Aalborg Universitet. Diffuse Ceiling Inlet Systems and the Room Air Distribution Nielsen, Peter Vilhelm; Jensen, Rasmus Lund; Rong, Li

Similar documents
The Performance of Diffuse Ceiling Inlet and other Room Air Distribution Systems Nielsen, Peter Vilhelm; Jakubowska, Ewa

Field Study of Diffuse Ceiling Ventilation Performance in a Landscape Office

Air Distribution and Ventilation Effectiveness in a room with Floor/Ceiling Heating and Mixing/Displacement Ventilation

Performance of Chilled Beam with Radial Swirl Jet and Diffuse Ceiling Air Supply in Heating Mode

Aalborg Universitet. CLIMA proceedings of the 12th REHVA World Congress Heiselberg, Per Kvols. Publication date: 2016

Comparison of radiant and convective cooling of office room: effect of workstation layout

Aalborg Universitet. CLIMA proceedings of the 12th REHVA World Congress volume 9 Heiselberg, Per Kvols. Publication date: 2016

On the Architectural Engineering Competences in Architectural Design MSc in Engineering with Specialization in Architecture Kirkegaard, Poul Henning

Aalborg Universitet. CLIMA proceedings of the 12th REHVA World Congress Heiselberg, Per Kvols. Publication date: 2016

Impact of Air Distribution on Heat Transfer during Night-Time Ventilation

Aalborg Universitet. CLIMA proceedings of the 12th REHVA World Congress volume 3 Heiselberg, Per Kvols. Publication date: 2016

Laboratory study on the cooling effect of flash water evaporative cooling technology for ventilation and air-conditioning of buildings

power-saving period in summer, in which one of the indoor units was forced to change from a cooling mode to a fan mode, was introduced, and the effect

Can painted glass felt or glass fibre cloth be used as vapour barrier?

Air and operative temperature measurements in a plus-energy house under different heating strategies

AIRFLOW PATTERN AND PERFORMANCE ANALYSIS OF DIFFUSE CEILING VENTILATION IN AN OFFICE ROOM USING CFD STUDY

Aalborg Universitet. CLIMA proceedings of the 12th REHVA World Congress volume 3 Heiselberg, Per Kvols. Publication date: 2016

American Society of Heating, Refrigerating and Air-Conditioning Engineers

Diffuse Ceiling Ventilation Zhang, Chen; Yu, Tao; Heiselberg, Per Kvols; Pomianowski, Michal Zbigniew; Nielsen, Peter Vilhelm

Impact of heat load distribution and strength on airflow pattern in rooms with exposed chilled beams

Diffuse Ceiling Ventilation Zhang, Chen; Yu, Tao; Heiselberg, Per Kvols; Pomianowski, Michal Zbigniew; Nielsen, Peter Vilhelm

Modeling of Ceiling Fan Based on Velocity Measurement for CFD Simulation of Airflow in Large Room

COOLED PLATE TESTS ON TEXTILE MATERIALS IN SIMULATED COCKPIT UNDER SOLAR RADIATION

Maximum Obtainable Efficiency For Engines And Refrigerators Based On The Stirling Cycle

Villa Bagatelle Technical Report

Vertical Distribution of Air Temperatures in Heated Dwelling Rooms

The Research of Performance Comparison of Displacement and Mixing Ventilation System in Catering Kitchen *

The impact of thermal loads on indoor air flow

To describe human body heat transfer, the concept. Thermal comfort with radiant and convective cooling systems. Articles. REHVA Journal June

Numerical Simulation of Thermal Comfort Degree in Radiant Floor Cooling Room. Architecture, Beijing , China

MODELLING AND SIMULATION OF A ROOM WITH A RADIANT COOLING CEILING. Technicka 4, Prague 6, Czech Republic

IMPLEMENTATION OF DISPLACEMENT VENTILATION SYSTEM BY USING A WALL-MOUNTED AIR CONDITIONER

Shuzo Murakami, Shinsuke Kato, and Taeyeon Kim Institute of Industrial Science, University of Tokyo Tokyo, Japan

Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland

Human response to thermal environment in rooms with chilled beams

INFLUENCE OF SOLAR RADIATION AND VENTILATION CONDITIONS ON HEAT BALANCE AND THERMAL COMFORT CONDITIONS IN LIVING-ROOMS

CFD Analysis of a 24 Hour Operating Solar Refrigeration Absorption Technology

CHAM Case Study Numerical Simulation of a Air-to-air Cross-flow Heat Exchanger

Numerical analysis of diffuse ceiling ventilation and its integration with a radiant ceiling system

Thermal Comfort with Convective and Radiant Cooling Systems

INDOOR CLIMATE IN HEATING CONDITION OF A LARGE GYMNASIUM WITH UNDER-FLOOR SUPPLY/RETURN SYSTEM

Numerical analysis of diffuse ceiling ventilation and its integration with a radiant ceiling system

The cooling capacity of the Thermo Active Building System combined with acoustic ceiling

EXPERIMENTAL AND CFD STUDIES ON SURFACE CONDENSATION

Comparison of Thermal Comfort by Radiant Heating and Convective Heating

Modeling of a regenerative indirect evaporative cooler for a desiccant cooling system

The Experimental Validation of Numerical Modeling of the Air Distribution in the Indoor Ice Rink Arena

Thermal comfort investigation on a naturally ventilated two- storey residential house in Malaysia

COMPARISON OF THE THERMAL ENVIRONMENT IN ROOMS WITH CHILLED BEAM AND RADIANT PANEL SYSTEMS

Thermal Environment Evaluation in Commercial Kitchens of United States

Households' energy use - which is the more important: efficient technologies or user practices? Gram-Hanssen, Kirsten

Modeling and Simulation of Axial Fan Using CFD Hemant Kumawat

Typologies of Hybrid Ventilation in Schools

Space Air Diffusion II

Cooling load calculations of radiant and all-air systems for commercial buildings

NUMERICAL STUDIES ON BARE CABIN FIRES WITH OPERATION OF SMOKE EXTRACTION SYSTEM

An interdisciplinary approach to identify adaptation strategies that enhance flood resilience and urban liveability

Displacement Ventilation

STUDY ON TEMPERATURE, RH AND AIR FLOW VELOCITY DISTRIBUTION INSIDE THE GREENHOUSE EFFECT SOLAR DRYER

Feasible Working Domains Decision Support for Heat Pump Projects

Solar Sustainable Heating, Cooling and Ventilation of a Net Zero Energy House

FLOW CONDITIONS IN A MECHANICALLY VENTILATED ROOM WITH A CONVECTIVE HEAT SOURCE

Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland

Heat Transfer in Evacuated Tubular Solar Collectors

State of the Art of HVAC Technology in Europe and America

Hygrothermal evaluation of a museum storage building based on actual measurements and simulations

Numerical Simulation of Ventilation Efficiency in Commercial Kitchen

GAS DETECTOR LOCATION. Ø.Strøm and J.R. Bakke, GexCon AS, Norway

IEA EBC Annex 59 - Possibilities, limitations and capacities of indoor terminal units

ZONE MODEL VERIFICATION BY ELECTRIC HEATER

APPLICATION OF MINI HEAT PIPES FOR THERMAL MANAGEMENT OF OPTO-ELECTRONIC INSTRUMENTS

Modeling water-mist based suppression of 34 GJ car-deck fires using FDS

Design And Analysis Of Centrifugal Pump

High efficient heat pump system using storage tanks to increase COP by means of the ISEC concept - Part 1: Model validation

Effect of the Use Pattern on Performance of Heat Pump Water Heater

Aalborg Universitet. Responsive City Lighting Skouboe, Esben Bala; Andersen, Hans Jørgen; Jensen, Ole B. Publication date: 2013

Moisture permeability of some porous materials

DESIGN OF AIR-CONDITIONING SYSTEM FOR SARS WARDS. By Yuguo Li and SARS Busters * Background

Evaluation of a dynamic model for a cold climate counter flow air to air heat exchanger

STUDY FOR SAFETY AT A RELATIVELY SHORT TUNNEL WHEN A TUNNEL FIRE OCCURRED

Influence of Compressor Control Strategy on Energy Efficiency and Product Temperature for Professional Counter Cabinets

