DESIGN GUIDELINES SECTION HVAC

Similar documents
DIVISION 15 MECHANICAL

PITTSBURG STATE UNIVERSITY. HVAC and BUILDING AUTOMATION SYSTEM STANDARDS

A. Section includes Factory Packaged, Modular units, providing cooling and heating for air distribution systems.

AIR HANDLING UNITS Vibration Isolation Air Filtration Equipment Ductwork.

1.1 This section applies to air handling units for HVAC Systems.

A. Section includes split-system air-conditioning units consisting of separate evaporator-fan and compressor-condenser components.

Brown University Revised August 3, 2012 Facilities Design & Construction Standards SECTION AIR HANDLING UNITS

HVAC 101. H V A C S y s t e m s

Update In Progress. Division 23 Heating, Ventilation, and Air Conditioning Page Section FLUID SYSTEMS EQUIPMENT PART 1 GENERAL

System Components with ` Emphasis on Packaged Rooftop Application and Installation. Jerry Cohen President Jacco & Assoc.

SECTION SPLIT-SYSTEM AIR-CONDITIONERS

Internal ridged board 1" x 1.5 foil face installation shall be installed on roof, walls and base of casing.

Stanford University Facilities Design Guidelines SECTION DECENTRALIZED UNITARY HVAC EQUIPMENT

SECTION PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS

Hood Depot Internatioonal, Inc., Phone S. Powerline Road, Deerfield Beach, FL

COHASSET, MA March 6, The following is the HVAC outline specifications, which defines the scope of work of the HVAC system.

Heat Pumps SA SERIES. Vertical Self-Contained Unit Water-Source Heat Pumps (23-70 tons) Features:

VariCool VAV Engineering Guide

UNIVERSITY OF MISSOURI Central Station Air-Handling Units March

SECTION SPLIT-SYSTEM AIR-CONDITIONERS

Series. Packaged Rooftop Units, heat pumps and Outdoor air handling Units. Features:

Series PACKAGED ROOFTOP UNITS, HEAT PUMPS AND OUTDOOR AIR HANDLING UNITS. Features:

Direct Fired Heater Model AD Specification

Commercial Packaged Rooftop Systems

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION REFRIGERATION

Innovative Design, Performance, & Serviceability

Heat Pumps M2 SERIES. Modular Self-Contained Unit Water-Source Heat Pumps (3-70 tons) Features:

ALL PRODUCTS BROCHURE

Maverick II Commercial Rooftop Systems 15 to 75 tons

Appendix 13. Categories of Cooling and Heating systems

XeteX, Inc. All Rights Reserved.

SECTION AIR-COOLED SPLIT SYSTEM AIR CONDITIONING UNITS

VariCool VAV. (Variable Air Volume) 9 to 70 tons Variable Air Volume Water-Cooled and Chilled Water. Unique Solutions for All-Indoor HVAC Projects

FAARM-Underground Facility. Conceptual Design Review. Mechanical Systems. Dunham Associates, Inc.

1. Use air systems in combination with perimeter radiation. Perimeter radiation shall be capable of being operated independent of the air system.

SECTION AIR COILS

H3/V3 Series Horizontal and Vertical Indoor Air Handling Units. Engineering Catalog

CONTENTS. B. System Design and Performance Requirements

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS - CUSTOM

DIVISION 23 - HVAC HVAC Air Distribution

SECTION REFRIGERATION. 1. Reciprocating Compressors (Hermetic). 2. Reciprocating Compressors (Open Drive). 3. Water Cooled Condensing Units.

SECTION 7 AIR CONDITIONING (COOLING) UNIT 38 INSTALLATION

THE ULTIMATE ROOFTOP SOLUTION

Guide Spec Summary. Option List. Date: 05/21/2001. EarthWise Modular Climate Changer Full Spec. Prepared by: Phone Number: Prepared for:

VertiCool CLASSIC. Engineering Guide. Effective March Air-Cooled, Water-Cooled, Chilled Water and Water Source Heat Pump

VertiCool Aurora Engineering Guide

Evaporative Condensers

A. Product Data: Include rated capacities, operating characteristics, furnished specialties, and accessories.

Technical Development Program COMMERCIAL HVAC SYSTEMS. Water Source Heat Pump Systems PRESENTED BY: Ray Chow. Sales Engineer

Construction Standards Page

Efficient, Long Lasting Evaporative Condensers

Rooftop Ventilator. Models RV and RVE. with Packaged Cooling & Heating

A. Codes and Standards that are Standard at the University:

SECTION DUCTWORK

SECTION DUCTWORK

PACKAGED ROOFTOP UNITS, AIR-SOURCE HEAT PUMPS, WATER-SOURCE / GEOTHERMAL HEAT PUMPS, & OUTDOOR AIR HANDLING UNTS. RQ Series.

