FIRE CONTROL PANEL. Revision 1.1 January 1997 USER MANUAL. Emergi-Lite Safety Systems Ltd Bruntcliffe Lane Morley Leeds LS27 9LL

Similar documents
FTEN1, FTEN2, & FTEN4 1, 2 & 4 ZONE FIRE DETECTION AND ALARM CONTROL PANELS

EUROFIRE Fire Control Panel

6100 SINGLE LOOP DIGITAL ADDRESSABLE FIRE ALARM CONTROL PANEL

INTELLIGENT FIRE TECHNOLOGY. Twinflex and Multipoint V3. User Guide (TO BE RETAINED BY USER) Issue 3

Control Panel User Guide

Syncro AS. Analogue Addressable Fire Control Panel. User Manual

Installation, Operating and Maintenance Manual

ZX1e ZX2e ZX5e. Document No Issue 01 user manual

3500 CONVENTIONAL FIRE ALARM CONTROL PANEL

2) This manual covers Fire and General Alarm systems. The differences are described in the appropriate sections.

ID2000. operating manual

Installation and user manual for the FX range of fire panels. 1, 2, 4 and 8 zone panels

Operating instructions SENTRI4 Control panel based Fire detection and alarm system

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel

Intelligent Security & Fire Ltd

Operating instructions Vigilon panel and Network node Fire detection and alarm system

JUNO-NET. Fire Alarm Control Panel OPERATION & MAINTENANCE MANUAL

SERIES 3000 INTELLIGENT FIRE ALARM CONTROL PANEL ENGINEERING PROGRAMING MANUAL TABLE OF CONTENTS.. 1 INTRODUCTION.. 3 SYSTEM POWER UP.

one Operating instructions SenTRI ONE panel-based Fire detection and alarm system

3200 NON-ADDRESSABLE FIRE ALARM CONTROL PANEL

user manual Document No , Revision 03 November 2015

Intelligent Security & Fire Ltd

USER MANUAL COMBINED FIRE & EXTINGUISHING CONTROL PANEL COMPLIES WITH BS EN PART 1 & EN54 PARTS 2 & 4

Algo-Tec 6500/6600 INTERACTIVE ADDRESSABLE FIRE CONTROL SYSTEM

SYSTEM 5000 USER MANUAL

Fire detection and alarm system Operating instructions

ZERIO PLUS EDA-Z5008, Z5020 & Z5100

Surveyor Envoy-MINI 4

Installation and user manual for the CF5000, MF5000 and FXP5000 range of fire panels

Control Panel User Guide (TO BE RETAINED BY THE USER)

Document No Issue 4 user manual

LC1 & 2. Fire Alarm Panel 6\VWHPLQVWDOODWLRQRSHUDWLQJ PDLQWHQDQFH LQVWUXFWLRQV

BT1 SINGLE ZONE FIRE ALARM SYSTEM OPERATORS MANUAL

SOLO Single Loop Addressable Fire Control Panel

Scimitar user manual & log book. Petersfield Business Park, Bedford Rd, Petersfield, Hampshire GU32 3QA Tel: Fax:

USER MANUAL & MAINTENANCE GUIDE OG OO

XFP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM CONTROL PANEL. user manual and log book. approved document no. DFU Rev 1

ZXe INTELLIGENT MULTI PROTOCOL FIRE ALARM CONTROL PANEL

3500 CONVENTIONAL FIRE ALARM CONTROL PANEL

Intelligent Security & Fire Ltd

System 800 Addressable Fire Detection & Alarm System

The EN54 Part 2 & 4 Fire System

Fire Alarm Control Panel. System Maintenance and Log Book

MAG2/4. AL MAG2 Soft. Version 2.1 MAG4 Soft.Version 2.0 USER MANUAL

ZP3 Operator & Maintenance Manual Version 1

Saffire User & Installation Manual. IMPORTANT This manual should be left with the panel after installation.

