HVAC/R Refrigerant Cycle Basics

Similar documents
AIR CONDITIONING. Carrier Corporation 2002 Cat. No

HEAT PUMPS. Carrier Corporation GT72-01 Cat. No

HVAC Basics RESIDENTIAL AIR CONDITIONING

Energy Use in Refrigeration Systems

THERMODYNAMICS PREPARED BY DW & JD

PRESSURE-ENTHALPY CHARTS AND THEIR USE By: Dr. Ralph C. Downing E.I. du Pont de Nemours & Co., Inc. Freon Products Division

Refrigeration Systems and Accessories

B. A. T. Basic Appliance Training

Otherwise, you can continue reading the file on the following pages.

Technical Training Associates Presents. Commercial Refrigeration Equipment Servicing Part 1

Section 1: Theory of Heat Unit 3: Refrigeration and Refrigerants

The Saturation process

Changes of phase usually involve a transfer of energy Evaporation

Use this Construction/HVAC Glossary to answer the questions below.

Instructors: Contact information. Don Reynolds Doug McGee Factory Tech Support

Before I start on this one At HVAC School we focus on a wide range of topics, many of them are very basic. My experience as a trainer for over 16

SECTION 2 SAFETY, TOOLS AND EQUIPMENT, SHOP PRACTICES UNIT 10 SYSTEM CHARGING

THERMOSTATIC EXPANSION VALVES Part 1

Heat Reclaim. Benefits,Methods, & Troubleshooting By Dave Demma, Manager Supermarket Sales, Sporlan Division - Parker Hannifin Corporation

What Is Liquid Subcooling?

To accomplish this, the refrigerant fi tis pumped throughh aclosed looped pipe system.

Thomas J Kelly. Fundamentals of Refrigeration. Sr. Engineering Instructor Carrier Corporation. August 20, Page number: 1.

SECTION 8 AIR SOURCE HEAT PUMPS UNIT 43 AIR SOURCE HEAT PUMPS

CONTENTS. Air Conditioning Fundamentals TC S

Negative Superheat? Time to Check Your Tools

PowerPoint Presentation by: Associated Technical Authors. Publisher The Goodheart-Willcox Company, Inc. Tinley Park, Illinois

Refrigeration Basics from a Brewery Perspective

HVAC Fundamentals & Refrigeration Cycle

RTP Technical Bulletin

Refrigerant Transfer and Compressor Damage

Checking the Charge on a Heat Pump in the Winter

HEAT PUMPS. Carrier Corporation GT72-01A Cat. No

For an administrative fee of $9.97, you can get an un-locked, printable version of this book.

Refrigeration System Overview. ASTI 32 Hour Managing Ammonia Course September 27 30, 2016

The Refrigeration Cycle

REFRIGERATION CYCLE Principles of Mechanical Refrigeration Level 2: Cycle Analysis

It pays to go green with solakool

The Refrigeration Cycle

HVAC-201. Syllabus. Prerequisites: HVAC-101and R-410a Safety Course (The R-410a Safety course may be completed while enrolled in HVAC201)

Refrigeration Manual. Part 1 - Fundamentals of Refrigeration

SERVICE ASSISTANT OVERVIEW FDSI Online Training

The Essentials Of Working With R-410A

Service Step by Step Trouble-Shooting Check-List

Pressure Enthalpy Charts

Chapter-8 Capacity Control of Refrigeration Systems

CHAPTER 3 BASIC STEAM CYCLE

Table of Contents. Service Procedures. Service Procedures. Measuring Superheat (4) Measuring Subcooling (5) Airflow Calculation (6-8)

A Series Inertia Compressor Applications. Application Bulletin 115

Math. The latent heat of fusion for water is 144 BTU s Per Lb. The latent heat of vaporization for water is 970 Btu s per Lb.

