IMR IX176 Portable Gas Detector User Manual

Similar documents
IMR EX610. Portable Gas Detector. Operation Manual

E1000 Portable gas detector

User s Guide HHAQ-109. Portable Multi-gas Detector. Shop online at omega.com SM

IMR 5000 IMR 400. CEMS Operating Manual IMR USA S/N: Sample IMR Sensors Inside IMR 400. Gas Dryer Inside. IMR Environmental Equipment Inc.

TC100N. Fixed Gas Detector Operation Manual

ENMET Corporation. PO Box 979 Ann Arbor, MI RECON. Manual. Manual Part Number MCN-410, 12/03/08

QD6310. Fixed Gas Detector Operation Manual

Macurco Single-Gas XL Series Monitor, CM-1XL Carbon Monoxide (CO), HS-1XL Hydrogen Sulfide (H2S) User Instructions

GasAlertMicroClip X3 Specifications

BST-MG07 Multi-gas Detecting Alarm Manual Instruction

BST-MG08/09 Multi-gas Detecting Alarm. Manual Instruction

RECON/4a Portable Multi-Gas Detector Operation and Maintenance Manual

CO2 RESPONDER Portable Carbon Dioxide Detector QUICK REFERENCE GUIDE

Confined Space Monitoring. Leak Investigation. Functions 4. Bar Hole Sampling. Line Purge Testing. Actual Size GX-2012

GasAlertMicro 5. 1, 2, 3, 4, and 5 Gas Detectors. Quick Reference Guide

MODEL: SP12C7. (Portable 4 gas detector) Operating Manual

IMR 5000 Operating Manual S/N: SAMPLE For information only! IMR Environmental Equipment Inc.

1, 2, 3, and 4-Gas Detector. Technical Reference Guide

QUICK REFERENCE GUIDE

Operator s Manual. 1, 2, 3, and 4-Gas Detector

MODEL: SP12C7. (Portable 4 gas detector) Operating Manual

For the Safety of Your

Operator s Manual. 1, 2, 3, and 4-Gas Detector

5 Operating Modes GX Smallest 6 gas sample draw PID library of over 600 VOC s 2 Interchangable smart sensor slots

5 Operating Modes GX Smallest 6 gas sample draw PID library of over 600 VOC s 2 Interchangable smart sensor slots

ALTAIR 5X Multigas Detector Product Specification

Safe Operation Manual. Honeywell IQ Force Gas Detector

GasAlert. Introduction. WWarning. Table 1. GasAlert Models. Gas Monitored

1.1 Definitions of alert icons. For your safety

GasAlertMicro 5 and GasAlertMicro 5 PID O 2, CO, H 2 S, PH 3, SO 2, Cl 2, NH 3, NO 2, HCN, ClO 2, O 3, VOC, and Combustibles

Operate the Mutli-Gas Monitor PID

NH 3 RESPONDER Portable Ammonia Leak Detector QUICK REFERENCE GUIDE

EAGLE 2. 6 Channel Capacity. Inlet fitting. Loud buzzer (95dB) IrDA communication port Low flow shutoff and alarm Alarm LED s with wide visibility

TS400. Operating Manual. Test Station for Microtector II Series (G450/G460)

MODEL: SP2nd (Portable Single Gas Detector) Operating Manual

1, 2, 3, and 4-Gas Detector. Technical Reference Guide

User Manual R1.0 CO2Meter, Inc. Personal CO2 Monitor SAN-10

Using the QRAE Plus personal multigas monitor

NH3 RESPONDER PORTABLE AMMONIA LEAK DETECTOR. Quick Reference Guide

X5 Personal Gas Detector. Operating Manual

Dräger X-am 5000 Multi-Gas Detection

Warranty Registration

Sirius MultiGas Detector

EST User Manual. (Please read this manual carefully before using)

BST-MG01 Single Gas Detecting Alarm Manual Instruction

Technical Reference Guide. 1, 2, 3, and 4-Gas Detector

G450. Multi-gas Detector. Field Operation Manual Oak Valley Dr, Ste 20, Ann Arbor MI USA (800) (734)

