Lago SD3. Differential Controller with Speed Control. Operating and Installation Instructions

Similar documents
SD2. Differential Controller. Operating and Installation Instructions F2 72.3

Safety. DANGER Indicates potentially fatal situations. WARNING Indicates possible danger to life and limb.

Installation and Operating Manual. Merlin 5064 V3. System Manager

1 DOCUMENT REVISION SOFTWARE VERSION BASIC DESCRIPTION BASIC OVERVIEW OF HYDRAULIC DIAGRAMS HYDRAULIC DIAGRAMS...

1 DOCUMENT REVISION CONTROL ELEMENTS... 9

Boiler controller S-Tronic Plus

E System Manager Operating instructions

Installation and Operating Manual. Merlin IO 5064 V4 with BM-T. System Manager

Operating instruction. Remote control station WCM-FS /

Boiler controller Lambdatronic S 3200

Installation and operating instructions. Temperature difference controller 6 inputs, 3 outputs, integrated data logger for SD card

For the owner and the heating engineer. Operating and Installation Manual VRC 400. Programmable weather compensator with separat HW time control

Operating instructions

OPERATION MANUAL RK-2006LPP AUGER FITTED SOLID FUEL BOILER TEMPERATURE CONTROLLER. Version DC19

HEATING REGULATOR EPC11 End user manual.

Heating Controller SDC. District Heating Controller DHC 43 OPERATING INSTRUCTIONS

ST Wiring diagram. Product description. Four-stage controller. Order number

USER MANUAL. OPTIMA 312 ES960C circuit board

Boiler controller SPS 4000

ST 53.1 User s manual

Operating instructions

danfoss Heating Solutions 5

Installation and servicing instructions

Dryer Controller M720

Service instructions. FM443 solar module. Function module. For contractors. Read carefully prior to commissioning or service

Installation and Operating Manual. System Regulator for Solar Thermal Systems 7 inputs, 4 outputs

Heating and D.h.w. Controller RVL482 Basic Documentation

RVP360 and RVP361 Heating controllers for 2 heating circuits and d.h.w. Basic Documentation

REA22 Room Temperature Controller

Installation and Operating Manual

Operating instructions THETA control unit for heating contractors. ROTEX control unit: - THETA 23R - THETA RS - THETA HEM1

Electronic Pellet Burner Controller NPBC-V3-1

Electronic Pellet Burner Controller NPBC-V3M

User Manual. Dryer Controller M720

Heating Controller SDC Remote Heating Controller DHC

Climapro 2. User manual. wireless room thermostat without receiver. To be left with the user.

SAS908WHB-3-RF/B WIRELESS THERMOSTAT

GH10PA USER MANUAL. Program version 01 MANUAL FOR CONTROLLER FOR CONTROLLING CENTRAL HEATING BOILERS FIRED WITH PELLETS AND OATS

Operating instructions

RVP340 Heating controller for 1 heating circuit RVP350 and RVP351 Heating controllers for 1 heating circuit and d.h.w. Basic Documentation

INSTRUCTION MANUAL REMOTE CONTROL DEVICE EASYREMOTE

User Instructions For TopTronic RS-30

1/8. Field settings table. Applicable indoor units *HYHBH05AAV3 *HYHBH08AAV3 *HYHBX08AAV3. Notes - 4P C

1/8. Field settings table [6.8.2] =... ID66F3. Applicable indoor units *HYHBH05AAV3 *HYHBH08AAV3 *HYHBX08AAV3. Notes - 4P E

Operating instructions. For the operator. Operating instructions VRT 350. Room temperature-controlled controller GB, IE

Mounting and Operating Instructions EB 5610 EN. TROVIS 5600 Automation System TROVIS 5610 Heating and District Heating Controller

OPERATION MANUAL. Daikin Altherma indoor unit EKHVMRD50ABV1 EKHVMRD80ABV1 EKHVMYD50ABV1 EKHVMYD80ABV1

APC BC300 Series 40kW 208/450/480V User Guide

Heating Controller SDC Remote Heating Controller DHC

Operating Instructions for use by heating contractor. VITOTRONIC r 100 VITOTRONIC r 300-K IMPORTANT

WATER HEATER ELECTRONIC CONTROLLER USER MANUAL

Solar regulator DIEMASOL C. Installation and Service Manual. User Guide G

BrainQ RSC/2 USER MANUAL. BrainQ RSC/2 Thermostat 8G /10.05

RVA /109. Heating Circuit ZONE Controller. Instructions for the INSTALLER

USE AND MAINTENANCE. Cm Pelet-set (60-90 kw) TECHNICAL INSTRUCTIONS

RF Programmable Room Thermostat User Instructions

Operation manual FR EN NL DE IT. intended for professionals and end users. To be saved for future consultation

These Assembly and Operating Instructions are an integral part of the product.

PROGRAMMABLE 7-DAY RF THERMOSTAT

Synergy 405PLUS User Guide Manual

Albatros 2 Solar compact controller User manual RVA Building Technologies

E V1. System Manager Installation Manual

Solar Controller SUNGO SL

Operating Instructions

GEYSERWISE INSTRUCTION MANUAL

VERSO-P, VERSO-R Series Air Handling Units with C3 Control System Electrical Installation and Operation Manual

RVL471 Heating and Domestic Hot Water Controller Basic Documentation

Heating Controller SDC Remote Heating Controller DHC

Room panel. for ecomax800 R or T regulators. OPERATION AND MAINTENANCE MANUAL ISSUE: 1.3 APPLICABLE TO SOFTWARE: v , v , v08.21.

Controller PCSol 300 FOR SOLAR COLLECTORS. INSTALLATION AND OPERATION MANUAL 62.X.2 REVISION SOFTWARE

G2484. Installation. - Control panel (in the panel front, on the inner wall, or on a DIN rail)

Declaration of Conformity No. 27/2008

USER MANUAL S203. Controller for three circuits. - control for 2 heating circuits - 1 domestic hot water control. Saving energy, creating comfort

USE AND MAINTENANCE. Cm Pelet-set TECHNICAL INSTRUCTIONS. (14-35 kw) For boilers: EKO-CK P (EKO-CK 20-40) EKO-CKB P (EKO-CKB 20-40)

Owner s Manual. Part Number 33CSSP2-FC BACK LIT LIQUID CRYSTAL DISPLAY MODE BUTTON

BM Programming Module. For the heating engineer Installation instructions

ENERGY LIGHT USER S GUIDE ENERGY LIGHT USER S GUIDE

R. Room temperature controller with solar control FR 120. Operating instructions for the user (2012/02)

G a

ecomax 200 W Boiler regulator FOR SOLID FUEL BOILERS WITH A FAN OPERATION AND MAINTENANCE MANUAL ISSUE:

EBC20. Instructions for fitting, installation and operation. Read and save these instructions!