Product Data Sheet. Remote Terminals. Features:

PAT E N T System 88. COMPLIES WITH Singapore Standard : SS CP10 : 2005 British Standard : BS EN54-2 : 1998 BS EN54-4 : 1998 REV.00

ZM2 OPERATING AND MAINTENANCE INSTRUCTIONS

USER MANUAL, MAINTENANCE GUIDE & LOG BOOK

Algo-Tec 6300 INTERACTIVE DIGITAL ADDRESSABLE FIRE CONTROL SYSTEM (1-4 LOOPS)

User Operation Manual

SYSTEM 3400 ANALOGUE ADDRESSABLE FIRE DETECTION. (with Devices) Operating Manual Version 3.3X Issue 2 September 1996

Noby-448 User Operating Manual & Log Book Page 1 of 12. Fire Control Panel. User Operating Manual & Log Book

Installation and user manual for the BiWire / Conventional Repeater Panel

Sigma. K1000 Series 1, 2, 4 & 6 Zone Fire Control Panels. Operation and Maintenance Manual. Man-1048 Issue 05 October 2009

Surveyor Excel. Fire Alarm Control Equipment Network version. Programming Manual MASTER MANUAL. VERSION 14.0 and Above

Control Panel User Guide

FIREPRO INSTALLATION MANUAL FIRE ALARM CONTROL PANEL INSTALLATION MANUAL. Approved Document No. GLT Issue: 1. 8 Author: NRPJ Date: 7/ 3/201 4

Control Panel Engineering and Commissioning Instructions

CONTENTS Installation Precautions... 1 Chapter 1 Product Introduction... 2 Chapter 2 Technical Specifications... 3

FIRE ALARM CONTROL PANEL FVC01-08

Application, Installation, Operation & Maintenance Manual

QA16 Addressable System

OPERATION AND INSTALLATION MANUAL

Operation and Maintenance Manual

To operate the 5207 you can use either the built-in touchpad or the Model 5230 Remote Annunciator.

Maintenance Guide EMS Security Group Ltd. All rights reserved. MK154 Iss5 18/11/15 AJM

Zerio Plus EDA-D6000 Radio Combined Heat Detector and Sounder Installation Instructions

Logbook. Precept EN Fire Detection/Alarm Panel. & Precept EN Repeater

user manual and log book XFP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM CONTROL PANEL

ORION Mini-Rep INSTALLATION MANUAL

CSP-204 CSP-208 CSP-104 CSP-108

HARDWIRED CONTROL PANELS

Door Release Power Supply

NZ 400 AUTOMATIC FIRE ALARM SYSTEM OPERATORS MANUAL

RE 102 RE Fire Alarm Control Panel. Installation, Commissioning & Operating Manual

CPA6. Installation & User Guide. Intelligent Security & Fire Ltd. Compatible Equipment

Installation and Operating Instructions

ZSC100 Gas Detection and Alarm System Controller

Written by: A.C. Amended by G.G. Checked by: JBJ/PB Approved by:jbj

INFINITY 8 INSTALLATION MANUAL FIRE ALARM CONTROL PANEL INSTALLATION MANUAL

GAS SUPRESSION CONTROL PANEL:

INDEX 1- Introduction The Control Pane...7l 4.1- The Control Panel 1 and 2 Loops The Control Panel 4 and 8 Loops...

Networked Access Control Panel. Installation Guide

FIRE ALARM CONTROL PANEL. COMPLIES WITH EN54 part 2 & part 4 MEETS THE FUNCTIONAL REQUIREMENT OF BS:EN 5839 part 1 INSTALLATION MANUAL

SIMPLICITY CO CARBON MONOXIDE DETECTION & VENTILATION PANEL

Conventional Leaflets

SECURIT 703 USER MANUAL

SECURIT 700L PLUS ENGINEERING MANUAL

Zerio Plus EDA-R6000 Radio Combined Optical Smoke Detector and Sounder Installation Instructions

5000 INSTALLATION GUIDE

Precept Marine Control Panel Application Guide

Installation Manual (version 4-2 )

CW9000 Wireless Fire System. Installation Manual

USER GUIDE HARDWIRED CONTROL PANELS

USER MANUAL CEF AP28 CONTROL PANEL

Firetrax Professional Conventional Fire Control Panel

BSR Addressable Fire Detection control panel. Installation operation manual

Operating manual and Log book for the range of 1,2,4 and 8 zone fire Control and Repeat panels

Transcription:

FIRE CONTROL PANEL Revision 1.1 January 1997 USER MANUAL Emergi-Lite Safety Systems Ltd Bruntcliffe Lane Morley Leeds LS27 9LL Tel: 0113 281 0600 Fax: 0113 281 0601

C O N T E N T S PAGE INTRODUCTION... 3 USER FUNCTIONS... 4 MENU FUNCTIONS... 5 Lamp Test...5 Look/Change Panel...5 List Faults...5 Time & Date...5 Event Log...6 Event Types...6 Walk-Walk Test...7 Isolate Zone...8 Isolate Detector...9 Isolate Printer...9 SYSTEM OPERATION... 10 Normal...10 Fault Condition...10 Fire Condition...12 INSTALLATION DETAILS... 13 Cable Types...14 Mains Supply...16 SYSTEM MAINTENANCE... 17 APPENDIX - MENU TREE STRUCTURE... 18 ANATEC 2

INTRODUCTION The Anatec is a modern microprocessor controlled analogue addressable fire control panel built using the latest technologies to give a sophisticated yet reliable fire detection system. What does Analogue Addressable Mean? Unlike conventional fire detection systems, an Analogue addressable system can pinpoint a fire activation down to a single detector or callpoint. Also unlike conventional systems an Analogue Addressable panel can monitor the fire detectors for contamination or degradation or other faults which could cause the performance of the system to deteriorate over a period of time. Panel Basics The Anatec is very easy to operate as there are only four buttons. Three of which are common to almost all fire alarm panels, these are mounted under the liquid crystal display, see diagram below. ANATEC FIRE CONTROL PANEL EMERGI-LITE SAFETY SYSTEMS RESET EVACUATE MORE SILENCE ALARMS RESET This button will try to return the panel to it s normal state. Obviously if a fire or fault is still present the system will return to the appropriate condition (if in a fire condition the bells could resound!). Reset can only be operated if first the panel has been silenced (the alarm silenced light must be lit). NEVER reset the panel before the condition of the building is known, and thus the reason for the alarm. EVACUATE This button operates the alarm sounders and signals to other fire panels connected to it via a network, however any digital diallers or other devices connected to the panel via its auxiliary contacts will NOT operate. MORE SILENCE ALARMS This button is unique to the Anatec, from this button all the user functions can be accessed (see relevant section for more information). It should be noted that in a fire condition this button will scroll through all current fires. This button stops all alarm sounders from sounding, or if there is a fault on the system it will increase the time between bleeps of the fault buzzer (reducing the annoyance factor). ANATEC 3

USER FUNCTIONS The user menu is accessed by pressing the MORE button. Note: the user menu cannot be accessed when the panel is in fire, you must silence & reset panel - TAKING ANY NECESSARY ACTION TO DETERMINE CAUSE OF THE FIRE ACTIVATION The operation of the menu is as follows. When the MORE button is pressed the LCD changed, the top line gives a list of abbreviated choices. The bottom line gives a description of the presently selected choice. The current choice will be flashing (shown in this manual in bold). To move to the next option press the MORE button again, to select the flashing option press the SILENCE ALARM button. The menu system works like an upside down tree (see appendix 1) each menu allows the user to branch down the tree. To exit the menu the user must return back up the tree, this is done by selecting the BACK option in the menu, at the top level select QUIT to leave the menu system. On entry to the top level user menu the LCD display will show:- LAM PAN ISOL ENG QUIT* 1) LAMP TEST Press the MORE button to cycle through the available options, when the required function has been selected press the SILENCE ALARM button to execute the function. For example, to perform a lamp test press the MORE button until the LAM - lamp test option is selected & then press the SILENCE ALARM button to perform the lamp test. To return the panel to the normal condition press the MORE button until the QUIT option is selected & then press the SILENCE ALARM button. The available options are:- 1) LAM - LAMP TEST - Perform lamp test. 2) PAN - LOOK/CHANGE PANEL - Fault/Clock/Log sub menu. 3) ISOL - ISOLATE ZONES ETC - Isolate detector - zones - printer sub menu. 4) ENG - ENTER ENGINEERS MODE - Engineering menu s, authorised access only. 5) QUIT - LEAVE MENU SYSTEM - Returns panel to normal state. ANATEC 4

