INVITATION TO TENDER ITT NO. PS KILLARNEY COMMUNITY CENTRE ENERGY UPGRADE ADDENDUM NO. 2

Similar documents
.2 Section Waste Management and Disposal..4 Section Electrical General Requirements.

Fort Rouge Leisure Centre Section HVAC Upgrades Phase 2 Page 1 of 5 Bid Opportunity No March 2013 FIRE ALARM SYSTEMS

CONTENTS AUTOMATIC TRANSFER SWITCHES

TECHNICAL STANDARDS SECTION

A. Section includes distribution panelboards and lighting and appliance branch-circuit panelboards.

Student Services & Classroom Addition. A. Section includes distribution panelboards and lighting and appliance branch-circuit panelboards.

CALL FOR TENDER - MUNICIPALITY OF THE DISTRICT OF CLARE LITTLE BROOK, N.S.

A. This Section includes the following lighting control devices:

A. This Section includes the following lighting control devices:

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 11/06/2018

SECTION AUTOMATIC TRANSFER SWITCHES

IN2 Lighting Control Devices

Project No Belleville Fire Hall/Headquarters and Emergency Operations Centre Section Belleville, Ontario Page 1 of 10

SECTION AUTOMATIC TRANSFER SWITCHES

SLATE. Base Module INSTALLATION INSTRUCTIONS R8001A1001

.4 Do complete installation in accordance with latest Electrical Bulletins of the local inspection authority.

CERTIFICATION BULLETIN

Updated: September 12, 2018 DIVISION INTEGRATED AUTOMATION. INTEGRATED AUTOMATION Page 1 of INTEGRATED AUTOMATION

INVITATION TO TENDER ITT PS CONSTRUCTION OF STANLEY PARK MINI TRAIN STATION. AMENDMENT No. 4

SECTION LIGHTING CONTROL DEVICES

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL

FIRE ALARM SYSTEM 1.1 GENERAL REQUIREMENTS

SECTION SAMPLE SPECIFICATION FOR BOILER CONTROLLER CONVERSION KIT

.2 Section Waste Management and Disposal.

SECTION ENCLOSED CONTROLLERS

SECTION DOMESTIC WATER PRESSURE BOOSTING SYSTEMS (VFD) PART 1 - GENERAL 1.1 SUMMARY

CSI Master Format 2004 Guide Specification for: Freezer Frost Heave Prevention (Mineral Insulated)

VACUUM BREAKER MEDIUM VOLTAGE AUTOMATIC TRANSFER SWITCHES

COMMON WORK RESULTS FOR ELECTRICAL: Basic Electrical Materials Methods

SECTION LOW VOLTAGE LIGHTING CONTROLS

EG Controls. SLIMVIEW 120 VOLT FLOAT SERIES DUPLEX PUMP CONTROL PANEL SPECIFICATION for CITY OF E G

SPECIFICATION: AlarmLine TM INTELLIGENT LINEAR HEAT DETECTION

Brown University Revised June 29, 2012 Facilities Design & Construction Standards SECTION ELECTRICAL DESIGN CRITERIA

DTW Works Master Specification Version 2006 Issued 2006/08/01 Section15621 Packaged Reciprocating Water Chillers Page 1 of 5

SECTION P01 LIGHTING AND APPLIANCE PANELBOARDS - A-SERIES

DIGITAL CENTRALIZED Section NANOMASKIT

SECTION BUILDING AUTOMATION SYSTEM

M001. Revenue Services ISSUED FOR CONSTRUCTION SEPTEMBER. 2, East State Parkway Schaumburg, Illinois Do Not Scale Drawings

SECTION CENTRIFUGAL WATER CHILLERS

UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW

Replacement of Fire Pump and Generator Upgrade, H Building, Sexton Campus

1.1 REFERENCES.1 American National Standards Institute/National Fire Protection Association (ANSI/NFPA).1 ANSI/NFPA 20, Centrifugal Fire Pumps.