ROOM THERMOSTATS KNX BASIC DOCUMENTATION

Movement controller comfort, Flush-mounted (Up) xx, xx

Control System THETA. Operating Instructions. Room control unit RSC and RSC-OT

Field settings table [6.8.2] =... ID66F2. Applicable units *BLQ05CAV3 *DLQ05CAV3 *BLQ07CAV3 *DLQ07CAV3. Notes (*1) *B* (*2) *D* 1/8

OPERATION AND INSTALLATION

HIGH EFFICIENCY FIRETUBE CONDENSING GAS BOILER

Operating Instructions. Luxtronik. Heating- and Heat Pump Control

Installation and Service Instructions SM1 SOLAR CONTROL MODULE IMPORTANT. Read and save these instructions for future reference.

Service Instructions for use by heating contractor

Entwicklung + Fertigung + Service: Heerweg 15 D, Denkendorf Tel.: / Fax.: /

Connections, displays and operating elements C D E G H. Installing the control unit

Operating instructions

Operation Manual of Solar controller SR1568 for split solar system

Please read this manual carefully before installation and use.

RVL47. Heating Controller. Installations Instructions. Installation

Installation and Operating Instructions DÜRR Regeneration Unit for X-ray developers XR 24, XR24 II, XR 24 Nova, XR 24 Pro

M116 / M450 USER AND MAINTENANCE MANUAL FOR MODULATING-CONTROL BOILER WITH GAS BURNER EQUIPPED FOR NATURAL GAS. Type : B23 ATLANTIC 2000

OPERATING MANUAL. for the modular heat presses. Secabo TC5 SMART and TC7 SMART

Drayton Digistat +3RF

Transcription:

Lago SD3 Differential Controller with Speed Control Operating and Installation Instructions Please observe the safety instructions and read through this manual carefully before commissioning the equipment.

Safety information General information Safety information Power connection regulations Please note the connection conditions specified by your local electrical power supply utility and the VDE regulations. Your heating control system may be installed and serviced only by appropriately authorized specialists. E For fixed devices, a facility for mains disconnection in accordance with EN 60335 must be installed in compliance with the installation specifications (e.g. switch). E The mains lines insulation must be protected against damage caused by overheating (e.g. insulation hose). E The minimum distance to installation objects in the vicinity must be chosen so that the permitted ambient temperature is not exceed during operation (see table - Technical Data). E If the system is not installed properly, persons using it are at put at risk of fatal or serious injury (electric shock). Ensure the controller is de-energized prior to performing any work on the controller! General information Warranty conditions If the system is not installed, commissioned, serviced and repaired professionally, this will render the manufacturer's warranty null and void. Important text passages! Important information is highlighted with an exclamation mark. E This attention symbol is used to point out dangers in this manual. Installation Information on installation of the system is provided in Part 2 of this manual together with a connection diagram. 2

General information Description Description Declaration of conformity This device corresponds to the requirements of the relevant guidelines and standards, if the corresponding installation regulations and the manufacturer s instructions are complied with. General Function This controller enables the regulation of various types of system: 1) Solar regulation 2) Solid fuel regulation for two storage tanks 3) Solid fuel regulation with solar integration 4) Solar regulation with two collectors 5) Solar regulation with two storage tanks valve switch-over 6) Solar regulation with two storage tanks 2 feeding pumps 7) Solar regulation with reheating function 8) Solar regulation with return flow temperature increase of the heating system 9) Solid fuel regulation with return flow temperature increase via mixer 10) Solar regulation with two storage tanks in cascade 11) Solar regulation with two-layer storage tank 12) Solar regulation with three-layer storage tank 3

Contents Contents General information 2 Safety information 2 Power connection regulations 2 Warranty conditions 2 Important text passages 2 Installation 2 Description 3 Declaration of conformity 3 General Function 3 Contents 4 Operation 6 Explanation of the operating elements 6 Selector switch 6 Rotary knob Key: Manual Operation / OK / Reset 6 6 Display (mode) 7 Starting up 7 Change User set values 8 Exiting the operating level 8 List of the User Set Values 9 Change Expert set values 10 General information List of the Expert Set Values 11 Explanation of the set values / functions 14 User set values 14 01 Set time 14 02 Weekday 14 Resetting the production indicators 14 Pump kick function 14 Reheating function 15 Circulation pump 15 Fitter set values 16 Speed control for A1 16 Switch-On/Off difference 17 Special functions 18 Collector protection function 19 Hot water short time heating function 21 Functions additional relay A2 / A3 21 Circulation in case of impulse Reheating 22 22 Return flow temperature increase 22 Pump kick function (temperature test function) 23 Production estimate / Volume flow counter 23 Other functions 25 Pump blocking protection 25 Stop pumps (temperature control) 25 4

General information Contents Assembly / Dismantling 26 Dimensions 26 For the fitter 27 Electrical connection 27 Special functions 28 Reheating 28 Circulation pump 28 Return flow temperature increase 29 Superposed protection functions 29 Remote controls 29 Remote indication for solar values Lago FB T-SD 29 Connecting 29 Explanation to that System diagrams 30 System diagrams 31 System 1 31 System 2 32 System 3 34 System 4 35 System 5 37 System 6 39 System 7 40 System 8 41 System 9 42 System 10 43 System 11 44 System 12 45 Sensors data 46 Technical data Sensors 46 Errors 47 Technical data 48 5

Explanation of the operating elements Operation Explanation of the operating elements Selector switch i No function (indicator in display i and "OFF") / Indicator F1 temperature collector 2 Indicator F2 Additional sensor (lower storage tank 2, return flow collector, Collector 2) Indicator F3 temperature upper storage tank Indicator F4 temperature lower storage tank 5 Indicator F5 Additional sensor (upper storage tank 2, return flow temperature increase) Indicator C1 production day [kwh] Indicator C2 production total [kwh] User and Expert Parameters indicator "01 and initial set value Rotary knob Selection of a function Selection of a set value Adjusting a set value Operation Key: Manual Operation / OK / Reset x = Manual operation: If the key is pressed for longer than 1 second, all pumps are started for 30 minutes. A premature deactivation is only possible if the key is pressed again. OK: Selecting or saving a parameter at the user level RESET : In order to reset the controller to the default setting, keep the key pressed while defining the operating voltage. All user values and expert values will be lost during this procedure! For this reason, please take a note of your own parameters in this manual. Key Rotary knob Selector switch 6

Starting up Display (mode) Display (mode) 1 Weekday Monday - Sunday 2 Display of the selected temperature / heat production Pump operation indicator (Arrow = Pump ON) a = Pump A1 is ON (see connection diagram) b = Pump A2 is ON (see connection diagram) c = Pump A3 is ON (see connection diagram d = As soon as the total solar production in the display exceeds 10 MWh, the fourth arrow appears pointing towards the text: "x1000". A Bus symbol when remote control is connected B Symbol when a request is made for reheating C Operation indicator i = OFF, F = ON, (h = Manual => Pumps ON max. duration = 30min all three pump symbols flashing) 1 2 A B C Mo Tu We Th Fr Sa Su A1 A2 A3 a b c d Starting up Starting up After the device has been properly installed, switch on the power supply. The software number for your device appears briefly in the display. Finally, the standard display indicators appear.! It is essential for correct operation that the system installed, as well as time and weekday is provided. For this reason, please first set these parameters [P1]/[P2]/[P22]. (see Change User set values and Change Expert set values). Following the next restart, the controller is operational using the default settings (except parameter [P1]/[P2]/[P22]). 7