Dräger X-am approved as type MQG 0010 Multi-Gas Monitor Technical Manual _01.eps

User Manual. Single Gas Detector

ALTAIR 4 Four Gas Multigas Detector

RAE Systems Systems. User Presentation. October Protection Through Detection

Instruction Manual for FORMALDEHYDE GAS DETECTOR MODEL FP-30/FP-40

Portable Oxygen Monitor OX-07. (Type B) <No Gas alarm type> Operating Manual

Dräger Pac Ex 2. Elegant and smart... Explosive hazards and lack or surplus of oxygen under control

INSTRUCTION MANUAL GAS LEAK DETECTOR CD200

Personal Single Gas Monitor. Activation Operation Troubleshooting

MGC Dock User s Manual

G450. Multi-gas Detector. Operations Manual Oak Valley Dr, Ste 20, Ann Arbor MI USA (800) (734)

Bacharach Bodyguard 4 User's Guide

Clip SGD. Portable single Gas Detector. User manual

Dräger X-am approved as type MQG 01** Multi-Gas Monitor. Technical Handbook. CO2 Vol% CH4 %UEG. CO ppm. ppm NH _01.

Dräger X-am 7000 Multi-Gas Detection

MODEL OX-07 Type A INSTRUCTION MANUAL FOR RIKEN PORTABLE OXYGEN MONITOR PT0E-0860

Dräger X-am 2500 (MQG 0011) Technical Manual

Single Gas Detector. Quick Reference Guide

Activation Operation Troubleshooting Part Number: Edition: Release Date:

T.ex Single Gas Detector VISA

NATURAL GAS DETECTOR. Confined Space Monitor. Leak Investigation. Line Purge Testing. Bar Hole Sampling

G460. Multi-gas Detector. Operations Manual Oak Valley Dr, Ste 20, Ann Arbor MI USA (800) (734)

SC-01 Operator s Manual

Operations Manual TS400. Test Station for G450/G460 Gas Detector

Beacon 200 Gas Monitor Operator s Manual. Part Number: RK Released: 6/6/08

Single Gas Monitor 777

Dräger X-am 5000 Multi-Gas Detection

Operations Manual TS400. Test Station for G450/G460 Gas Detector

Portable Oxygen Monitor OX-07. (Type A) Operating Manual

Dräger X-am Dräger X-am 7000: Modular, rugged and waterproof.

03 Series: OX-03, CO-03, HS-03 Versions Operator s Manual

ToxiRAE II. PGM-1100 Series Personal Toxic Gas Monitor. User Manual

Dräger X-am 2500 Multi-Gas Detection

Quality. Water. Water Quality. Testing. Testing. Toxic Gas Detection. Toxic Gas. Detection. Air Quality. Monitoring. Monitoring. Monitoring.

Dräger X-am 5600 Personal Monitor Multi-Gas Detection Device

Operating Instructions Compur Monitox plus

Dräger Pac 3500 Single-Gas Detection Device

MGC Dock User s Manual

RAE Systems RAE Systems RAE Systems Presented by David Lucha RAE Systems Protectio n Through Detection

Model:AS8900 MULTI-GAS MONITOR O 2 %VOL H 2S PPM LEL%VOL CO PPM. Version number:as

aspida User Manual T: +44 (0) F: +44 (0) W: E:

Pioneer-R16 Gas Monitor Operator s Manual

Model GX-2001 Canadian Version Operator s Manual Part Number: RK Revision: 0 Released: 1/17/05

II 2 G. SENSIT HXG-2d. Ex ib IIB T3 IP20. Suitable for combustible gases such as Methane, Butane, Propane and Natural Gas MADE IN USA

testo 316-EX gas leak detector Instruction manual

GasAlertMicro 5 / PID / IR

CP01 Fixed gas detector

Multi-gas Monitor. Product Manual Set-up Operation Service. Part Number: Version 12

OI-2400-DOCK Multi Gas Docking Station. Operation Manual trevision 2.2w

testo Leakage detector for gas Instruction manual

Gas leak detectors. For a quick overview. testo testo testo testo gas detector testo 316-Ex

