For an ideal gas mixture, Dalton s law states that the sum of the partial pressures of the individual components is equal to the total pressure.

Similar documents
Department of Mechanical Engineering ME 322 Mechanical Engineering Thermodynamics

ME 410 MECHANICAL ENGINEERING SYSTEMS LABORATORY MASS & ENERGY BALANCES IN PSYCHROMETRIC PROCESSES EXPERIMENT 3

Chapter 14 GAS VAPOR MIXTURES AND AIR-CONDITIONING

Thermodynamics II Chapter 6 Mixtures & Psychrometry

ME 410 MECHA ICAL E GI EERI G SYSTEMS LABORATORY

Chapter 8 Balances on Nonreactive Processes PSYCHROMETRIC CHART

ME Mechanical Engineering Systems Laboratory. Experiment 3 - Mass and Energy Balances in Psychrometric Processes

MECHANICAL ENGINEERING THERMAL AND FLUID SYSTEMS STUDY PROBLEMS

AND AIR-CONDITIONING. Dr Ali Jawarneh Department of Mechanical Engineering Hashemite University

Week 4. Gas-vapor mixtures Air conditioning processes. ME 300 Thermodynamics II 1

Air Conditioning Clinic

CE311 Fall 2016 Mid-Term Exam 1

S.A. Klein and G.F. Nellis Cambridge University Press, 2011

The Basics - B Practical Psychrometrics. Jerry Cohen President Jacco & Assoc.

Psychrometrics. Outline. Psychrometrics. What is psychrometrics? Psychrometrics in daily life and food industry Psychrometric chart

HVAC (Heating, Ventilating, and Air Conditioning)

Chapter 14, Problem 27.

A/C Cooling Load calculation and measurement

UNIT-III PSYCHROMETRY. Though there are many psychometric terms, yet the following are important from the subject point of view :

THE PSYCHROMETRIC CALCULATOR By: Stanley F. Gallos, The Bastian-Blessing Company INTRODUCTION PROPERTIES OF THE RSES CALCULATOR

Thermo-physical properties found on most psychrometric charts

CE311 Fall 2016 Mid-Term Exam 1

s. Properties for R134a are as follows : Saturated R-134a Superheated R-134a

PhEn-602 Pharmaceutical Facility Design. Notes #7 J. Manfredi

FS 231: Final Exam (5-6-05) Part A (Closed Book): 60 points

Fundamentals of Psychrometrics. By James L. Murphy, Colorado Building Environments Sales Engineer

Psychrometrics: The Science of Moisture in Air. Presented by Tom Peterson, CEO and Founder. Climate by Design International

ω = (1) Kirby S. Chapman Ph.D.

Chapter 14. At temperatures below the critical temperature, the gas GAS VAPOR MIXTURES AND AIR-CONDITIONING. Objectives

Dhulapally, Secunderabad Subject: REFRIGERATION AND AIR CONDITIONING QUESTION BANK

SIDDHARTH GROUP OF INSTITUTIONS :: PUTTUR Siddharth Nagar, Narayanavanam Road AUTONOMOUS QUESTION BANK (DESCRIPTIVE) UNIT I

Scientific Principals and Analytical Model. Charcoal Cooler. Lisa Crofoot MECH 425, Queens University

There are (at least) four reasons why you need to understand moisture and humidity in building physics:

TDSHS Air Change Requirements and the Basics of Psychrometrics. Presented by: Aric Murray December 06, 2013

UNIT 1 AIR CONDITIONING 1. Write the various psychometric processes? Explain any four processes with neat sketches?

R07. Answer any FIVE Questions All Questions carry equal marks *****

Standards and Guidelines. Presented by: Aric Murray December 12, 2014

COMPARING AIR COOLER RATINGS PART 1: Not All Rating Methods are Created Equal

INSTITUTE OF AERONAUTICAL ENGINEERING

Institute of Aeronautical Engineering (Autonomous) Dundigal, Hyderabad B.Tech (III II SEM) MECHANICAL ENGINEERING

Air Conditioning Clinic. Psychrometry One of the Fundamental Series TRG-TRC001-EN

PRESSURE-ENTHALPY CHARTS AND THEIR USE By: Dr. Ralph C. Downing E.I. du Pont de Nemours & Co., Inc. Freon Products Division

EXPERIMENTAL STUDY OF AIR FLOW RATE EFFECTS ON HUMIDIFICATION PARAMETERS WITH PREHEATING AND DEHUMIDIFICATION PROCESS CHANGING

Psychrometric Chart Fundamentals

AR/IA/UP 241 Lecture 5: Psychrometrics

CARRIER edesign SUITE NEWS. Interpreting High (Low) Peak Design Airflow Sizing Results for HVAC. Equipment Selection.

