The Development of Heat Pump Water Heaters Using CO 2 Refrigerant

Similar documents
A study of high efficiency CO2 refrigerant VRF air conditioning system adopting multi-stage compression cycle

ETI-Z Series Centrifugal Chiller Applied Low GWP Refrigerant to Contribute to the Prevention of Global Warming

CHAPTER 1 INTRODUCTION

Experimental Study on Compact Heat Pump System for Clothes Drying Using CO 2 as a Refrigerant. Abstract

R&D ON HEAT PUMPS WITH NATURAL WORKING FLUIDS IN JAPAN

Ammonia. Background on ammonia as a refrigerant

Current status of Japan s legislation on F-gases and RACHP using Low-GWP Refrigerants

Development of centrifugal chiller and heat pump using low GWP refrigerant

High Efficiency Technologies for Small and Medium-Sized Air Conditioning Equipment Using R410A. Hitachi Appliances, Inc.

"ETI-Z, GART-ZE/ZEI" Centrifugal Chillers using Low-GWP Refrigerants for Full Capacity Range

HFCs or the Old Refrigerants - what is the best Choice?

Global Solutions for Ammonia Industrial Refrigeration

Transcritical CO2 Bottle Cooler Development

Development of R744 Two Stage Compressor for Commercial Heat Pump Water Heater

Natural Refrigerants: Future-proof Solutions for Today. eurammon End-Users Day 2011

CO 2. ECO Water Heaters. Energy efficient and environmentally friendly water and space heating. SANYO Air Conditioners. The natural choice.

Introduction of Transcritical Refrigeration Cycle Utilizing CO2 as Working Fluid

DAIKIN Modular Inverter Air Cooled Chiller

Chapter 10. Refrigeration and Heat Pump Systems

Low GWP Refrigerants for Air Conditioning Applications

Industry co-operation on Natural Refrigerant technology development Kenji Matsuda

Assuring Reliability of Compressors Using HFC Refrigerants By Hideto NAKAO Mitsubishi Electric Corporation Amagasaki-City, Hyogo, Japan

RS-70 is suitable as a direct replacement for R-22 in low, medium and high temperatures in a great number of applications:

Improving and Comparing the Coefficient of Performance of Domestic Refgirator by using Refrigerants R134a and R600a

Thermodynamics I. Refrigeration and Heat Pump Cycles

Due to its low temperature glide about 1.5 approx. (75% less than R-407C and R-427A), it is suitable for a wide range of applications.

EVALUATION OF ALTERNATIVERS TO R404 THE MOST COMMON REFRIGERANT IN SWEDISH GROCERY STORES

PERFORMANCE EVALUATION OF CO 2 HEAT PUMP HEATING SYSTEM ABSTRACT 1. INTRODUCTION

Development and Performance Measurements of a Small Compressor for Transcritical CO2 Applications

Daikin s Policy. and Comprehensive Actions on the Environmental Impact of

Chapter 2. Alternatives to HCFCs and their Characteristics

PERFORMANCE OF DEEP FREEZER BY USING HYDROCARBON BLENDS AS REFRIGERANTS

Recommendations to retrofit positive existing installations running with HFCs (R404A & R507) RETROFIT POSITIVE & MEDIUM REFRIGERATING SYSTEMS

EFFECT OF PAG OIL CIRCULATION RATE ON THE HEAT TRANSFER PERFORMANCE OF AIR-COOLED HEAT EXCHANGER IN CARBON DIOXIDE HEAT PUMP SYSTEM

NATURAL REFRIGERANTS FOR HEAT PUMPS AND AIR-CONDITIONING SYSTEMS. Bernard Thonon Greth

HYBRID GAS HEAT PUMP WATER HEATER WITH THERMAL EFFICIENCY 120% 23rd World Gas Conference, Amsterdam Main Author. Atsuya Tajima Japan

Development of Environmentally Benign Heat Pump Water Heaters for the US Market

Responsible Care Product Stewardship for Refrigerants

FACT SHEET 9 Large Air-Conditioning (air-to-air)

Evaluation and Development of Air-conditioners using Low GWP Refrigerant

Brazed Plate Heat Exchanger for CO Applications

High-efficiency Turbo Chiller (NART Series)

FACT SHEET 9 Large Air-Conditioning (air-to-air)

Q. Which hydrocarbons can be used as a refrigerant? The following hydrocarbons can be used as a refrigerant in cooling & heating applications:

Current use of HFCs and HCFCs. Trends, alternatives and climate impact. YEREVAN, Armenia, May 18-19, International Institute of Refrigeration

Transitioning to Alternatives and Challenges in Japan

Refrigeration Cycle And Compressor Performance For Various Low GWP Refrigerants

GEA Blu chillers. GEA BluAstrum, GEA BluGenium, GEA BluAir: A new generation of compact ammonia chillers

Design of LPG Refrigeration System

Role of Nano-technology for improving of thermal performances of vapour compression refrigeration system (VCRS): An Overview

Development Of 2-Cylinder Rotary Compressor Series For Light Commercial Use With R410A

AN EXPERIMENTAL STUDY OF A REFRIGERATING PLANT WHEN REPLACING R22 WITH HFCs REFRIGERANTS

EVALUATION OF REFRIGERANT R290 AS A REPLACEMENT TO R22

A study on retrofit methodologies for legacy air-conditioning systems to reduce their impact on global warming and ozone depletion

Experimental Study on Performance Parameters for Refrigerants R22, R410a and R404a at Various Air Outlet Temperatures

DEMONSTRATION OF ADVANCED INTEGRATED HVAC&R SYSTEMS IN A LOBLAWS SUPERMARKET IN CANADA

IJISET - International Journal of Innovative Science, Engineering & Technology, Vol. 2 Issue 12, December

The natural solution for domestic refrigeration

Evaluation of HCFC Alternative Refrigerants

Natural refrigerants - naturally efficient

THE BIG FIVE NATURAL REFRIGERANTS IN DIFFERENT INDUSTRIAL APPLICATIONS. MAYEKAWA EUROPE S.A.,Leuvensesteenweg 605, 1930 Zaventem, Belgium

Alternatives in the AC & Chiller Sectors. Sukumar Devotta and Lambert Kuijpers OORG Refrigeration

Main Anthropogenic Sources of Greenhouse Gases Refrigerants

Featuring Ozone-safe HFC134a. Hitachi Centrifugal Chillers. NEW GXG-S Series GSG-S Series Debut

Refrigerants & Cooling in renovation buildings

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger

Torad Rotary Spool Compressor

EXPERIMENTAL INVESTIGATIONS ON AUTOMOBILE AIR CONDITIONERS WORKING WITH R134a AND R290/R600a AS AN ALTERNATIVE

Refrigeration Cycles MOHAMMAD FAISAL HAIDER. Bangladesh University of Engineering and Technology

Development of CO2 Compressor and Its Application Systems

Thermodynamics II Chapter 5 Refrigeration

FACT SHEET 6 Transport Refrigeration

Experimental study of Hydrocarbon Refrigerant Mixture R290/R600a as an alternative to Refrigerant R134a used in a Domestic Refrigerator

Study of R161 Refrigerant for Residential Airconditioning

Featuring Ozone-safe HFC134a. Hitachi Centrifugal Chillers NEW. GXG-S Series GSG-S Series. Debut

Policies and Measures for HCFCs in Japan

Department of MCE, Islamic University of Technology 2. Abstract

ASSESSMENT OF R430A REFRIGERANT AS A POSSIBLE SUBSTITUTE TO R134A REFRIGERANT IN LARGE CAPACITY FREEZER

The 10 th Three Associations Meeting JRAIA. The Japan Refrigeration and Air Conditioning Industry Association. August 31, 2016.

Compressor Explosion Accident at Pump-Down of Air Conditioners

Selection of a refrigeration oil for the R32 refrigerant and evaluation of the compressor reliability

The analysis proceeded by adopting the ASHRAE guideline for conventional HVAC chiller applications. This guideline is summarized in Table II.

Making equipment decisions

This presentation is posted for public use. ACEEE does not endorse any product or service.