Heat transfer and heating rate of food stuffs in commercial shop ovens

incorporating Contractors guide to car park ventilation A no-nonsense guide to the safe ventilation of underground and covered car parks

Numerical Study on Improvement of COP of Vapour Compression Refrigeration System

OPTIMIZATION OF VENTILATION MODE OF SMOKE CONTROL SYSTEM IN HIGH-RISE BUILDING FIRE

Ventilation Strategies for Healthy IEQ and Energy Efficiency

ROOM AIR STRATIFICATION IN COMBINED CHILLED CEILING AND DISPLACEMENT VENTILATION SYSTEMS

CFD Simulation of the Water Mist Effect on Fire

CFD Analysis of Fire Characteristics on Subway Junction Station

Numerical investigation on the effect of channelled and unchannelled screens on smoke contamination in atriums upper balconies with open upstand

maximize displacement ventilation Opportunities

Halton Vario Design Guide

Physical Mechanism of Convection. Conduction and convection are similar in that both mechanisms require the presence of a material medium.

Comparison of fin-and-tube interlaced and face split evaporators with flow maldistribution

Tunnel Fire Dynamics and Evacuation Simulations

VENTILATIVE COOLING CONTROL STRATEGIES APPLIED TO PASSIVE HOUSE IN ORDER TO AVOID INDOOR OVERHEATING

Sprinklers Modeling for Tunnel Road Fire Fighting

Analysis of Constant Pressure and Constant Area Mixing Ejector Expansion Refrigeration System using R-1270 as Refrigerant

Numerical Stability Analysis of a Natural Circulation Steam Generator with a Non-uniform Heating Profile over the tube length

HOW TO REDUCE ENERGY CONSUMPTION OF BUILT-IN REFRIGERATORS?

Transcription:

Aalborg Universitet Diffuse Ceiling Inlet Systems and the Room Air Distribution Nielsen, Peter Vilhelm; Jensen, Rasmus Lund; Rong, Li Published in: Clima 2010 : 10th Rehva World Congress Publication date: 2010 Document Version Publisher's PDF, also known as Version of record Link to publication from Aalborg University Citation for published version (APA): Nielsen, P. V., Jensen, R. L., & Rong, L. (2010). Diffuse Ceiling Inlet Systems and the Room Air Distribution. In Clima 2010 : 10th Rehva World Congress: Sustainable Energy Use in Buildings Antalya: Clima 2010 : 10th Rehva World Congress. General rights Copyright and moral rights for the publications made accessible in the public portal are retained by the authors and/or other copyright owners and it is a condition of accessing publications that users recognise and abide by the legal requirements associated with these rights.? Users may download and print one copy of any publication from the public portal for the purpose of private study or research.? You may not further distribute the material or use it for any profit-making activity or commercial gain? You may freely distribute the URL identifying the publication in the public portal? Take down policy If you believe that this document breaches copyright please contact us at vbn@aub.aau.dk providing details, and we will remove access to the work immediately and investigate your claim. Downloaded from vbn.aau.dk on: august 24, 2018

Diffuse Ceiling Inlet Systems and the Room Air Distribution Peter V. Nielsen 1, Rasmus L. Jensen 1*, Li Rong 1 1 Aalborg University, Denmark * Corresponding email: rlj@civil.aau.dk SUMMARY A diffuse ceiling inlet system is an air distribution system which is supplying the air through the whole ceiling. The system can remove a large heat load without creating draught in the room. The paper describes measurements in the case of both cooling and heating, and CFD predictions are given for the heating case. INTRODUCTION This paper describes a new air distribution system which is able to remove a large heat load from a room without creating thermal discomfort in the occupied zone of the room [1]. Preliminary experiments show that the system can remove a larger heat load than other systems, as e.g. mixing ventilation, displacement ventilation and vertical ventilation (active displacement ventilation), [2]. The whole ceiling is the supply opening because air is supplied through standard acoustic ceiling elements and through the slots between the ceiling elements. It is characteristic of this type of air distribution system that it is the heat sources in the room that generate the air flow pattern in the room and the draught. Few examples of this system are known in comfort ventilation, but it is used extensively in livestock buildings. Figure 1 shows the design chart for a typical system. It indicates the limit of the flow rate q o and the temperature difference between return and supply T o giving a draught of 0.15 cm/s in the occupied zone [1]. The product of q o and T o is constant, which is typical of all systems with low supply velocity where heat loads generate the flow in the room. Figure 1. Design chart for a room with diffuse ceiling inlet.