LIGHTING CONTROL DEVICES

SECTION LIGHTING CONTROLS

CONSTANT PRESSURE CONTROLLER

FTA550 JOCKEY PUMP CONTROLLERS

Allegany College of Maryland ACM Welcome Center M&D Project No

Installation and Maintenance Manual IM Single Duct VAV Terminals. Group: Controls Part Number: IM 1093 Date: February 2015

SECTION PANELBOARDS Painting Wire and Cable Overcurrent Protective Devices.

PWGSC Ontario MULTIPLEX FIRE ALARM SYSTEM Sect Region Project Page 1 Number R

SECTION SOLAR PHOTOVOLTAIC (PV) POWER GENERATION SYSTEM

SmartVFD HVAC and BYPASS

Single Point Freeze Protection Heat Trace Control TRACON MODEL FPT 130 Installation and Operation Manual

This is a preview - click here to buy the full publication. High-voltage switchgear and controlgear

SECTION AUTOMATIC TRANSFER SWITCHES

SPECIFICATIONS - DETAILED PROVISIONS Section Magnetic Flowmeters C O N T E N T S

SECTION PANELBOARDS. A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section.

"ESDDR" Series Electric Humidifier

SECTION ROTARY-SCREW WATER CHILLERS

SECTION POWER SUPPLIES AND DISTRIBUTION

AT10.1 Series Microprocessor-Controlled Float Battery Charger (single phase input)

TOWER IQ Stand Alone or Building Automation Controlled Options Scalable to meet any application Energy Saving VFDs

POINT OBSTRUCTION CONTROLLER POC TOUCHSCREEN CONTROLLERS

DIESEL Engine Fire Pump Controllers Features

Union County Vocational - Technical Schools Scotch Plains, New Jersey

Dual Point General Purpose Heat Trace Control TRACON MODEL GPT 230 Installation and Operation Manual

NGC-40 Advanced Heat-Tracing Control System

MODEL FPT-130 SINGLE POINT FREEZE PROTECTION HEAT TRACE CONTROL

Water-Cooled Modular Chillers. Product Data Catalog. Standard and Total Access Modules MS010X, MS015X, MS020X, MS030X, MS040X, MS050X, MS070X, MS085X

APC BC300 Series 40kW 208/450/480V User Guide

PART GENERAL 1.01 SECTION INCLUDES

Wilo Top S Wet Rotor Circulation Pumps. Engineering Specification

PRODUCTS AND SOLUTIONS FOR PUMPING, IRRIGATION AND PIPING

1. Division 26 Section Electrical General Requirements. 2. Division 26 Section "Wiring Devices" for wall-box dimmers and manual light switches.

SECTION GENERATOR PARALLELING CONTROLS

DETEX ARCHITECTURAL SPECIFICATIONS, June 2012 AO19 SERIES HEAVY DUTY LOW-ENERGY ELECTRIC SWING DOOR OPERATOR

Dual Point General Purpose Heat Trace Control TRACON MODEL GPT 230 Installation and Operation Manual

SmartVFD HVAC and BYPASS

This guide will discuss the scope of work, and technical requirements of connecting to the Energy Transfer Station(s) (herein referred to as ETS).

A. Hydraulic calculations shall be prepared in accordance with Chapter 23 of NFPA 13 with the following exceptions:

CITY OF MEXICO BEACH REQUEST FOR QUOTES: LIFT STATION PANELS REPLACEMENT

Guide Specification Model CTG Automatic Transfer Switch

Static Pressure Control

MODEL GPT-130 SINGLE POINT HEAT TRACE CONTROL THERMOSTAT

elite Model ELN Centralized Emergency Lighting Inverter Systems 550 W to 1.5 KW Systems

SECTION C. Section Cable Trays for Electrical Systems: Additional identification requirements for cable tray systems.