TYPICAL INITIAL OUTPUT OF A CO 2 HEAT PUMP

International Research Journal of Engineering and Technology (IRJET) e-issn: Volume: 04 Issue: 05 May p-issn:

Effect of capillary diameter on the power consumption of VCRS using different refrigerants

Air to water Heat Pump System

Development of a Novel Structure Rotary Compressor for Separate Sensible and Latent Cooling Air-Conditioning System

Performance analysis of ejector refrigeration system with environment friendly refrigerant driven by exhaust emission of automobile

Chillers and Refrigerants. Purpose of Today s Presentation. Agenda. GLHN Architects & Engineers, Inc. APPA Institute Session 322 EU

U.G. Student, Department of Mechanical Engineering, J D Engineering College, Nagpur, Maharashtra, India

Trends and Perspectives in Supermarket Refrigeration

Waste Heat Utilization of Vapor Compression Cycle for Operation of Vapor Absorption System

Available online at ScienceDirect. Energy Procedia 109 (2017 ) 56 63

Kawasaki centrifugal chiller using water as a refrigerant. Sep 26 th 2017 Kawasaki Heavy Industries, Ltd. Machinery Division Hayato Sakamoto

A refrigeration system for supermarkets using natural refrigerant CO 2

PERFORMANCE OF A VERY LOW TEMPERATURE REFRIGERATION SYSTEM OPERATING WITH NATURAL FLUIDS

Development of centrifugal chiller and heat pump using low GWP refrigerant

A Comparison Between Refrigerants Used In Air Conditioning

Transcription:

- 1 - The Development of Heat Pump Water Heaters Using CO 2 Refrigerant Abstract: Water heating consumes about one-third of total residential energy in Japan. Therefore, addressing the carbon dioxide (CO 2 ) emissions from this energy use is one of the top priorities for Japan in order to mitigate climate change. Further, heat pumps that rely on HFCs pose another problem in the form of direct greenhouse gas emissions, due to their high GWPs. To reduce energy and minimize emissions of both greenhouse gases and ozone depleting substances, CO 2 was chosen as a refrigerant. This paper describes how the properties of CO 2 are not only suitable for hot water heaters, but why CO 2 is actually preferred because of the electric power generating composition and resulting charge rate structure in Japan. It also discusses the latest product development and describes Japanese national policy to expand the use of this type of product in order to reduce climate emissions. 1 INTRODUCTION Recently, there has been a move towards energy saving design and the use of natural refrigerants over fluorocarbons in refrigeration, air-conditioning, and water heating equipment in order to protect the ozone layer and address global warming. Regarding refrigerants, in particular, research has been actively underway in Europe to use natural substances (e.g., ammonia, hydrocarbons, CO 2 ) to replace HFC refrigerants, which contribute to global warming. In Japan, roughly one-third of the energy consumed by households is used for water heating. More than 90 percent of this total is accounted for by combustion type water heaters. Hence, increasing the energy-efficiency of water heaters is an important measure to reduce CO 2 emissions from this source, and a key priority for the Japanese government (including the New Energy and Industrial Technology Development Organization [NEDO]), power companies, manufacturers, and others towards reducing emissions by 2010. Power generation systems tend to generate excess power at night. Therefore, to reduce energy consumption in Japan, power companies promote the use of electricity at night for power load equalization. An efficient thermal storage system using night-time electric power is ideal for this situation, and a high-efficiency heat pump has the potential to fill this role. However, for heat pumps to be most effective in reducing greenhouse gas emissions, they must not only be efficient in their energy use, they must also move away from reliance on HFCs a key refrigerant used in the air conditioning and refrigeration sector. Although research into CO 2 refrigerant is currently underway (especially in Europe), it is not yet considered to be practical; mass production of CO 2 in air conditioning units has not yet become a reality. However, CO 2 refrigerant used for water heating has the possibility to offer performance equal to or greater than that of HFCs. That is why the Japanese government, as its national policy, has provided subsidies since September 2002 for introducing CO 2 refrigerant heat pump water heaters, with the goal of expanding the market in Japan. At the same time, power companies are involved in the development and promotion of high-efficiency electric water heaters designed to improve electric power load equalization by operation at night. Against such a background, Daikin has developed a swing compressor design to match the characteristics of CO 2 natural refrigerant, as well as a residential CO 2 heat pump water heater (hereafter referred to as a CO 2 water heater) that includes a water heat exchanger. This paper describes these new products.

