Perspectives of Aluminum As A Construction Material for Stationary Refrigeration and Air Conditioning Systems

Similar documents
Potential of Brazed Finned Tube Heat Exchangers in Compari- son to Mechanically Produced Finned Tube Heat Exchangers

Experimental Research On Gas Injection High Temperature Heat Pump With An Economizer

Study of R161 Refrigerant for Residential Airconditioning

Drop-in Testing of Next-Generation R134a Alternates in a Commercial Bottle Cooler/Freezer

Performance Comparisons Of A Unitary Split System Using Microchannel and Fin-Tube Outdoor Coils, Part I: Cooling Tests

Effects of Frost Formation on the External Heat Transfer Coefficient of a Counter-Crossflow Display Case Air Coil

Performance of R-22, R-407C and R-410A at Constant Cooling Capacity in a 10

Lower GWP Refrigerants Compared to R404A for Economizer Style Compressors

The Design Of A New Generation Of Twin Screw Refrigeration Compressors

Experimental Study About An Amount Of Oil Charge On Electric Driven Scroll Compressor For Electric Vehicle

Development and Performance Measurements of a Small Compressor for Transcritical CO2 Applications

Low GWP Refrigerants for Air Conditioning Applications

Development of a Transient Simulation Model of a Freezer Part II: Comparison of Experimental Data with Model

Performance Investigation of Refrigerant Vapor- Injection Technique for Residential Heat Pump Systems

Air-Cooled Heat Exchanger Performance for R410A

Experimental Study on Match for Indoor and Outdoor Heat Exchanger of Residential Airconditioner

Control Method Of Circulating Refrigerant Amount For Heat Pump System

Effects of Flash and Vapor Injection on the Air-to- Air Heat Pump System

Performance Evaluation and Design Optimization of Refrigerated Display Cabinets Through Fluid Dynamic Analysis

Performance Characteristics and Optimization of a Dual-Loop Cycle for a Domestic Refrigerator- Freezer

R-407A R-448A R-449A

A Performance-Enhancing Additive for Vapor- Compression Heat Pumps: Additional Test Results

Reference Document RD-0007-E GUIDELINES FOR THE UTILIZATION OF R-404A R-452A. Page 1 of Tecumseh Products Company LLC. All rights reserved.

An Experimental Investigation Of Oil Retention Characteristics In CO2 Air-Conditioning Systems

Experimental Study of Fouling Performance of Air Conditioning System with Microchannel Heat Exchanger

Conceptual Design of a Better Heat Pump Compressor for Northern Climates

EFFECT OF PAG OIL CIRCULATION RATE ON THE HEAT TRANSFER PERFORMANCE OF AIR-COOLED HEAT EXCHANGER IN CARBON DIOXIDE HEAT PUMP SYSTEM

STUDY ON THE CONTROL ALGORITHM OF THE HEAT PUMP SYSTEM FOR LOAD CHANGE

Visualization of Evaporatively Cooled Heat Exchanger Wetted Fin Area

Energy Savings Potential of Passive Chilled Beam System as a Retrofit Option for Commercial Buildings in Different Climates

A study of high efficiency CO2 refrigerant VRF air conditioning system adopting multi-stage compression cycle

Introduction of Transcritical Refrigeration Cycle Utilizing CO2 as Working Fluid

Tribology Characteristics of HFO and HC Refrigerants with Immiscible Oils - Effect of Refrigerant with Unsaturated Bond -

Experimental Investigation on Condensation Performance of Fin-and-Flat-Tube Heat Exchanger

Development of an Open Drive Scroll Compressor for Transportation Refrigeration

Experimental Study on Fractionation of R-407C and Recharge Operations

Some Modeling Improvements for Unitary Air Conditioners and Heat Pumps at Off-Design Conditions

Design of Divided Condensers for Desiccant Wheel-Assisted Separate Sensible and Latent Cooling AC Systems

Low Global Warming Refrigerants For Commercial Refrigeration Systems

Efficiency of Non-Azeotropic Refrigerant Cycle

Refrigeration Cycle And Compressor Performance For Various Low GWP Refrigerants

Heat Transfer of R-22 and Alternatives in a Plate- Type Evaporator

Responsible Care Product Stewardship for Refrigerants

Two-Phase Evaporation Pressure Drop Experimental Results for Low Refrigerant Mass Flux

Chapter 6. Do s & Don ts in Refrigeration & Air-Conditioning Servicing

R32 Compressor for Air conditioning and Refrigeration applications in China

Purdue e-pubs. Purdue University. T. Hamada Mitsubishi Heavy Industries Ltd. N. Nishiura Mitsubishi Heavy Industries Ltd.