Heat Pumps SB SERIES. Vertical Self-Contained Unit Water-Source Heat Pumps (3-18 tons) Features:

T-CLASS Commercial Split Systems Up to 20-Ton TSA/TPA Models

KINGS COUNTY JAIL EXPANSION PHASE III COUNTY OF KINGS SECTION

Catalog Destiny Indoor Air Handler. Models Horizontal Configuration. Vertical Configuration

Series. Chillers and. Features: Application Flexibility Minimizes Installation Time and Reduces Cost

Heat Pumps SA SERIES. Vertical Self-Contained Unit Water-Source Heat Pumps (23-70 tons) Features:

AIR HANDLING. B. Section Building Automation and Control System Guidelines. C. Section Air Cleaning Devices and Filters

Construction Standards Page Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA

Cultivator & Hybrid Cultivator

SECTION HVAC TABLE OF CONTENTS PART 1 - SYSTEM DESCRIPTION / OUTLINE SPECIFICATIONS FILED SUB BID PROJECT OVERVIEW...

Bulletin C6200 MAY Buffalo. Big Buffalo. Air Handling. Custom Applications

TYPICAL CPA SPECIFICATIONS

B. Unit construction shall comply with ASHRAE 15 Safety Code, NEC, and ASME applicable codes (U.S.A. codes).

CoolSpot Engineering Guide

SECTION AIR HANDLING UNITS WITH COILS. 1. Central Station Air Handling Units. 1. Section Basic Mechanical Requirements.

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS

From 230 tons to. Water-Source Heat Pump Products. Premium Performance Environmentally Friendly Superior Construction

A. Air Handling Units shall be designed to the specific requirements of the application: Recirculation or 100% Makeup.

THIS IS A DESIGN GUIDE NOT A SPECIFICATION. Montgomery County Public Schools Facilities Guide DIVISION 15 MECHANICAL

C13-Series Engineering Guide

The ultimate fresh air solution.

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION EXHAUST FANS

Heat Pumps SB SERIES. Vertical Self-Contained Unit Water-Source Heat Pumps (3-18 tons) Features:

November 11, City of Sparks 215 S. 21 st St. Sparks, NV

Product Lines

Chiller Plant Design. Julian R. de Bullet President debullet Consulting

A. This Section includes air-handling units with coils for indoor installations.

INTRODUCTION. Special Applications of Package Air Conditioners. Instant Cooling Requirement in Wedding Ceremonies

2. CURRICULUM. Sl. No.

DARTMOUTH COLLEGE DESIGN January 3, 2012 & CONSTRUCTION GUIDELINES

Performance and rugged durability. Commercial Split Systems Up to 20-Ton TSA/TPA Models

The Creative and Performing Arts High School (CAPA) Pittsburgh, PA 11/11/2002 Andrew Tech Mechanical Option Prof. S. A. Mumma

Mission Critical. Series 6, 8 & 9. vertical floor mount Ton Units. Air Conditioning Systems

General Catalogue. FORM SSI - G.C (94)

BUILDING DESIGN STANDARDS. AIR CONDITIONING DIVISION 23 Heating, Ventilation and Air Conditioning

Mammoth Water Source Heat Pumps

AIR HANDLERS. Central Station (CS3) Roof Mounted (RT) (Modular AL Frame AHU)

SKYPAK II, 3 Ton Series, gives you a

Greensource Residential Water Source Heat Pumps. Simply Smart. i Series: SV Model. boschheatingandcooling.com

Variable refrigerant flow (VRF) systems

THE RIGHT SPEC. RIGHT NOW.

A. American National Standards Institute (ANSI) : Establishes requirements applicable to certifying direct gas-fired heaters.

SECTION FAN COIL UNITS

********************************************************************************************************** SYSTEMS REQUIREMENTS HVAC TEMPLATE 02/18

Transcription:

3/15/17 Cooling Methodology Chiller Plants Configurations monitoring Preferred DESIGN GUIDELINES SECTION 15700 HVAC Air-cooled chillers < or = 300 tons; water-cooled chillers > 300 tons Variable volume primary Per latest ASHRAE recommendation and Florida Building Code Mechanical. Status tied to EMCS. New Construction and Renovations Not-Preferred Direct expansion; water-source heat pumps Primary/constant volume secondary; Primary/variable volume secondary Water-Cooled Chillers Trane, York, Daikin Others not allowed Efficiency Centrifugal, screw, scroll (2 separate refrigerant circuits for screw and scroll) R134A or DCPS approved refrigerant. Per DCPS Maintenance Dept. standard spec Multi-compressor, single refrigeration circuit not preferred. HCFCs not allowed. Warranty From project substantial completion (not from chiller start up), 5 year parts, labor, refrigerant on entire chiller. Cooling Towers Evapco, Marley Others Dual cell, common sump with provisions for cell sump isolation Other during maintenance. Construction Stainless steel. Reinforced fiberglass may be considered for certain applications upon Other DCPS approval Fan Motor Variable speed; belt drive; premium inverter rated. 2 speed; single speed; direct drive