- 2-2 REFRIGERANT CHARACTERISTICS Studies were conducted to compare the performance of non-fluorocarbon refrigerants (e.g., CO 2 ) to HFC refrigerants, namely R-410A (HFC32/125=50/50wt%) and R-407C (HFC32/125/134a=23/25/52wt%) for use in residential heat pump water heaters. Table 1 presents the characteristics of the HFCs and R-744 (CO 2 ). As shown, R-410A and R-407C have somewhat higher COP but far higher GWP than R-744. As Table 1 shows, suitable refrigerants must be selected for different applications, i.e., HFCs are suitable for residential air conditioners and packaged air conditioners, while CO 2 is suitable for water heaters. The CO 2 water heater systems consist of three-unit components: the heat pump unit, the hot water storage unit and the remote controller. The heat pump unit draws heat from the atmosphere, compresses the heated refrigerant to heat it further, and transfers the heat to water to make it hot. The storage unit stores the hot water. The remote controllers installed in the kitchen and the bathroom enable the user to draw hot water when needed. The advantages of the CO 2 water heater are that: the ODP of the refrigerant is 0 and GWP of that is 1; it can heat water up to 90 without a heater; the heat pump method offers energy saving and safety; and it is of the night-time thermal storage type, contributing to electric power load equalization in Japan [1]. In addition, a CO 2 heat pump water heater can boil additional water more efficiently than traditional electric water heaters of night-time thermal storage type. Based on design requirements, the size of the tank can be reduced, so the 370 L tank has grown to be more popular than the 460 L tanks of most traditional electric water heaters. Hot water is typically used differently by Japanese households compared to other countries. The Japanese are the fondest of bathing in the world. Given this, they need a large amount of hot water at one time to fill a bath almost everyday. The quantity used for this purpose is double that in Western countries. On the other hand, the hourly water heating capacity of most CO 2 water heaters is lower than that of combustion type water heaters due to cost considerations. Accordingly, it is hard to heat a large amount of water at one time using a CO 2 water heater. This means that, if a large amount of hot water is required at one time, it is more cost-effective to heat water in advance. Considering these conditions, in order to achieve a system favorable to both consumers and electric power companies, and to compensate for the drawbacks of a heat pump, the heat pump unit is run at night, when electric power is cheaper to pool hot water in the tank and provide it in the daytime [2]. Figure 1 shows the electricity rates. The CO 2 water heater has been designed to maximize the benefit of this kind of rate system, which promotes the use of electricity at night for power load equalization. 3. TECHNOLOGICAL DEVELOPMENT OF MAJOR COMPONENTS New compressors and water heat exchangers were the major components developed for heat pump units of CO 2 water heaters. These components are outlined below. 3.1 Swing In a CO 2 water heater that is heating water to a high temperature, the pressure on the high pressure side of the refrigeration cycle is typically more than three times that of R-410A used in an air conditioner. Therefore, when a conventional rotary compressor is used, the reduction in compressor efficiency caused by internal leaking and the reliability of the sliding area on high differential pressure become concerns. Figure 2 shows the structure of a conventional rotary compressor and our developed swing compressor. With a rotary compressor, imposing a vane on the roller by pressure difference (between high pressure and the pressure in the compressor chamber) results in areas of high and low pressure, as shown in Figure 2. Because the differential pressure is several times larger in a CO 2 water heater, wear or burning at the tip of the vane causes problems; due to the increase in differential pressure and the speed of sound, internal gas leakage across the vane from the high to low pressure areas increases. To address this, the Daikin swing compressor combines a vane and roller, as shown in Figure 2. With the swing compressor, there is no sliding between the vane and roller, so they do not