Numerical Simulation of a New Cooling System for Commercial Aircrafts

Systematic Study of the Solution Properties of Low Global Warming Potential R-404A Replacement Refrigerant Blends with Various Polyol Ester Lubricants

HEFAT th International Conference on Heat Transfer, Fluid Mechanics and Thermodynamics Sun City, South Africa Paper number:pp1

Diagnosing Troubles in Refrigeration Units with Screw Compressors

Experimental Investigation on the Performance of Ground-source Heat Pump with the Refrigerant R410A

Modelling of an Integrated Supermarket Refrigeration and Heating System Using Natural Refrigerants

Quantification of Liquid Refrigerant Distribution in Parallel Flow Microchannel Heat Exchanger Using Infrared Thermography

Numerical Study on the Design of Microchannel Evaporators for Ejector Refrigeration Cycles

Real Time Upright Freezer Evaporator Performance Under Frosted Conditions

Selection of a refrigeration oil for the R32 refrigerant and evaluation of the compressor reliability

Investigation, Analysis and Solution of Higher Noise of Heat Pump Water Heater

Hunting Phenomena Of Automotive Air Conditioning Systems With Variable Displacement Compressor

Analysis of Oil Pumping in the Hermetic Reciprocating Compressor for Household Refrigerators

Improving Heating Performance of a MPS Heat Pump System With Consideration of Compressor Heating Effects in Heat Exchanger Design

An Investigation Into The Influence Of Improved Refrigeration Cycle And Refrigerants On An Energy Efficient Domestic Refrigerator

Purdue e-pubs. Purdue University

Compressor Capacity Control

Sub-Critical Operation of the CO2 Expander/ Compressor

Global Journal of Engineering Science and Research Management

Experimental Study on the Performance and Oil Return Characteristics of Multi-Split Air- Conditioning System for Medium Size Building

Comparison of the High Side vs

Performance Characteristics of Air-Conditioner Under Tropical Ambient Condition

Design and Research of the Digital VRV Multi- Connected Units With Three Pipes Type Heat Recovery System

Oil Return Measurements In A Unitary Split System Air Conditioner Using Different Refrigerant Mixtures

Application of two hybrid control methods of expansion valves and vapor injected compression to heat pumps

Experimental Investigation of a New High Temperature Heat Pump Using Water as Refrigerant for Industrial Heat Recovery

Development Of 2-Cylinder Rotary Compressor Series For Light Commercial Use With R410A

Study of R-161 refrigerant as an Alternate Refrigerant to various other refrigerants

Experimental Analysis of a Stirling Refrigerator Employing Jet-Impingement Heat Exchanger and Nanofluids

Enhancement of Round Tube and Flat Tube- Louver Fin Heat Exchanger Performance Using Deluge Water Cooling

CHAPTER 1 INTRODUCTION

Load Sharing Strategies in Multiple Compressor Refrigeration Systems

Development of HFC-134a Compressor for Domestic Refrigerator

Development of Large Refrigerant Compressors

Effect of Modification in Refrigerant Passage of an Automotive Air Conditioning Compressor

The Use Of Attic Space For Cooling and Dehumidification

Experimental Investigation of Purification Function of Air Conditioner

Evaluation The Effect Of Washing On The Heat Transfer Capacity And Air-Side Flow Resistance Of Air Cooled Condensers

Experimental Study on the Thermal Behavior of a Domestic Refrigeration Compressor during Transient Operation in a Small Capacity Cooling System

Experimental Research and CFD Simulation on Microchannel Evaporator Header to Improve Heat Exchanger Efficiency

Development of a Novel Structure Rotary Compressor for Separate Sensible and Latent Cooling Air-Conditioning System

System Using Exhaust Heat from Residential GHPs

Heat Transfer Characteristics and Heat Exchanger Performances for R407C Using Herringbone Heat Transfer Tube

Geothermal ORC Systems Using Large Screw Expanders

Comparison of Energy Efficiencies of Commercial Refrigeration Direct and Indirect Systems

The Effect of the Ventilation and the Control Mode on the Performance of a VRV System in Cooling and Heating Modes

Experimental Study on Performance Parameters for Refrigerants R22, R410a and R404a at Various Air Outlet Temperatures

