AIR CURTAIN COMPACT 2 SURFACE MOUNTED RANGE

Similar documents
AIR CURTAIN T SURFACE MOUNTED RANGE

AIR CURTAIN HX RECESSED RANGE

AIR CURTAIN PHV SURFACE MOUNTED RANGE

AIR CURTAIN HX RECESSED RANGE

PHV-RECESSED RANGE AIR CURTAINS INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS

T-RECESSED RANGE AIR CURTAINS INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS

INCORPORATION & INSTALLATION INSTRUCTIONS. For incorporating a heat pump control system by others

HP RECESSED HEAT PUMP RANGE AIR CURTAINS INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS. For use with Mr Slim Outdoor Units

Instruction Manual WARNINGS

PHV2000NT CHILLED WATER HEAT PUMP, SENSIBLE/DRY COOLING UNIT INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS

VRF HP HEAT PUMP RANGE AIR CURTAINS INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS. For use with City Multi (VRF) systems

Recessed. Air Curtain. Fig 1. Recessed air curtain

MRXBOX95-WALL. Mechanical Ventilation Unit with Heat Recovery for Wall Mounting Installation and Maintenance. Extract air.

RECESSED WARM CEILING HEATERS MODELS HSRCH3000RF, HSRCH4500RF INSTALLATION AND OPERATING MANUAL

SURFACE WARM CEILING HEATERS

The CAB & DAB Air Curtains

Natural Ventilation. e-stack A-Series Ventilation System for Buildings with Atria. Installation and Maintenance. Palletised

Original instructions AR

MRXBOX95B-LOFT. Mechanical Ventilation Unit with Heat Recovery & Summer Bypass for Loft Mounting. Installation and Maintenance

MEV-DC. Continuous Mechanical Extract Ventilation Units Installation and Maintenance. Figure 3. Fixing screw hole.

Installation Instructions & Operating Manual IMPORTANT

ECOSMART TWINFANS. (EST) 1 phase, Direct Drive, Run & Standby Fans for indoor use. Installation and Maintenance

MEV Ecosmart. Installation and Maintenance. Continuous Mechanical Extract Ventilation Units. 1.0 Introduction

INFRARED IP55 HEATER INSTRUCTIONS FOR: MODEL:- QZWP45N 1. SAFETY INSTRUCTIONS

XB-EFA-8L-BK & XB-EFA-8R-BK

CASSETTE UNIT. Comfort Circle

Surface Warm Ceiling Heaters

isense & isense-ht 230V Flush Mounted Domestic Continuous Extract Fans

AP-EH500-L/RQA9837. Installation Guide

Recessed Warm Ceiling Heaters

Installation, operation and Maintenance Manual

CENTRIFUGAL FAN IN SCROLL CASING. Helix S-Vent OPERATION MANUAL

FAITH (dmev) 230V / 24V DC SELV Flush Mounted Domestic Continuous Extract Fans

Commercial Fan Heater

INDOOR USE ONLY. Installation and Maintenance XTRACTOR. (ESX) 1 and 3 phase, Direct Drive, Fans for indoor use

ECOSMART TWINFANS. (EST-X/R/B) 1 phase, Direct Drive, Run & Standby For External, Roof Mounted and Internal use Installation and Maintenance

User Instructions for Remote Controlled 2kW Rotisserie Effect Fan Heater Model 1276

Wind. Service instruction

Imperial Electric Fires

TECHNICAL MANUAL CX(E) SPLIT SYSTEMS. Tel: Fax:

Hand Dryer Installation & User Manual

ECOSMART XTRACTOR. (ESX-X/R/B) 1 phase, Direct Drive For External, Roof Mounted and Internal use Installation and Maintenance.

EVG Extractors. Manual for Installation, Use and Maintenance

MODELS HSCFH60WX, HSCFH90WX, HSCFH120WX

Manual Comfort Air Curtain

QUALITY SPACE HEATERS

Ecosmart Boxer. AHU s (Fan Speed Control only) Installation and Maintenance. LPHW Heater

Contact Details. Please note that some of the contact details on this PDF document may not be current.

Model 1174 Electric Heater User instructions for LED effect 2kw Inset Heater

INLINE СENTRIFUGAL FAN BOX BOX-R OPERATION MANUAL

AC25. Art.nr:

USER S MANUAL. VKP Series INLINE FAN

Installation and Maintenance. Opus OK / Genie NKF1 Kitchen Extract Unit. Contents IMPORTANT WARNING IMPORTANT! Introduction WARNING!

Unvented Electric Water Heater 10/15 litre Undersink

IMPORTANT INSTRUCTIONS READ & SAVE

Original instructions. Panther 6-15 kw

INLINE CENTRIFUGAL FAN. Centro-M OPERATION MANUAL

MRXBOX95-LH1/LH2. Mechanical Ventilation Unit with Heat Recovery for Loft Mounting Installation and Maintenance. Spigot 4.