Pipe Freeze Protection Control SCFP-CO-F130 Installation and Operation Manual

NITROGEN-GENERATING SPRINKLER CORROSION INHIBITING SYSTEM

ELECTRIC AIR HEATER INSTALLATION AND SERVICE MANUAL

.4 Section Ductwork Low Pressure Metallic to 500 Pa..3 ANSI/ARI 640 Commercial and Industrial Humidifiers.

AS950 REFRIGERATED SAMPLERS

Princeton Joint Unified School District Invitation for Bid Installation of District-Wide Lighting Occupancy Sensors

November 11, City of Sparks 215 S. 21 st St. Sparks, NV

Sintrol Snifter A2 EX. Manual. Version 1.2.3

UW Purchase Specification Section Steam Condensate or Hot Water Meter Page 1 of 9

PUMP CONTROL CENTER (PCC)

Model LTN-3R Outdoor Rated Uninterruptible Power System Single Phase

PANELBOARDS & BUILDING DISTRIBUTION

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION IBAS LIGHTING CONTROL

MASTER JOCKEY PUMP CONTROLLER. Model JPCE INSTRUCTION MANUAL. C 2018 Master Control Systems, Inc

Transcription:

FINANCE, RISK AND BUSINESS PLANNING GROUP Supply Chain Management November 4, 2015 INVITATION TO TENDER ITT NO. PS20151058 KILLARNEY COMMUNITY CENTRE ENERGY UPGRADE ADDENDUM NO. 2 RE: Insert attached Section 26 29 11 Variable Speed Drives into the specifications Please refer to the attached document Section 26 29 11 to be inserted into the Mechanical System Energy Upgrade Specifications. RE: Additional drawing related to M-4 Schematic Room Plan Please refer to MSK-2 for the following Heating Water Distribution Schematic New a. New high temperature return header, piping and valves; b. Additional shut off valves on low temperature return line. This addendum must be completed, and attached to your Tender form. If you have already submitted your Tender, this addendum shall be submitted to the Supply Chain Management Office, City of Vancouver, 453 West 12 th Avenue, Vancouver, British Columbia, Canada, V5Y 1V4, (Courier Delivery and Drop off is at the Information Desk, Main Floor Rotunda of the same address), prior to the Closing Time: 3:00:00 pm Local Vancouver, BC Time, in an envelope clearly marked Addendum No. 2 to Invitation to Tender No. PS20151058: Killarney Community Centre Energy Upgrade. NAME OF VENDOR SIGNATURE OF AUTHORIZED SIGNATORY DATE Donabella Bersabal Contracting Specialist City of Vancouver, Finance, Risk and Business Planning Supply Chain Management 453 West 12th Avenue Vancouver, British Columbia V5Y 1V4 Canada tel: 604.873.7263 fax: 604.873.7057 website: vancouver.ca

Part 1 General 1.1 RELATED SECTIONS.1 Section 26 05 00 Common Work Results.2 Section 26 05 21 Wires and Cables 1.2 SECTION INCLUDES.1 Variable speed drives for fan as indicated. 1.3 REFERENCES.1 Canadian Standards Association (CSA International).1 CSA C22.1-06, Canadian Electrical Code, Part 1 (20th Edition), Safety Standard for Electrical Installations..2 CAN/CSA-C22.3 No. 1-01(Update March 2005), Overhead Systems..3 CAN3-C235-83(R2000), Preferred Voltage Levels for AC Systems, 0 to 50,000 V..2 Electrical and Electronic Manufacturer's Association of Canada (EEMAC).1 EEMAC 2Y-1-1958, Light Gray Colour for Indoor Switch Gear..3 Institute of Electrical and Electronics (IEEE)/National Electrical Safety Code Product Line (NESC).1 IEEE SP1122-2000, The Authoritative Dictionary of IEEE Standards Terms, 7th Edition. 1.4 ACTION AND INFORMATIONAL SUBMITTALS.1 Provide submittals in accordance with Section 01 33 00 - Submittal Procedures..2 Product Data:.1 Provide manufacturer's printed product literature, specifications and datasheet and include product characteristics, performance criteria, physical size, finish and limitations..3 Shop Drawings:.1 Provide shop drawings: in accordance with Section 01 33 00 - Submittal Procedures..1 Provide shop drawings for each type of variable speed drive to indicate:.1 Mounting method and dimensions..2 Variable Speed Drive size and type..3 Layout and components..4 Enclosure types..5 Wiring diagram. Prism Engineering Ltd. Page 1