This paper examines the details of the system, as e.g. test of new ceiling elements compared to the ceiling in [1], test of a new office layout, test of return opening location, and especially tests of some situations where the system is used for heating. The heating situation is studied both by fullscale experiments and by Computational Fluid dynamics (CFD). All the experiments are made to test this application for a new 8000 m 2 administration building made for Videx A/S, Denmark. FULL-SCALE EXPERIMENTS AND CFD PREDICTIONS The system is tested in a full-scale room with the length, width and height equal to 4.1 m, 3.2 m and 2.45 m, respectively. Both cooling (in a general situation), and heating (for the night situation) are tested. Figure 2. Full-scale room with location of the heat loads, which are a wall (cold/warm), a manikin, a computer and a lamp. Figure 2 shows the layout of the office with the person as a heated manikin, a PC and a lamp. The numbers indicate the positions of the measured vertical temperatures. The cold/warm wall is represented by a plastic folio where cold or warm air can be circulated to represent a cold window during winter or a hot window during the summer, see figure 3.

Figure 3. Cold/warm wall and a thermographic picture of the wall as a cold wall. The air is supplied above the diffuse ceiling in the right side of the room (close to position 5). The exhaust opening can be located at different positions, and experiments are made with a position in the upper right corner just below the ceiling or below the desk in the opposite corner close to the floor. Figure 4 shows the supply duct, the diffuse ceiling and the return opening. The flow from the diffuse ceiling is mainly taking place through small slots and openings between the support of the acoustic ceiling and the ceiling elements, and to some extent through the elements. Figure 4. Supply duct above the diffuse ceiling (the acoustic ceiling elements are removed in the photo), the diffuse ceiling and the movable return opening. The room in figure 2 is only one quarter of the full room in the Widex office building. The experiments are therefore extended by CFD predictions for the full room with the dimensions, length, width, height equal to 7.2 m x 10 m x 2.7 m. The CFD predictions are focused on the heating situation. Figure 5 shows the geometry with an indication of the boundary conditions at the ceiling, which consists of a number of slots with a size of 2 cm and a length of 8.2 m. This inlet geometry gives a flow in the vicinity of the ceiling which corresponds to the measured velocity conditions. The supply air velocity is 0.102m/s (airflow rate of 3.5 h -1 ), and the supply air temperature is 27 ºC. The heat flux through the window in winter is -40.8 W/m 2 and -5.1W/m 2 for the outer wall, which is calculated according to the Danish design criteria with a room air temperature of 22 ºC, and an outside temperature of -12 ºC. The boundary conditions at the other solid surfaces are adiabatic.

Figure 5. Geometry of the CFD predictions of a room with diffuse ceiling inlet. RESULTS AND DISCUSSION One smoke experiment and three comfort experiments as well as one CFD prediction are carried out. The comfort experiments consist of one cooling experiment (8 h -1 ) and two heating experiments (3.5 and 6.0 h -1 ), and the CFD experiment covers the heating situation in a four times larger room without any internal heat load. Smoke experiment The smoke experiments are made for both cooling and heating, and they are made for air change rates from 3.5 to 8.0 h -1. It is shown that it is the internal heat sources that generate the flow and thus the mixing and draught in the occupied zone. It is also shown that the level of draught in the room is low, which is also documented in /1/. The air is supplied to the room through small slots between the sound absorbing elements and the support of these elements. The smoke experiments show that high velocities with high entrainment take place in microjets below the ceiling and up to 0.5 m down into the room. Therefore it is appropriate with a distance of at least 0.5 m from the occupied zone to the ceiling surface. Experiments with different locations of the return opening show that the location is, as expected, of minor importance to the air distribution pattern. Comfort experiment, cooling case, 8 h -1 The measurements of temperature and velocity distribution indicate a sufficient level of thermal comfort in the office, although the heat load and air change rate are high. Vertical temperature gradients in the room, figure 6, are small and the temperatures are at all positions between 22.5 ºC and 25.0 o C. There is a horizontal gradient in the room with the highest temperatures in the right side of the room, figure 2, while positions close to the warm (window) wall have slightly lower temperatures. The return temperature is equal to 22.6 ºC. Figure 6. Vertical temperature gradients in the room. The positions 2 to 5 of the vertical measuring lines are shown in figure 2.