MULTI-GAS MONITOR. Eastern Energy Co., Ltd. 40/4 Vitoondumri Rd., Banbueng Banbueng, Chonburi, Thailand

Single Gas Clip and SGC Plus User s Manual Rev 2.1 READ FIRST BEFORE OPERATION WARNING STATEMENTS / AVERTISSEMENT Activating tthe detector for the

Transcription:

IMR Portable Gas Detector User Manual Read this manual carefully before using this device. (727) 328-2818 / (800) RING-IMR Fax: (727) 328-2826 www.imrusa.com Ver. 1.0A4

CONTENTS SERVICE GUIDELINES... 3 SAFETY INFORMATION... 3 1. Brief Introduction... 4 2. Features and Specifications... 4 2.1. Main Features:... 4 2.2. Technical Specifications:... 4 3. Structure and Functions... 5 3.1. Appearance... 5 3.2. Display Information... 5 3.3. Button functions... 5 4. Operating instruction... 6 4.1. Power On the Detector... 6 4.2. Power Off The Detector... 6 4.3. Menu... 6 4.4. Alarm Codes... 8 4.5. Check Device Status... 9 4.6. Zero Calibration... 9 4.7. Bump Test... 9 5. Calibration and Alarms... 10 5.1. Calibration and Alarming Level:... 10 5.2. Zero Calibration... 10 5.3. Calibration Span Adjustment... 10 5.4. Calibration Span Set Up... 10 5.5. L-alarm Set Up... 11 5.6. H-alarm Set Up... 11 6. Battery Charging... 11 7. Data Upload... 11 8. Sensor Usage and Replacement... 11 9. Carry Clip Configuration... 11 10. Troubleshooting Guide... 12 11. Usage Notices... 12 Target Gas List... 13 12. Warranty... 14 13. Contact Information... 15 THE PRIDE OF THE COMPANY MADE IN THE USA Page 2 of 15

SERVICE GUIDELINES 1. Thank you for purchasing this product. Before operation, please read this manual carefully to help prevent any accidents or damage to the device due to miss use. 2. Do not modify, repair, or replace parts in the device without contacting IMR, we assume no liability for any harm caused due to improperly modified equipment. 3. Any damage caused due to incorrect operation shall not be covered. SAFETY INFORMATION Before using the detector please carefully read the below safety information first and follow the operation requirement: 1. Do not use if damaged or defective. Before use check physical damage or missing parts. 2. Each day before use it is recommended to perform a bump test to ensure the detector is operation properly. See section 4.7 3. It is recommended that a bump test be performed periodically to ensure that the audible, visual and vibration alarms are set to the correct level and are functioning properly. 4. Only use authorized accessories provided by IMR. Use of unauthorized accessories may result in damage to the device. 5. Only use the charger provided with the instrument to charge the detector. Only charge in a safe environment. Charging in a hazardous environment is not advisable. 6. Detectors using catalytic sensors or semi-conductor sensors cannot be exposed to gases with concentrations over the detector s range. Doing so will overload the detector and interfere with its performance or even cause damage. 7. Detectors using catalytic sensors or semi-conductor sensors cannot be exposed to gas environments that contain lead compounds, sulfur compounds, phosphorous compounds or silicon. These environments will damage a catalytic sensor or semi-conductor sensor. 8. Detectors using catalytic sensors or semi-conductor sensors cannot be exposed to gas environment which contain hydrogen sulfide, halogenated hydrocarbon or highly corrosive environments. These environments will dampen the sensor s response and decrease the sensor s sensitivity to gases. If the detector has to be used in the above environments. Then preform a bump test after use. 9. Do not expose the detector to electric shock, strong electromagnetic fields or intense continuous mechanical vibration. 10. Do not discard the battery in the standard trash. Please follow all local regulatory and environment regulations pertaining to lithium battery disposal. 11. Disassembly, modification, or repair of the detector by the end user is prohibited. 12. Take precautions to prevent the detector from being dropped at high elevations and intense vibration. 13. For any usage or trouble shooting not covered in this manual contact IMR. THE PRIDE OF THE COMPANY MADE IN THE USA Page 3 of 15