ASE 7 - HVAC. Module 2 AC Compressors

Campbell Soup Company Extends Use of CO2 Systems Into Their Operations

EXPANSION VALVES. See Red Dot Catalog Also. * 2 ton valves - all other valves are 1 1/2 ton (1) Includes M1 Adapter 71R8050 EX02280

How to Diagnose a TXV Failurek

LIQUID REFRIGERANT CONTROL IN REFRIGERATION AND AIR CONDITIONING SYSTEMS

A Treatise on Liquid Subcooling

Superheat charging curves for technicians

RSES Technical Institute Training Manual 1 70 hours, 70 NATE CEHs, 7.2 CEUs

6. Within an internal combustion engine, the can-shaped component that moves up and down the cylinder

14. The center port of the manifold is used for evacuation, charging and refrigerant recovery.

SECTION 5 COMMERCIAL REFRIGERATION UNIT 21 EVAPORATORS AND THE REFRIGERATION SYSTEM UNIT OBJECTIVES 3/22/2012 REFRIGERATION

Sporlan Valve Division Parker Hannifan/CIC Group

LESSON CLUSTER 9 Explaining Condensation and the Water Cycle

Some of these procedures need to be performed to conform to requirements of the Clean Air Act.

Class 1: Basic Refrigera0on Cycle. October 7 & 9, 2014

Case 15 Refrigeration System for Chemical Fertilizer Plant Ammonia Storage

June 2001 / BULLETIN Way Valves. The right solenoid valve for any job.

MECHANICAL ENGINEERING ME.2017 FUNDAMENTAL OF REFRIGERATION AND AIR CONDITIONING. Sample Questions and Answers

TWO- AND THREE-STAGE CASCADE REFRIGERATION SYSTEM By: Paul B. Reed

KE2 EvaporatorEfficiency Theory of Operation

APPLICATION DATA SHEET

DAVE DEMMA ACHIEVING HEAD PRESSURE CONTROL

Reference Document RD-0007-E GUIDELINES FOR THE UTILIZATION OF R-404A R-452A. Page 1 of Tecumseh Products Company LLC. All rights reserved.

How Ground Source Heat Pumps Work

MECHANICAL SCIENCE Module 2 Heat Exchangers

a. CFCs. b. HCFCs. c. Pressurized nitrogen. d. Compressed dry air. 17. The state of the refrigerant leaving the condenser of a refrigeration system

UNITED STATES MARINE CORPS ENGINEER EQUIPMENT INSTRUCTION COMPANY MARINE CORPS DETACHMENT 686 MINNESOTA AVE FORT LEONARD WOOD, MISSOURI

RS-70 is suitable as a direct replacement for R-22 in low, medium and high temperatures in a great number of applications:

Air Conditioning Clinic. Refrigerant Piping One of the Fundamental Series TRG-TRC006-EN

USING THE P-T CARD AS A SERVICE TOOL

CO2 TRANSCRITICAL BOOSTER SYSTEMS

Activity Sheet Chapter 1, Lesson 1 Molecules Matter

LESSON CLUSTER 8 Explaining Evaporation and Boiling

Thermal Energy. Conduction, Convection, and Radiation. Before You Read. Read to Learn. Conduction. section 2

Executive Summary. Number of Low Number of High Number of Faults , Number of OK

1. What are the scales of temperature? What are the formulas to convert among them? Fahrenheit, Celsius, Kelvin

The Book of AERMEC NRL Sequence of Operation

Residential Piping and Long Line Guideline

Refrigeration System with a Capillary Tube and a Thermostat

Publication # RD-0003-E Rev 1, 10/17 SERVICE GUIDELINES HCFC R22 TO HFC REFRIGERANT BLENDS

Thermal Energy On a sunny day you can feel

H29A Series Compressor Applications. Application Bulletin 139

Application Engineering

Air Conditioning Components

IGCSE PHYSICS GRADE 11 TERM 1 ASSESSMENT BOOKLET

RDT Refrigeration Book

Suction Accumulators. Introduction. Suction Accumulators

Table of Contents. Table of Contents Introduction... Intro-1

SECTION 7 AIR CONDITIONING (COOLING) UNIT 41 TROUBLESHOOTING

Efficient Steam System Design

Thermal Energy Study Guide

Transcription:

HVAC/R Refrigerant Cycle Basics This is a basic overview of the refrigeration circuit and how it works. It isn t a COMPLETE description by any means, but it is designed to assist a new technician or HVAC/R apprentice in understanding the fundamentals. First, let s address some areas of possible confusion 1. The Word Condenser Can Mean two Different Things Many in the industry will refer to the outside unit on a split air conditioner, heat pump or refrigeration unit as a condenser even though it will often contain the

condenser, compressor, and other parts. It s better to call the outside component the condensing unit or simply the outside unit to reduce confusion. 2. Cold and Hot are Relative terms Cold and Hot are both an experience, a description, a comparison or an emotion. Cold is a way to describe the absence of heat in the same way that dark describes the absence of light. We will often use the words cold and hot to compare two things Today is colder than yesterday or to communicate comfort It feels hot in here. These are useful communication tools, but they are comparisons not measurements. 3. Heat and Absolute Zero Can be Measured We can measure heat in BTUs and light in lumens, we cannot measure cold or dark. Absolute cold is the absence of all heat. -460 F(-273.3 C) (cold) is known as absolute zero, -460 F(-273.3 C) is the temperature at which all molecular movement stops. Any temperature above that has a measurable level of heat. While this is a known point at which all molecular movement stops, it has not (and likely cannot) be achieved. 4. Boiling Isn t Always Hot When we say it s boiling outside we mean it s hot outside. This is because when we think of boiling we immediately think of water boiling in a pot at 212 F (100 C) at atmospheric pressure, which is 14.7 PSI (Pounds Per Square Inch)(1.01 bar) at sea level. Boiling is actually just a change of state from liquid to vapor, and the temperature that occurs varies greatly based on the substance being boiled and the pressure around the substance. In an air conditioner or a refrigeration system, refrigerant is designed to boil at a low temperature that corresponds to the design of the system. On an average air conditioning system running under normal conditions with a 75 (23.88 C) indoor temperature, the evaporator coil will contain refrigerant boiling at around 40 F(4.44 C). In air

conditioning and refrigeration when we refer to boiling, flashing or evaporating of refrigerant we are talking about the process of absorbing heat, otherwise known as cooling. 5. Cooling and Heating Cannot be Created We are not in the business of making heat or creating cool; it cannot be done. We simply move heat from one place to another or change it from one form to another. When we cool a room with an air conditioner, we are simply absorbing heat from the air into an evaporator and then moving that heat outside to the condenser where it is rejected or moved to the outdoors. 6. Heat and Temperature Aren t the Same Imagine a shot glass of water boiling away at 212 F(100 C). Now imagine an entire lake sitting at 50 F(10 C). Which has a higher (hotter) temperature? That answer is obvious-i just told you the shot glass had 212 F(100 C water in it so it is CLEARLY hotter. But, which contains more heat? The answer is the lake. You see, heat is simply energy and energy at its basic form is movement. When we measure heat we are measuring molecular movement; the movement of molecules atoms stuck together to make water or oxygen or nitrogen. When molecules move FASTER they have a HIGHER temperature and when they move SLOWER they have a LOWER temperature. Temperature is the average speed (velocity) of molecules in a substance, while heat is the total amount of molecular movement in a substance. The lake has more heat because the lake has more water (molecules). 7. Compressing Something Makes it Get Hotter (Rise in Temperature) When you take something and put pressure on it, it will begin to get hotter. As you pack those molecules that make up whatever you are compressing, they get closer together and they start moving faster. If you drop the pressure the molecules will have more space and will move slower causing the temperature to go down.

8. Changing the State of Matter Moves Heat Without Changing Temperature When you boil pure water at atmospheric pressure it will always boil at 212 F(100 C). You can add more heat by turning up the burner, but as long as it is changing state (boiling), it will stay at 212 F(100 C). The energy is changing the water from liquid (water) to vapor (steam) and the temperature remains the same. This pressure and temperature at which a substance changes state instead of changing temperature is called its boiling point, condensing temperature or more generally saturation point. 9. Superheat, Subcool, Boiling, and Saturation Aren t Complicated If water is boiling at sea level it will be 212 F(100 C). If water is 211 F(99.44 C) at sea level we know it is fully liquid and it is 1 F(-17.22 C) subcooled. If water is 213 F(100.55 C) at sea level we know it is vapor and superheated. If something is fully liquid it will be subcooled, if it is fully vapor it will superheated, and if it is in the process of change (boiling or condensing) it is at saturation. Where to start Take a look at the diagram at the top of this piece and start at the bottom left. Are you looking at the part at the bottom left? OK, now read this next line OUT LOUD: Compressor > Discharge line > Condenser > Liquid Line > Metering Device > Expansion Line > Evaporator > Suction line and then back to the Compressor When I first started in HVAC/R trade school this was the first thing my instructor forced me to LITERALLY memorize forward and backwards before he would allow me to proceed. While I am not always a huge fan of rote memorization as a learning technique, in this case, I agree with committing this to memory in the proper order.