: REFRIGERATION & AIR CONDITIONING COURSE CODE : 6023 COURSE CATEGORY : A PERIODS/ WEEK : 6 PERIODS/ SEMESTER : 90 CREDIT : 6 TIME SCHEDULE

Psychrometric Engineering Applications

R10. IV B.Tech I Semester Regular/Supplementary Examinations, Nov/Dec REFRIGERATION & AIR-CONDITIONING (Mechanical Engineering)

Basic Principals of Air conditioning By Dr. Esam Mejbil Abed

UNIT - 3 Refrigeration and Air - Conditioning

Use this Construction/HVAC Glossary to answer the questions below.

SECTION THIRTEEN HEATING, VENTILATION, AND AIR CONDITIONING

All rights reserved, Armando B. Corripio, PhD, PE, Solid Dryer Design Introduction Continuous Dryer Design...

December 6, 2018 Optimizing Solutions through Superior Dehumidification Technology SM

Feasibility of Controlling Heat and Enthalpy Wheel Effectiveness to Achieve Optimal Closed DOAS Operation

Pressure Enthalpy Charts

Capt. Tim s s Duct Design Mythbusters. The bitterness of poor quality is remembered long after the sweetness of low price is forgotten!

Session: HVAC 101 HVAC 101. Steve Sain Sain Engineering Associates, Inc. August 9, Rhode Island Convention Center Providence, Rhode Island

Humidity Control & Psychrometrics

HVAC Psychrometric Analysis to Avoid Moisture Problems

Pharmaceutical Facility Design

Dehumidification for Industrial Coating Applications. By: Jay Kranker Munters MCS

Humidity Generation and Humidity Measurement The Complete Guide

Comfort and health-indoor air quality

Mechanical Engineering Laboratory

Short Questions with Answers APPLIED THERMODYNAMICS(5 TH MECHANICAL) Chapter No-1

Humidity Control Design Tips. R. Mark Nunnelly, PE, CxA, LEED AP President

Introduction to HVAC. American Standard Inc Air Conditioning Clinic TRG-TRC018-EN

Hawaii Energy and Environmental Technologies (HEET) Initiative

Armstrong Cool-Fog Systems

Development of a Psychrometric Test Chamber. Michael J. Swedish. Associate Professor Mechanical Engineering Department Milwaukee School of Engineering

REFRIGERATION AND AIR CONDITIONING

PINNACLE SERIES DEDICATED OUTDOOR AIR SYSTEM ENERGY EFFICIENT DEHUMIDIFICATION

Steam humidification: Reducing energy use, airstream heat gain, and condensate production

Humidity An excuse for the 80s

Article Energy Saving Benefits of Adiabatic Humidification in the Air Conditioning Systems of Semiconductor Cleanrooms

SIR C.R.REDDY COLLEGE OF ENGINEERING, ELURU DEPARTMENT OF MECHANICAL ENGINEERING ETD-II. Model Short Answer Questions And Answers

Chapter 6 ALL-AIR HVAC SYSTEMS 6.1 CONTEXT

Redesign of Bennett Hall HVAC System

Atmospheric Moisture: Relative Humidity and Dew Point

Reducing energy use, airstream heat gain, and condensate production

HVAC Fundamentals & Refrigeration Cycle

Hygrometry. The art or science of humidity observation

4th International Conference on Sensors, Measurement and Intelligent Materials (ICSMIM 2015)

3. (a) Explain the working of a rotary screw compressor. [10] (b) How the capacity control is achieved in refrigerant compressor?


Available online at Energy Procedia 6 (2011) MEDGREEN 2011-LB

Desiccant Dehumidification in Air Conditioning for a Large Commercial Building

Energy Use in Refrigeration Systems

VH Series B ENVIRO-STAC Vertical Hi-Rise Fan Coil Unit with Enhanced Humidity Control

100% Outdoor Air Dehumidification Methods

Adding More Fan Power Can Be a Good Thing

Heat pump and energy recovery systems

Don t Turn Active Beams Into Expensive Diffusers

MODULE 6 HUMIDIFICATION AND AIR CONDITIONING

Temperature. In the HVAC area, we talk about two kinds of temperatures.

