SCHULTE & ASSOCIATES Building Code Consultants 880D Forest Avenue Evanston, IL /

Similar documents
Significant Advancements in Water Based Fire Suppression for Storage Occupancies

SCHULTE & ASSOCIATES Building Code Consultants 880D Forest Avenue Evanston, IL /

Storage Protection Using Horizontal Barriers and Large K-Factor, Extended Coverage In-Rack Sprinklers

SCHULTE & ASSOCIATES Building Code Consultants 880D Forest Avenue Evanston, IL /

Requirements for the protection of High-Piled Combustible Storage (HPCS) Effective Date: January 2011

Protection of Rack Stored Exposed Expanded Group A Plastics with ESFR Sprinklers and Vertical Barriers

H gh-p led Combust ble Storage. Application Guide 2009 Edition

NFPA Edition. NFPA 13 (2016 Edition) Hot Topics and NFPA 13 FAQ s. Highlights of 2016 Changes. Storage Commodity Classification 4/29/2014

Table EXIT ACCESS TRAVEL DISTANCE a OCCUPANCY SYSTEM SYSTEM. A, E, F-1, I-1, M, b,d R, S-1. B c. F-2, S-2, U c

TECHNICAL DATA. * Refer the Approval Charts and Design Criteria on pages 3-5 for culus Listing and FM Approval requirements that must be followed.

TECHNICAL DATA. * Refer the Approval Chart on page 120c and Design Criteria on page 120d for culus and FM approval requirements that must be followed.

By: Russell Bainbridge March 18th, 2016 FPE 596

TECHNICAL DATA OBSOLETE. * Refer the Approval Chart on page 121c and Design Criteria on page 121d for FM approval requirements that must be followed.

Plan Submittal Checklist

Warehouse Protection of Exposed Expanded Group-A Plastics with Electronic Sprinkler Technology

Tire Storage. Michigan Fire Inspectors Society Fall Conference

esfr pendent sprinkler vk510 (k25.2)

IFC Significant Changes from the 2009 to the 2015 Edition Tier 1

esfr pendent sprinkler vk510 (k25.2)

culus Listed: Category VNIV Refer to the Approval Chart on page 3. VK697 Attic Upright Sprinkler Specifications:

Early Suppression Fast Response Sprinklers and Obstructions

SCHULTE & ASSOCIATES Building Code Consultants 880D Forest Avenue Evanston, IL fpeschulte.

ESFR PENDENT SPRINKLER VK510 (K25.2) TECHNICAL DATA

Storage Sprinkler U.S. Quick Reference Guide

SPRINKLER TECHNOLOGY:

DEPARTMENTAL GUIDELINES CHAPTER 6 TACTICAL OPERATIONS

STANDARD/QUICK RESPONSE ECOH ELO FUSIBLE ELEMENT UPRIGHT SPRINKLER VK535 (K11.2) TECHNICAL DATA

Model ESFR K-factor Pendent Sprinkler Early Suppression, Fast Response General Description. Sprinkler Identification Number (SIN)

New Facilities. Minimum Requirements

esfr dry pendent sprinkler Vk502 (k14.0)

ICC CODE CORNER 2012 IFC Code & Commentary

ESFR PENDENT SPRINKLER VK500 (K14.0) TECHNICAL DATA

TECHNICAL DATA NOTICE

ROLL PAPER STORAGE. Table of Contents

TECHNICAL DATA OBSOLETE

High-Piled Combustible Storage

Storage Sprinkler. Model LP-46 (SIN) V4603, K25, Standard Response Storage Upright Sprinkler, Patent Pending

ATTIC UPRIGHT SPECIFIC APPLICATION SPRINKLER VK696 TECHNICAL DATA

Model ESFR-17 Early Suppression, Fast Response Upright Sprinklers 16.8 K-factor General Description

TECHNICAL DATA. Refer to the Approval Chart and Design Criteria for UL and FM Listing/Approval requirements that must be followed.