Change User set values Starting up Change User set values Rotate the selection switch to the spanner [ ] set values The user set values are the set values smaller than 20 "01 "19 Display: Left no. of the set value, Right set value Use the rotary knob +/- to select the number of the desired set value [indicator: left].! A list of all the set values is provided on the following pages. Press the key OK => Selection of the set value. The value starts to flash and can now be changed using the rotary knob. By pressing the button key OK once more, the value is stored in the device. Exiting the operating level! You can exit setting mode at any time by moving the selection switch to a different position. Changes which have been entered but not stored by pressing the key OK have no effect. 8

Starting up List of the User Set Values List of the User Set Values No. Designation Setting range Setting ex works Own settings User set values 01 Set time 0.00 24.00 10.00 02 Set weekday 1 7 1 (Monday) 03 Day's production Display only /Clear 0 kwh 04 Total production Display only /Clear 0 kwh 05 Switching time pump kick function ON 00.00 24.00 07.00 06 Switching time pump kick function OFF 00.00 24.00 22.00 07 Switching time reheating function ON 00.00 24.00 05.00 08 Switching time reheating function OFF 00.00 24.00 21.00 09 Switching time circulation pump ON 00.00 24.00 05.00 10 Switching time circulation pump OFF 00.00 24.00 21.00 9

Change Expert set values Starting up Change Expert set values Rotate the selection switch to the spanner [ ] set values The Expert set values are the set values greater than 19 "20 "99! Protected values (from No. 20) It is only possible to change the set values from no. 20 after entering the code number. These set values may only be modified by an authorised fitter. E If these values are set incorrectly, they may cause malfunctions or damage to the system. Select set value 20 (code no. input). Press the key OK and enter the 1 to 4-digit code number. Confirm each digit by pressing the key OK. Select the set value to be modified. Press the key OK and change the set value. Conclude the input by pressing the key OK. If an attempt is made to enter an impermissible value, the system automatically returns to set value 20 (enter code number). 10

Starting up List of the Expert Set Values List of the Expert Set Values No. Designation Setting range Setting ex works Own settings Fitter set values 20 Enter code no. 0000-9999 21 Code no. 0000-9999 0000 22 Select system (see hydraulic diagrams) 1-12 1 23 Speed level Actual value Display only % 24 Operating mode Speed control 0 1 (AUTO, 0 (AUTO) MANUAL) 25 Speed level Set Value (Manual) 30 100 % 100 % 26 Min. Speed level (Auto) 30 100 % 30 % 27 Max. Speed level (Auto) 30 100 % 100 % 28 Difference temperature for 100% control 10K 90 K 35 K Switching thresholds / Hystereses 30 One switching difference 1 1K 30K 6K 31 Off switching difference 1 1K 30K 3K 32 One switching difference 2 1K 30K 6K 33 Off switching difference 2 1K 30K 3K 34 Switching hysteresis reheating 1K 30K 5K 11

List of the Expert Set Values Starting up No. Designation Setting range Setting ex works Own settings Special functions 40 Enable temperature, collector(s) (-20) C (+95) C 40 C 41 Disable temperature, collector(s) (-20) C (+95) C 35 C 42 Maximum collector temperature 80 C 180 C 110 C 43 Enable temperature 2nd heat generator 0 C 90 C 60 C 44 Maximum solid fuel boiler temperature: 30 C 130 C 90 C 45 Collector safety temperature 80 C 180 C 110 C 46 Switching threshold for storage tank Recooling 1K 30K 0 K (0=OFF) 47 Set temperature for storage tank (reheating) 10 C 90 C 40 C 50 Maximum storage tank temperature, tank 1 10 C 130 C 60 C 51 Maximum storage tank temperature, tank 2 10 C 130 C 85 C 52 Tolerance during solar production (see P47) 0K 90K 10K 53 Hot water short time heating function 0, 1 (OFF, ON) 0 (OFF) Additional relay function (outlets A2/A3) 54 Function A2 0 7 0 Function A3 0 7 0 55 Circulation pump switch-on time 1 min 10 min 1 min 56 Circulation pump reclose blocking 1 min 20 min 5 min 12

Starting up List of the Expert Set Values No. Designation Setting range Setting ex works Own settings Return flow temperature increase 57 Minimum return flow temperature 0 C 90 C 60 C 58 Mixer dynamic Off 5K 25K 18K 59 Mixer dynamic Closed 5K 25K 12K Pump kick function (temperature test function) 60 Kick duration 0.2s 59s 0 = OFF 61 Kick pause 10 min 60 min 30 min 62 Measuring time for 0.5K increase 1 min 5 min 1 min Production estimate/volume flow counter 70 Pulse rate [millilitre/pulse] or [litre/pulse] 0 100 1.1 71 Pulse rate unit (0=ml/pulse; 1=l/pulse) 0.1 0 (ml/pulse) 72 Volume flow distribution with 2 collector system 1:99 99:1 50:50 75 Volume flow fix for collector 1 [litre/min] 0-100 0.0 = OFF 76 Volume flow fix for collector 2 [litre/min] 0-100 0.0 = OFF 78 Mixing ratio 0 70 vol. % 40 % 79 Glycol type 0 1 0 Hardware/Software 98 Bus terminating resistor 0, 1 (OFF, ON) 1 (ON) 99 Software number with index 00 00 99 99 13

Explanation of the set values / functions Explanation of the set values / functions In order to modify the standard settings, refer to the chapter "System diagrams", select the relevant system according to the types of system and define these settings first of all [P22]. The chapter "Explanation of set values / functions" describes the various set values according to their dependence on the selected/realised system (1-11). If the controller, e.g. for System 1 is used, only refer to the function descriptions related to this system. User set values 01 Set time Set the current time. 02 Weekday Set the current weekday (1-7, 1=Monday) (Display only) Resetting the production indicators 03 Day's production indicator [kwh] Reset the value to "0000" by pressing the key OK (for at least 2 seconds). The value is reset to "0000 at 24:00 and the day's production is added to the total production. Starting up 04 Total production indicator [kwh] This value is updated at 24:00. To determine the current total value accurately, the day's production value must be added to the "indicated" total production value. Reset the value to "0000" by pressing the key OK (for at least 2 seconds). Pump kick function System 2,9: No function System 1,3,4,5,6,7,8,10,11,12: The pump kick function can be executed during the time period of the day in which solar production is expected [P05-P06]. This function should ensure that the actual collector temperature can be measured by the collector sensor even when the collector pumps are not operating. The function is deactivated if no switching time (P05=P06= ----") or no kick duration (P60=0) was selected. Each time the kick pause [P61] has ended, the corresponding collector pump is switched on for the period of the kick duration [P60] (heat transport to the sensor). If a temperature increase of 0.5K is detected on the respective collector sensor during the measuring period [P62], the collector pump is activated for one minute. Finally, the switch-on conditions for the collector pump are checked. 14

