Combi C30 & C35. User Guide FAN POWERED HIGH EFFICIENCY MODULATING DOMESTIC CONDENSING GAS COMBINATION BOILER

Similar documents
System s30. User Guide FAN POWERED HIGH EFFICIENCY MODULATING DOMESTIC CONDENSING GAS SYSTEM BOILER

Logic+ Combi

i 24, i 30, i 35 combination boilers USER GUIDE For Installation Guide see reverse of book UIN A05 October 2017

USER GUIDE VOGUE COMBI GEN2 C26 C32 C40

USER GUIDE LOGIC HEAT H

USERS GUIDE. Esprit eco 24, 30. For installation guide see reverse of book

USERS GUIDE. LOGIC+ Combi 24, 30, 35

USER GUIDE VOGUE MAX SYSTEM

USERS GUIDE 24, 30. For installation guide see reverse of book

Heat 45 & 55. User Instructions FAN POWERED HIGH EFFICIENCY MODULATING DOMESTIC CONDENSING GAS COMBINATION BOILER

USER GUIDE. IMAX XTRA EL kW. For Installation Guide see reverse of book

GB24 & GB30. User Manual

2 Minimiser SE - User's

WARMCAIR. Condensing Air & Water Heater. High Efficiency Downflow Condensing Air & Water Heater USERS INSTRUCTIONS

Ultracom cxi. Instructions for Use. High Efficiency Condensing System Boilers. To b e l e f t w i t h t h e u s e r.

Maximiser SE. USER S INSTRUCTIONS Natural gas only INSTALLER: TELEPHONE:

USERS GUIDE. Electronic Timer, 7 day. LOGIC+ Combi, LOGIC Combi & LOGIC Combi E 24, 30, 35

Open Vented Condensing Boilers

USER INSTRUCTIONS & CUSTOMER CARE GUIDE Si II SERIES

Ultracom hxi. Instructions for Use. High Efficiency Condensing System Boilers. To b e l e f t w i t h t h e u s e r.

RF ELECTRONIC PROGRAMMABLE ROOM THERMOSTAT, 7 DAY

Baxi Maxflow Combi WM

User's Instructions. Alpha CB50

Baxi Maxflow Combi FS

British Gas 330+ High Efficiency Condensing Boiler. Instructions for Use. To b e l e f t w i t h t h e u s e r. British Gas Service Tel:

User's Instructions. Alpha CD25X/28X. Range of Wall Mounted, Fan Assisted, Room Sealed, Gas Fired, High Efficiency Condensing Combination Boilers

Baxi System 100 HE Plus. User s Operating Instructions. Wall Mounted Powered Flue Condensing Gas Fired Central Heating Boiler

MERIDIAN HE 30 C. User instructions. Please read the Important Notice within this guide regarding your boiler warranty

iheat 25c iheat 30c iheat 35c

Format System 25 HE. User instructions. Please read the Important Notice within this guide regarding your boiler warranty

FORMAT DGT HE. User instructions. Please read the Important Notice within this guide regarding your boiler warranty

User's Instructions. Alpha CD24C/32C. Range of Wall Mounted, Fan Assisted, Room Sealed, Gas Fired, High Efficiency Condensing Combination Boilers

PLEASE LEAVE THIS INSTRUCTION WITH THE USER. Ecomfort 30 HE. User instructions

Baxi Combi 133 HE Plus Baxi Combi 100 HE Plus Baxi Combi 80 HE Plus. User s Operating Instructions

condens Instructions for Use Betacom 2 24 G.C. No Betacom 2 28 G.C. No

24CDi, 28CDi & 35CDi II COMBI

O. Gas boiler. Gaz 6000 W WBN H-E-N/L-S2400. Operating instructions for the end customer (2017/09) en

Greenstar 25Si/30Si USER INSTRUCTIONS & CUSTOMER CARE GUIDE

Combi Eco Elite Range. User s Guide and Important Warranty Information

The guarantee on this appliance is valid for 12 months from the first day of installation.