MULTI-CHANNEL R134A TWO-PHASE FLOW MEASUREMENT TECHNIQUE FOR AUTOMOBILE AIR-CONDITIONING SYSTEM

Automated Optimization of Air Conditioning Systems using Geometry based Simulation Models

The Effects of Hydrophilicity on Water Drainage and Condensate Retention on Air-Conditioning Evaporators

CHAPTER I INTRODUCTION. In the modern life, electronic equipments have made their way

HVAC-R INDUSTRIAL EQUIPMENT AUTOMOTIVE AND COMERCIAL VEHICLES RAILWAY EQUIPMENT CONSTRUCTION AND MINING EQUIPMWENT AGRICULTURAL AND FORESTRY EQUIPMENT

High Efficiency R-134a Compressor for Domestic Refrigerator

Transcription:

Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2000 Perspectives of Aluminum As A Construction Material for Stationary Refrigeration and Air Conditioning Systems F. Flohr Solvay Fluor und Derivate GmbH C. Meurer Solvay Fluor und Derivate GmbH H. W. Swidersky Solvay Fluor und Derivate GmbH H. J. Belt Solvay Fluor und Derivate GmbH Follow this and additional works at: http://docs.lib.purdue.edu/iracc Flohr, F.; Meurer, C.; Swidersky, H. W.; and Belt, H. J., "Perspectives of Aluminum As A Construction Material for Stationary Refrigeration and Air Conditioning Systems" (2000). International Refrigeration and Air Conditioning Conference. Paper 518. http://docs.lib.purdue.edu/iracc/518 This document has been made available through Purdue e-pubs, a service of the Purdue University Libraries. Please contact epubs@purdue.edu for additional information. Complete proceedings may be acquired in print and on CD-ROM directly from the Ray W. Herrick Laboratories at https://engineering.purdue.edu/ Herrick/Events/orderlit.html

2000 International Refrigeration Conference at Purdue PERSPECTIVES OF ALUMINUM AS A CONSTRUCTION MATERIAL FOR STATIONARY REFRIGERATION AND AIR-CONDITIONING SYSTEMS ABSTRACT F. Flohr, C. Meurer, Dr. H.-W. Swidersky, Dr. H.-J. Belt Solvay Fluor und Derivate GmbH, Hannover, Germany Today Aluminium is more and more recognized as an attractive construction material for the refrigeration and air conditioning industry. The choice of joining techniques for Aluminium parts in refrigeration systems is receiving significant interest. Following up investigations of the influence of the Aluminium brazing processes on systems operating on R134a and PAG lubricant in a previous publication for this conference, analogous investigations were performed on a system operating on R407C and POE lubricant. ln the automotive industry the production of Aluminium brazed heat exchangers is already successfully established. Micro channel heat exchanger designs are discussed for stationary systems as well. In addition to the discussions about the system chemistry this paper will outline possible benefits of brazed heat exchangers when compared to mechanically expanded types. INTRODUCTION Since brazed Aluminium heat exchangers were successfully introduced in automotive air-conditioning systems, the interest of using them in stationary refrigeration and air-conditioning has grown. Compared to automotive applications where R134a I PAG lubricant is mostly used, mixtures of refrigerants and POE lubricants are used in stationary applications, especially for the substitution of R22. Investigations with R407C, a blend containing R32/R125/R134a and a POE lubricant, were performed to provide information on possible interactions between brazed flux residues and the refrigerant lubricant mixture within the refrigeration system. With these results it will also be possible to comment on its components R125 and R32, which have not been examined before and consequently also on R410A, a second promising R22 substitute which contains R12.S and R32. The refrigeranuoil mixture, which circulates through a refrigeration unit, is complex. The used POE oil shows hygroscopic behaviour. The flux residues remain on the surface of the brazed parts as a thin adherent non- corrosive layer. It cannot be excluded that these residues have contact to the circulating refrigerant oil mixture. This paper discusses possible interactions between the refrigerant-oil mixture and the flux residues. The test results relate to a procedure that was established to investigate interactions among R134a/PAG lubricants and 'Flux residues [1]. Commonly used heat exchangers for stationary air-conditioning applications are manufactured by mechanically expanding the tubes in order to achieve a firm contact with the fin collars. A metallurgical bond as achieved by brazing may reduce the heat transfer resistance when compared to the mechanical bond. To estimate the heat transfer benefit, a literature research about different theoretical calculation methods for the evaluation of thermal contact resistance between tube and fin-collar is included in this work. Comparative performance tests with mechanically expanded and brazed heat exchangers are planned for the future. TEST PROGRAM R407C I POE OIL AND FLUX RESIDUES The test program that is described in figure 1 was carried out to obtain knowledge on interactions of 'Flux residues in refrigeration and air conditioning systems operating with R 407C and POE lubricant. The program consists of four tests in which the operating conditions have gradually been debased, up to the point in which a much higher amount of moisture than normally accepted was in the system. Each test took about 500 h, except test 0, which was performed to generate a base line and to exclude any malfunctions of the test rig. 481 Purdue University, West Lafayette, IN, USA- July 25-28, 2000