High challenge warehouse case study Summary

FIRE PROTECTION FOR NON-STORAGE OCCUPANCIES WITH HIGH CEILING CLEARANCES

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION CHECKLIST HIGH PILED STORAGE

Today's Topics & Sustainability Themes

COSTCO, SAN FRANCISCO A PRESCRIPTIVE AND PERFORMANCE BASED ANALYSIS OF FIRE PROTECTION SYSTEMS AND DESIGN

CITY OF GREATER SUDBURY (CGS) ARENA EVENTS FIRE REGULATIONS

RESEARCH TECHNICAL REPORT. SMART Sprinkler Protection for Highly Challenging Fires - Phase 2: Full-Scale Fire Tests in Rack Storage

esfr dry pendent sprinkler Vk501 (k14.0)

Modeling a real backdraft incident fire

High Ceiling Protection

Obstructions and ESFR Sprinklers Phase 2 FINAL REPORT

The Effect of Large Orifice Sprinklers on High-Challenge Fires

Box-in-Box Cold Storage Fire Protection Options

Report on First Revisions with Statement June 2014 NFPA 101

Wilson County Emergency Management Agency 110 Oak Street Lebanon, Tennessee 37087

STANDARD/QUICK RESPONSE ECOH ELO FUSIBLE ELEMENT PENDENT SPRINKLER VK537 (K11.2) TECHNICAL DATA

Models BB, SD, HIP, and AP Specific Application Sprinklers For Protecting Attics General Description

California Fire Code (CFC) Part III contains requirements. Building and Equipment Design Features PART. Chapters 5 through 19

standard response elo upright and pendent sprinklers (storage-density/area)

Sprinkler Identification Numbers

GUIDELINES FOR INSPECTING GROUND BASED SPARKLING DEVICE (GBSD) RETAIL SALES FACILITIES

NFPA 1124 (2006 Edition) Compliance List. Permanent Store

Based on NFPA 1003: Standard for Airport Fire Fighter Professional Qualifications 2015 Edition

Sprinkler Solutions for Storage Applications

NFPA 1124 (2006 Edition) Compliance List. Permanent Facility

Standard Spray concealed horizontal sidewall sprinkler VK481

RAPID RESPONSE Series LFII Residential Sprinklers 4.2 K-factor Flush Pendent Wet Pipe and Dry Pipe Systems General Description

TECHNICAL DATA MODEL V-HIP SPECIFIC APPLICATION ATTIC SPRINKLER VK660

MODEL V-BB SPECIFIC APPLICATION TECHNICAL DATA

CHAPTER 56 EXPLOSIVES AND FIREWORKS SECTION FIREWORKS 1.4G RETAIL STORAGE, DISPLAY, AND SALE

Performance Metrics for First Responder Locating/Tracking Technologies

Models BB, SD, HIP, and AP Specific Application Sprinklers for Protecting Attics General Description

Protection of Rack Stored Exposed Expanded Group A Plastics with ESFR Sprinklers and Vertical Barriers

Model ESFR-17 Dry Type Pendent Sprinklers Early Suppression Fast Response 16.8 K-factor General Description

RESIDENTIAL SPRINKLER INSTALLATION GUIDE

Enclosure 4- RISK ASSESSMENT

First Revision No. 632-NFPA [ Global Input ] Supplemental Information. Submitter Information Verification. Committee Statement

2017 Annual Fire Safety Report

Cumru Township Fire Department 4/27/10 Standard Operating Guidelines Page: 1 of 6 Section 15.07

RAPID RESPONSE Series LFII Residential Sprinklers 4.2 K-factor Flush Horizontal Sidewall Wet Pipe Systems

Family Foster Home Fire Safety Evaluation Checklist Instructions

FIRE PROTECTION & PREVENTION

a) Establishment of emergency procedures to be followed at the time of an emergency;

2009 International Residential Code Draft of New Fire Sprinkler Related Requirements

EASTERN ARIZONA COLLEGE Fire Department Operations II

FEMA Recommendations for Protection of Curtained Limited Finishing Workstations using UL 1254 Listed Pre engineered Dry Chemical Systems

EC/QREC ORDINARY HAZARD UPRIGHT SPRINKLER VK570 (K14.0) TECHNICAL DATA

standard response Fusible Link Upright sprinkler VK204 (K8.0)

FIRE PREVENTION 29 CFR Ursinus College, Collegeville, PA

Agency for Health Care Administration

SENJU SPRINKLER CO.,LTD. Residential Flush Pendent Sprinkler Model ZN-RES,K=4.2 (SIN / SS4421) (PTFE gasketed orifice seal design) General Description

Residential Flush Horizontal Side-Wall Sprinkler Model HF-RES,K=4.2 (SIN / SS4423) (PTFE gasketed orifice seal design)

Quick response concealed horizontal sidewall sprinkler VK481

TECHNICAL DATA. Refer to Approval Chart 1 and UL Design Criteria for culus Listing requirements that must be followed.