Chapter 5: Atmospheric Moisture

3.4 Humidity. Types of instruments

Optimizing Electric Humidifier Operation with an Air Side Economizer

Transcription:

1 PSYCHROMETICS Psychrometry is the study of the characteristics of moist air. We will see soon that evaporation of moisture from the skin can have a significant impact on thermal comfort. The rate of evaporation depends on the amount of moisture in the surrounding air. Therefore, before we can give serious consideration to thermal comfort in buildings, we must understand the characteristics of moist air. Basic Definitions There are several indices for defining the amount of moisture in air. For our purposes, we will find it useful to assume that moist air is a mixture of ideal gases dry air and water vapor. This assumption generally gives errors of less than 1% compared to the true thermodynamic properties. Partial Pressure, p w For an ideal gas mixture, Dalton s law states that the sum of the partial pressures of the individual components is equal to the total pressure. p = p + p (1 1 w da The total pressure is typically driven by atmospheric pressure. At altitude, the atmospheric pressure can be estimated from the elevation, H, in feet above sea level. p p e H / 27,000 atm = sealevel (1 2 Relative Humidity, φ Moist air at a given temperature can only hold so much moisture before it becomes saturated. (The temperature of moist air is often referred to as the dry-bulb temperature, which is the temperature we all know from experience. Referring to basic thermodynamics, if you increase the pressure of pure water vapor at a fixed temperature, you will eventually reach the saturation pressure and the water vapor will condense to a liquid. In a mixture of ideal gases, moist air is saturated at a given temperature when the partial pressure of the water vapor reaches that saturation pressure. The relative humidity is simply the ratio of the partial pressure of the water vapor in the moist air mixture to the saturation pressure of water vapor at the same temperature. p w φ = (1 3 psat When saturated, moist air has a relative humidity of 1.0 or 100%. 1-1

Humidity Ratio, W Humidity ratio of moist air is defined as the ratio of the mass of water vapor to the mass of dry air in the mixture. (Note, it is not the ratio of the mass of water vapor to the total mixture mass. An ideal gas analysis can show that the humidity ratio is directly related to the partial pressures. W pw = 0.622 p p w (1 4 The denominator is simply the partial pressure of the dry air and the coefficient of 0.622 is the ratio of the molecular weight of water vapor to that of dry air. Dew Point, T dew The dew point temperature of moist air is the temperature at which the moisture would condense if the moist air were cooled at a constant pressure. We defined the relative humidity in terms of the saturation pressure at a given temperature. The humidity ratio is defined in terms of the saturation temperature at a given partial pressure. The dew point temperature is a function only of the partial pressure. Using the definition of the humidity ratio above, the dew point temperature can also be considered a function only of humidity ratio. Wet-Bulb, T wb The wet-bulb temperature is an odd variable. It is defined only because it is easy to measure and it is often used in HVAC applications as an intermediate variable for calculating humidity ratio, dew point temperature, or relative humidity. It is measured simply by wrapping a wetted wick around a conventional dry-bulb thermometer. Blowing moist air across the wick causes water to evaporate, which depresses the measure temperature below the dry-bulb temperature of the air. When the moist air is relatively dry, the depression can be very large. As the air becomes more humid, the depression becomes smaller until, at saturation (100% relative humidity, the water will not evaporate and the web-bulb thermometer measures the same as the dry-bulb thermometer. Enthalpy, h The enthalpy of a mixture of water vapor and dry air is the sum of the component enthalpies. For our purposes, we will find it convenient to express the enthalpy of moist air in terms of the energy per unit mass of dry air in the mixture. That is, enthalpy, h, will have units of Btu/lb da or kj/kg da. h= h + Wh (1 5 da w The enthalpies of dry air and water vapor are functions of temperature. Approximately, h = c ( T T da pa ref h = h + c ( T T w g, ref pw ref (1 6 h g,ref is the enthalpy of saturated water vapor at T ref. In US (or IP units, T ref = 0 F while in SI units, T ref = 0 C. With T ref = 0 for both sets of units, the equations can be combined as 1-2