1.5 CLOSEOUT SUBMITTALS.6 Interconnection diagrams..1 Provide maintenance materials in accordance with Section 01 78 00 - Closeout Submittals..2 Submit operation and maintenance data for each type and style of variable speed drive for incorporation into maintenance manual. Part 2 Products 2.1.1 Variable Speed Drive shall be as manufactured by:.1 Danfoss/Graham;.2 ABB;.3 Schneider;.4 Or Eaton..2 To be mounted in a metal enclosure with hinged door; Drives shall be CSA and ULC certified;.3 Drives shall carry a minimum 3-year on-site parts and labour warranty;.4 Rating: at 20 HP, 600V, 3 phase, 60 Hz. VSD to be rated for RF-1.5 Rating: at 25 HP, 600V, 3 phase, 60 Hz. VSD to be rated for SF-1 2.2 General Features:.1 Suitable to be capable of continuous operation at a minimum of 100% of rated motor full load current..2 Door interlocked, padlock able circuit breaker that will disconnect all input power from the drive and all internally mounted options;.3 Door mounted keypad with complete programmability of display, including Hand- Off-Auto, Run, Digital Speed Control on hand mode, and Help key;.4 Real time clock including date and time stamp on all fault conditions;.5 Unit shall be mounted in a metal enclosure with temperature controlled cooling fans as per manufacturers recommendation;.6 Drive efficiency of 97% or greater at full load;.7 Over voltage and under voltage protection;.8 Built in PID controller;.9 Programmable analog inputs shall be provided and shall accept a direct-or-reverse acting signal. Analog reference inputs accepted shall include voltage (0 to 10 V DC, 2 to 10 V DC) and current (0 to 20 ma, 4 to 20 ma) input;.10 Programmable 0 to 20 ma analog outputs shall be provided for indication of VSD status. These outputs shall be programmable for output speed, frequency, current and power. They shall also be programmable to provide a selected 24 V DC status indication;.11 Network communication with DDC system with BACnet protocol;.12 USB port for PC programming access; Prism Engineering Ltd. Page 2

.13 Drives shall fail to ByPass (full speed) in the event of a Variable speed drive or control system failure..14 Factory wired and tested bypass system consisting of an output contactor and bypass contactor. Overload protection shall be provided in both drive and bypass modes. Operation shall switch to bypass mode automatically upon failure of VSD..15 Provide on cover or adjacent to each VSD an operations, laminated tips sheet. Each sheet shall include steps for general operation and methods for general operation including steps for switching to bypass. Include emergency contact information for support..16 Provide universal harmonic filter for VSD to mitigate harmonics as per manufacturer recommendations for each VSD specified. 2.3 Primary Protection Between VSD and Power Supply (Line Reactor).1 EMI/RFI filters to attenuate radio frequency interference conducted to the AC line..2 The VSD shall have a 5% impedance inductive line reactor, DC Link Choke, upstream of each VSD to reduce the harmonics to the power line and to add protection from AC line transients. The 5% impedance may be from dual (positive and negative DC bus) reactors, or 5% AC line reactors. 2.4 Secondary Protection Between VSD and Motor (Load Reactor).1 Secondary protection between drive and motor shall include a 5% load reactor. 2.5 FINISHES.1 Apply finishes to enclosure in accordance with Section 26 05 00 - Common Work Results for Electrical. 2.6 EQUIPMENT IDENTIFICATION.1 Provide equipment identification in accordance with Section 26 05 00 - Common Work Results for Electrical..2 Supply nameplates for VSD identification. Nameplates shall indicate equipment being controlled and voltage. Fasten or cement nameplates to equipment in a conspicuous location. Part 3 Execution 3.1 INSTALLATION.1 Install variable speed drives and control devices in accordance with manufacturer's instructions..2 Confirm fan nameplate and adjust overload device to suit..3 Provide wiring and any additional devices required to integrate the new drives to existing DDC system and alarm system. Reroute or extend all control wiring to suit. Prism Engineering Ltd. Page 3