Model ESFR-25 Early Suppression, Fast Response Pendent Sprinklers 25.2 K-factor General Description

Moving Target: A Case Study in Providing Fire Protection Below a Reconfigurable Concert Hall Seating System. Part 1: Concept Design

Model MBEC-14. Extended Coverage Ordinary & Extra Hazard Horizontal Sidewall Sprinklers for Metal Building Applications. Model MBEC-14 (SIN R6932)

Fire Prevention Coffee Break Training. May 2017

standard/quick response extended coverage light and ordinary hazard elo sprinklers

First Aspen Federal Regulation Set: K LSC 2000 Health Existing

Transcription:

SUMMARY NFPA FIRE INVESTIGATION REPORT BULK RETAIL STORE FIRE TEMPE, ARIZONA MARCH 19, 1998 SCHULTE & ASSOCIATES Building Code Consultants 880D Forest Avenue Evanston, IL 600 fpeschulte@aol.com 504/0-7475 1. Building Description. One story, reinforced masonry structure measuring 400 ft by 50 ft and ranged from 4 ft to 9 ft high. This resulted in an area of 100,000 ft. The roof was supported by lightweight, parallel chord, wood trusses measuring 4 feet deep........ The roof assembly consisted of 4 ft x 8 ft panels constructed of ½ inch. plywood resting on in. x 6 in. wooden supports. The building was constructed in 1988. (Pages 1 and, NFPA Fire Investigation Report). Sprinkler System Design. The building was equipped with three ceiling level, wet sprinkler systems. The systems were designed to provided water at a density of 0.495 gpm/ft over,000 ft and were designed to protect a Class IV commodity for a maximum storage height of 0 ft. The maximum number of sprinkler that it was designed for was 9 sprinklers operating simultaneously. The upright sprinklers were equipped with 86F fusible elements and with 17/3 in. diameter [large orifice] orifices. (Page, NFPA Fire Investigation Report) Schulte & Associates 1 October 9, 006

3. Fire Location. Investigators from the Tempe Fire Department determined that the area of origin was in a rack that contained lawn furniture seat cushions. The cause was determined to be incendiary and was started by someone using a point-and-click type of lighter to ignite the seat cushions. 4. According to eyewitness testimony, when the fire was first observed it was located approximately chest hieght on one side of a 1 ft high double-row rack. (Page 1, NFPA Fire Investigation Report) 5. Smoke Conditions On Arrival of the Fire Department. Upon arrival, they (Phoenix Fire Department) made entry in through the northeast door, advancing a handline. They reported that smoke had fillled the building from floor to ceiling and that visibility was zero. (Page 1, NFPA Fire Investigation) 6. Roof Vents. A ladder company was assigned to ventilate the roof. When they reached the area over the fire, they reported that one skylight had burned through and that three automatic roof vents had opened. They proceeded to open approximately 4 more, either by popping them open with an axe or sawing through the fiberglass panels. (Page, NFPA Fire Investigation Report) 7. Sprinkler Operation/Fire Damage. 66 [large orifice] sprinklers were activated over an area of 5,08 ft. Fire damage from flame impingement was limited to 1,500 ft. The fire destroyed product in the rack of origin for a length of 3 ft and for the full height of the rack. It also spread to the other side of the double-row rack, destroying product over a length of 3 ft and for the full height of the rack. Schulte & Associates October 9, 006

The fire spread across a 10 ft aisle and ignited the commodity being stored on the shelves in that rack. This commodity was comprised of barbecue gas grill products wrapped in plastic or cardboard material. (Page, NFPA Fire Investigation Report) 8. Roof Vents/Draft Curtains. A series of draft curtains were loated throughout the building. They were constructed of sheet metal and measured 78 inches [6 feet, 6 inches] in depth. One draft curtain was located directly over the aisle where the fire occurred. There were a total of 93 skylights and 9 automtic, thermal activated roof vents, each measuring 4 ft x 8 ft. The roof vents were o equipped with 165 F fusible links. (Page 3, NFPA Fire Investigation Report) 9. Significant Factors. Based on the NFPA s investigation and a- nalysis of this fire, the following significant factors were considered as having contributed to the loss of property in this incident: a. Commodity Classification/Sprinkler Hydraulic Design Criteria. At the time the building had been constructed, the sprinkler system was designed for Class IV commodities. However, at the time of the fire, the commodity in the area of origin was predominantly Group A expanded and unexpanded plastics. This commodity would have required a greater ceiling sprinkler density. b. Flue Spaces. Inadequate transverse flue spaces within the racks. c. Draft Curtains. Due to the activation profile of the sprinklers, it would appear that the draft curtains effected [affected] which sprinklers opened. Schulte & Associates 3 October 9, 006