Ultracom 2. sxi. Instructions for Use. 12sxi. 18sxi. 30sxi. High Efficiency Condensing System Boilers. To be left with the user. G.C. No.

User Guide and Important Warranty Information. Suprima HE. Condensing Central Heating Boiler. Please read this document and keep it safe.

PLEASE LEAVE THIS INSTRUCTION WITH THE USER ECOMFORT PLUS 25 HE. User instructions

MURELLE EV HE 25/55-30/55

Osprey 2 CFL

Vote for your Installer of the year at. 9/14, 14/19 & 19/24CBi. Worcester supports the Benchmark code of practice

Greenstar 12i/24i System

GREENSTAR Ri ErP. User instructions UK/IE. Wall hung RSF gas fired condensing regular boiler. For central heating systems

Baxi Bahama 100. Gas Fired Wall Mounted Combination Boiler. User s Operating Instructions

GREENSTAR i SYSTEM USER MANUAL WALL HUNG RSF GAS FIRED CONDENSING SYSTEM BOILER FOR CENTRAL HEATING SYSTEMS UK/IE (2013/08)

GREENSTAR HIGHFLOW 440/550CDi

Baxi Combi 80Eco. Gas Fired Wall Mounted Combination Boiler. User s Operating Instructions

Mikrofill Ethos Condensing combination boiler. Maintenance Instructions 24cc

User Manual RBS 24. for model CE series ENERGY. Wall mounted instantaneous combi boiler room sealed chamber

USER INSTRUCTIONS & CUSTOMER CARE GUIDE HIGHFLOW 400 ELECTRONIC SERIES

With a power output ranging from 13kW to 24kW, they provide the flexible answer for the majority of traditional installation scenarios.

Baxi Megaflo System HE IE Range. User s Operating Instructions & Important Warranty Information. Gas Fired Wall Mounted Condensing Boiler

User Manual for model

Vote for your Installer of the year at HEATSLAVE

GREENSTAR Ri USER INSTRUCTIONS UK/IE WALL HUNG RSF GAS FIRED CONDENSING REGULAR BOILER FOR CENTRAL HEATING SYSTEMS a (2010/10)

Users Manual. Gas wall hung Boiler condensing Buderus /S. Please read thoroughly before operating the unit

GREENSTAR HIGHFLOW 440/550CDi

SIME FORMAT WALL HUNG BOILERS MODEL 34i AND MODEL 34e. cod A

User Manual FLOWMAX-90. for model. Condensing water heater 85,000 BTU. Installation, operating, commissioning and maintenance instructions.

WALL HUNG RSF GAS FIRED CONDENSING REGULAR BOILER

VIESMANN. Operating instructions VITODENS 100. for system users. Heating system with control unit for constant temperature operation

Greenstar 12i system / 24i system

GREENSTAR i JUNIOR USER INSTRUCTIONS UK/IE WALL HUNG RSF GAS FIRED CONDENSING COMBINATION BOILER

Grant Vortex. Boiler House Floor Standing Condensing Oil Boiler Range User Handbook. Model shown: VTXBH3646

INDEPENDENT COMBINATION & SYSTEM BOILERS.

INSTALLATION, OPERATION AND MAINTENANCE MANUAL

WEATHER COMPENSATION KIT

Linea HE. High efficiency combi boiler. Users Instructions THESE INSTRUCTIONS TO BE RETAINED BY USER

Baxi Combi 105 HE. User s Operating Instructions. Gas Fired Wall Mounted Condensing Boiler

condens Instructions for Use Ultracom 2 35 Store G.C. No

Residential Gas Condensing Boiler Greenstar combi 100 p / 151 p ZWB28-3A... ZWB42-3A...