1. BRIEF INTRODUCTION The portable single gas detector can make continuous detection to combustible and toxic gases. It is suitable for combustible and toxic gas leakage detection in underground pipe or mines, keeps workers safe and prevents damage to facilities. The detector uses high quality sensors. The shell is special high strength material with anti-slip rubber. It has a functional and watertight design (IP 65). 2. FEATURES AND SPECIFICATIONS 2.1. MAIN FEATURES: Large LCD display Adjustable low and high alarm level High concentration protection for combustible gas Self-test of the combustible gas sensor Low battery alert Real time clock Replaceable sensor module Self-adjustment function Data upload to PC (optional) STEL and TWA alarming for toxic gases Intrinsically safe 2.2. TECHNICAL SPECIFICATIONS: Detection method: Natural diffusion Target gas: LEL, O2, toxic gases etc. Accuracy: ±5% F.S. Response time: T<30s Indication: o LCD indicates the time and state o Audible, visual and vibration alarm signals Working temperature: o -40 ~70 (for combustible gas) o -20 ~50 (for toxic gas) Working humidity: <95%RH IP rating: IP65 Power supply: DC3.7V, 1300mAh Li-ion battery Continuously working time: o Combustible gas: 8h continuously o Toxic gas: 300h continuously Charging time: 4~6 hours Sensor life: 3 years Dimension and weight: 104.0mm 60.8mm 30.5mm about 125g THE PRIDE OF THE COMPANY MADE IN THE USA Page 4 of 15

3. STRUCTURE AND FUNCTIONS 3.1. APPEARANCE 1. Alarm LED 2. Display 3. Buttons 4. Gas port 5. Data / Charging port 6. Buzzer 7. Hand strap 3.2. DISPLAY INFORMATION 1. Battery voltage 2. Lock 3. Buzzer 4. Vibrator 5. Alarm type 6. Warning 7. Value figure 8. Fault 9. Record 10. Clock 11. Zero calibration 12. Calibration span & status 13. Charging 14. Settings 15. Unit of measurement Note: Data upload function is only available only if requested at time of purchase. 3.3. BUTTON FUNCTIONS Button Description To power on the detector press and hold for 3 seconds Press to cancel an operation Calibration: When the device is powered off press and for more than 3s To power off the detector press and hold for 3 seconds Press to increase the display value To check the device status press and. This will display Temperature, time, STEL & TWA levels2, and maximum level3 Press and for more than 3s to access the configuration menu Press to decrease the display value To start zero calibration press & then hold for more than 3s 1 Confirm entered information Press to enable/disable the beep and vibration Note: 1 Password is needed when this operation does. 2 Only the detector for toxic gas has this function. 3 Only O2 sensor has maximum and minimum level. THE PRIDE OF THE COMPANY MADE IN THE USA Page 5 of 15

4. OPERATING INSTRUCTION 4.1. POWER ON THE DETECTOR Hold for 3 seconds and the detector will power on. The detector then begins a self-test. 1. The LCD displays all of the screen elements. 2. Alarm check: audible, visual and vibration signal. 3. Software version number: Note: If the self-test fails the display will show relevant information. For details refer to the table in section 4.4. The countdown occurs when there are no faults. The device will automatically select the necessary time for the countdown of 3-30s according to the installed sensor. 4.2. POWER OFF THE DETECTOR Hold the screen will display OFF and the buzzer will sound. After 3 seconds the following figure is seen. Release and the detector will power off. 4. Date and Time: 5. Preset Low Alarm and High Alarm value: 6. STEL and TWA values Note: The above pictures can only appear with toxic gas sensors. 7. Self-test and Warm up If the detector passes the self-test then it will begin a short countdown for warm up. After that it begins normal operating mode. The ambient gas reading is then displayed. Note: When not in detection mode press several times until it returns to detection mode. 4.3. MENU Setup date and time On/off of the vibration On/off of the key sound Communications Mode 1 Setup the password Note: 1 Data upload function is only available only if requested at time of purchase. In normal detection mode hold and simultaneously until the screen displays the following figure for 1 second and then release the buttons. It enters the menu. THE PRIDE OF THE COMPANY MADE IN THE USA Page 6 of 15