MENU FUNCTION DESCRIPTION 1) LAMP TEST This function is used to test the operation of the light-emitting diode (LED) indicators & buzzer on the panel. The LED s are illuminated 8 at a time, starting with the panel status LED s on the left of the panel then moving to the Zone Fire LED s and finally the processor fail LED & fault buzzer. After the completion of the test the panel returns to the main user menu. 2) PAN - LOOK / CHANGE PANEL This option enters a sub menu which allows the user to list all current faults on the fire alarm system, set time / date for the system clock and print even log. PAN SUB MENU DESCRIPTION The available options are:- FAU TIM LOG WALK BACK 1) LIST PRESENT FAULTS 2a) FAU - LIST PRESENT FAULTS This function is used to show all the current faults on the fire alarm system, starting with the most recent fault press the MORE button to show other faults, if there are no more faults the display will return to the PAN sub menu. 2b) TIM - SET THE TIME AND DATE This function sets the fire alarm systems clock, which is used to time/date stamp any events which might occur. On entry to the date menu, the LCD shows the current system date as shown:- DATE: 16 05 96 OK DAY MONTH YEAR The push buttons on the panel are then associated with the function above it on the bottom line of the LCD for example:- Press EVACUATE button to increment the DAY. Press MORE button to increment the MONTH. Press SILENCE ALARMS to increment the YEAR. When the date is correct press RESET to move to the TIME menu as shown below:- TIME: 12 15 OK HOUR MIN ANATEC 5

The operation is similar to the DATE set menu. Press EVACUATE to increment the HOUR. Press MORE to increment the MINUTE. Press RESET when the time is correct the LCD returns to the main user menu. 2c) LOG - PRINT LOG This function is used to print the event log the range of events printed can be selected, however, printing a full event log may take a significant period. Each function on the bottom line of the LCD is allocated to the button below it, the LCD will display: PRINT 000 0045 QUIT FROM TO Press the EVACUATE button to increase the event number to print FROM. Press the MORE button to increment event number to print TO. Press the RESET button to QUIT and return to main user menu. EVENT LOG PRINT FORMAT Print log output format. ========================================== Event description EVENT LOG Time & date of event Event number EV# TEXT TIME DATE 001 SYSTEM POWER UP V6.03 09:31 20:03 002 FIRE ZONE 2 11:35 23:03 CORRIDOR GROUND FLOOR Example device location text LOOP 1 ADDRESS 5 TYPE ION 003 ALARM SILENCED 11:37 23:03 RESET OPERATED 11:45 23:03 25/03/95 Date of event log printout ========================================== EVENT TYPES Listed below are all the events that are stored in the Anatec log. PRINTER MESSAGE EVENT DESCRIPTION SYSTEM POWER UP - Anatec initial sign on message. ROM FAULT - Indicates that the fire panels self check procedure has detected an error in it s computers program memory. DATA RAM FAULT - Indicates that the fire panels self check procedure has detected an error in its site configuration information. EVACUATE OPERATED - A manual evacuation event. ALARMS SILENCED - Panels alarm/fault sounders silenced. RESET OPERATED - Panel was returned to normal condition. EXTERNAL PSU FAULT - A remote power supply connected to the Anatec has developed a fault. ANATEC 6