Performa 24. Gas Fired Wall Mounted Combination Boiler. User s Operating Instructions

Powermax HE 85, 115 & 150 Litre Condensing Boilers with Integrated Hot Water Storage

DANESMOOR 12-14, 15-19, 20-25, 26-32, 32-50, FLOOR-STANDING OIL-FIRED PRESSURE-JET BOILERS USER INSTRUCTIONS & CUSTOMER CARE GUIDE

ir-range 8G /03.15 Changes reserved.

VIESMANN. Operating instructions VITODENS 100-W. for the system user

Aqua Balance. AquaBalance TM CONTROL MODULE QUICK START GUIDE LEGEND

WALL HUNG RSF GAS FIRED CONDENSING COMBINATION BOILER GREENSTAR 24i Junior/28i Junior

Operating instructions

/2005 GB(EN) For the user. Wall-mounted condensing gas combi boiler Buderus /C, /C

GREENSTAR HEATSLAVE II ErP+ 12/18, 18/25 & 25/32

AquaNova. Water heater. Users Instructions THESE INSTRUCTIONS TO BE RETAINED BY USER

The Ideal Logic. Combination, Heat Only and System Boilers. Heating Solutions.

BOILING UNIT REDITAP. Installation and User Guide. IMPORTANT: This booklet should be left with the user after installation and demonstration

Operating instructions

GREENSTAR HEATSLAVE II EXTERNAL 12/18, 18/25 & 25/32

User Guide and Important Warranty Information. Promax System HE Plus A Range. Condensing System Boiler

User Manual for model RK 18 RK 25 RK 34 CE 0694 RK 18_25_34 - RAD - ING - MAN.UT A - DIGITECH 2 - REGNO UNITO - EXTRAHEAT - CBD

Residential Gas Condensing Boiler Greenstar ZBR16/21/28/35/42-3A... ZWB28/35/42-3A...

User Guide. Platinum Combi Gas Fired Wall Mounted Condensing Combination Boiler

GB24 & GB30. User & Installation Instructions BOILER OUTPUT

User Guide. Main Eco Elite Combi Condensing Central Heating Boiler

Performa 24 Eco HE. User Guide and Important Warranty Information. Condensing Combination Boiler

Mikrofill Ethos Condensing combination boiler

Greenstar 24i junior / 28i junior

Transcription:

Combi C30 & C35 User Guide FAN POWERED HIGH EFFICIENCY MODULATING DOMESTIC CONDENSING GAS COMBINATION BOILER When replacing any part on this appliance, use only spare parts that you can be assured confirm to the safety and performance specification that we require. Do not use reconditioned or copy parts that have not been clearly authorised by Keston. For the very latest copy of literature for specification and maintenance practices visit our website www.keston.co.uk where you can download the relevant information in PDF format. July 2016 UIN 215417 A01

CONTENTS 1. Introduction... 3 Safety... 3 Electricity Supply... 3 Important Notes... 3 2. Boiler Operation... 4 Controls Diagram... 4 To Start the Boiler... 4 Operation Modes... 5 Preheat Domestic Hot Water... 5 Control of Water Temperature... 5 Efficient Heating System Operation... 6 Weather Compensation... 6 Boiler Frost Protection... 6 Boiler Restart... 6 Mains Power Off... 6 3. System Water Pressure... 7 4. Condensate Drain... 8 5. General Information... 9 Boiler Pump... 9 Minimum Clearances... 9 Escape of Gas... 9 Cleaning... 9 Maintenance... 9 6. Points for the Boiler User... 10 Troubleshooting...11 7. Display Functions - Normal Operation... 12-13 8. Display Functions - Settings Changed... 13 9. Display Functions - Fault Messages... 14-18 Keston is a member of the Benchmark scheme and fully supports the aims of the programme. Benchmark has been introduced to improve the standards of installation and commissioning of central heating systems in the UK and to encourage the regular servicing of all central heating systems to ensure safety and efficiency. THE BENCHMARK SERVICE INTERVAL RECORD MUST BE COMPLETED AFTER EACH SERVICE 2