Starting up Explanation of the set values / functions 05 Pump kick function switch-on time Temperature verification starts from this time. 06 Pump kick function switch-off time Temperature verification stops from this time. Reheating function For most systems, this can be selected as an additional function. (see P54 and section "Special Functions A set temperature [P47] can be entered for the selected storage tank when the reheating function is active. During the enable time [P07-P08], this temperature is set by activating an additional heat generator. The additional heat generator is activated when the set temperature P47 of P34 (in case of solar production by P52+ P34) drops below. It is deactivated when the set temperature P47 is reached (in case of solar production P47-P52). 07 Reheating function ON The set temperature [P47] starts from this time. 08 Reheating function OFF Set temperature [P47] stops from this time. Circulation pump For many systems, this can be selected as an additional function. (see P54 and section "Special Functions P54=1: The circulation pump is continuously switched on during the enable time P09-P10. P54=2: The circulation pump is switched on during the enable time P09-P10 when triggered by a pulse. P54=3: Circulation pump and the hot water short time heating function, 09 Switch-on time circulation pump ON Starts enabling the circulation pump. 10 Switch-off time circulation pump OFF The circulation pump is disabled. 15

Explanation of the set values / functions Fitter set values 20 Enter code no. After entering the code number, the set values assigned to the fitter level can be modified. Standard value: 0000 21 Valid code no. The code number currently valid can be modified with this setting. (Value only visible after entering the currently valid code no.) 22 System selection (see appended diagrams) On selecting the system, the function of the device is redefined. Set the system number according to the connection descriptions (System 1 System 11).! After changing the System Selection parameter, all the set values are reset to the default factory values (including the code no.). The fitter level is closed. Speed control for A1 23 Speed level Actual Value Displays the actual speed value for A1 in %. Starting up 24 Operating mode Speed control (AUTO, MANUAL) Select the operating mode for speed control 0 = Automatic mode (Controller detects speed) 1 = Manual operation (set speed value has an effect on A1) 25 Set value of speed level Only in manual operating mode [P24=1]! Specifies the speed for A1. 26 Min. speed level Only in automatic operating mode [P24=0]! (P26 < P27) regulates the setting of the minimum speed to that of the controller. The value must be selected in such a way that the pump must run safely with this control. 27 Max. speed level Only in automatic operating mode [P24=0]! (P27 > P26) regulates the setting of the maximum speed to that of the controller 28 Difference temperature for 100% control Only in automatic operating mode [P24=0]! The pump is started at full speed [100%] for the temperature difference between collector 1 and the active storage tank that is set here. The pump is slowed down if the temperature difference is lower. 16

Starting up Explanation of the set values / functions Switch-On/Off difference 30 One switching difference for difference 1 The feeding function for storage tank 1 via pump A1 is enabled when the temperature difference between sensor F1 (collector/solid fuel) and sensor F4 (lower storage tank) exceeds the switch-on threshold. 31 Off switching difference for difference 1 The feeding function for storage tank 1 is deactivated when the difference drops below the set switching threshold. 32 One switching difference for difference 2 33 Off switching difference for difference 2 System 1,7,9: No function Systems 2, 5: The feeding function for storage tank 2 via pump A1 is enabled when the temperature difference between sensor F1 (collector/solid fuel) and sensor F2 (storage tank 2) exceeds the switch-on threshold. The feeding function for storage tank 2 is deactivated when the difference drops below the set switch-off threshold. The valve A2 is switched in the direction of storage tank 2 when the feeding function for storage tank 2 is enabled and storage tank 1 cannot be fed. System 3,4: The feeding via pump A1 is enabled when the temperature difference between sensor F2 (solid fuel/ collector 2) and sensor F4 (lower storage tank) exceeds the switch-on threshold. System 6: The feeding function for storage tank 2 via pump A2 is enabled when the temperature difference between sensor F1 (collector) and sensor F2 (storage tank 2) exceeds the switch-on threshold. The feeding function for storage tank 2 is deactivated when the difference drops below the set switch-off threshold. System 8: see Special Functions return flow temperature increase System 10: The refeeding function via pump A2 is enabled when the temperature at sensor F3 (upper storage tank 1) exceeds the temperature at sensor F2 (lower storage tank 2) by the switch-on threshold. The refeeding function is deactivated when the difference falls below the set swtich-off threshold. 17

Explanation of the set values / functions System 11: Valve A2 switches on when the temperature at sensor F1 (collector) exceeds the temperature at sensor F3 (upper storage tank) by the value P32 ( feeding into the upper storage tank section). A2 switches off when the difference drops below the Off switching difference ( feeding into the upper storage tank section). System 12: Valve A3 switches on when the temperature at sensor F1 (collector) exceeds the temperature at sensor F3 (upper storage tank) by the One switching difference ( feeding into the upper storage tank section). A3 switches off when the difference drops below the Off switching difference ( feeding into the middle storage tank section). Valve A2 switches on when the temperature at sensor F1 (collector) exceeds the temperature at sensor F5 (middle storage tank) by the One switching difference ( feeding into the middle or upper storage tank section). A2 switches off when the difference drops below the Off switching difference ( feeding into the lower storage tank section). Starting up 34 Switching hysteresis for reheating Reheating is activated, if the target temperature is fallen below around hysteresis stopped here. Reheating becomes again closed with the exceeding of the target temperature Special functions 40 Temperature activation collector(s) 41 Deactivation temperature collector(s) System 2,9: No function System 1,3,4,5,6,7,8,10,11,12: The collector pump is enabled when the associated collector temperature exceeds the enable temperature. It is disabled when the collector temperature drops below the disable temperature. This function prevents pump operation without relevant heat production. 42 Maximum collector temperature System 2,9: No function System 1,3,4,5,6,7,8,10,11,12: The collector pumps are deactivated when the 18

Starting up Explanation of the set values / functions related collector temperatures exceed the safety limits set here. -> System protection The pumps are reactivated when the temperature falls below the temperature [maximum collector temperature 10K]. 43 Enable temperature of 2nd heat generator (solid fuel) System 1,4,5,6,7,8,10,11,12: No function Systems 2, 3, 9: The relevant pumps are activated when the temperature of the 2nd heat generator (System 2,9 = F1, System 3 = F2) exceeds the limit value set here by 5K. It is stopped when the temperature of the heat generator drops below the enable temperature. This function ensures that the heat generator can reach its operating temperature. 44 Maximum solid fuel boiler temperature System 1,4,5,6,7,8,10,11,12: No function System 2,3,9: The feeding pump of the solid fuel boiler is deactivated when the temperature of the boiler exceeds the limit temperature set here. -> System protection. The pump is reactivated when the, temperature falls 10 K below the limit value. Collector protection function 45 Collector protection temperature System 2,9: No function System 1,3,4,5,6,7,8,10,11,12: The collector protection temperature protects the collector against overheating. It gets activated when the set maximum collector temperature P42 is greater than the collector protection temperature P45 set here. If the collector temperature F1 or F2 exceeds the set collector protection temperature P45 and the storage tank temperature is less than 92 C, then the storage tank is fed beyond its maximum temperature to 95 C to cool the collector. The function is interrupted when the collector exceeds its maximum temperature P42. The function is activated again when the collector temperature drops below the temperature P42-3K. 46 Switching threshold for storage tank recooling P46 = 0 No storage tank recooling P46 > 0 Storage tank cooling active If the collector protection function has fed the storage tanks during the day to temperatures in excess of the set maximum storage tank temperatures P50, P51, then the storage tank can automatically be cooled at night between 19