USER S MANUAL. VCU/VCUN Series CENTRIFUGAL FAN IN SCROLL CASING

IMPORTANT INSTRUCTIONS READ & SAVE

Calm. Service Instructions

SOUND-INSULATED FAN. Iso-K OPERATION MANUAL. Iso-K_v.1(2)-EN.indd :20:59

Electronic Dual Cylinder Thermostat Installation Instructions

ZIP InLine. Models: ES3, ES4 & ES6. Electronic Instantaneous Water Heaters. ES3, ES4 & ES6 Instructions. V1.09 Page 1 November / 2015

Whole Room Dryer WRD, WRD/110

FLCH4R Garage and Utility Electric Heater

WORLDWIDE DISTRIBUTORS

Sanitary Water Tank INSTALLATION & SVC MANUAL

IMPORTANT INSTRUCTIONS READ & SAVE

Installation and Maintenance

FHHT 18 3 PHASE /32A / 400V ELECTRIC HEATER PRODUCT MANUAL P

Instructions for the fan motor control system with integrated wiring terminals SILVER C

IMPORTANT INSTRUCTIONS READ & SAVE

Installation & Service Manual. Models ALF 20, 30, 40, 50, 60, 80

SMARTELEC 2 ENERGY SAVING CONTROL INSTALLATION AND OPERATING MANUAL

General Care and Safety Guide

HHWCH51 Galvanised Hot Water Coil Heater

Installation and Maintenance

EDGE PATIO HEATER. User Manual. English

Installation, operating and servicing instructions

"WHHR125DC" Whole House Heat Recovery Unit with Low Energy DC Motor. Installation, Operating and Maintenance Instructions domestic and commercial use

USER'S MANUAL INLINE CENTRIFUGAL FANS IN SOUND-INSULATED CASING VS, VS EC SERIES

ECONOPLATE H1-heat only HEAT INTERFACE UNIT. Installation, Commissioning and Servicing Instructions for vented systems.

Turbo. Service Instructions

OWNERS INSTRUCTION MANUAL

INSTALLATION, OPERATION AND MAINTENANCE MANUAL. Air curtain SMART

ISCG90SS _03 ISCG90SS

ECONOPLATE H1-heat only HEAT INTERFACE UNIT. Installation, Commissioning and Servicing Instructions for unvented systems.

LUCCI AIRFUSION FRASER DC CEILING FAN

VK902 Compact Combination Microwave Oven Installation, Use and Maintenance

Installation and Operating Manual Drying Cabinet

WARNING: Warns of health hazards and identifies possible risks of injury. CAUTION: Indicates possible dangers to the machine or other objects.

Titon HRV1 Q Plus HRV1.5 Q Plus HRV2 Q Plus Heat Recovery Ventilation Units

RE-PR3-E-27 3-Phase Panel Mount 27kW

SUPER ASTRA PRODUCT MANUAL. PM R20 Issue 3 1/00

PH1000T PH1500T PH2000T

LC3000 Level Controller Installation and Maintenance Instructions

IMPORTANT INSTRUCTIONS READ & SAVE

HS&S Alert No: 103 Date: 9 March 2017

Topvex SR 09, 11, Topvex TR Compact Air Handling Units

Transcription:

AIR CURTAI COMPACT SURFACE MOUTED RAGE ISTALLATIO, OPERATIO AD MAITEACE ISTRUCTIOS English T9900-- UK Page

` COTETS Page COTETS... ELECTRICAL SAFETY... SPECIFICATIOS.... ITRODUCTIO.... DELIVERY COTETS... 6. TOOLS REQUIRED... 7. ISTALLATIO... 6 8. ACCESS FOR ELECTRICAL COECTIO... 9 9. EXTERAL COTROLS... 0 0. MULTIPLE AIR CURTAI SYSTEMS.... SYSTEM COFIGURATIO.... FA SPEED SELECTIO.... COMMISSIOIG THE SYSTEM.... SIG OFF.... FAULT CODITIOS... 6. SERVICE & MAITEACE... 6 7. WARRATY... 7 APPEDIX A Dimensions of C Air Curtain Wall Mounted... 8 APPEDIX B Dimensions of C Air Curtain Ceiling Mounted... 9 APPEDIX A WIRIG DIAGRAM C-000E and C-00E... 0 APPEDIX B WIRIG DIAGRAM C-000E... APPEDIX C WIRIG DIAGRAM C-00E... APPEDIX D WIRIG DIAGRAM C-000W, C-00W, C-000W and C-00W... APPEDIX E WIRIG DIAGRAM C-000A, C-00A, C-000A and C-00A... 8. DECLARATIO OF COFORMITY... T9900-- UK Page