1. INTRODUCTION The Keston Combi C is a combination boiler providing both central heating and instantaneous domestic hot water. Featuring full sequence automatic ignition and fan assisted combustion. Due to the high efficiency of the boiler, condensate is produced from the flue gases and this is drained to a suitable disposal point through a plastic waste pipe at the base of the boiler. A condensate plume will also be visible at the flue terminal. Safety CURRENT GAS SAFETY (INSTALLATION & USE) REGULATIONS OR RULES IN FORCE. In your own interest, and that of safety, it is the law that this boiler must be installed by a Gas Safe Registered Engineer, in accordance with the above regulations. In IE, the installation must be carried out by a Registered Gas Installer (RGII) and installed in accordance with the current edition of I.S. 813 Domestic Gas Installations, the current Building Regulations and reference should be made to the current ETCI rules for electrical installation. It is essential that the instructions in this booklet are strictly followed, for safe and economical operation of the boiler. ELECTRICITY SUPPLY This appliance must be earthed. Supply: 230 V ~ 50 Hz. The fusing should be 3A. IMPORTANT NOTES This appliance must not be operated without the casing correctly fitted and forming an adequate seal. If the boiler is installed in a compartment then the compartment MUST NOT be used for storage purposes. If it is known or suspected that a fault exists on the boiler then it MUST NOT BE USED until the fault has been corrected by a Gas Safe Registered Engineer or in IE a Registered Gas Installer (RGII). Under NO circumstances should any of the sealed components on this appliance be used incorrectly or tampered with. This appliance can be used by children 8 years and above. Also persons with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, provided they have been given supervision or instruction concerning use of the appliance in a safe way and understand the hazards involved. Children shall not play with the appliance. Cleaning and user maintenance shall not be made by children without supervision. 3

2. BOILER OPERATION Legend A. Domestic Hot Water Temperature Knob B. Central Heating Temperature Knob C. Mode Knob D. Boiler Status Display E. Burner on Indicator F. Central Heating Economy Setting G.Pressure Gauge H. Restart Button I. Preheat button G MIN MAX MIN MAX HOT WATER CENTRAL HEATING MODE e BOILER OFF A I E D H B F C TO START THE BOILER If a programmer is fitted refer to separate instructions for the programmer before continuing. Start the boiler as follows: 1. Set the mode knob (C) to BOILER OFF. 2. Set the Domestic Hot Water temperature knob (A) and Central Heating temperature knob (B) to MAX. 3. Ensure that all hot water taps are turned off. 5. Switch on electricity to the boiler and check that all external controls, e.g. programmer and room thermostat, are on. 4. Set the mode knob (C) to (winter). The boiler will commence ignition sequence, supplying heat to the central heating, if required. Note. In normal operation the boiler status display (D) will display messages (see section 7). Note. Boiler frost protection - boiler will fire if temperature is below 5ºC. During normal operation the burner on symbol (E) will remain illuminated when the burner is lit. Note. If the boiler fails to light after five attempts the following fault messages will be displayed: Ignition Lockout 1/2 Check Other Gas Appliances Work Restart Boiler Restart Ignition Lockout 2/2 If Fault Persists Restart To restart the boiler, press restart. The boiler will repeat the ignition sequence. If the boiler still fails to light consult a Registered Gas Installer, or in IE a Registered Gas Installer (RGII). 4