MAINS POWER FAIL - 230V mains has become disconnected. BATTERIES NOT CHARGING - The standby batteries have become disconnected or faulty AUXILIARY FUSE BLOWN - The Auxiliary 24v output s fuse has blown. OPEN CCT ON ALARM NO. - Indicates that sounder circuit x(1-4) wiring has become open circuit. SHORT CCT ON ALARM NO. - Indicates that sounder circuit x(1-4) wiring has become short circuit. NET DEVICE MISSING PANEL xx - A device on the Anatec RS485 network is not responding. NET FAULT PANEL xx - Indicates that a device on the Anatec s RS485 network has developed a fault. NET FIRE PANEL xx - Indicates that a fire panel on the Anatec s RS485 network signalled a fire condition. LINE BREAK LOOP x - Indicates that the fire detector wiring on loop X(1-4) has developed a fault. COMMS ERROR LOOP x - Indicates that the signals on the detector wiring on loop x(1-4) is garbled, this could be due to short/open circuits in the loop wiring. FIRE ZONE x - Indicates a fire event. Device location text goes here LOOP x ADDRESS xx TYPE xx PRE ALARM - Indicates that a detector s alarm value is approaching Device location text goes here a fire level. This could be due to contamination - LOOP x ADDRESS xx TYPE xx dust or high temperature (e.g. if located in a kitchen). DEVICE MISSING - Indicates that a detector is not responding, could be Device location text goes here physically missing etc. LOOP x ADDRESS xx TYPE xxx 2d) WALK-WALK TEST This option allows a person to test individual sensors/callpoints on the fire alarm system. The user must chose the loop and address for the test to start from. When a sensor/callpoint is selected for test it s LED indicator is turned on and when triggered the LED will flash. Its location text will be printed, the bells will pulse, briefly sound and then the address will be incremented to the next address to be tested. On entry to the menu the LCD display shows:- GROUND FLOOR LOBBY L 1 A 4 ON QUIT Device location text loop address bell mode To select the required loop press the RESET button. To increment the address press the EVACUATE button. Use the MORE button to disable the bells and when the walktest is complete press the SILENCE ALARMS button to quit back to the main user menu. ANATEC 7

2d) BACK-BACK UP ONE LEVEL This operation returns to the main user menu. 3) ISOL SUB MENU FUNCTION DESCRIPTION It is important to realise that isolating one or more devices will reduce the scope of the fire alarm system to detect fires. LAM PAN ISOL ENG QUIT* 2) LOOK/CHANGE PANEL This menu is used to isolate (turn off) a zone of detectors or an individual detector, the printer, or to clear all isolations. Why would you want to isolate a detector or zone of detectors? Possibly if building work was being carried out in that particular zone where smoke or dust from the work may cause a false alarm. (Detectors may require protection to prevent contamination). When a device or printer has been isolated the DEVICE ISOLATED indicator on the Anatec will flash to inform the user. On entry to the isolation menu the LCD displays:- ZONE DET CLR PRI BACK 1) ISOLATE BY ZONES Use the MORE button to select the available options & then press SILENCE ALARMS to perform the require function, the available functions are:- 1) ZONE - ISOLATE BY ZONES - Isolate a zone of detectors/callpoints 2) DET - ISOLATE A DETECTOR - Isolate a single detector 3) CLR - CLEAR ALL ISOLATIONS- Does just that 4) PRI - PRINTER OPTIONS- Turns on or off the printer 5) BACK - BACK UP ON LEVEL- Returns to the main user menu MENU FUNCTION DESCRIPTION 3a) ZONE - ISOLATE BY ZONES This menu is used to isolate zones of the fire alarm system, on entry to the function the LCD displays:- ZONES 1-16 17-32 LOW HIGH QUIT To isolate the required zone press LOW or HIGH which ever contains the desired zone. When only one number is shown select the desired zone and it will be isolated. To abort the procedure press QUIT at any time. ANATEC 8

3b) DET - ISOLATE A DETECTOR This menu allows the user to isolate a particular device, on entry the LCD shows:- Isolated indicator Device location text Corridor ground floor * L1 A1 ISOL QUIT loop address To select the required loop press the RESET button. To increment the address press the EVACUATE button. The device location text is shown on the top line of the LCD. Press the MORE button to isolate/re-instate a device. When a device is isolated a * appears on the top right of the LCD display. To quite press the ALARM SILENCE button. 3c) CLR - CLEAR ALL ISOLATIONS This function clears all isolations on the panel after confirmation. On entry the LCD displays:- DO IT! BACK CLEAR ALL ISOLATIONS Use the MORE button to select either DO IT! or BACK, press the SILENCE ALARM button to perform function. DO IT! Clears all isolations BACK Returns to mains user menu 3d) PRI - PRINTER OPTIONS This function is used to stop or start the printer. On entry the LCD shows:- STOP GO ISOL BACK 1) ISOLATE PRINTER Use the MORE button to select the required function and then press SILENCE ALARMS to perform function. STOP - ISOLATE PRINTER Stops printer from printing all events apart from fires GO - TURN ON PRINTER Restarts the printer ISOL - PRINT ISOLATIONS Prints a list of isolated detectors BACK - BACK UP ONE LEVEL Returns to main isolation menu ANATEC 9