These four refrigerant components and four lines listed above make up the basic circuit that every compression refrigeration system follows. Many more parts and controls may be added, but these basics are the cornerstone on which everything else you will learn is based. Once you have these memorized we can move on to describing each. Compressor The compressor is the heart of the refrigerant circuit. It is the only mechanical component in a basic refrigeration system. The compressor is like the heart that pumps the blood in the body or like the sun that provides the earth its energy. Without the compressor to move the refrigerant through compression, no work would be done and no heat would be moved. The compressor creates a pressure differential, resulting in high pressure on the high side (discharge line, condenser &

liquid line) and low pressure on the low side (suction line, evaporator and expansion line). There are many different types of compressors, but you will most likely see Scroll and Reciprocating type compressors most often. A reciprocating type compressor uses pistons, valves, and a crankshaft. Reciprocating compressors operate much like car engines; pulling in suction vapor on the down-stroke and compressing that vapor on the up-stroke. A scroll compressor does not have any up-down motion like a reciprocating compressor. A scroll compressor uses an oscillating motion to compress the low-pressure vapor into high-pressure vapor. The compressor pressurizes low-pressure vapor into highpressure vapor, but it also causes the temperature of the gas to increase. As stated in the gas laws, an increase in pressure causes an increase in temperature and a decrease in volume. In the case of refrigerant cooled compressors, heat is also added to the refrigerant off of the kinetic (bearings, valves, pistons) and electrical (motor windings) mechanisms of the compressor. Compressors require lubrication; this is accomplished through oil that is in the compressor crankcase, as well as oil that is carried with the refrigerant. Liquid entering the compressor through the suction line is a very serious problem. It can cause liquid slugging, which is liquid refrigerant entering the compression portion of the compressor. Liquid slugging will most likely cause damage to the compressor instantly. Another problem is bearing washout or flooding. This occurs when liquid refrigerant dilutes the oil in the compressor crankcase and creates foaming, and it will greatly reduce the life of the compressor because it will not receive proper lubrication and too much oil will be carried out of the compressor and into other parts of the system. The compressor also (generally) relies on the cool suction gas from the evaporator to cool the compressor properly, so it s a delicate balance to keep a compressor from being flooded and also keep it cool.

Condenser Condensers come in all different types, shapes, and sizes. Regardless, they all perform the same function: rejecting heat from the refrigerant. The refrigerant entering the condenser was just compressed by the compressor, and this process increased the temperature by packing the molecules together which added heat to the vapor refrigerant due to the motor and mechanical workings of the compressor. This process in the compressor also greatly increased the pressure from a lowpressure in the suction line entering the compressor, to a high-pressure vapor leaving the compressor. The condenser has three jobs: 1. 2. 3. Desuperheat the refrigerant (Drop the temperature down to the condensing temperature) Condense (saturate) the refrigerant (Reject heat until all the refrigerant turns to liquid) Subcool the refrigerant (Drop the temperature of the refrigerant below the condensing / saturation temperature) The condenser s job is to reject heat (drop the temperature) of the refrigerant to its condensing (saturation) temperature,