OPERATION MODES Winter Conditions - (Central Heating and Domestic Hot Water required) Set the mode knob (C) (winter). The boiler will fire and supply heat to the radiators. The domestic hot water preheat will operate with the preheat button (I) set to Preheat On. Summer Conditions - (Domestic Hot Water only required) Set the mode knob (C) to (summer). Set the central heating demand on the external controls to OFF. The domestic hot water preheat will operate with the preheat knob (I) set to Hot Water On. Boiler Off Set the mode knob (C) to BOILER OFF. The boiler mains power supply must be left on to enable frost protection (see Frost Protection). PREHEAT - DOMESTIC HOT WATER The domestic hot water heat exchanger within the boiler can be kept preheated to provide faster delivery of hot water at the tap. This is achieved by pressing the PREHEAT button to PREHEAT ON. The boiler will operate periodically for a few seconds to maintain the domestic hot water heat exchanger in a preheated condition. The average time period between operation is 90 minutes. This may vary considerably due to the surrounding ambient temperature of the boiler. The boiler will operate whenever there is a demand for domestic hot water. If standard hot water delivery is satisfactory press the PREHEAT button to PREHEAT OFF. CONTROL OF WATER TEMPERATURE Domestic Hot Water The domestic hot water temperature is limited by the boiler controls to a maximum temperature of 65 º C, adjustable via the domestic hot water temperature knob (A). However at low DHW draw off rates the maximum temperature may exceed 65ºC. Approximate temperatures for domestic hot water: Knob Setting Hot Water Temperature (approx.) Minimum 40ºC Maximum 65ºC Due to system variations and seasonal temperature fluctuations domestic hot water flow rates/temperature rise will vary, requiring adjustment at the tap : the lower the flow rate the higher the temperature, and vice versa. Central Heating The boiler controls the central heating radiator temperature to a maximum of 80 o C, adjustable via the central heating temperature knob (B). Approximate temperatures for central heating: Knob Setting Central Heating Radiator Temperature (approx.) Minimum 30ºC Maximum 80ºC For economy setting Operation. refer to Efficient Heating System 5

EFFICIENT HEATING SYSTEM OPERATION The boiler is a high efficiency, condensing appliance which will automatically adjust its output to match the demand for heat. Therefore gas consumption is reduced as the heat demand is reduced. The boiler condenses water from the flue gases when operating most efficiently. To operate your boiler efficiently (using less gas) turn the central heating temperature knob (B) to the position or lower. In winter periods it may be necessary to turn the knob towards the max position to meet heating requirements. This will depend on the house and radiators used. Reducing the room thermostat setting by 1ºC can reduce gas consumption by up to 10%. WEATHER COMPENSATION When the Weather Compensation Kit (supplied as standard) is fitted to the system then the central heating temperature knob (B) becomes a method of controlling room temperature. Turn the knob clockwise to increase room temperature and anticlockwise to decrease room temperature. Once the desired setting has been achieved, leave the knob in this position and the system will automatically achieve the desired room temperature for all outside weather conditions. BOILER FROST PROTECTION The boiler is fitted with frost protection that operates in all modes, provided the power supply to the boiler is always turned on. If the water in the boiler falls below 5ºC, the frost protection will activate and run the boiler to avoid freezing. The process does not guarantee that all other parts of the system will be protected. If a system frost thermostat has been installed, the boiler must be set in winter mode,, for the system frost protection to run. If no system frost protection is provided and frost is likely during a short absence from home it is recommended to leave the system heating controls or built in programmer (if fitted) switched on and run at a reduced temperature setting. For longer periods, the entire system should be drained. BOILER RESTART To restart the boiler, when directed in the listed fault messages (see section 9), press Restart. The boiler will repeat its ignition sequence. If the boiler still fails to start consult a Gas Safe Registered Engineer or in IE a Registered Gas Installer (RGII). MAINS POWER OFF To remove all power to the boiler the mains power switch must be turned off. 6