Press or to change menu items. The following table outlines each item: Display Description Press to adjust the time Press to turn on or turn off the key press sound Press to turn on of turn off vibration Press to enter communications mode with a PC 1 Press to modify the password (initial : 0000) Note: 1 Data upload function is only available only if requested at time of purchase. After entering into an item press or to change settings. Press to confirm and press to exit without saving. The following table outlines each option: Display Description Enable the function Disable the function THE PRIDE OF THE COMPANY MADE IN THE USA Page 7 of 15

4.4. ALARM CODES The following table describes detector alarms and shows how the LCD looks for each alarm: Alarm type Display Low-alarm: Slow tone Flash Vibration 1 High-alarm: Fast tone Flash Vibration 1 High concentration protection: 2 Slow tone Flash Sensor Fault: Fast tone STEL alarm: Slow tone Flash Vibration 1 TWA alarm: Slow tone Flash Vibration 1 Over F.S. alarm: Slow tone Flash Time error: In this state the device will try to automatically correct it. If successful then after start-up it will open the time menu set up. If saving a new time fails the device will power off. Please contact IMR for repair. Memory error: When detecting the device will try to automatically correct it. If this fails it will power off. Please contact IMR for repair. Low voltage: Alternating alarm sound per second When battery is near empty the icon will flicker. The device can continue to operate for about 15min. THE PRIDE OF THE COMPANY MADE IN THE USA Page 8 of 15

Note: 1 It will only vibrate if the vibration setting is enabled. 2 Only for combustible gases. If the alarm is triggered for extended periods press to suppress the audible and vibration alarms and will flash. 4.5. CHECK DEVICE STATUS Pressing and together will display the Temperature, Time, STEL & TWA levels1, maximum level and minimum level2. Note: 1 Only available for toxic gases. 2 Only O2 sensors have min/max levels. 4.6. ZERO CALIBRATION In clean air if the detector does not 0 then select zero calibration to reset the zero point. In detection mode pressing both and for 1 second will prompt to please input password once this is displayed release the buttons. Input the password to access zero point calibration. Note: When it is calibrated the concentration of oxygen in clean air for O2 is 20.9%VOL. Warning: This operation should be carried out in clean air. Otherwise the accuracy of the detector will be affected due to gas concentrations in the air. 4.7. BUMP TEST In order to make sure the is working correctly it is suggested to do a bump test before every use. Test method: With the device is powered on expose it to the target gas or standard gas environment with high a concentration that is beyond the high alarm level. If the device reacts correctly and the reading is accurate then the detector may be used in the field. If the reading is beyond the regular error ranges recalibrate the device. See section 5. If the device does not respond or display is faulty (error) contact IMR. The detector will display the following: Status? Display Pressing both and will display this. After 1 second it will continue to the next step. At this step enter the password. The digit that is flickering figure can be modified by pressing or. The zero point will automatically calibrate. Press to save the new setting. THE PRIDE OF THE COMPANY MADE IN THE USA Page 9 of 15