- 3 - wear, thereby eliminating gas leakage through the gap. Due to these characteristics, a swing compressor can perform superbly with CO 2. 3.2 Water Heat Exchanger Generally, a double tube construction is used in water heat exchangers. When this is applied to heat pump water heaters, a leakage detection ditch is added to prevent mixture of refrigerants or oil and water in the event of refrigerant leakage (see double tube shown in Table 2). However, this type of double tube has the drawbacks of being heavy, expensive, and difficult to reduce in size because the bending R cannot be reduced. To address this, Daikin developed a new heat exchanger with a capillary tube acting as a flow channel for CO 2 (see smooth tube shown in the table 2), wound around the core pipe as water flow and both brazed. The shape of the water heat exchanger is presented in Figure 3.As shown, the core pipe is wound on a plane surface, and the wound pipe is arranged to produce a double layer. Therefore, the weight and volume of the water heat exchanger is about 10 to 30% less than those of a double-tube exchanger. For further energy conservation, a water heat exchanger using an innovative dimple water tube was developed. As Figure 3 shows, water in the dimpled tube is stirred, which results in efficient mixing of high temperature and low temperature water compared with conventional heat exchangers to heat water, in which the water flow is straight. The improvement in performance was proven by the image of the dimple tube. Figure 4-a) shows an image of the dimple tube. The image of the protrusion captured from the side of the acrylic tube show the detailed flow around the protrusion. Figure 4-b) shows the downstream whirlpool structure around the protrusion. The flow near the wall continuously forms a small vertical vortex after passing the protrusion; the vortex has with its central axis along the tube axis, and is about the size of the radius of the protrusion. Along with this vortex, the flow of the main flow side forms a similar vortex as if it is induced, and both are then mixed as shown in Figure 4-a). As shown by the dashed arrow in Figure 4- b), a small vertical vortex is formed after the protrusion, which reaches to the tube center on both sides. The improvement in performance was proven by the time-series images of the dimple tube. By using the dimple tube, the heat transfer performance is doubled compared to a smooth tube. The accelerated heat transmission can be seen especially in the low Reynolds number field as shown in Figure 5 [3]. 3.3 Steps For The Next Generation CO 2 Water Heater A number of technological challenges still need to be resolved for water heaters. Two characteristics in particular the use of ambient air as a heat source, and the storage of hot water are problematic when larger capacity is required. In Japan s high density urban areas, space is at a premium. The development of compact products to fit tight space will be critical for future expansion of the CO 2 water heater market. In addition, in order to improve performance of CO 2 water heaters, Daikin is developing an expander to recover energy in the process of expansion of refrigerant, which is currently believed to be the most effective way to improve the efficiency of the CO 2 cycle [4]. Figure 6 shows that the expander recovers the energy of expansion, which was historically used only for expanding using the expansion valve. Typically, the expansion of isoenthalpy is driven by using an expansion valve wherein refrigerant cooled by a gas air conditioner expands from the high to low pressure. However, using an expander can lead to recovery of power produced in the process of expansion. When the recovered power is utilized as compression energy, the power consumption of the refrigerant cycle is reduced. Figure 7-a) shows an outline of - Unit. The figure also shows that recovery of energy loss due to restriction during decompression process is improved. Figure 7-b) shows the schematic drawing of the hermetically sealed expander-compressor unit. The expander built in the expander-compressor is the swing type, like the compression system mentioned earlier. Daikin developed this prototype for a CO 2 water heater where the expander is connected with the compressor in one line and the compressor and the motor are located below and the expander is located above in a closed container, and tested it. As shown in the Figure 7-b), low-pressure refrigerant sucked into the suction side of the compressor is compressed by the compressor system, goes through the motor and is discharged from the compressor s discharge side. High-pressure refrigerant sucked into the suction side of the expander is expanded by the expander system and is

- 4 - discharged from the discharge side of the expander. In the expander system, the refrigerant s expansion energy generated when it expands is recovered and converted into rotation torque to use it as part of the energy for the compressor. Table 3 shows specifications of a CO 2 water heater system using an expander-compressor. From Table 3, the heating capacity of the heat pump is set at 10 kw. The system s performance was evaluated by relative COP under conditions shown in Figure 8 with equal capacity with a conventional compressorbased system. Figure 8 shows the results of a performance test of a CO 2 water heater system using an expander-compressor. Figure 8 also shows relative evaluation of performance of an expander and a compressor, tested separately with and without an expander. Figure 8 shows that the performance (COP) of a system with an expander-compressor was 6.4% higher than that of a conventional compressor. The result is confirmed in number between square brackets, in which the efficiency calculated from the separate test results of an expander and a compressor is 108% of the efficiency of the compressor, which agrees with the test result of the expander. This is probably caused by a heatloss caused by systematization of the heat pump equipment and a difference of optimization between ideal control and actual control. The results showed that energy requirements for the compressor were reduced. The engineering development work for this CO 2 water heater, expected to be complete in March 2008, has been carried out by Daikin together with NEDO since June 2005. The work has focused on downsizing the water heater for the purpose of expanding its use in high density urban areas, and on improving system efficiency. However, as there are still cost barriers, more advanced development of this system is needed for market-oriented commercialization. 4. CONCLUSION The development of heat pump water heaters using CO 2 natural refrigerant can be summarized as follows: - The heat transfer performance of the dimpled tube used in this water heat exchanger is twice that of a smooth tube. - The mechanism of the improved performance was confirmed in a visualizing test. - This water heat exchanger with improved performance is 10-30% lighter and smaller in volume than the conventional double-tube heat exchanger, allowing a compact, lightweight design. - The CO 2 expander for residential Eco Cute products recovers the energy loss of the compressor. Single-unit and system performance tests have demonstrated about 6-8% improvement in efficiency. - Thanks to development of water heat exchangers, expander-compressors, and other key components and improvement of system technologies, heat pumps may contribute significantly in future to addressing the challenge of global warming.