3. SYSTEM WATER PRESSURE The system pressure gauge (G - see page 4) indicates the central heating system pressure. If the pressure is seen to fall below the original installation pressure of 1-2 bar over a period of time and continue to fall then a water leak may be indicated. In this event re-pressurise the system as shown below. If unable to do so or if the pressure continues to drop a Gas Safe Registered Engineer or in IE a Registered Gas Installer (RGII) should be consulted. THE BOILER WILL NOT OPERATE IF THE PRESSURE HAS REDUCED TO LESS THAN 0.3 BAR UNDER THIS CONDITION. To Top up the system :- 4. Turn the Domestic Hot Water (DHW) Inlet A blue handle to the horizontal position. 5. Ensuring no leaks are seen, gradually turn the filling loop handle (blue) B to the horizontal position. 6. Wait for the pressure gauge to reach 1 to 1.5 bar. 1. Ensure both A & B handles (blue) are in closed position (as shown below) 2. Remove the plug and cap and retain. 3. Connect the filling loop to the Domestic Hot Water (DHW) inlet and tighten. Also ensure that the other end of filling loop is hand tight. Starting Position Domestic Hot Water (DHW) Inlet Valve 7. Once pressure is reached turn valves A & B back to the closed position. 8. Disconnect the filling loop, replace cap and plug. Note there can be some water spillage at this point. Filling Position Cap Filling Loop Cap B Plug A Filling Loop Plug B A Filling Loop Handle (Blue) 7

4. CONDENSATE DRAIN This appliance is fitted with a siphonic condensate trap system that reduces the risk of the appliance condensate from freezing. However should the condensate pipe to this appliance freeze, please follow these instructions: a. If you do not feel competent to carry out the defrosting instructions below please call your local Gas Safe Registered installer for assistance. b. If you do feel competent to carry out the following instructions please do so with care when handling hot utensils. Do not attempt to thaw pipework above ground level. If this appliance develops a blockage in its condensate pipe, its condensate will build up to a point where it will make a gurgling noise prior to locking out displaying Ignition Lockout on the display. If the appliance is restarted it will make a gurgling noise prior to it locking out displaying Ignition Lockout on the display.. To unblock a frozen condensate pipe; 1. Follow the routing of the plastic pipe from its exit point on the appliance, through its route to its termination point. Locate the frozen blockage. It is likely that the pipe is frozen at the most exposed point external to the building or where there is some obstruction to flow. This could be at the open end of the pipe, at a bend or elbow, or where there is a dip in the pipe in which condensate can collect. The location of the blockage should be identified as closely as possible before taking further action. 2. Apply a hot water bottle, microwaveable heat pack or a warm damp cloth to the frozen blockage area. Several applications may have to be made before it fully defrosts. Warm water can also be poured onto the pipe from a watering can or similar. DO NOT use boiling water. 3. Caution when using warm water as this may freeze and cause other localised hazards. 4. Once the blockage is removed and the condensate can flow freely, restart the appliance. (Refer to To Start the boiler ) 5. If the appliance fails to ignite, call your Gas Safe Registered engineer. Preventative Solutions During cold weather, set the central heating temperature knob (B) to maximum, (Must return to original setting once cold spell is over). Place the heating on continuous and turn the room thermostat down to 15ºC overnight or when unoccupied. (Return to normal after cold spell). 8

5. GENERAL INFORMATION BOILER PUMP The boiler pump will operate briefly as a self-check once every 24 hours, regardless of system demand. MINIMUM CLEARANCES Clearance of 165mm (6 1 /2 ) above, 100mm (4 ) below, 2.5mm (9 1 /8 ) at the sides and 450mm (17 3 /4 ) at the front of the boiler casing must be allowed for servicing. BOTTOM CLEARANCE Bottom clearance after installation can be reduced to 5mm This must be obtained with an easily removable panel, to enable the system pressure gauge to be visible and to provide the 100mm clearance required for servicing. SERVICE REQUEST FUNCTION When the boiler has been installed for more than 1 year the following message will appear on screen: ESCAPE OF GAS Should a gas leak or fault be suspected contact the National Gas Emergency Service without delay. Telephone 0800 111 999. Ensure that; - All naked flames are extinguished - Do not operate electrical switches - Open all windows and doors CLEANING For normal cleaning simply dust with a dry cloth. To remove stubborn marks and stains, wipe with a damp cloth and finish off with a dry cloth. DO NOT use abrasive cleaning materials. MAINTENANCE The appliance should be serviced at least once a year by a Gas Safe Registered Engineer or in IE a Registered Gas Installer (RGII). Press Restart to clear this message. 9

