Installation Instructions. Remanufactured Veeder-Root Position Sensitive Sump Sensor. PMP # Replaces Veeder-Root #

Similar documents
Remanufactured Veeder-Root Discriminating Dispenser Pan and Containment Sump Sensors

Installation Instructions. Remanufactured Veeder-Root Sump Sensor. PMP # 62208, Replaces Veeder-Root # , -209

Installation Instructions. Remanufactured Veeder-Root Steel Tank Interstitial Sensor. PMP # 62420, Replaces Veeder-Root # , -460

Installation Instructions. Remanufactured Veeder-Root Overfill Alarm and. Acknowledgement Switch. Overfill Alarm PMP # OEM #

Manual No: Revision: D. Mag Sump Sensor. Installation Guide

Manual No: Revision: D. Sump Sensor. Installation Guide

Manual No: Revision: E. Groundwater Sensor. Installation Guide

Single-Point Mini Hydrostatic Sensor for Double-Wall Sumps

Interstitial Liquid Sensor - Fiberglass Tanks

Manual No: Revision: J. Groundwater Sensor. Installation Guide

2 To 1 Sensor Input Box

Manual No: Revision: H. MicroSensor. Installation Guide

Manual No: Revision: G. Sensor Products. Application Guide

FMP-ULS UNIVERSAL LIQUID SENSOR INSTALLATION GUIDE

60 Liter Infinity Storage Reservoir

Installation Manual February Opticom Infrared System. Model 575 Confirmation Light Kit

FMP-DIS & FMP-EIS. Interstitial BriteSensor & Standard Sensor. Installation Instructions

Installation Manual September Opticom Infrared System. Model 798 Emitter Bezel Mount Kit

Manual No: Revision: C. Overfill Alarm. Installation Guide

Operation and Maintenance Manual

FMP-DVS. Monitoring Well Discriminating Vapor Sensor (BriteSensor ) Installation Instructions

Ion Genesis II Pump Controller Digital Level Control with Pump Alternation and High Water Alarm

Required Tools The following tools are required for the installation of the kit: Open-end Wrench Set Flat-tip Screwdriver Cross-tip Screwdriver

COOPER POWER SERIES. CT Protector Retrofit Kit. Voltage Regulators MN225057EN. Effective March 2017 Supersedes March 2010 (S )

ELSTON 52 CEILING FAN

FLCH4R Garage and Utility Electric Heater

FMP-MWS. (Discriminating Monitoring Well Sensor BriteSensor ) Installation Instructions

Model: EF34. Owner's Guide & Installation Manual

Ion Endeavor Pump Controller Digital Level Control with Pump Alternation and High Water Alarm

FMP-DDS & FMP-DTS. Discriminating Dispenser Sump & Turbine Sump BriteSensor. Installation Instructions

LED Traffic Clearing Light

OPERATORS MANUAL FOR Mi-T-M CORONA DISCHARGE OZONE GENERATORS

ion Genesis Pump Controller

FMP-HIS AND FMP-HIS-U INSTALLATION GUIDE

Application Note on Reading the Vigilohm IM400 Insulation Monitoring Device Installed in Conext Core XC and XC-NA Series Inverters

WARNING. Pro Pack Portable Spray Pack 3A1292C. Operation. Model 24F893 Maximum Working Pressure 12 psi (0.83 bar, MPa)

TLS-300 UST Monitoring and Leak Detection System

Instruction Manual. Dogeroo, Super Dogeroo, and Mini Dogeroo

MAYFIELD CEILING FAN LISTED E ITEM # MODEL #BTH44ABZC5C BTH44BNK5C Español p. 20 ATTACH YOUR RECEIPT HERE.