SYSTEM OPERATION NORMAL In normal operation the LCD will show:- SYSTEM HEALTHY 14:45:20 with only the SUPPLY HEALTHY indicator illuminated. current time System status message If a detector/zone or printer is isolated the n the DEVICE ISOLATED indicator will flash FAULTS what to do in the event of a fault Fault conditions on the system are indicated by the amber COMMON FAULT indicator illuminating and a pulsing internal buzzer. The LCD and printer will give a more accurate fault diagnosis. IT IS IMPORTANT THAT THE FAULT IS INVESTIGATED IMMEDIATELY AND AN ENGINEER IS CALLED IF NECESSARY TO RECTIFY THE FAULT OTHERWISE THE CAPABILITY OF THE FIRE ALARM SYSTEM TO DETECT FIRES COULD BE REDUCED. The pulsing frequency of the internal buzzer can be reduced by pressing the SILENCE ALARM button. FAULT DESCRIPTION a) FAULT MAINS POWER FAIL The 230v AC mains supply to the panel is missing. The fire panel system will have the Standby capacity to run for a minimum of 24 hours, after this period the fire monitoring by the system could be lost. It is important that the cause of the failure is investigated and rectified. The POWER FAILED indicator will also illuminate. b) FAULT BATTERIES NOT CHARGING Indicates that the alarm systems standby batteries have become disconnected or are faulty. The POWER FAILED indicator will also illuminate. C) FAULT DEVICE MISSING LP1 ADD 5 TYPE OPT A fire detector or callpoint is not responding to the fire panel. If the device is a detector check that the detector has not been removed. The second line of the display alternates between showing the loop - address - device type and device location text. d) FAULT: PRE-ALARM ANATEC 10

LP-1 ADD 5 TYPE TEMP Indicates that a detector alarm threshold has risen to an abnormal value, this could be due to dust or smoke for ionisation or optical smoke detectors and a high ambient temperature for heat detectors. e) FAULT FAULT OPEN CCT ON ALARM NO.4 or SHORT CCT ON ALARM NO.4 Indicates that a fault has developed in the fire alarm systems sounder circuit wiring. The ALARM FAULT indicator will also illuminate. f) FAULT: FAULT: LINE BREAK LOOP 1 or COMMS ERROR LOOP 1 A fault has developed in the fire detector wiring on the loop indicated, SOME FIRE COVER COULD BE LOST thus it is important to have the fault rectified as soon as possible. g) FAULT NET DEVICE MISSING 07 A device connected to the Anatec s RS485 network is not responding, possibly due to a wiring defect. h) FAULT: NET DEVICE FAULT 08 Indicates that a device connected to the Anatec s RS485 network is in a fault condition, if possible investigate the cause. i) FAULT: FAULT: DATA RAM FAULT or ROM FAULT The Anatec s internal self checking procedure has detected corruption of the fire panels configuration information or software. j) FAULT: AUXILIARY FUSE BLOWN The 24v DC auxiliary output fuse has blown, any devices powered by this output will cease to function. k) FAULT: EXTERNAL PSU FAULT ANATEC 11

Indicates that an external power supply monitored by the Anatec has developed a fault. FIRE INDICATIONS If a fire occurs, follow your particular fire routine. The fire alarm panel will sound the internal buzzer and turn on the alarm sounders in a sequence pre-programmed when the fire alarm system was commissioned. The panel will indicate what zone the fire is in on the top line of the LCD as well as lighting the appropriate zone fire indicator. The number of fires is shown in the top right of the LCD. If this number is greater than one then there are fires in the queue. To view these fires press the MORE button. The printer will also print the sensor location and zone description as well as the type of sensor that triggered the alarm. If a callpoint was responsible then the CALL POINT indicator will be illuminated. The COMMON FIRE indicator will also be illuminated. a) Fire number Total no. of fires FIRE: ZONE 3 1 OF 1 corridor ground floor Sensor location text Loop and address number including zone text are printed on the local printer. b) FIRE: PANEL 7 : LP1 A1 FACTORY ONE Indicates that a fire panel connected to the Anatec s RS485 network is signalling a fire, investigate the panel concerned and take any action as required. Loop and address number including the local text assigned during programming for that network panel are printed on the local printer. Anatec INSTALLATION INSTRUCTIONS Persons carrying out system design and installation should be familiar with BS5839 part 1, which is the code of practise regarding the installation of fire detection and alarm systems in buildings. The ANATEC 12