then to further reject heat until the refrigerant fully turns to liquid. The reason it must fully turn to liquid is that, in order for the refrigerant to boil in the evaporator, it must first have liquid to boil. The way in which the condenser removes the heat from the refrigerant varies. Most modern condensers flow air over the tubing where the refrigerant is flowing. The heat transfers out of the refrigerant and into the air. The cooling medium can also be water. In the case of a water source system, water is circulated across the refrigerant in a heat exchanger. In either case, the condenser relies on the removal of heat to another substance (air, water, glycol etc..). For instance, if you turned off the condenser fan so that no air was flowing over the condenser coil, the condenser would get hotter and hotter. This would cause the pressures to get higher and higher. If it kept going that way it would trip the internal overload on the compressor or cause other damage. The hot vapor from the compressor enters the condenser and the superheat (temperature above condensing temperature) is then removed. The refrigerant then begins to change state from vapor to liquid (Condense). The refrigerant maintains a constant temperature until every molecule of vapor is condensed. The temperature of the liquid again starts to fall. This is known as subcooling. When we measure subcooling we are measuring degrees of temperature rejected once the refrigerant has turned completely to liquid. Temperature above the saturation temperature is called superheat. Temperature below the saturation temperature is called subcool or subcooling. So when something is fully vapor (like the air around us) it will be superheated, and when it is fully liquid (like the water in a lake) it is subcooled.

Metering Device The metering device is a pressure differential device that creates a pressure drop to facilitate refrigerant boiling in

the evaporator coil. The metering device is located between the liquid line and the evaporator. The liquid line is full of high-pressure liquid refrigerant. When the high-pressure liquid hits the small restrictor in the metering device, the pressure is immediately reduced. This drops the pressure of the refrigerant to such a degree, that the saturation temperature is lower than the temperature of the air surrounding the tubing that the refrigerant is in. This causes the refrigerant to start changing from liquid to vapor. This is called boiling or flashing. This flashing brings the refrigerant down from the liquid line temperature to the boiling (saturation) temperature in the evaporator, and in this process a percentage of the refrigerant is immediately changed from liquid to vapor. The percentage of the refrigerant that changes during flashing depends on how great the difference is. A larger difference between the liquid line temperature and the evaporator boiling temperature results in more liquid lost to flashing and reduces the efficiency of operation. There are a few different types of metering devices. The most common ones being the Thermostatic Expansion Valve (TXV/ TEV) and the Fixed Orifice (often called a piston) as well as electronic expansion valves, capillary tubes, and others.

Evaporator The evaporator is also known as the cooling coil, because the purpose of the evaporator is to absorb heat. It accomplishes this through the refrigerant changing from liquid to vapor (boiling). This boiling process begins as soon as the refrigerant leaves the metering device, and it continues until the refrigerant has absorbed enough heat to completely finish the change from liquid to vapor. As long as the refrigerant is boiling it will remain at a constant temperature; this temperature is referred to as saturation temperature or evaporator temperature. As soon as the refrigerant is done boiling, the temperature starts to rise. This temperature increase is known as superheat. When the indoor air temperature or the air flow going over the coil is higher, the evaporator pressure and temperature will also be higher because more heat is being absorbed into the coil. When the air temperature or airflow over the coil is lower, it will have lower pressure and temperature in the coil due to less heat being absorbed in the coil. The refrigerant leaves the evaporator, travels down the suction line and heads back to the compressor where the cycle

starts all over again. Refrigerant Lines Suction Line = Line Between the Evaporator and the Compressor The suction line should contain low-pressure superheated suction vapor. Cool to the touch on an air conditioning system, and cold to the touch in refrigeration. Discharge Line = Line Between the Compressor and the Condenser The discharge line should contain high temperature, high pressure superheated vapor Liquid Line = Line between the Condenser and the Metering Device The liquid line should be high pressure, slightly above outdoor temperature subcooled liquid Expansion Line (When applicable) = Line Between the Metering Device and the Evaporator On most systems, the metering device will be mounted directly to the evaporator making the expansion line a non-factor. Some ductless mini-split units will mount the metering device in the outside unit making the second, smaller line and expansion line. The expansion line is full of mixed vapor/liquid flash gas. Yes, this was long, but more than anything else just keep repeating over and over: compressor>discharge line>condenser>liquid line>metering device>expansion line> evaporator>suction line and on and on and on Jim Bergmann did a great whiteboard video on the MeasureQuick YouTube page that explains the basic refrigerant circuit -Bryan