Compatibility of Flux Residues in refrigeratio Systems operating with R-407C and POE Lubricant R-407CIPOE Aluminum Literature Research D Refrigerant Cycle TestO Filter Dryer (Wear in/baseline) H20 (low) HX R-407CIPOE Refrigerant Cycle HX Aluminum Test 1 No Filter Dryer (Worst Case baseline) H2o (medium) R-407CIPOE _ HX, Refrigerant Cycle Brazed Samples, Aluminum Test2 Powder No Filter Dryer (Worst Case) H20(medium) - ~-- R-407CIPOE Refrigerant Cycle HX, Brazed Samples, Test3 Aluminum Powder (Accelerated Worst NoFilterD()'er Case) H20 (high) Figure 1: Research Program: Compatibility of operating on R 407C and POE lubricant Flux in refrigerating systems TEST APPARATUS The test rig that was used for the stability tests was already described in [1 1- For easier understanding, a schematic diagram is given in figure 2. Automotive Condenser Frequency Changer Figure 2: Evaporator Schematic diagram of the test apparatus Purdue University, West Lafayette, IN, USA- July 25-28,2000 482

For building the test apparatus, only selected materials were utilized. Apart from sealing material (mostly PTFE and paper sealing of the compressor) the complete test rig is made of stainless steel and aluminium for the evaporator and the condenser. It was essential to choose those components to minimise the amount of influencing parameters in order to be able to detect possible sources of problems. A test section consisting of filter elements and a sample vessel was located in the liquid line. The filter elements are made of wire mesh-and dry powdered-stainless steel and are used as an indicator of chemical reactions or corrosion effects. Before and after the sample vessel a combination of a 40 micron filter followed by three 15 micron filters in parallel and in direction of the flow was implemented. Before each test, a new set of filter elements was fitted into the test section to ensure equal conditions for each test. A frequency converter was added to the setup in order to adapt the rotational speed of the compressor to the volumetric capacity of R407C. SAMPLE PREPARATION Angle on Coupon Samples: For test 2 and 3, the surface of 45 aluminium coupons (see Figure 3) were coated with simulate joints as produced by continuos furnace processes, aluminium angels were nitrogen to these coupons. Angle on Coupon Flux. To brazed under Figure 3: Angle on Coupon Samples The following dimensions and materials were used for the samples: Coupon: Basic Material AA 3003 Brazing Material: Thickness. Angle: Coating: Brazing: Sizes 25 x 25 x 0.4 mm 10% AA 4343 (7.5% Si) 0.4 mm Sizes 40 x 5 x 0.5 mm, Angle 45, Material 99.5 AI 5 g I m 2 30 C I min. until 600 C, for 2 min. 40 of the 45 coupons were introduced in the sample vessel on different levels. The remaining five coupons were used as a reference after the tests. The preparation of the angles on coupon are described in detail in [2]. MECHANICALLY DETACHED RESIDUES: For the stability tests 2 and 3, Flux residues as generated by flame brazing processes were mechanically detached and also added into the sample vessel of the test section. The sample that was used to produce these residues was prepared as follows: 483 Purdue University, West Lafayette, IN, USA- July 25-28, 2000