It is not possible to obtain any indication of unstable flow in the room, although heat loads are cooled from above with cold air with a minimum of momentum flow. Comfort experiment, heating case, 3.5 and 6.0 h -1 The heating case demonstrates a night situation without any heat load in the room but with the cold window wall. The idea with the heat supply is to maintain comfort conditions in the room until people show up at work. It is obvious that the situation with the supply of heated air from above creates a vertical temperature gradient in the room, and the absence of heat loads in the occupied zone also minimises the mixing flow in the room. Figures 7A and B show that the gradient is acceptable, and measurement of velocities does also indicate an acceptable level of thermal comfort. The temperature gradient at position 1, close the cold wall, shows a low level of the temperature, which is also to be expected. The return temperature is equal to 22.6 ºC and 22.0 o C in the two cases. A B Figure 7. Vertical temperature gradients in the heating case. A) 3.5 h -1 and B) 6.0 h -1. The positions 1 to 5 of the vertical measuring lines are shown in figure 2. In this kind of heating case we will always recommend the use of a convector or floor heating for the support of heat. CFD predictions for the full room The heating situation is the most interesting situation with respect to comfort. Therefore the experiments are extended by CFD simulations in the full room, which is four times as large as the full-scale room shown in figure 2. The room is without any internal heat load in order to study the situation with a maximum vertical temperature gradient. The CFX11.0 software is used for the predictions, and the geometry is designed by 433,935 grid points in a structured grid. A high resolution numerical scheme with blend factor values is used. In flow regions with low variable gradients, the blend factor is close to one for accuracy (second-order accuracy). In areas where gradients change sharply, the blend factor is close to zero to prevent overshoots and

undershoots and to maintain robustness (first-order accuracy). The predictions are based on timedependent RANS equations, and the results are presented in T=1800s. It was not possible to obtain a converged solution with steady state equations. Figure 8 shows a typical prediction of the velocity distribution in the room. The high velocity area above the occupied zone is obvious in the figure. Figure 8. CFD predictions of the velocity distribution in the office room with diffuse ceiling inlet. The prediction of the vertical temperature distribution in the office indicates larger vertical gradients that the ones measured in the full-scale room. The temperature in figure 9 is 27 ºC at the ceiling, and 23 ºC at floor level. Figure 9. CFD prediction of the temperature distribution. CONCLUSIONS The experiments show that the diffuse ceiling inlet system is working well in the case of cooling. There is no indication of any unstable flow situations, although cold air is supplied with a low momentum flow above warm air in the occupied zone. The system is also working in a satisfactory way when it is used in the heating situation. Some low temperatures close to the cold surface in the experiments, and the indication of large vertical temperature gradients in the CFD predictions show that in this case areas with low temperatures may exist. On the other hand, smoke experiments show that a few heat sources generate sufficient mixing flow in the room to obtain thermal comfort. It should be recommended to use the system together with convectors in the heating mode. Smoke experiments show that the location of the return opening is of minor importance.

The return temperature is lower than the averaged room temperature in the cooling case, and higher than the room temperature in the heating case. This means that the temperature effectiveness is slightly below 1.0 in both cases. ACKNOWLEDGEMENT This paper discusses some of the measurements made for - and supported by - the company Widex A/S in Denmark. The results are used for the design of the air distribution system in their new administration building. The system is designed by Wessberg A/S in Copenhagen. REFERENCES 1 Nielsen, P V and Jakubowska, E. 2009. The performance of diffuse ceiling inlet and other room air distribution systems, Cold Climate HVAC, Sisimiut, Greenland. 2 Nielsen, P V. 2007. Analysis and design of room air distribution systems, HVAC&R Research, Vol. 13, No. 6, pp. 987-997.