h= c T + W( h + c T (1 7 pa g, ref pw Table 1 1: Values of Variables in Enthalpy Equation Variable US Units SI Units c pa 0.240 Btu/lb da F 1.0 kj/kg da C c pw 0.444 Btu/lb w F 1.86 kj/kg w C h g,ref 1061.2 Btu/lb w 2501.3 kj/kg w Specific Volume, v Like the enthalpy, the specific volume is expressed as the volume of the mixture per unit mass of dry air. Since water vapor has a lower molecular weight than dry air, the specific volume of moist air is greater than that of dry air. (The density of moist air is less than that of dry air. Psychrometric Chart All of the above properties, with the exception of the partial pressure of water vapor, are conveniently given on a psychrometric chart. A psychrometric chart is constructed from the fundamental relationships among thermodynamic properties. A given chart is constructed assuming a specific atmospheric pressure and is comprised of a set of lines of constant property values. (Note that the atmospheric pressure appears in the relationship between humidity ratio and partial pressure. With all these properties given on a single chart, it can be confusing. Figure 1-1 identifies the basic property values displayed on a typical psychrometric chart. Enthalpy Saturation Curve (100% Relative Humidity Specific Volume Wet-Bulb Humidity Ratio Wet-Bulb Wet-Bulb Humidity Ratio Dew Point Dry-Bulb Figure 1-1 Basic Properties on Psychrometric Chart The psychrometric chart has two main uses. First, it is useful to identify the properties of moist air. (If I know the temperature and relative humidity, I can find the enthalpy. Second, it is very useful in analyzing processes in building systems. We will explore psychrometric processes later, but for now will focus on the psychrometric chart as a tool for property evaluation. 1-3

Moisture in Buildings Most discussions about the heating and cooling requirements of buildings focus on the need to control the temperature in the building to maintain comfort. If we don t control the temperature with heating or cooling equipment, the indoor temperature would be near the outdoor temperature. Actually it would typically be slightly above the outdoor temperature due to the influence of solar radiation and internal heat gains. The same occurs with humidity. If we don t control the humidity in the building with humidifying or dehumidifying equipment, the indoor humidity ratio would be slightly above the outdoor humidity ratio due to the influence of internal moisture gains. Figure 1-2 shows hours of occurrence of outdoor conditions in Atlanta. The figure suggests that, in winter, indoor humidity will be approximately 0.001 0.006, which corresponds to an indoor relative humidity of approximately 5% 35% at typical indoor temperatures. In summer, outdoor humidity is approximately 0.012 0.018, giving indoor relative humidity of 60% 90%. These high indoor humidities cause two problems. First, they are inherently uncomfortable. Second, indoor dewpoint temperatures are 62 F 74 F. Any effort to cool air at this high dew-point temperature will surely result in condensation and corresponding dehumidification of the air. Therefore, any discussion of cooling also involves dehumidification, necessitating a need to discuss psychrometric process in HVAC systems. Atlanta, GA Humidity Ratio 0.03 0.028 Hours of Occurrence all hours 0.026 0.024 0.022 0.02 0.018 0.016 0.014 0.012 0.01 0.008 0.006 500-550 450-500 400-450 350-400 300-350 250-300 200-250 150-200 100-150 50-100 0-50 0-10 -5 0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105 110 [F] 0.004 0.002 Figure 1-2 Outdoor air conditions in Atlanta Heating or Cooling of Moist Air, No Moisture Added or Removed The humidity ratio of an air stream will remain constant if no moisture is added or removed. Figure 1-3 and Figure 1-4 show the equations and processes on a psychrometric chart. 1-4

q = m ( h h = mc ( T T W = W 2 1 2 1 p 2 1 Heating Humidity Ratio Figure 1-3 Heating of moist air, no moisture addition q = m ( h h = mc ( T T W = W 2 1 2 1 p 2 1 Cooling Humidity Ratio Figure 1-4 Cooling of moist air, no moisture removed Humidification Air can be humidified by injecting water or steam into an air stream. If water or steam is injected at a mass flow rate m w and an enthalpy h w, simple energy and mass balances can be performed to 1-5