ITEM # SAIL STREAM CEILING FAN MODEL #40048

SUTTON 52 CEILING FAN

Parts and Service Manual BURNISHER MODEL: MR , MR , MR , MR

ITEM # SAIL STREAM CEILING FAN MODEL #41695

Installing the assembly SIMATIC. Installing the assembly. Overview 1. Installing the assembly. Getting Started A5E

TILGHMAN CEILING FAN. LISTED For Damp Location E ITEM # MODEL #WCK52LMW5N WCK52NWZ5N. Español p. 20 ATTACH YOUR RECEIPT HERE

Instruction Manual. Double Candy Apple Cooker

TOUCHDOWN 48 CEILING FAN

VSA Series Air Dryer. User s Guide

SEISCO SUPERCHARGER EXTENDER/BOOSTER INSTALLATION GUIDE & OWNERS MANUAL

Heliport Perimeter Light Type MIJ

ECCOTEMP. Point of Use Tankless Water Heaters EP-2.4 / EP-7.0. Installation and Operating Instruction Manual. Shop Online.

DUST FREE CARBON Whole House Air Purifier

Installation Instructions

Gas Connector Installation Instructions

CurrentGuard TM. Installation, Operation and Maintenance Manual. CurrentGuardTM. Flush Mount. Surge Protective Devices A00

PWW Drinkwell 2 Gallon Pet Fountain

MDH Series Air Dryer. User s Guide

ST. KITTS CEILING FAN

RK/ RK Oxygen Detector Operator s Manual

Fire Bowls and Fire Bowl Inserts (Automated Operation) Operating and Maintenance Instructions

Register at

52 CEILING FAN. Owner s Manual Models #50336, 50337

Installation Manual PS-225 & PS-275

RK / RK Methane Detector Operator s Manual

Silicone Rubber Heating Tape with Adjustable Thermostat Control (HSTAT Series) Instruction Manual

Fire-Water Bowls Model 100

Safety Message to Installers of Federal Signal Siren Speakers

Instructions for using the KWA LS-2003 Leak Detector Tester are on Page 7 of the Veeder-Root Operational Testing Guide

Be sure the siren amplifier and speaker(s) in your installation have compatible wattage ratings.

ITEM # BUILDER S SERIES CEILING FAN MODEL #41391

KWA. Evaluation of the Morrison Bros. Co. Liquid Sensor, Adjustable Level Sensor and Multi-Level Sensor. Final Report

CORDLESS HAND VACUUM USER GUIDE BOLT 1316 SERIES

DUVAL 52 CEILING FAN MODELS #50201, Español p. 19 LISTED FOR DAMP LOCATION

RK-02 Multi Point Detector Operator s Manual

Safety Message to Installers of Federal Signal Siren Speakers

BOLT ION 2-IN-1 CORDLESS VACUUM USER GUIDE REMANUFACTURED 1312R. For How-To videos, go to

TECHNICAL INSTRUCTIONS

MARTIN Insertable Dust Collector

Instruction Manual. Nacho Cheese Dispenser and Warmer

INSTALLATION INSTRUCTIONS and OPERATING MANUAL. *Aquastat is a registered trademark of Honeywell International, Inc.

690 Power Fishing System

Retrofit Instructions for Tower Dryer Moisture Sampler Blower Kit

INSTALLATION INSTRUCTIONS TXV Coils for Manufactured Housing EMA

2-in-1 Corded Stick Vacuum Cleaner

Installation and Operation Manual

INSTALLATION INSTRUCTIONS TABLE OF CONTENTS

Operating & Maintenance Manual. Alert-4 Ethernet LCD Master Alarm

HI Industrial Utility Heater HI Soleus Air International

TLS-350R UST Monitoring and Leak Detection System With Automatic Business Reconciliation

INSTALLATION INSTRUCTIONS

OPERATING AND INSTALLATION MANUAL

INSTALLATION INSTRUCTIONS

Drink Mixer Operation Manual

INSTALLATION AND OPERATING INSTRUCTIONS. For Reliance Controls Emergency Power Transfer Switch Kit Model Number 30216BRK

MaxLite LED High Bay Fixtures

Instruction Manual. Portion Cup Cheese Warmer

CARMEL 48 CEILING FAN

Three Phase Simplex. Installation (937) Installation Instructions and Operation/Troubleshooting Manual. Installation of Floats.