- 5-5. TABLES AND GRAPHS Refrigerant Practical examples of commercialization Table 1. Refrigerant characteristics HFC Natural refrigerant R410A R407C R744(CO 2 ) RAC PAC Residential Water Heater PAC Chiller (Eco Cute) & Commercial Commercial Water Commercial Water Water Heater Heater Heater ODP 1 0 0 0 GWP 2 1975 1652.5 1 Combustible No No No Toxic Low Low Low Pressure (MPa) (low/ high) 2.7/3.0 1.8/2.0 9.5/11 COP(compared to R410A) 100 95/100 60/80 (low/high) Note: RAC= residential air-conditioning; PAC= packaged air-conditioning. 1 Ozone depletion potential 2 Global warming potentials are based on IPCC 2001. Daytime Summer: 29.76/kWh Other seasons: 27.06/kWh Price (\/kwh) Night time 7.22/kWh Living time 20.67/kWh Living time 20.67/kWh Time (O clock) Figure 1. Electricity rates by season and time (KANSAI ELECTRIC POWER CO.) At the tip of vane: wear, burn gas leak Combined vane and roller No wear, improved reliability, improved performance due to less leakage Vane Swing Bush Compression chamber Roller Intake Crankshaft Piston Crankshaft Figure 2. Comparison of conventional rotary and swing compressors

- 6 - Table 2. Comparison of water heat exchanger Former type New type Spec Double tube Smooth tube initial time Dimple tube latest Outline of shape Water Leckage detection ditch Dw,i Water p CO 2 CO 2 refrigerant piping Water piping CO 2 Dimple Capacity ratio 1.00 0.89 0.89 Weight ratio 1.00 0.74 0.64 Performance 1.00 1.00 1.00 CO 2 Pipe wall CO 2 Water Improvement Water Water tube CO 2 refrigerant tube Dimple Figure 3. Improvement of a heat transfer rate of a water heat exchanger Flow direction (a)flow pattern (b)vortex structure Figure 4. Images around the dimple.

- 7-3 2 SD tube Inner grooved tube Smooth tube Nu/Nu0 1 0 0 2000 4000 6000 8000 Re Figure 5. Evaluation of the water heat exchanger high Heating Capacity P iso-entropic expansion Traditional Cycle Pressure (MPa) low low Energy Recovered by h Enthalpy (kj/kg) Figure 6. Principle of expander-compressor Input high Gas air conditioner Inlet Mechanism Outlet Energy recovery Power recovery M Evaporator Discharge DC Motor Mechanism Suction a) Outline of improvement of efficiency b) Schematic drawing Figure 7. Outline of - Unit

- 8 - Table 3. Spec of prototype expander-compressor Shape Swing type Capacity of cylinder [cc] 0.7 Shape Swing type Capacity of cylinder [cc] 11.1 Concentrated winding Shape Motor DC motor Dimension Thickness [mm] 125 90L COP ratio 110% 105% 100% 6.4% with expander [100%] [108%] Number in [ ] : a unit performance of an expander-compressor. Test condition JRA rated condition (Between summer and winter period) Outdoor temperature DB/WB 16/12 Inlet/Outlet water temperature 17/65 Without an expander With an expander Figure 8. Evaluation of system performance 6 REFERENCES [1] Hirosi NAKAYAMA, Mitsuharu UCHIDA, Masahide HIGUCHI, Yutaka SHIBATA, and Yasuhiko OKA, The development of heat pump water heater system with a carbon dioxide hermetic swing rotary compressor, the 9th Power and Energy Technology Symposium (2004) [2] Hirofumi IDA, The development trend and future view of the CO 2 refrigerant heat pump water heater,, September 2007, vol. 82, No. 959. [3] Mitsuharu NUMATA, Shuji FURUI, and Kazushige KASAI., Heat transfer enhancement of water- CO 2 heat exchanger for CO 2 heat-pump water heaters, JSRAE (2006). [4] Katsumi SAKITANI, Michio MORIWAKI, Masakazu OKAMOTO, Eiji KUMAKURA, and Tetsuya OKAMOTO., Development of two-phase flow expander for CO 2 air-conditioners, 8th IEA Heat Pump Conference 2005.