Coupon Thickness: Aluminium-sheet: Brazing Material (clad): Coating: Brazing: The weight of" before test 3. Base Material 1.5 mm AA 3003 1 0% AA 4343 (7.5% Si) >10g/m 2 until the melting point of the filler metal was reached (577-591 oc) Flux-powder" given into the vessel was 0,5004g before test 2 and 0,5005g The excess flux residue was introduced to create a large surface area in direct contact with the refrigerant I lubricant mixture. Consequently, any potential interactions in the system would be maximised under these conditions. TEST PROCEDURES The tests were performed for a period of SOOh. The evaporating temperature was held at roughly ooc and the condensing temperature was set to approximately 55 C. The operating parameters were constantly tracked by a data acquisition. A total of 7 temperatures and 4 pressures were recorded to evaluate the system performance. The pressure drop over the test section was also measured. This is of particular importance, since the loose residues, that were incorporated into the test section, were expected to block the filters to a certain degree. The incorporated water amount in test 3 was 1, 7 g which corresponded to 400 ppm related to the combined weight of refrigerant and oil. The water was injected into the evacuated test rig before the charging ofthe installation. TEST CYCLES - RESULTS Lubricant analysis of test 2 and 3: Both oil-samples of test 2 and 3 showed no significant impurities. Both samples are in good condition and comparable with fresh oil quality. The water contents from the lubricant analysis reflect the means that were taken to increase the humidity in the system. Table 1: Oil-analysis DEA RENISO TRITON SE 55 by FUCHS PETROLUB AG: 0,01 ppm <50 128 217 ppm Not detectable Not detectable Not detectable Weight analysis of the angle on coupon samples of Test 2 and 3: Table 2: Weight analysis of angle on coupon samples of Test 2 and Test 3 38,252366-0,0079 : :Diffe.:.:.:.re.:.:.:.nce:=c(g"":.] ~o.j 02 i :'1---------l 0,1S g ot 0,1 ~ The measured weight differences of the coupons are close to the precision tolerance of the scale(± 0,0001g) Weight deviations between test 2 and virgin Figure 4: Frequency distribution Test 3 conditions are within the inaccuracy of the scale and therefore insignificant. A slight weight loss between virgin conditions and test 3 was detected which could have been caused by abrasion effects. 484 Pnrdue University, West Lafayette, IN, USA- July 25-28,2000

Refrigerant analysis GC analysis of the refrigerant was performed after each test. Due to the zeotropic nature of R407C the composition of the three components varied among the analysis. None of the tests however showed any proof of additional substances that would indicate decomposition of the refrigerant. Optical analysis Optical analysis were made on the surfaces of the tube elements, the compressor's valve plate, the coupons and the filter elements. The results were documented with photos. Neither on the surface of the coupons nor on the tubes' surfaces or on the compressor's valve plate any kind of corrosion effects were visible. Figure 5 shows the condition of a stainless wire mesh filter element before and after test 3. The residues which are visible after test 3 consist of loose Flux powder which was incorporated into the sample vessel prior to the test. a) Figure 5: 1000-fold increase shot of a stainless-wire-mesh filter element a) before test 3 b) after test 3 DISCUSSION OF RESULTS Neither the analysis of the refrigerant and the oil, nor the gravimetrical and optical analysis of the filter elements, the "angle on coupons" and the tubes or the compressor gave reason to assume any interactions between Flux the refrigerant and the oil. It can be excluded that the presence of flux residues accelerates any corrosive effects. The amount of flux residues present in the system by far exceeds the amount that would be found in practice. The water content, especially in the last test significantly exceeds practical values. All parameters of the system chemistry remained stable. The analysis of the neutralisation number by the oil's manufacturer showed that the oil is in good condition comparable with fresh oil quality. BRAZED HEAT EXCHANGERS FOR STATIONARY REFRIGERATION SYSTEMS Mechanically expanded finned tube heat exchangers are the most prominent choice for the air-side heat exchange of stationary refrigeration and air-conditioning systems. Copper and aluminium for the tube and fin respectively are the materials of choice. The fins have bear collars which serve to fix the fin on the tube through mechanical or hydraulical expansion of the tube. Two surfaces in contact create an imperfect interface that impedes heat transfer between the two surfaces (figure 6). The impedance is known as the contact resistance. A simplified description of the heat transfer through a finned tube heat exchanger is shown in figure 7. Five sectors can be assigned to the temperature curve. Sector I describes the heat transfer from the fluid 1 to the inner tube surface, sector II the heat conductance through the tube wall, sector Ill the heat transfer between outer tube wall and fin collar, sector IV the heat conductance through the fin and sector V the heat transfer from the fin surface to the air. Purdue University, West Lafayette, IN, USA- July 25-28, 2000 485