5. CALIBRATION AND ALARMS This section covers recalibrating the detector and adjusting alarm levels. 5.1. CALIBRATION AND ALARMING LEVEL: When the device is powered off press and hold and for 5 seconds and the detector will begin a self-test. If the self-test passes the enter password prompt will be displayed: is damaged. Move to another location and test again. If the problem persists replace the sensor. 5.3. CALIBRATION SPAN ADJUSTMENT Set the calibration gas concentration. The currently selected number will be flashing. Press or to modify this value: Entering the correct password will result in the detector entering into zero calibration mode. Note: A misconfiguration in this section can endanger the safety of the operator and equipment. Take care during this process Ten seconds after entering the password if no buttons are pressed or if the password is incorrect the detector will power off. 5.2. ZERO CALIBRATION The currently detected concentration will be shown: If is pressed or no input is made within 1 minute. The detector will use the current concentration as the zero point and then enter into the calibration span set up. Press to skip calibration set up and enter into alarm level set up. Continue at section 5.5 and 5.6. Warning: This operation should be carried out in clean air. Otherwise the accuracy of the detector will be affected due to gas concentrations in the air. If the detector displays an E this indicates that air is not clean or that the sensor If is pressed or no input is made within 1 minute. The detector will use the current concentration as the calibration gas concentration. It will then enter into calibration span set up. 5.4. CALIBRATION SPAN SET UP The detector will now display the currently detected gas concentration: Attach the calibration cover. Open the calibration gas tank and adjust the flow to 120mL/min. If the detector senses the calibration gas within 30 seconds it will begin to automatically analyze the applied gas. The detector will automatically process and save the new span setting. The detector will then advance to L-alarm set up. Note: Avoid pressing any of the buttons as this can cause the detector to save incorrect information. If the detector does not reach half of the calibration gas concentration within 30 seconds or the detected calibration gas concentration goes into overflow the E error icon will illuminate. This indicates that the calibration gas concentration is too high for the installed sensor or that the sensor is THE PRIDE OF THE COMPANY MADE IN THE USA Page 10 of 15

defective. Test again with a lower calibration gas concentration or replace the sensor of the issue persists. Calibration of an O2 sensor will skip section 5.3 and 5.4. 5.5. L-ALARM SET UP Now the L-alarm can be adjusted. The screen will display the current alarm setting. Press or to adjust the flashing value as needed and then press to complete set up. The detector will then advance to H-alarm set up. 5.6. H-ALARM SET UP Now the H-alarm can be adjusted. The screen will display the current alarm setting. Press or to adjust the flashing value as needed and then press to complete set up. Note: Data upload function is only available only if requested at time of purchase. 8. SENSOR USAGE AND REPLACEMENT The sensors that this detector utilizes are modularized. It is important to keep track of the sensors age and replace it every 3 to 5 years depending on sensor type. The device should be calibrated every 6 months to ensure best accuracy of the installed sensor. Sensor replacement should only be done by IMR or an authorized repair center. In the event that neither of these options are possible contact IMR for support. Do not replace the sensor with unauthorized parts. 9. CARRY CLIP CONFIGURATION The device can have either a belt clip or a crocodile buckle and ring. See the diagram below for more information. The detector will then power off. 6. BATTERY CHARGING If the battery is low or the detector is not being responsive the battery need to be charged. Note: The detector cannot be powered on while it is charging. To avoid fire or explosion do not charge the detector on site at a hazardous location. Attempting to charge the detector while it is powered on will prolong the time needed to fully charge the device. 7. DATA UPLOAD Connect the detector to a PC with the provided USB cable. Then open the data software. 1. Crocodile Buckle 2. Ring 3. Mounting hole 4. Belt clip 5. Screw hole THE PRIDE OF THE COMPANY MADE IN THE USA Page 11 of 15

10. TROUBLESHOOTING GUIDE Issue Possible Reason Solutions Unable to power on Low battery Charge for the recommended duration Unresponsive Contact IMR Circuit fault Contact IMR No response to gas Warm up not finish Wait till it finishes PCB fault Contact IMR Testing reading incorrect Sensor overdue for Replace the sensor replacement Calibration out of date Calibrate the sensor Incorrect time Battery depleted Charge the device and set the time Electromagnetic interference Reset the time Unable to complete a Zero Sensor drift Calibrate or replace the sensor calibration It displays -0 Sensor drift Calibrate or replace the sensor It displays Sensor fault Replace the sensor 11. USAGE NOTICE Avoid intense dropping or shocking. If using in high concentration gas environments the device will not work normally. Strictly follow this manual while using the device. Failure to do so will cause incorrect detection result or damage the device. It is forbidden to use and store the device in corrosive environments (high concentrations of CL2) or harsh environments (exceedingly high or low temperature, high humidity, electromagnetic field, intense sunlight etc.) After prolonged use if the device is dusty use a clean soft cloth to clean it. Otherwise the surface may become scratched or damaged. In order assure detection accuracy the re-calibration period is every 6 months and cannot be more than 1 year. Do not discard the battery in the standard trash. Please follow all local regulatory and environment regulations pertaining to lithium battery disposal. For any usage or trouble shooting not covered in this manual contact IMR. Disassembly, modification and repair of the device should be carried out by authorized personnel only. It is dangerous to charge the device or upload data to a PC in hazardous environments. THE PRIDE OF THE COMPANY MADE IN THE USA Page 12 of 15