6. POINTS FOR THE BOILER USER Note. In line with our current warranty policy we would ask that you check through the following guide to identify any problems external to the boiler prior to requesting a service engineers visit. Should the problem be found to be other than with the appliance we reserve the right to levy a charge for the visit, or for any pre-arranged visit where access is not gained by the engineer. FOR ANY QUERIES PLEASE RING THE KESTON CONSUMER HELPLINE : 01482 443005 NOTE. BOILER RESTART PROCEDURE - To restart boiler, press the Restart button. 10

TROUBLESHOOTING NO HOT WATER NO CENTRAL HEATING NO HOT WATER OR CENTRAL HEATING Check the mains power is turned on and ensure mode knob (C) is in the summer or winter position Check the mains power is turned on and ensure mode knob (C) is in the winter position Check the mains power is turned on and ensure mode knob (C) is in the winter position Is water coming out of the hot water tap when turned on? YES See boiler Display Functions section. If Boiler off is displayed then contact Keston Customer Services Helpline if your appliance is under warranty or a Gas Safe Registered Engineer, in IE a Registered Gas Installer (RGII), if out of warranty NO Check the programmer (internal or external to the boiler) is in an ON position and the room thermostat is turned up Does the boiler operate and provide central heating? YES Check the time settings on the programmer are as you require and adjust if necessary NO Does the boiler have a display showing on the front control panel? YES See boiler Display Functions section Contact a Gas Safe Registered Engineer or in IE a Registered Gas Installer (RGII) NO Contact a Gas Safe Registered Engineer or in IE a Registered Gas Installer (RGII) See boiler Display Functions section. If Boiler off is displayed then contact a Gas Safe Registered Engineer or in IE a Registered Gas Installer (RGII) 11

7. DISPLAY FUNCTIONS - NORMAL OPERATION MODE Note. The temperatures shown below are for illustration purposes only. The measured temperatures will be shown on the boiler. Mode Knob in BOILER OFF position: Domestic hot water operation with call for CH: Mode knob in position and no heat demand: Central Heating Operaton: Mode knob in heat demand: and no Preheat operation: Domestic hot water operation without call for CH: Boiler frost protection: 12

Service required: 8. DISPLAY FUNCTIONS - SETTINGS CHANGED Note. The temperatures shown below are for illustration purposes only. The measured temperatures will be shown on the boiler. DHW temperature knob moved: CH temperature knob moved: Pre-Heat If preheat is switched on, then the boiler will periodically fire the burner. Thereby reducing the time taken to provide hot water. If preheat is switched off the response time will be reduced, although gas consumption will also be reduced. To switch preheat on press the Hot Water Preheat Off button: CH temperature knob moved with outside sensor connected: To switch preheat off press the Hot Water Preheat On button: 13

9. DISPLAY FUNCTIONS - FAULT MESSAGES BOILER DISPLAY MESSAGE Outside Sensor Fault ACTION Restart the appliance - if the boiler fails to operate then please contact Keston (if under warranty) or alternatively a Gas Safe Registered Engineer if outside of the warranty period. In IE contact a Registered Gas Installer (RGII). Restart Low Mains Voltage Contact a qualified electrician or your electricty provider. Contact Electricity Provider PCB Fault Unconfigured PCB. Please contact Keston (if under warranty) or alternatively a Gas Safe Registered Engineer if outside of the warranty period. In IE contact a Registered Gas Installer (RGII). Restart Too Many Restarts Restart 1. Turn power off and on at the fused spur. 2. If the boiler fails to operate plese contact Keston (if under wrranty) or alternatively a Gas Safe Registered Engineer if outside of the warranty period. In IE contact a Registered Gas Installer (RGII). 14