Explanation of the set values / functions 1.00 and 6.00 hours by activating this function by switching on the feeding pumps to the set maximum temperature of the storage tank P50/51. The storage tank cannot be fed during this period. This function is meant to protect the storage tank. Recooling can take place only when the temperature of the storage tank exceeds the collector temperature at least by the value of switching threshold P46 (+3K hysteresis). 47 Set temperature for reheating Only when special function "Reheating is selected The additional heat generator (A2/A3) is enabled when the storage tank temperature at the upper storage tank sensor (F3/F5) drops below the limit set here by P34. It is stopped when the temperature of the storage tank exceeds the enable temperature. If there is solar production, the switching threshold is moved down by the parameter P52: Enabling occurs at an upper storage tank temperature below P47-(P52+ P34. 50 Maximum storage tank temperature, tank 1 E If a top of tank sensor (F3) is mounted, it is used to monitor the maximum temperature. If this sensor is not installed, the maximum storage tank temperature is monitored by F4. In this case, the layering of the tank must be taken into account. Starting up System 1,3,4,7,8,9,10,11,12: The feeding pumps are disabled when the temperature of storage heater 1 exceed the safety limit temperature set here. System protection The pumps are reactivated when the temperature falls below the temperature [maximum storage tank temperature 5K]. System 2,5,6: For these systems it is also possible to additionally keep feeding storage tank 2. 51 Maximum storage tank temperature, tank 2 System 1,3,4,7,8,9,11,12: No function System 2,5: Feeding pump A1 is stopped when the temperature of storage heater 2 exceeds the safety limits set here and storage tank 1 cannot be fed 2 1 (A2 set towards storage tank 2). System protection The pump is reactivated when the temperature drops below the temperature [maximum storage tank temperature 5K]. System 6,10: Feeding pump A2 is disabled when the temperature of the 20

Starting up Explanation of the set values / functions storage heater 2 exceeds the safety limit set here system protection The pump is reactivated when the temperature drops below the temperature [maximum storage tank temperature 5K]. 52 Tolerance with solar production System 1,2,3,4,5,6,7,8,10,11 (only for P54=3 recharging): If the storage tank temperature is fed from the collector/ solid fuel boiler, the additional heat generator is only activated when the storage tank temperature drops below the set temperature P47 by the value [tolerance value + P34]. It is deactivated again when the storage tank temperature has reached the value [set temperature P47- tolerance value]. Hot water short time heating function Only when special function "Reheating is selected Every Saturday at 01.00 hours the storage tank is heated once to the temperature of 65 C (= increase in set temperature). This function is only performed when the storage tank temperature of 65 C was not reached during the previous week. The temperature is monitored by sensor F4 "bottom of storage heater". The hot water short time heating function is stopped when the set temperature cannot be reached within 3 hours or when the programmed maximum storage temperature (at least 65 C) is detected at sensor F3 (only when installed). E The hot water short time heating function can only be successfully performed when the external heat generator (reheating function) is capable of generating the corresponding temperatures. 53 Hot water short time heating function 0 = Function not active (standard) 1 = Function active Functions additional relay A2 / A3 As soon as the outlets A2 and A3 are not specifically assigned by system scheme, it becomes possible to assign a freely selectable special function to these outlets. 54 Function A2 / A3 0 = outlet not active 1 = Circulation pump, outlet is continuously ON within the enable time [P09-P10] 2 = Circulation pump in case of impulse, outlet is ON only during impulse within the enable time [P09-P10] 3 = Circulation in case of hot water short time heating, outlet is ON during hot water short time heating function 21

Explanation of the set values / functions 4 = Reheating storage tank 1, reference sensor F3 5 = Reheating storage tank 2, reference sensor F5 6 = Return flow temperature increase, storage tank 1 7 = Return flow temperature increase, storage tank 2 Circulation in case of impulse If there is a short-circuit at the impulse inlet, the circulation pump gets switched on for the set switching duration P55. The pump can be switched on again only after the set reclose blocking period P56 has elapsed. The set circulation program has highest priority Activation occurs only during the enable time [P09-P10]. Reheating The reheating function is active only during the enable time [P07-P08]. If the set temperature for storage tank drops by at least 5K (in case of solar production by P52+5K) during this period, then the selected outlet switches on ( reheating) till the set temperature has been reached ( reheating OFF). If there is heat input into the storage tank via solid fuel/ solar, then the reheating function gets activated only when the temperature drops below the tolerance value (refer P52). 55 Circulation pump on-period Switching duration of circulation pump in minutes after occurrence of an impulse (water drawn from tap) Starting up 56 Circulation pump reclose blocking If the circulation pump has been switched on, then it can be started again only after the period of reclose blocking has elapsed. Return flow temperature increase Also refer to special function "Return flow temperature increase : System 9: The built-in mixer motor (A2=OPEN, A3=CLOSE) regulates the return flow temperature of the heat generator to the set minimum return flow temperature P57. If this temperature is not reached in the heat generator, then the mixer is closed completely. If the return flow temperature increases beyond this value, the mixer opens. 57 Minimum return flow temperature System 9: The built-in mixer motor regulates the temperature to this value. 58 Mixer dynamic OPEN System 9: Speed setting at which the mixer motor opens when a control difference occurs. The control difference at which the mixer motor opens without interruption is entered in Kelvin. 22

Starting up Explanation of the set values / functions 59 Mixer dynamics CLOSE System 9: Speed setting at which the mixer motor closed when a control difference occurs. The control difference at which the mixer motor closes without interruption is entered in Kelvin.! Small values cause the mixer motor to adjust quickly and can lead to oscillation. Pump kick function (temperature test function) System 2 and 9: No function System 1,3,4,5,6,7,8,10,11,12: The heated heat generation medium of the collector is transported to the sensor when the collector pump gets switched on for a short period so that the collector temperature can be measured. 60 Kick duration [sec] Collector pump runtime following pump kick. 61 Kick pause [min] If the collector pump has not run for the duration set here, the pump is activated for the kick duration period [P 60]. 62 Measuring time for 0.5 K increase [min] The course of the collector temperature is controlled during this period following a pump kick. If an increase of 0.5K is detected, the pump is started for a further minute. Production estimate / Volume flow counter While the feeding pump is running, the pulses of an optionally connectable flow rate counter can be evaluated (see Connection Plan: Pulse). The controller can calculate the heat production from the volume flow determined (input of the counter pulse rate in P70) and the temperature difference between collector and storage tank.! If sensor F2 is available and installed as return flow sensor for the collector, the temperature difference between heat generator and F2 is calculated. Otherwise the feeder point of the charged storage tank is used for the calculation! System 4: The heat production for both the collectors is ascertained here respectively [F1-F4 and F2-F4]. If both collector pumps are in operation, the heat flows are calculated according to the ratio of the volume flows [P72]. For the calculation, the heat transport medium used in the system (glucol type = P79) and the mixture ratio with water [P78] must be set. 23