characterize the change in moist air enthalpy and humidity ratio. In these equations, it doesn t matter whether the moisture is added with liquid water or with steam. Note that liquid water has a much lower enthalpy than steam, due to the heat of vaporization, h fg. Figure 1-5 shows the equations and process on a psychrometric chart. Notice that the enthalpy of the entering water defines the slope of the process line on the psychrometric chart. m w, h w m ( h h = m h a 2 1 w w m = m ( W W h w w h = W a h W 2 1 2 1 2 1 Humidity Ratio Heating Figure 1-5 Humidification of moist air Cooling and Dehumidification If moist air comes in contact with a surface that is below the dew-point temperature of the air, moisture will condense on the surface and the air will be dehumidified. Typical cooling coils in air conditioning systems operate at approximately 40-50 F, below the dew-point temperature of typical indoor air conditions. Mass and energy balances can be performed to relate the moist air properties to the energy and moisture removed from the air stream. Figure 1-6 shows basic process between an entering and leaving air state. The figure also shows a third point, defined as the apparatus dew point (ADP. The ADP represents an effective coil surface condition and the apparatus dew point temperature can loosely be thought of as the coil temperature. The ADP is determined by extending the straight line between the entering and leaving air states until it reaches the saturation curve. The fundamental mass and energy balances are given by the following. m = m ( W W w a m ( h h = q+ m h q a w w (1 8 1-6

Since the enthalpy of the condensed water is typically small, it is common to relate the energy removed by the cooling coil, q, as the energy removed from the air. The total heat removed by the coil is commonly known as the total capacity of the coil. It is also common to separate the total energy removal into separate terms one to account for the sensible cooling of the air and one to account for the energy required to dehumidify the air by condensing the water vapor. The total capacity is then the sum of the sensible and latent capacities. q = m ( h h tot a q = m c ( T T sen a p q = q q = m h ( W W lat tot sen a fg (1 9 Recall that the specific heat, c p, account for the specific heats of both the air and the water vapor in the moist air mixture. c = c + Wc (1 10 p p, a p, v m w, h w q = m ( h h tot a q = m c ( T T sen a p q = q q W lat tot sen = W( h, T 2 2 2 Humidity Ratio Apparatus Dew Point Figure 1-6 Cooling and dehumidifying moist air Note that the specific heat is actually a function of the humidity ratio, which changes between point 1 and 2. Also, the latent heat of vaporization, h fg, is a function of temperature. As a result, the sensible and latent capacities are rather loosely defined. Since the value of the specific heat is less variable than the heat of vaporization, it is common to calculate the specific heat from either than entering or leaving humidity ratio and then calculate the latent capacity as the difference between the total and sensible capacities. The sensible heat ratio is defined as the ratio of the sensible capacity to the total capacity. 1-7

q c ( sen p T1 T2 SHR q h h = = tot (1 11 The relationships among the psychrometric states, capacities, and sensible heat ratio are shown graphically in Figure 1-7. For a given pair of entering and leaving air states, the figure shows that sensible, latent, and total capacities are proportional to the differences in temperature, humidity ratio, and enthalpy, respectively. The SHR is defined by the slope of the line connecting the two points. SHR = 1 Slope defines SHR h a,lvg h a,ent SHR = 0 w a,ent w a,lvg Humidity Ratio Q lat Q sen T a,lvg T a,ent Figure 1-7 Coil capacities and sensible heat ratio on psychrometric chart Adiabatic Mixing Air streams are regularly mixed in HVAC systems. The properties of the mixed moist air stream can be readily determined from those of the individual air streams. If streams 1 and 2 are mixed to form stream 3, a mass balance and energy balance allow calculation of the mixed air humidity ratio and enthalpy m = m + m (1 12 a3 a1 a2 W 3 mw = m m h h3 = m + mw + m a1 1 a2 2 a1 a2 + m h + m a1 1 a2 2 a1 a2 (1 13 (1 14 Intuitively, we also think of analogous temperature relationship in which the mixed air temperature is a mass weighted average of the entering temperatures. However, strictly speaking, 1-8

the relationship is only approximate, due to the effect of both temperature and moisture on the air enthalpy. mt T3 m + mt + m a1 1 a2 2 a1 a2 (1 15 On a psychrometric chart, the mixed air state lies on a line connecting the two entering states. The process is shown in Figure 1-8 1 3 h 3 W 3 = = 2 m h + m h m + m da1 1 da2 2 da1 da2 m W + m W m + m da1 1 da2 2 da1 da2 Humidity Ratio Figure 1-8 Adiabatic mixing of moist air 1-9