.4 Add a lamicoid warning label to existing safety switch. Label to read as follows, Emergency Use Only. Do not operate unless VSD has first been turned off..5 Where required, construct a structural mounting stand, seismically secured to floor, for the mounting of the VSD s..6 Remove and dispose old motor starters after the variable speed drive installation and testing. 3.2 WIRING.1 Include for the VSD wiring and conduit installation..2 Use separate conduit installation for each of the following: motor wiring, fire alarm wiring, power wiring, and control wiring. Install all wiring in conduit. Flexible liquid tight flexible conduit to be used for connection to motor..3 Provide all required relays, contactors and equipment for interfacing any specified equipment with fire alarm system and provide verifications of system as required..4 Once transfer of existing power and control wiring to new VSD is complete, remove all redundant or obsolete wiring from the existing starter. 3.3 GENERAL WIRING.1 All wiring, devices, starters and equipment shall be new and CSA or suitably approved unless otherwise noted. Obtain Warnock Hersey or local electrical inspection authority approval for any specified non-csa electrical equipment. Equipment of same type shall be of same manufacturer..2 Fusible devices shall be of heavy-duty type with fuse clips and English Electric or Gould Shawmut class J fuses..3 Ground electrical equipment and wiring in accordance with Canadian Electrical Code and Local Inspection Authority s Rules and Regulations. Ground wire for drive shall be hydraulically crimped to the building ground wire..4 All wiring shall be colour coded copper minimum #12 AWG RW-90 X-link for runs up to 23 m (75 feet) and minimum #10 AWG over 23 m (75 feet) sized to suit load or as otherwise noted. Wire shall be run concealed in EMT conduit..5 Provide code sized ground line in each new service. Conduit cannot be used as ground..6 Conduit shall be of sufficient size to permit easy removal of conductors at any time. Do not end conduit over sharp objects. Improperly formed bends will not be accepted. Do not use bends and fittings together..7 Run conduits in finished areas concealed, above finished ceiling, in walls and in partitions. Run conduit in fan rooms and penthouses exposed and installed at right angles or parallel to building lines, accurate in line and level..8 Install conduits and cables to provide maximum head room and to interfere as little as possible with free use of spaces through which they pass. They shall be installed as close to building structure as possible. Install conduit and cables to avoid proximity to water and heating pipes. They shall not be run within 6 (150mm) of such pipes except where Prism Engineering Ltd. Page 4

crossing are unavoidable, in which case they shall be kept at least 1 (25mm) from covering of pipe crossed..9 Carefully routes new conduits and other new services so that they do not interfere with existing installation. Arrange and pay for any necessary relocation of existing conduit, cable tray, bus duct or any other services required for the proper installation of new Work, regardless of whether the conduit, tray or duct to be moved is the work of trade doing new Work. 3.4 FIELD QUALITY CONTROL.1 Perform tests in accordance with Sections 26 05 00 - Common Work Results for Electrical, 01 91 13 Testing and Commissioning and manufacturer's instructions..2 Check that sequence controls, interlocking with other separate related starters, equipment, control devices, operate as indicated..3 An approved representative of the drive manufacturer shall set-up, start and commission the drive and fan combinations on site..4 A complete report with all VSD parameters and readings, which includes but not limited to VSD and accessories technical information, model and serial number, installation check-out, voltages and amperages on normal and bypass mode, motor information data, ambient and inside enclosure temperatures, measurements of the harmonics and voltage peaks at the motor, and all setup parameters, shall be submitted to the Consultant. END OF SECTION Prism Engineering Ltd. Page 5