Explanation of the set values / functions The day's production and total production are displayed in [kwh]; in the case of values in excess of 10 MW, the display of the total production changes to [MWh]. The change is indicated in the display by means of three arrows. The day's production is reset to zero at midnight. Both values can be reset to zero at user level by means of the key OK.! The circulation pump must not be on via parameter 54 = 2 while measuring the production via the connected pulse generator.! If no pulse counter is connected, a production estimate can be executed. To do this, enter the average volume flow through the respective collector when the feeding pump is in operation [P75+P76]. The volume flow can be established by installing a counter for a short time or by calculation (installation technician).! The production estimate does not give the correct production value for the speed regulated pump A1 because the volume flow can only be estimated for the reduced pump speed. Guideline for volume flow quantity: Approx. 0.8 [l / min] sq. meter of collector surface. E Caution! This value does not apply to low flow systems. Starting up 70 pulse rate [millilitre/pulse] [litre/pulse] (Only with volume flow counter) Refer to the flow rate counter documents for the pulse rate of the counter connected (option). 71 Set pulse rate unit (Only with volume flow counter) Switching between [ml/pulse] and [l/pulse]. 72 Volume flow distribution with 2 collector system System 4: Enter the ratio of the volume flows through the two collectors in case both feeding pumps are in operation. 75 Volume flow fix for collector 1 [litre/min] (Only without volume flow counter - see "Production estimate") 76 Volume flow fix for collector 2 [litre/min] (Only without volume flow counter - see "Production estimate") 78 Mixture ratio Refer to the documents supplied for information on the mixture ratio of the heat transport medium (filling of the solar energy system) or ask the installation technician. 24

Starting up Other functions 79 Glycol type (Solar-electricity system documents / installation technician) 0 = Propylene glycol 1 = Ethylene glycol 98 Bus terminating resistor 1 => With enterprise with remote indication/operation without boiler automatic controllers on the BUS 0 => With enterprise with boiler automatic controller/manager on the BUS 99 Software number with index (ss.ii; Display only) Other functions Pump blocking protection The controller effectively prevents the pumps blocking following longer periods out of operation. The integrated protection function activates all the pumps which have not operated within the last 24 hours each day for approx. 5 seconds between 12:00 and 12:01. Stop pumps (temperature control) System 2,5,6: Filling of the secondary storage tank (sensor F3) is interrupted for 60 sec. every 30 minutes. After the interruption period, the start conditions for filling the primary storage tank (sensor F4) are checked. This function is only executed when the highest priority storage tank has not reached its maximum storage tank temperature [F4 < (P50-5K)]. 25

Assembly / Dismantling Starting up Assembly / Dismantling Mounting material, e.g.: Version 1 => Through the hole at the side A: Mounting holes B: Mounting holes, for assembly on switch box C: Breakthrough for leading cable through Version 2 => From the front Dimensions 26

For the fitter Electrical connection For the fitter Electrical connection! Sensor: The KLF 1000 must be used (silicone cable) as the collector sensor. E Attention: For the connection (230 V) fixed or flexible lines with the factory-standard lead end sleeves are to be installed. E Attention: Bus lines and sensor lines are to be installed separately from supply lines! 27

Special functions Special functions Depending on the system selected, the outlets A2 and A3 can be assigned to special functions. The parameter P54 is used to set the desired function separately for A2 and A3. Reheating The special functions can be used to activate a reheating function, for example via an electric submersion heater: [P54=4 (storage tank 1), P54=5 (storage tank 2)] The additional heat generator is activated when the storage tank temperature at F3 at storage tank 1 (F5 at storage tank 2) drops below set temperature [P47] by [P34] (set temperature in case of solar production = [P47]-[P52]). It is stopped when the temperature of the storage tank exceeds the set temperature This function takes effect during the enable time [P07- P08]. For the fitter Circulation pump The special functions can be used to activate the circulation pump: [P54=1, P54=2, P54=3] P54=1 => The circulation pump is continuously switched on during the enable time [P09-P10]. P54=2 => If there is a short-circuit at the pulse inlet, the circulation pump is switched on for the set switching duration P55 in minutes. The pump can be switched on again only after the set reclose blocking period P56 in minutes has elapsed. Switching on takes place only during the enable time [P09-P10]. P54=3 => Activation when hot water short time heating function is active P54=1, P54=2, P54=3 P54=3 28

For the fitter Remote controls Return flow temperature increase The special functions can be used to activate the return flow temperature increase: [P54=6 (storage tank 1; F4), P54=7 (storage tank 2; F2)] The return flow of the heating system is passed through the storage tank and is heated by it. The system is switched on via A2 when the temperature in the storage tank has exceeded the temperature of the return flow (F5) by the One switching difference 2 [P32]. The return flow temperature increase is stopped when the temperature of the storage tank drops below the temperature of return flow + One switching difference 2 [P33]. Superposed protection functions With respect to the following diagrams, please note that the respective control functions may be superposed by protection functions. An active collector protection function (see P45) or storage tank recooling (see P46) can therefore also trigger collector pump operation. Remote controls Remote indication for solar values Lago FB T-SD Indicate the following values over BUS in the dwelling: T- Solar collector 1 T- Charging zone storage tank 1 T- Storage tank 1 upper T- Solar collector 2 T- Charging zone storage tank 2 T- Storage tank 2 upper Solar production (current, day and entire) Status (pump 1 und 2, Switchover valve, ext. heating) Connecting CAN BUS Connection H, L, -, + 29

Explanation to that System diagrams For the fitter Explanation to that System diagrams F1 = temperature Sensors F1 F2 = temperature Sensors F2 F3 = temperature Sensors F3 F4 = temperature Sensors F4 F5 = temperature Sensors F5 P30 = parameter 30 Switching conditions: e.g.: On: F1-F4 > P30 und F1 > P40 (Temperature F1 minus temperature F4 larger parameter 30 und temperature F1 larger parameter 40) Off: F1-F4 < P31 or F1 < P41 (Temperature F1 minus temperature F4 less parameter 31 or temperature F1 less parameter 41) 30