Configuration Fan Counter flow or cross flow; external motor; dual access ladders or service platform; service access panels; drain at bottom of pan; welded seams. Dual water feed per cell for back up water feed. Adjustable pitch, heavy duty, extruded aluminum, axial flow; re-lubricatable ball bearings rated at 100,000 hours min. Internal motor Air-cooled chillers Not allowed on new construction within 5 miles of IC waterway. Trane, York, Daikin Others not allowed Screw, scroll with 2 separate refrigerant circuits Multi-compressor, single refrigeration circuit not preferred. Efficiency Warranty Equipment Yard Condenser coil coating Watersource HVAC efficiency R134A, R410A or DCPS approved refrigerant. Per DCPS Maintenance Dept. standard spec From project substantial completion (not from chiller start up), 5 year parts, labor, refrigerant on entire chiller. Per SREF entirely fenced or walled in; concrete slab extended at least one foot past fence or wall. Sound attenuation when specified. Factory-applied, sea coast coated or DCPS Maintenance Dept. approved alternative. Florida Heat Pump, Trane, Daikin or DCPS Maintenance Dept. approved units. Better than minimum needed to receive utility rebate. Others Gravel and natural materials not allowed s

DX RTUs, Split Systems, Wall Hung Units, etc. type Heat Pump Cooling Only Trane, Carrier, York, Daikin, AAON, Bard with stainless s steel drain pan. efficiency Cooling for Server Rooms, IT Areas type controls Dedicated split system, minisplit Bacnet tied to EMCS and set to 78 degf cooling per DCPS IT guidelines. Primary building AC system only Standalone unit manufacturer Heating methodology Water Piping material insulation Mitsubishi, Fujitsu, LG, Daikin, Carrier, Trane, York, Gree Electric or heat pump Mains and branch lines above ground black iron, sched 40 Mains and branch lines below ground pre-insulated, black iron, sched 80 Condensate lines CPVC/PVC sched 40 or copper type L Chilled water -- Foamglass on all fixed piping; aluminum jacket on exterior, ASJ jacket on interior; flexible 2 on all serviceable components. Hot water -- fiberglass. s installation Glued with mastic on joints taped Hot water not allowed (unless approved by DCPS Maintenance Dept.) soft drawn copper tubing Fiberglass not allowed on chilled water piping. Expansion tanks Bladder type Non-bladder type Pumps B&G, Aurora, TACO Others Single, horizontal base mounted Duplex, dual volute, vertical not allowed configuration For multiple pump applications, triple-duty valve for each pump electrical VFD shaft Stainless steel

installation 6 concrete housekeeping pad with vibration isolation; 2 nd floor and above installations require inertia base with drain to floor drain Air Distribution Methodology Primary air Variable air volume Constant volume not allowed Outdoor air/ventilation Outdoor air ducted to AHU Dedicated outdoor air units Air Handling Units Trane, York, Carrier; Daikin s Filter Standard 2 Other construction Auxiliary condensate pan and drain line Access panels 2 double wall; foam insulation; stainless steel drain pan; internally isolated blower section. 16 gauge stainless steel, water tight auxiliary drain pan with float switch to disable unit; drain line pitched properly Hinged, latched and removable; minimum width must be adequate to remove all serviceable parts. single wall; fiberglass insulation not allowed Condensate pumps motor High-efficiency, VFD rated. Standard efficiency Single sheave for larger motors VAV boxes Access Locker Room HVAC Envirotech, Trane, American Air Filter, Titus Provide for easy access for all serviceable parts. s Air source From adjacent conditioned space if possible; with GPS needlepoint 100% outdoor air ionization Ductwork Insulation Externally insulated Internally lined is not allowed Galvanized metal; flex up to 8 ft Material in length; per SMACNA, Ductboard not allowed ASHRAE, Florida Building Code -- Mechanical Openings covered and sealed during construction; cleaned after installation fasteners Per SMACNA, ASHRAE, FBC s Return ducted Plenum return not allowed

Exhaust Fans (excl. kitchens) Location Wall or duct mounted Roof Direct driven Belt driven Variable Frequency Drives ABB, Danfoss, Trane, JCI s Energy Conservation Target operation Design Energy star rating of 75 or greater Minimum --per latest FBC; LEED certified, utility rebate eligible Water Treatment method Chemical treatment all open and closed cooling and heating loops s with shot feeders Air Diffusers Supply air Multi-directional; adjustable s Filtration size 2 filter media MERV 8 minimum location Accessible through hinged, latched door Inaccessible not allowed Service Ladders for Equipment Mezzanines type Staircase and per FBC Vertical or ship ladder