). Depending upon application may require setting to lower value. Factory Jumper Installed. hange "system type", set up function, from 5 ( heat/ cool heat pump) to 6 ( heat/ cool conventional). hange model configuration from heat pump to heat/cool, and must be configured for economizer for YO/D output to be active as first stage cooling. Factory installed jumper. For immediate emergency shutdown of all HVA operation, remove jumper and connect normally closed (N) contact to R and Rt terminals. Page of