For the fitter System diagrams System diagrams System 1 Outlets: A1 Collector pump (speed control) A2 Additional relay, function can be freely assigned A3 Additional relay, function can be freely assigned Maximum collector temperature: OFF: F1 > P42 ON: F1 < P42-10K Inlets: F1 Collector F4 Lower storage tank / Max. temp. monitoring A1 (when F3 is not available) F2 (opt) return for heat volume count F3 (opt) upper storage tank / Max. temp. monitoring A1 / Reference sensor for reheating F5 (opt) additional sensor (without function, indication only) or reference sensor for return flow temperature increase Pulse (opt) pulse input for volume flow counter or pulse controlled circulation pump Switching conditions A1 Heat input (difference to storage tank and min. temp.) ON: F1-F4 > P30 and F1 > P40 OFF: F1-F4 < P31 or F1 < P41 Maximum storage tank temperature: OFF: F3 (or F4) > P50 ON: F3 (or F4) < P50-5K 31

System diagrams System 2 Outlets: A1 Feeding pump for solid fuel boiler A2 Switch-over valve to storage tank 2 (when F2 available), otherwise additional relay, function can be freely assigned A3 Additional relay, function can be freely assigned Inlets: F1 Solid fuel boiler sensor F4 Lower storage tank 1 / Max. temp. monitoring A1 (when F3 is not available) F2 (opt)lower storage tank 2 F3 (opt) upper storage tank 1 / Max. temp. monitoring A1 / Reference sensor for reheating F5 (opt) upper storage tank 2 or reference sensor for return flow temperature increase Pulse (opt) pulse input, pulse controlled circulation pump Maximum storage tank temperature: OFF: F3 (or F4) > P50 and F5 (or F2) > P51 ON: F3 (or F4) < P50-5K or F5 (or F2) < P51-5K Maximum solid fuel boiler temperature: OFF: F1 > P44 ON: F1 < P44-10K Switching conditions A2: ON: A1 = ON and F3 (or F4) > P50 or F1 - F4 < P31 OFF: A1 = OFF or F3 (or F4) < P50-5K or F1 - F4 > P30 For the fitter Switching conditions A1 Heat input (difference to storage tank and min. temp.) ON: F1-F4 > P30 and F1 > P43 + 5K or F1-F2 > P32 and F1 > P43 + 5K OFF: F1-F4 < P31 and F1-F2 < P33 or F1 < P43 32

For the fitter System diagrams 33

System diagrams For the fitter System 3 Outlets: A1 Collector pump (speed control) A2 Feeding pump solid fuel boiler A3 Additional relay, function can be freely assigned Inlets: F1 Collector F2 Solid fuel boiler F4 Lower storage tank / Max. temp. monitoring A1 (when F3 is not available) F3 (opt) upper storage tank / Max. temp. monitoring A1 / Reference sensor for reheating F5 (opt) additional sensor (without function, indication only) or reference sensor for return flow temperature increase Pulse (opt) pulse input for volume flow counter or pulse controlled circulation pump Maximum collector temperature: OFF: F1 > P42 ON again: F1 < P42-10K Switching conditions for A2: Heat input (difference to tank and min. temp.) ON: F2 - F4 > P32 and F2 > P43 + 5K OFF: F2 - F4 < P33 or F2 < P43 Maximum storage tank temperature: OFF: F3 (or F4) > P50 ON again: F3 (or F4) < P50-5K Maximum solid fuel boiler temperature: OFF: F2 > P44 ON again: F2 < P44-10K Switching conditions A1 Heat input (difference to storage tank and min. temp.) ON: F1-F4 > P30 and F1 > P40 OFF: F1-F4 < P31 or F1 < P41 Maximum storage tank temperature: OFF: F3 (or F4) > P50 ON: F3 (or F4) < P50-5K 34

For the fitter System diagrams System 4 Outlets: A1 Collector pump 1 (speed control) A2 Collector pump 2 (On/Off) A3 Additional relay, function can be freely assigned Inlets: F1 Collector 1 F2 Collector 2 F4 Lower storage tank / Max. temp. monitoring A1 (when F3 is not available) F3 (opt) upper storage tank / Max. temp. monitoring A1 / Reference sensor for reheating F5 (opt) additional sensor (without function, indication only) or reference sensor for return flow temperature increase Pulse (opt) pulse input for volume flow counter or pulse controlled circulation pump Maximum collector temperature: OFF: F1 > P42 ON: F1 < P42-10K Switching conditions for A2: Heat input (difference to tank and min. temp.) ON: F2 - F4 > P32 and F2 > P40 OFF: F2 - F4 < P33 or F2 < P41 Maximum storage tank temperature: OFF: F3 (or F4) > P50 ON: F3 (or F4) < P50-5K Maximum collector temperature: OFF: F2 > P42 ON: F2 < P42-10K Switching conditions A1: Heat input (difference to tank and min. temp.) ON: F1-F4 > P30 and F1 > P40 OFF: F1-F4 < P31 or F1 < P41 Maximum storage tank temperature: OFF: F3 (or F4) > P50 ON again: F3 (or F4) < P50-5K 35

System diagrams For the fitter 36

For the fitter System diagrams System 5 Outlets: A1 Collector pump (speed control) A2 Switch-over valve to storage tank 2 A3 Additional relay, function can be freely assigned Inlets: F1 Collector 1 F4 Lower storage tank 1 / Max. temp. monitoring A1 (when F3 is not available) F2 Lower storage tank 2 F3 (opt) upper storage tank 1 / Max. temp. monitoring A1 and reference sensor for reheating F5 (opt) upper storage tank 2 / Max. temp. monitoring A1 and reference sensor for reheating or return flow temperature increase Pulse (opt) pulse generator for volume flow counter or pulse controlled circulation pump Maximum collector temperature: OFF: F1 > P42 ON: F1 < P42-10K Switching conditions A2: ON: A1 = ON and F3 (or F4) > P50 or F1 F4 < P31 OFF: A1 = OFF or F3 (or F4) < P50-5K or F1 - F4 > P30 Switching conditions A1: Heat input (difference to tank and min. temp.) ON: F1 - F4 > P30 or F1 - F2 > P32 and F1 > P40 OFF: F1 - F4 < P31 and F1 - F2 < P33 or F1 < P41 Maximum storage tank temperature: OFF: F3 (or F4) > P50 and F2 > P51 ON: F3 (or F4) < P50-5K or F2 < P51-5K 37

System diagrams For the fitter 38

For the fitter System diagrams System 6 Outlets: A1 Feeding pump storage tank 1 (speed control) A2 Feeding pump storage tank 2 (On/Off) A3 Additional relay, function can be freely assigned Inlets: F1 Collector 1 F4 Lower storage tank 1 / Max. temp. monitoring A1 (when F3 is not available) F2 Lower storage tank 2 F3 (opt) upper storage tank 1 / Max. temp. monitoring A1 and reference sensor for reheating F5 (opt) upper storage tank 2 / Max. temp. monitoring A2 and reference sensor for reheating or return flow temperature increase Pulse (opt) pulse generator for volume flow counter or pulse controlled circulation pump Switching conditions A1: Heat input (difference to tank and min. temp.) ON: F1-F4 > P30 and F1 > P40 OFF: F1-F4 < P31 or F1 < P41 Maximum storage tank temperature: OFF: F3 (or F4) > P50 ON: F3 (or F4) < P50-5K Maximum collector temperature: OFF: F1 > P42 ON: F1 < P42-10K Switching conditions A2: Heat production (difference to storage tank and min. temp.) ON: F1 - F2 > P32 and F1 > P40 and A1 = OFF OFF: F1 - F2 < P33 or F1 < P41 or A1 = ON Storage tank maximum temperature: OFF: F5 (or F2) > P51 ON: F5 (or F2) < P51-5K Collector maximum temperature as for A1! 39