Refrigerant Recovery Machine. Model No Operating Manual

ARMITAGE CEILING FAN ITEM # MODEL #CC52WW5L. Español p. 17 ATTACH YOUR RECEIPT HERE. Purchase Date

Transcription:

Manual Number: 01-61-141 Revision : 1.7 Date: 10/27/16 Installation Instructions Remanufactured Veeder-Root Position Sensitive Sump Sensor PMP # 62323 Replaces Veeder-Root #794380-323

Contents Disclaimer... 2 Related Manuals... 3 Safety Symbols... 3 BEFORE YOU BEGIN... 4 SAFETY PRECAUTIONS FOR INSTALLATION AND MAINTENANCE... 4 Description... 5 Sensor Models... 5 In the box... 5 Installation Prep... 5 Installation of the Sensor... 6 Installation... 6 Installation cont.... 7 How to use the Connector Sealing Kit... 8 Functional / Maintenance Test Procedure... 9 What you will need:... 9 Testing for a Low Liquid Alarm... 9 Quick Reference... 10 Installation and Operation manuals... 10 Equipment Check Guidelines... 10 Equipment Calibration... 10 Maintenance Procedures... 10 Test Results/Reports... 10 Technical Contact... 10 Disclaimer All product or company s names, trade names, trademarks, parts numbers and part descriptions may be the trademarks of their respective owners, and are used for reference or identification purposes only. PMP does not claim any right to or affiliation with such owners. The PMP product described here is remanufactured and sold by PMP and is not the product of any other identified manufacturer. 2

Related Manuals This installation requires specific knowledge of Veeder-Root equipment and you may need to refer to the following OEM manuals to complete the installation: 576013-879 TLS-3XX Series Console Site Prep and Installation Manual 577013-879 TLS-4XX Series Console Site Prep and Installation Manual 576013-306 Dispenser Pan Sensors & Containment Sump Sensors Installation Guide 577013-750 Sensor Product Application Guide 577013-814 Operability Testing Guide 576013-818 TLS-3XX Series Consoles Troubleshooting Guide Safety Symbols The following safety symbols are used to alert you to potential hazards and precautions that should be taken. These symbols are not intended to alert you to all of the potential hazards you could be exposed to while working in a service station environment. These symbols cannot replace common sense and industry practices. Read and understand all of the written material related to the installation of this product. If you are un-sure of any aspect of this product, contact PMP for clarification Attention. Pay particular attention to the text adjacent to the use of this symbol to alert you to safety or operational issues. Remove / disconnect all power before proceeding with this installation. Potential shock hazard. Test circuit to verify power has been disconnected Cordon off work area with barriers to avoid contact with traffic Potentially explosive materials and or atmosphere. Take necessary precautions. Potentially flammable materials and or atmosphere. Take necessary precautions. Use appropriate safety equipment including equipment that may be mandated by federal, state and local regulations 3

BEFORE YOU BEGIN Service station equipment has both electricity and hazardous, flammable and potentially explosive liquid. Failure to follow the precautions below and instructions in this guide may result in serious injury and death. Follow all rules, codes and laws that apply in your area. Veeder-Root requires training certifications for contractors who install and set up equipment related to the TLS-350. Installers of this product must have a Veeder-Root certification of Level 2/3. Be sure that you have familiarized yourself with these requirements and determined if you are qualified to perform this installation. PMP shall not be liable for errors contained herein or for incidental or consequential damages in connection with furnishing, performance or use of this publication. PMP reserves the right to change product features or the information contained in this publication. Failure to install this product in accordance with OEM instructions and warnings will result in voiding of all warranties connected with this product and may damage the environment. SAFETY PRECAUTIONS FOR INSTALLATION AND MAINTENANCE Only a person with knowledge and experience with service station equipment should perform this work. Always make sure ALL power to the equipment you are working with is turned OFF before starting any maintenance. Note that more than one disconnect switch may be required to de-energize the equipment for maintenance and servicing. Use a voltmeter to make sure ALL circuits in the dispenser are deenergized. Failure to do so may result in serious injury. 4