Anatec is an advanced fire detection system based on microprocessor control circuitry. It is therefore recommended that ESS are contacted for initial commissioning and future service requirements of any Anatec equipment. The following instructions should be followed, it is however recommended that installation is delayed until all building or maintenance work has been completed. If building work is being carried out in the vicinity of the installation it may result in damage to the panel. A. Remove the fire panel enclosure from its shipping carton Note: do NOT remove the lower packing cartons as these contain sensitive electronic equipment which should only be handled by an authorised ESS Engineer. B. Open the outer door using the key supplied, then unscrew the inner door retaining screw located on the rhs edge of the door. Remove the inner door by fully opening the door and then lift off the two 1hs hinges. Place the inner door inside the shipping carton for safe keeping. C. Once the cable entry routes have been decided remove the appropriate knock-outs from the top of the enclosure. D. Note the two 11mm-6mm keyhole slots and the two 6mm holes are cut in the back of the enclosure and set in dimples. E. The enclosure can now be securely fixed to the fabric of the building in the following way. Hold the enclosure on the wall in the desired mounting position and mark the location of the fixing holes. F. Drill and plug the wall in the four marked positions then fit the enclosure to the wall with appropriate fixing screws. G. Feed the required cables into the enclosure, then make off a reasonable working length (identify each cable). Remove any debris from the enclosure. Conduct all insulation tests (note the insulation tests must be done with the detectors and any other electronic devices disconnected from the wiring involved, failure to observe this could result in severe damage to the electronic parts in the associated detectors callpoints sounders etc). H. Once the detector loop(s) have been tested the detectors and callpoints can be fitted and addressed (fit the dust covers over the detectors). Install the sounders once the sounder circuit wiring has been verified, don t forget to fit the sounder Eol into the last sounder. Fill in the Anatec programming questionnaire and return to ESS Service Department. J. Refit the inner door and close outer lid. Contact ESS to arrange Commissioning of the fire alarm system. Cable Types A) Anatec Loop - As for B) panel alarm. ANATEC 13

B) Anatec Panel Alarm - Fire protected 2-core + screen. PVC sheathed MICC (PYRO TM ) CALFLAM TM FIRECEL TM FIRETEC TM FIRETUF TM FP200GOLD TM RADOX TM Conductor should be 1.5mm 2 minimum and 2.5mm 2 maximum using PCB mounted terminals. C) Network - 2-CORE TWISTED PAIR SCREENED (Reference: RS 362-184) However, if an alarm event at one panel affects the operation of another panel, a fire protected cable must be used especially when 8 way alarm auxiliary extender units are connected on the network. (Reference: CALFLAM CWZ). D) Repeater - 2 x 2-CORE TWISTED PAIR SCREENED (2 cores for signal + 2 (on network) cores for power). Again consideration must be made for using fire protected cable in the design. E) 8 Alarm Auxiliary - As for c) panel alarm. Extender Units (All < 100m) (output alarm/ (CALFLAM TM > 100m) auxiliary lines) When choosing your preferred cables you must take note of the following:- a) Cable must be 2 core with a screen + earth and must be insulated. b) The conductors should be 1.5mm 2 minimum. c) On the loop wiring the screen must be continuous along the full length of the loop. The screen of the cable should be connected to earth ONLY at the main control panel. d) Multicore cable should not be used for detector and loop wiring. e) Different loops or zones or alarms should NEVER be run within the same cable. However, use of 4 core (2 for loop and 2 for alarm level is permitted). f) Loop out and returns should NEVER be used within the same cable. g) Ensure correct polarity is maintained throughout all wiring. Cable Segregation All cables for the fire alarm system should be segregated from any other cables/wiring as defined in BS5839 Pt1 and IEE regulations. (For example, keep runs and devices at least 30cm away from fluorescent lights, 3 phase cables and heavy duty machinery and where necessary loop cables should cross power cables at 90 degrees. ANATEC 14