System diagrams For the fitter System 7 Outlets: A1 Collector pump (speed control) A2 Additional relay, function can be freely assigned A3 Additional relay, function can be freely assigned Maximum collector temperature: OFF: F1 > P42 ON: F1 < P42-10K Inlets: F1 Collector 1 F4 Lower storage tank 1 / Max. temp. deactivation A1 (when F3 is not available) F2 (opt) Return flow heat volume count or lower storage tank 2 in the case of return flow temperature increase F3 (opt) upper storage tank 1 / Max. temp. monitoring A1 and reference sensor for reheating F5 (opt) upper storage tank 2 / Reference sensor for reheating or return flow temperature increase Pulse (opt) pulse generator for volume flow counter or pulse controlled circulation pump Switching conditions A1: Heat input (difference to storage tank and min. temp.) ON: F1-F4 > P30 and F1 > P40 OFF: F1-F4 < P31 or F1 < P41 Maximum storage tank temperature: OFF: F3 (or F4) > P50 ON again: F3 (or F4) < P50-5K 40

For the fitter System diagrams System 8 Outlets: A1 Collector pump (speed control) A2 Switch-over valve heating return flow via storage tank A3 Additional relay, function can be freely assigned Inlets: F1 Collector F4 Lower storage tank / Max. temp. monitoring A1 (when F3 is not available) F2 (opt) return, heat volume count F3 (opt) upper storage tank / Max. temp. monitoring A1 / Reference sensor for reheating F5 Reference sensor for return flow temperature increase Pulse (opt) pulse input for volume flow counter or pulse controlled circulation pump Switching conditions A2: Return flow temperature increase: ON: F4 F5 > P32 OFF: F4 F5 < P33 Switching conditions A1: Heat input (difference to tank and min. temp.) ON: F1-F4 > P30 and F1 > P40 OFF: F1-F4 < P31 or F1 < P41 Maximum storage tank temperature: OFF: F3 (or F4) > P50 ON: F3 (or F4) < P50-5K Maximum collector temperature: OFF: F1 > P42 ON: F1 < P42-10K 41

System diagrams System 9 Outlets: A1 Feeding pump for solid fuel boiler A2 Return flow temperature increase mixer OPEN A3 Return flow temperature increase mixer CLOSE Inlets: F1 Solid fuel boiler F4 Lower storage tank / Max. temp. monitoring A1 (when F3 is not available) F3 (opt) upper storage tank / Max. temp. monitoring A1 F5 Reference sensor for return flow temperature increase Switching conditions A2: OPEN - Clocked according to mixer control when F5 > P57+1K (heat transport into storage tank) Switching conditions A3: CLOSED - Clocked according to mixer control when F5 < P57-1K (return flow temperature increase) For the fitter Switching conditions A1: Heat input (difference to tank and min. temp.) ON: F1 - F4 > P30 and F1 > P43 + 5K OFF: F1 - F4 < P31 or F1 < P43 Maximum storage tank temperature: OFF: F3 (or F4) > P50 ON again: F3 (or F4) < P50-5K Maximum solid fuel boiler temperature: OFF: F1 > P44 ON again: F1 < P44-10K 42

For the fitter System diagrams System 10 Outlets: A1 Collector pump (speed control) A2 Refeeding pump on storage tank 2 A3 Additional relay, function can be freely assigned Inlets: F1 Collector F4 Lower storage tank 1 F2 Lower storage tank 2 F3 upper storage tank 1 / Max. temp. deactivation A1 / Reference sensor for reheating F5 (opt) upper storage tank 2 / Reference sensor for reheating or reference sensor for return flow temperature increase Pulse (opt) pulse generator for volume flow counter or pulse controlled circulation pump Switching conditions A1 Heat input difference to storage tank and min. temp.: ON: F1 - F4 > P30 and F1 > P40 OFF: F1-F4 < P31 or F1 < P41 Maximum storage tank temperature: OFF: F3 > P50 ON: F3 < P50-5K Maximum collector temperature: OFF: F1 > P42 ON: F1 < P42-10K Switching conditions A2: ON: F5 (or F2) <= P51 5K and F3 F2 >= P32 OFF: F5 (or F2) > P51 or F3 F2 < P33 43

System diagrams For the fitter System 11 Outlets: A1 Collector pump (speed control) and feeding pump storage tank A2 Switch-over to central feeding area A3 Additional relay, function can be freely assigned Inlets: F1 Collector F4 Lower storage tank F3 Upper storage tank (storage tank max. monitoring) F2 Feed temperature, heat volume count F5 (opt) Reference sensor for return flow temperature increase Pulse (opt.) pulse generator for volume flow counter Switching conditions A1: Heat input (difference to storage tank and min. temp.) ON: F1 - F4 > P30 and F1 > P40 OFF: F1-F4 < P31 or F1 < P41 Maximum storage tank temperature: OFF: F3 > P50 or F4 > P50 ON: F3 < P50-5K and F4 < P50 5K Maximum collector temperature: OFF: F1 > P42 ON: F1 < P42-10K Switching conditions A2: ON: A1 = ON and F2 F3 > P32 and F3 < ( P50 - P32) OFF: A1 = OFF or F2 F3 < P33 or F3 > (P50 - P33) 44

For the fitter System diagrams System 12 Outlets: A1 Collector pump (speed control) and feeding pump storage tank A2 Switch-over to top feeding area A3 Switch-over to central feeding area Inlets: F1 Collector F5 Middle storage tank F3 Upper storage tank / Max. temp. monitoring A1 F4 Sensor bottom storage tank F2 (opt) return for heat volume count Pulse (opt.) pulse generator for volume flow counter Switching conditions A1: Heat input (difference to tank and min. temp.) ON: F1-F4 > P30 and F1 > P40 OFF: F1-F4 < P31 or F1 < P41 Maximum storage tank temperature: OFF: F3 > P50 ON: F3 < P50-5K Maximum collector temperature: OFF: F1 > P42 ON: F1 < P42-10K Switching conditions A2: ON: A1 = ON and F1 F5 > P32 and F5 < ( P50 - P32) OFF: A1 = OFF or F1 F5 < P33 or F5 > (P50 - P33) Switching conditions A3: ON: A1 = ON and F1 F3 > P32 and F3 < ( P50 - P32) OFF: A1 = OFF or F1 F3 < P33 or F3 > (P50 - P33) 45