3M 3570G-N 3M 3570G-N Description PMP Corporation s 62323 position sensitive sensors are used in dispenser pans and containment sumps. The sensor senses the presence of liquid while also ensuring the sensor remains in the installed position. If the sensor is raised, an integral sensor will trigger a Sensor Out alarm at the console. Sensor Models PMP OEM Number Description Number 62323 793480-323 Position Sensitive Sensor* *An Interstitial Sensor Interface Module is required for TLS-350 consoles. A Two-Wire Module is required for ILS-350 systems In the box Contents Sensor Qty 1 12 sensor cable 1 Installation instructions 1 Cable tie wrap, 2 Wire nut, P2 blue 2 Rubber insert for cord-grip 1 Cord-grip, 1/2 NPT 1 3M Scotchcast Seal Pack 1 Note: An additional rubber insert, for the cord grip, has been provided to accommodate smaller gauge wire such as the one used on this sensor. Depending on your installation, you may need to replace the rubber insert to ensure a water tight connection. Installation Prep Note: You must refer to the OEM manuals listed earlier in this manual for detailed instructions including console setup. Reminder: If you are unsure of the condition of the backup battery or the last time the console was backedup, now may be a good time to consider performing a system backup and replacing the battery prior to removing power from the console. The battery can be purchased from PMP using # 80200. 1. Turn-off power to the system. 2. Block off the work area. 3. Confirm you have the correct sensor for your application. 4. Confirm that there is no liquid in the sump prior to installing the sensor. 5

Installation of the Sensor Note: You must refer to the OEM manuals listed earlier in this manual for detailed instructions including console setup. The Position Sensitive Pan/Sump Sensor utilizes a position sensor to detect when the sensor is moved or installed improperly. It is essential that the sensor be mounted vertical and so that the position sensor is pressed-in. The illustration below shows the proper installation and the various alarm conditions: CORRECT INCORRECT Bottom of pan/sump MAR 8, 2016 2:21:33 PM L1:FUEL ALARM Position Sensor MAR 8, 2016 2:21:33 PM ALL FUNCTIONS NORMAL MAR 8, 2016 2:21:33 PM L1:SENSOR OUT Installation 1. Mount the sensor in a spot where it can easily be removed for testing. 2. Do not mount on flexible product lines. 3. Sensor must be mounted vertically at the lowest point in the sump. Some sumps will have a cup molded into the bottom of the sump specifically for mounting a sensor. 4. The sensor must also be mounted so that the position sensor is pressed-in (see illustration above). Containment Sump Do not mount the sensor to a flexible product line Weatherproof Junction box and cord grip 90 Seal-off Mount vertically with hardware provided. Additional hardware may be required for your application. A Universal Sensor Mounting Kit is available from PMP using # 80205 6

Installation cont. 1. Install the cord grip in the junction box Dispenser Pan Weatherproof Junction box and cord grip 2. Feed the sensor cable though the cord grip. 3. Using the wire nuts provided, connect the sensor wires to the field wiring in accordance with applicable codes..... Do not mount the sensor to a flexible product line.. Seal-off 4. Place the field wiring in the Connector Sealing Pack provided. See instructions below on how to use the Connector Sealing Pack. 5. Tighten the cord grip. 6. Enclose the wiring and seal kit in the junction box. 7. Re-install the junction box cover. 8. Check to be sure all of the cord grips have been tightened to make them water tight. 9. Restore power to the console and proceed with the setup process. 90 Mount vertically with hardware provided. Additional hardware may be required for your application. A Universal Sensor Mounting Kit is available from PMP using # 80205 7