9. (CONT D) DISPLAY FUNCTIONS - FAULT MESSAGES BOILER DISPLAY MESSAGE Flame on Before Gas On ACTION Restart the appliance - if the boiler fails to operate then please contact Keston (if under warranty) or alternatively a Gas Safe Registered Engineer if outside of the warranty period. In IE contact a Registered Gas Installer (RGII). Restart Water Pressure 1/3 With Boiler Off & System Cold Fill system to 1.0 Bar Check system pressure is between 1 & 1.5bar on the pressure gauge. If the boiler fails to operate then plese contact Keston (if under warranty) or alternatively a Gas Safe Registered Engineer if outside of the warranty period. In IE contact a Registered Gas Installer (RGII). Water Pressure 2/3 Bleed Radiators Refill System to 1.0 Bar Restart Water Pressure 3/3 If fault persists Restart 15

9. (CONT D) DISPLAY FUNCTIONS - FAULT MESSAGES BOILER DISPLAY MESSAGE Overheat Lockout 1/4 With Boiler Off & System Cold Fill system to 1.0 Bar Restart Overheat Lockout 2/4 Bleed Radiators Refill System to 1.0 Bar ACTION Check system pressure is between 1 & 1.5 bar on the pressure gauge. Restart the appliance. If the boiler fails to operate then pelase contact Keston (if under warranty) or alternatively a Gas Safe Registered Engineer if outside of the warranty period. In IE contact a Registered Gas Installer (RGII). Restart Overheat Lockout 3/4 Check Radiator Valves And Boiler Valves Are Open Restart Overheat Lockout 4/4 Restart Boiler If Fault Persists Restart 16

9. (CONT D) DISPLAY FUNCTIONS - FAULT MESSAGES BOILER DISPLAY MESSAGE Flame Loss Ignition Lockout 1/2 Check Other Gas Appliances Work Restart Boiler Restart ACTION 1. Check other gas appliances in the house are working to confirm a supply is present in the property. 2. If other appliances fdo not work or there are not other appliances, check the gas supply is on at the meter and/or pre payment meter has credit. If the boiler fails to operate then please contact Keston (if under warranty) or alternatively a Gas Safe Registered Engineer if outside of the warranty period. In IE contact a Registered Gas Installer (RGII). 1. Check other gas appliances in the house are working to confirm a supply is present in the property. 2. If other appliances fdo not work or there are not other appliances, check the gas supply is on at the meter and/or pre payment meter has credit. If the boiler fails to operate then please contact Keston (if under warranty) or alternatively a Gas Safe Registered Engineer if outside of the warranty period. In IE contact a Registered Gas Installer (RGII). Ignition Lockout 2/2 If Fault Persists Restart Fan Fault Restart the appliance - if the boiler fails to operate then please contact Keston (if under warranty) or alternatively a Gas Safe Registered Engineer if outside of the warranty period. In IE contact a Registered Gas Installer (RGII). Restart 17

9. (CONT D) DISPLAY FUNCTIONS - FAULT MESSAGES BOILER DISPLAY MESSAGE Flow Thermistor Fault ACTION Restart the appliance - if the boiler fails to operate then plese contact Keston (if under warranty) or alternatively a Gas Safe Registered Engineer if outside of the warranty period. In IE contact a Registered Gas Installer (RGII). Restart Return Thermistor Fault Restart the appliance - if the boiler fails to operate then plese contact Keston (if under warranty) or alternatively a Gas Safe Registered Engineer if outside of the warranty period. In IE contact a Registered Gas Installer (RGII). Restart 18

19

Keston pursues a policy of continuing improvement in the design and performance of its products. The right is therefore reserved to vary specification without notice. Keston Heating, PO Box 103, National Avenue, Kingston Upon Hull, HU5 4JN Tel. 01482 443005 Fax. 01482 467133. email info@keston.co.uk. www.keston.co.uk