1-10

1-11

Example Problems Calculate the boiling point of water in Boulder. Complete the following table for moist air at sea level. T d φ W h T wb T dew v 95 F 30% 80 F 67 F Complete the following table for moist air at an altitude of 5000 ft. T d φ W h T wb T dew v 95 F 30% 80 F 67 F Will water condense on a glass of ice water in this room today? Complete the following table of property data for water T, F p, psia v, ft 3 /lb Phase 80 Saturated vapor 1 Saturated vapor 212 Saturated vapor 80 0.1 12 Saturated vapor Use the Excel psychrometric spreadsheet on the website to solve the above problems. Air enters a cooling coil with a flow rate of 10,000 cfm at sea level. The air enters at a temperature of 80 F and 67 F web-bulb and leaves at 50 F and 90% relative humidity. What is the total cooling capacity of the coil? What is the sensible capacity of the coil? What is the latent capacity? What is the SHR of the coil? What is the apparatus dew-point temperature? The central cubical area of an office building at sea level has a floor area of 4000 ft 2 and is occupied by 30 people who each produce 200 Btu/h of sensible heat and 250 Btu/h of latent heat. Heat gains from the lighting for the space produces a load of 1.2 W/ft 2. (Heat gains from lights and people represent the only cooling load in the space. The office is to be maintained at 72 F and 50% relative humidity. Conditioned air is supplied at 60 F to meet the sensible and latent loads. What is the load SHR? To meet the loads, what must be the mass flow rate and humidity ratio of the supply air? 1-12

Psychrometric Process Problem #1 Moist air enters a heating coil at 40 F dry-bulb temperature and 36 F wet-bulb temperature at a rate of 2000 cfm. Barometric pressure is 14.696 psia. The air leaves the coil at a dry-bulb temperature of 140 F. a How much heat is added to the air by the heating coil? b If the heat is provided by hot water that enters the coil at 180 F and leaves at 160 F, what is the water flow rate? c If the heat is provided by a steam coil with saturated steam at 250 F, what steam flow rate is required? Assume that the steam leaves the coil as a saturated liquid. 1-13

Psychrometric Process Problem #2 A building space is to be maintained at 70 F dry-bulb and 30% RH when the barometric pressure is 14.696 psia. The total heating load on the space has been calculated to be 60,000 Btu/hr. Supply air is delivered to the space at a temperature of 120 F. The supply fan has a power consumption of 400 W. a What is the volumetric flow rate of supply air required to meet the space heating load? b What is the discharge air temperature leaving the coil? 1-14

Psychrometric Process Problem #3 Moist air enters a cooling coil at 78 F dry-bulb temperature and 50% RH at a rate of 2400 cfm. Barometric pressure is 14.696 psia. The air leaves the coil at a dry-bulb temperature of 55 F and a dew-point temperature of 53 F. The condensate leaves at a temperature of 52 F. The supply fan has a power input of 1200 W. a What is the total load (heat transfer rate on the cooling coil? b What is the sensible heat factor for the coil? c What are the supply air conditions? 1-15

Psychrometric Process Problem #4 Outdoor air is mixed with building return air in a mixing chamber prior to conditioning. The outdoor air is at 90 F and 40% RH with an airflow of 1000 cfm. The return air is 80 F and 67 F wet-bulb with an airflow rate of 3000 cfm. What is the mixed air condition? 1-16

Psychrometric Process Problem #5 A building space is to be maintained at 78 F dry-bulb and 65 F wet-bulb. The total cooling load on the space has been calculated to be 60,000 Btu/hr of which 42,000 Btu/hr is sensible heat gain. Supply air is delivered to the space at a temperature of 58 F. For acceptable air quality, 500 cfm of outside air is required. Outdoor conditions are 90 F and 50% RH. A schematic diagram of the HVAC system is shown below. a What is the airflow required for the space? b What is the supply air humidity ratio? c What is the capacity of the cooling coil? d What is the sensible heat ratio of the cooling coil? 1-17

Psychrometric Process Problem #6 A building space is to be maintained at 78 F dry-bulb. The total load on the space has been calculated to be 30,000 Btu/hr of which 27,000 Btu/hr is sensible heat gain. Supply air is delivered to the space at 58 F and 90% RH. The outdoor air mass flow rate is 25% of the total supply mass flow. Outdoor conditions are 80 F and 55% RH. A schematic diagram of the HVAC system is shown below. a What is the airflow required for the space? b What is the humidity ratio in the space? c What is the capacity of the cooling coil? d What is the apparatus dewpoint of the cooling coil? 1-18