d. Fusible Links [Temperature} on the Ceiling Vents. Since the temperature rating on the ceiling vent links was below those of the sprinkler system, the links could possibly have fused prior to sprinkler activation. If the ceiling vents then opened, they would have allowed for the release of heat that could have impacted upon the sprinkler activation profile. e. Obstructed Sprinkler Spray Pattern. The foil on the ceiling insulation became dislodged in may areas during the fire and obstructed the spray patterns on the sprinklers. In one case, the foil was draped completely over a sprinkler. (Page 4, NFPA Fire Investigation Report) 10. Fire Loss Estimate.......the fire was fueled by conventional fuel loads, and overwhelmed the inadequately designed sprinkler system, destroying 96 linear ft of racks and product, and causing six million dollar in damage. (Page, NFPA Fire Investigation Report) 11. Applicable Building Code. At the time of construction, [the City of] Tempe was enforcing the 1985 edition of the Uniform Building Code. (Page 11, NFPA Fire Investigation Report) 1. Roof Vents. There were 9 automatic ceiling vents located o throughout the store. These vents were equipped with 165 F fusi- ble links. During the course of the investigation it was noticed that a number of the roof vents had caulking applied along the edges of the exterior of the translucent panel to create a weather-tight seal. In addition to the ceiling vents the roof had 93 skylights. These skylights were similar in design to the ceiling vents, but were not designed to open. They measured 4 ft x 8 ft and were comprised of translucent material. Schulte & Associates 4 October 9, 006

(Page 15 and 16, NFPA Fire Investigation Report) 13. Draft Curtain Construction. This facility was equipped with draft curtains. The ceilign curtains were spaced 96 ft x 80 ft, creating cells 7,680 ft. The draft curtains were constructed of 6 guage galvanized sheet metal and had a depth of 78 in. This resulted in 3 a total volume of 49,90 ft. One draft curtain was located directly over the aisle where the of origin was located. (Page 18, NFPA Fire Investigation Report)??????? Check 14. Sprinkler Spacing. The ceiling sprinkler spacing was 8 ft x 9ft-7in, resulting in an are of coverage of 77 ft per sprinkler. (Page 19, NFPA Fire Investigation Report) 15. Heat Vent Performance. A skylight directly over the fire had burned out and three heat vents had automatically opened upon fire department arrival. An additional 4 vents and skylights were either manually opened or cut open by the fire department during fire-fighting operations. Fire department personnel reported that a number of ceiling heat vents thermal elements had fused, but these vents did not open. The heat vents that had not properly operated were forcibly opened by fire fighters. (Page 35, NFPA Fire Investigation Report) 16. Draft Curtain Performance. A draft curtain was located directly over the aisle of origin. The rack of origin was located approximately 5 ft to the north of this curtain. A total of 66 ceiling level sprinklers activated in this fire, 5 of which were located to the north of the draft curtain. The fire leapt the aisle, traveling under the draft curtain, and ignited the rack to the south of the draft curtain on fire. Another 1 ceiling-level sprinklers and one column sprinkler activated on the south side of the draft curtain over this second rack. (Page 37, NFPA Fire Investigation Report) Schulte & Associates 5 October 9, 006

17. Sprinkler/Vent/Draft Curtain Interaction. The precise role that the draft curtains and ceiling vents had on the operation of the sprinkler system is unknown. However, the sprinkler protection requirements called for in NFPA documents are not based on the presence of either of these features. (Page 41, NFPA Fire Investigation Report) 18. Draft Curtain Effects. Due to the activation profile of the sprinklers, it would appear that the draft curtains had a role in the operation sequence of the sprinklers. The impact they had is a case for further study to determine the value of draft curtains in fire protection scheme. (Page 4, NFPA Fire Investigation Report) 19. Vent Fusible Link Temperature Rating. Since the [temperature rating of the] links on the vents were below those of the sprinkler system, they should have opened prior to sprinkler activation. In this case, it was report that a number of the links had fused, but the vents had not opened. This may have occurred because of the weather caulking that had been applied to the translucent panels. If the ceiling vents had opened, this would have allowed for the release of heat, impacting the activation profile of the sprinklers. There is some debate over the value of having roof vents operate automatically during a fire as opposed to having the fire department open the vents manually. (Page 4, NFPA Fire Investigation Report) * * * * * Schulte & Associates 6 October 9, 006