Figure 6: Heat transfer through two surfaces in contact Section Ill that describes the contact resistance between tube wall and collar can take up to 12% of total heat resistance. l3). Radius r Figure 7: Temperature curve through a finned tube profile LITERATURE RESEARCH Some papers are published on the estimation of the contact resistance between tube and fin-collar. The first important investigation was done by Dart [4], who connected two tubes with fins and measured the temperature difference between both tubes. The difference served as an index for the quality of heat conductance. Eckels [5] continued the method of Dart and developed an equation that evaluates the contact resistance as a function of the interface pressure between. fin-collar and tube wall and the contact conductance. Sheffield [6] developed a semi theoretical calculation model which took geometric and material specific data into account. Critoph [3] created a test rig for measurements of industrial manufactured finned tube heat exchangers in comparison to brazed micro channel heat exchangers. According to the result, the contact resistance accounted for up to 12% of the total heat resistance on the air side. For brazed heat exchangers contact resistance between fins and tubes is virtually eliminated. The results from Critoph give practical evidence of increased efficiency, when brazed heat exchangers are used instead of mechanically assembled units. For automotive applications fu\ly brazed aluminium heat exchangers are the state of the art. In addition to the increased heat transfer behaviour, fully brazed aluminium heat exchangers show a number of other benefits like low material costs, low weight, good resistance against atmospheric influences and of course the easier way of recycling. Purdue University, West Lafayette, IN, USA- July 25-28,2000 486

For the practical and straight forward comparison of different heat exchanger designs SOLVAY built a two channel test-rig (figure 8) which allows direct comparison of differently designed and produced heat exchangers. First results of the investigations are expected in the second half of the year 2000. CONCLUSION Most materials have an influence on the stability of the couple refrigerant/lubricant. The test apparatus, described above, was created with a limited amount of materials. It can be excluded that the chosen materials have a negative effect on the stability of the couple refrigerant/lubricant. The test approach developed during the stability tests for R 134a/PAG-Iubricant, offers the possibility, by successive debasing of the operation conditions, to identify at what level of contamination a safe operation in the long term cannot be guaranteed and to retrace whence the problem is caused. The following conclusion was obtained: The presence of brazing flux residues has no negative influence on the apparent running conditions and the stability of a refrigeration system operating on R 407C and POE lubricant, even under worst conditions such as the absence of a filter dryer, and with an artificially high moisture content. Even under worst case conditions, there is no evidence that flux residue accelerates, contributes to or catalyses the decomposition of the lubricant, refrigerant components or damage any other component of this system. Fully brazed aluminium heat exchangers are already established in automotive air-conditioning systems. Theoretical investigations promise a heat transfer benefit of up to 12%, when fully brazed heat exchangers are used instead of conventionally manufactured ones. Other benefits for stationary refrigeration and air-conditioning systems which follow from the use of aluminium heat exchanger are lower material costs and weight, better resistance against environmental influences, and minimised recycling problems. OUTLOOK For the practical evaluation of the heat transfer benefit, SOLVAY will perform a series of tests. Therefore a test rig was built which allows to compare heat exchangers of different designs under same conditions (figure 8). First results are expected in the second half of the year 2000. Wind Channel Heat Exchanger (brazed) Figure 8 Res1stance Thermometer ~' Heat Exchanger (ndt brazed) Kryomat Test rig for the direct comparison of different heat exchangers Purdue University, West Lafayette, IN, USA- July 25-28,2000 487

ACKNOWLEDGEMENTS The authors would like to thank Martin Schwiegel, for his work on his diploma thesis and for performing the R407C I POE stability tests. Furthermore we would like to acknowledge FUCHS I DEA MINERALOELWERKE for their support with the analysis of the lubricant. REFERENCES: 1. Meurer,C.; Lauzon, D.; Koenig H.: Influence of Residues from Aluminum Brazing Processes on Refrigerant Systems Involving R134a and PAG Lubricants, Purdue Refrigeration and Compressor Engineering Conference '98 2. Meurer, C.; Lauzon, D. C.; Koenig, H.: Stability of R-134a in the Presence of Nocolok Fiux Residues; SAE 980052; SAE International Congress and Exposition, Detroit, 1998 3. Critoph, R.E., Holland, M. K.; Turner, L.: Contact Resistance in air-cooled Plate Fin-Tube air-conditioning Condensers, Int. J. Refrig., Vol. 19, 1996, No.6, Page 400-406 4. Dart, D. M.: Effect on Fin Bond on Heat Transfer, ASHRAE Journal, May 1959, Page 67-71 5. Eckels, P. W.: Contact Conductance of mechanically expanded Plate Finned Tube Heat Exchangers, ASME Paper No. 77-HAT-24, 1977 6. Sheffield, J.W.; Sauer, Jr., H.J.; Wood, R.A: Thermal Contact Conductance of Finned Tubes: A generalized Correlation Purdue University, West Lafayette, IN, USA- July 25-28, 2000 488