TARGET GAS LIST Gas Range L-alarm H-alarm TWA STEL CH 4 0-100%LEL 20%LEL 50%LEL C 3 H 8 0-100%LEL 20%LEL 50%LEL H2 0-100%LEL 20%LEL 50%LEL H2 0-1000ppm 35ppm 250 ppm H 2 S 0-100ppm 10ppm 15ppm 10ppm 15ppm CO 0-1000ppm 35ppm 200ppm 35ppm 200ppm CO 0-2000ppm 35ppm 200ppm 35ppm 200ppm O 2 0-30%vol 19.5%vol 23.5%vol C 2 H 5 OH 0-100%LEL 20%LEL 50%LEL NH 3 0-100ppm 25ppm 50ppm 25ppm 35ppm CL 2 0-20ppm 5ppm 10ppm 0.5ppm 1.0ppm SO 2 0-100ppm 2ppm 5ppm 2ppm 5ppm THE PRIDE OF THE COMPANY MADE IN THE USA Page 13 of 15

12. WARRANTY IMR states the following: IMR as manufacturer hereby grants the following worldwide IMR warranty for an IMR analyzer purchased from an authorized dealer. 1. The IMR warranty shall entitle every IMR customer to demand a free replacement or repair of the defective parts from any IMR dealer authorized for the respective IMR unit. 2. The IMR warranty shall be granted on the factory new unit and shall commence on the date of the delivery of the original IMR unit to the customer. 3. The IMR warranty shall refer to absence of faults with respect to the state of the art nature of the sold unit in terms of material and finish. The warranty for all parts fitted during the twelve-month warranty period shall end with the unit warranty. 4. After the establishment of a material or production fault by IMR or the authorized IMR dealer, the faults will be eliminated by means of free repair or replacement. Replaced parts shall become the property of IMR. 5. No warranty claims may be made for maintenance and setting work, cleaning or other utility materials required for the function of the unit and other wear parts unless they have a direct bearing on work performed under the warranty. 6. The terms and conditions for the acknowledgement of this warranty shall be the presentation of the fully completed warranty card, which must contain the confirmation from the authorized IMR dealer on its delivery and, if applicable, the prescribed maintenance work. 7. The IMR warranty shall only be applicable if 7.1. The analyzer has been maintained in accordance with the instructions issued by the manufacturers and the operating instructions by an authorized IMR dealer. 7.2. Only original IMR spare parts have been used for any repairs. 7.3. The unit has been used properly, the operating instructions observed and the unit has not been used for a purpose other than the one for which it has been designed. 7.4. The IMR unit has been left in its original design and meets the original IMR specifications. 7.5. The fault is not due to external influences or use for a purpose other than the one for which it has been designed. 7.6. Exclusively authorized IMR dealers have made repairs to the IMR unit. 7.7. The IMR unit has been sent to an authorized IMR dealer immediately after the fault was discovered. 8. Warranty time for the analyzer, including electrochemical sensors is 12 months. THE PRIDE OF THE COMPANY MADE IN THE USA Page 14 of 15

13. CONTACT INFORMATION 3632 Central Ave. St. Petersburg, FL 33711 USA Phone: 727/328-2818 Fax: 727/328-2826 1800#: 1-800/746-4467 Internet: Email: www.imrusa.com sales@imrusa.com technical_department@imrusa.com IMR is a registered Trademark of IMR THE PRIDE OF THE COMPANY MADE IN THE USA Page 15 of 15