Mains Supply The Mains supply should be installed in accordance with the current edition of the IEE wiring regulations. ANATEC 15

Connection to the mains supply must be via an isolating protective device (e.g. an isolating fuse) reserved solely for the fire alarm system. The cover should be coloured red and labelled FIRE ALARM - DO NOT SWITCH OFF. The isolating protective device should be secure from unauthorised operation and ideally installed in a securely closed box with a breakable cover. An additional warning label should be provided, depending on whether:- Or a) The isolating protective device is fed from the live side of the main isolating device in which case the label on the isolating protective device, should read in addition WARNING: THIS SUPPLY REMAINS LIVE WHEN THE MAIN SWITCH IS TURNED OFF. A further label should be placed on the main isolating device reading WARNING: THE FIRE ALARM SUPPLY REMAINS LIVE WHEN THIS SWITCH IS TURNED OFF. b) If the isolating protective device is fed from the dead side of the main isolating device, a label should be fixed to the main isolating device reading WARNING: THIS SWITCH ALSO CONTROLS THE SUPPLY TO THE FIRE ALARM SYSTEM. Additional Instructions for Electromagnetic Compatibility When used as intended these fire alarm products comply with EMC Directive (89/336/EEC) and UK EMC regulations 1992 (SI 2372/1992) by meeting the limits set by the standards BS5406 (Pts 2&3), EN50082-1:1991 and EN50081-1:1992. The following installation guidelines must be followed:- 1. External cables must be connected using the cable entries or knockouts provided. 2. When routing external cables inside the product they must be: a) Kept as short as possible b) Routed close to the panel/enclosure c) Kept as far away as possible from electronics Any modifications other than those stated in these guidelines on any other used for these equipments specified may cause interference and it is the responsibility of the user to comply with the EMC and Low Voltage Directive. SYSTEM MAINTENANCE The following checks are recommended by Emergi-Lite Safety Systems in accordance with BS5839 pt 1 1988. ANATEC 16

1) Daily Inspection Check the system healthy indication on the LCD display, check the supply indicator is illuminated. Inspect for any fault indicators showing or sounder operating. 2) Weekly Test Perform a lamp test, ensure all indicators illuminate. Operate a call point or sensor to test the fire alarm system and sounders. Each week choose a different zone in rotation, also use a different call point or sensor so that all sensors/call points are tested in rotation. 3) Quarterly Test Check all previous log book entry s and verify that remedial action has been taken. Visually examine the battery and its connections. Operate a callpoint or sensor in each zone to test the fire alarm as in 2) above. Return panel to normal mode, isolate mains supply & perform evacuate to ensure the battery is capable of supplying the alarm sounders. 4) Annual Test As in 2) and 3) above additionally test all callpoints and sensors for correct operation. 5) Every 2-3 years Have the smoke detectors cleaned by a fire alarm engineer to ensure correct operation and freedom from false alarms. Contact ESS if in doubt. 6) Every 5 years Replace the sealed lead acid batteries. Consult ESS for more information. Servicing Emergi-Lite Safety Systems can offer a regular maintenance contract. EMERGI-LITE SAFETY SYSTEMS LTD BRUNTCLIFFE LANE MORLEY LEEDS LS27 9LL TEL: 0113 281 0600 FAX: 0113 281 0601 APPENDIX 1 ANATEC USER MENU STRUCTURE ANATEC 17

MAIN USER MENU LAM PAN ISOL ENG QUIT PERFORM LAMP TEST NO ACCESS QUIT MENU SYSTEM FAU TIM LOG WALK LIST CURRENT FAULTS SET TIME/DATE PRINT EVENT LOG WALK TEST ZONE DET CLR PRI ISOLATE ZONE ISOLATE DETECTOR CLEAR ALL ISOLATIONS STOP GO ISOL ISOLATE PRINTER ENABLE PRINTER PRINT LIST OF ISOLATED DETECTORS ANATEC 18