How to use the Connector Sealing Kit a. Carefully cut the bag and remove the seal pack. b. Remove the two part seal pack. c. Grip the edges of the seal pack at the center and vigorously wiggle the plastic bag to weaken the barrier between the two halves. d. Squeeze the resin back and forth 25-30 times to thoroughly mix the two parts. e. Squeeze the mixed resin to one side of the packet and cut off the other side. f. Insert the connections made above. Be sure the connections are inserted to the full depth of the seal pack to ensure a watertight connection. g. Use the wire tie provided to cinch the packet, where shown, to secure the wires in the epoxy pack during the curing process. You can also use electrical tape to secure the wires if you prefer. h. Cure time is approximately 8-12 min @ 73 F. Complete the installation 1. Enclose the wiring and seal kit in the junction box. 2. Re-install the junction box cover. 3. Check to be sure all of the cord grips have been tightened to make them water tight. 4. Restore power to the console and proceed with the setup process. 8

Functional / Maintenance Test Procedure What you will need: Safety equipment including (but not limited to), barricades, safety glasses, safety vests, fire extinguisher etc. per federal, state and local requirements. 1 container for testing with water. This container must be larger in diameter than the sensor and tall enough to hold 12 of water and be marked with the heights outlined below. Testing for a Low Liquid Alarm 1. Remove the sensor from the pan or sump and move to a safe area. 2. Removing the sensor should trigger a Sensor Out alarm at the console 3. Inspect the sensor for any physical damage including cables and connections. 4. Place the sensor in the container, oriented as it would be installed. This should clear the Sensor Out alarm 5. Add a minimum of 2 inches of water. 6. The sensor should now trigger a Fuel Alarm on the TLS. Depending on the console and site configuration, it may take up to 5 minutes to trigger an alarm. 7. Clear the alarm on the TLS-350 by pressing the Alarm / Test key or pressing the Alarm button twice on the TLS-450. 8. If an alarm is not detected, the sensor has failed the test and must be replaced 9. If the sensor passed the test, allow the sensor to dry and reinstall per the installation instructions. 10. Record the test results for your records. One sensor per test ALARM Insert sensor in minimum of 2 of water Wait up to 5 minutes before failing the sensor Sensor should trigger a Low Liquid Alarm 9

Quick Reference Installation and Operation manuals PMP provides an overview of the sensor installation with each sensor shipped. These installation overviews can also be found on the internet at www.pmp-corp.com. Refer to the OEM manuals listed above for detailed installation instructions. Equipment Check Guidelines No vendor specific checklist is provided for the equipment used to monitor these sensors. However, the EPA provides a useful checklist for Underground Storage Tank (UST) owners. The current checklist as of the publication of this PMP Pulse is the document EPA 510-K-16-001, Operating And Maintaining Underground Storage Tank Systems dated February, 2016. It can be downloaded from the EPA s website at http://www.epa.gov/ust. Equipment Calibration No calibration is required for the sensors discussed in this document. Maintenance Procedures Periodic maintenance may be required by local regulations. Operability test guidelines for each sensor can be obtained from PMP or be found on the internet at www.pmp-corp.com. Sensors should be tested at least annually. However, Federal, State or Local regulations may require more frequent inspections and testing. Test Results/Reports Third party evaluations were conducted by Ken Wilcox and Associates. Test results can be obtained from PMP. Technical Contact Support questions can be directed to the Engineering department at PMP. Refer to the contact information printed at the bottom of this page. All product or company s names, trade names, trademarks, parts numbers and part descriptions may be the trademarks of their respective owners, and are used for reference or identification purposes only. PMP does not claim any right to or affiliation with such owners. The PMP product described here is manufactured or remanufactured and sold by PMP and is not the product of any other identified manufacturer. 10