ELECTRICAL SAFETY Electrical Supply and Wiring to the Air Curtain All electrical wiring and connections MUST be carried out by a competent qualified electrician in accordance with the latest edition of IEE wiring regulations and local statutory regulations if applicable. A phase or phase local isolator having a contact separation of at least mm on all poles must be fitted in the electrical supply to the air curtain and located in an accessible position adjacent to the unit. The appliance must be connected by cables having an appropriate heat resistant temperature rating. All supply cables, circuit breakers and other electrical installation equipment must be correctly sized for the air curtain model being installed; see Section : Specifications. Models operating on a phase electrical supply - see Section : Specifications - require a neutral connection (~). A mm size cable gland or conduit connector of IP rating or above should be used for the Electrical Supply into the air curtain. See Wiring Diagrams for connecting electrical supply and control cables to the air curtain. The air curtain must be earthed. SPECIFICATIOS Air Curtain Model o Electrical Supply (V/ph/Hz) Rated Electrical Power Input (kw) Rated Current per phase (A) Heat Output [Low/High] (kw) Weight (kg) C-000A 0//0 0. 0.7 9 C-00A 0//0 0.0 0.9 C-000A 0//0 0.. 7 C-00A 0//0 0..6 C-000W 0//0 0. 0.7 / 6 C-00W 0//0 0.0 0.9. / 9 0 C-000W 0//0 0.. 6 / C-00W 0//0 0..6 7. / C-000E 00//0 9..7.9 / 9 9 C-00E 00//0.0 8. 6. / 7 C-000E 00//0 8. 7. 9.7 / 8 9 C-00E 00//0..0. / 6 Table T9900-- UK Page

. ITRODUCTIO Established in the 960s, Thermoscreens is a leading air curtain manufacturer that exports to over 60 countries worldwide. As with all our products, the Compact range of air curtains is designed with energy efficiency in mind. Compact models suffixed E, W or A are designed to be surface mounted inside a building and located horizontally over a doorway. They must not be installed on the outside of a building or built into a cabinet or recessed in any way. Please complete the following details for your reference: Date of Purchase Place of Purchase Serial umber Proof of purchase is required to make a claim under warranty. Thermoscreens Ltd St. Mary s Road uneaton Warwickshire England CV AU Email: sales@thermoscreens.com http://www.thermoscreens.com Tel: + (0) 768 66 Fax: + (0) 768 878 T9900-- UK Page

. DELIVERY COTETS The following items are supplied in the box at delivery. OTE: If any parts are missing or damaged contact your place of purchase. Compact Surface Mounted Air Curtain Ceiling and wall retaining brackets with M6 Washers and Fixing bolts Ceiling Wall ote: End caps are supplied loose to be fitted during installation -port control valve (for water heated units) Outdoor Air Thermostat (Optional) For Controller options, refer to separate OEM instructions supplied with air curtain Fitted in pipework to air curtain by installer Used for simple weather compensation control (disables heating on a warmer day) 6. TOOLS REQUIRED The following tools are required for installation: Flat blade screwdrivers Pozi head screwdrivers 0mm spanner Adjustable spanner Electric drill Ladders Appropriate lifting equipment T9900-- UK Page

7. ISTALLATIO The air curtain is designed to be located horizontally over a doorway. It must not be installed outside of the building. 7. Location Mount the air curtain above and as close to the doorway as possible, with: air curtain mounted up to a maximum.0m. For exposed locations,.m is the recommended mounting height. at least 00mm clearance (air gap) above electric/water heated air curtains, see Fig Beware of doorway top edges, structural beams, door opening/closure devices, etc., which may interfere with the air stream and affect the location of the unit. Fig OTE: For the air curtain to work well the width of the open doorway should be less than the length A of the air curtain, see Appendix. 7. Wall Fixing OTE: Use suitable wall fixing bolts (not supplied) to fix the unit to the wall, taking into account the type of wall and the weight of the unit (see Section : Specifications). For wall mounting, if required, front ceiling rail from top of the air curtain may be removed. Step Fix two wall brackets above door opening with minimum B and maximum C dimensions ensuring minimum distance between brackets C min. (see Appendix A). Ensure brackets are level with each other. 0 0 C B Fig Step Angle air curtain over doorway and place outer edge of discharge grille on lower channels of both wall brackets. Fig T9900-- UK Page 6

Step Push and hold air curtain towards wall. Line up one hexagonal insert on each wall bracket with top rear rail slots. Fig Step Step Through top rear rail slots screw one M6 x mm fixing bolt and M6 x 0mm washer onto each wall bracket insert (see and, Fig ). Ensure air curtain is mounted horizontal level. Tighten all fixing bolts until the air curtain is safely secured to the wall. Fig 7. Ceiling Suspension OTE: M6 threaded rods (not supplied) are used to suspend the unit from the ceiling. Suspend the unit from the ceiling as follows: Step Step Ensure front ceiling suspension rail is fitted to air curtain. Screw and bolt threaded rods into ceiling brackets as shown in Fig 6. Fig 6 Step Secure each suspension rod to a suitable structure that can support the weight of the unit (see Section : Specifications for weights). Step Hook each ceiling bracket into top rear and front hanging system rails as shown in Fig 7. Fig 7 T9900-- UK Page 7

Step Place retaining bracket on top front hanging system rail (see, Fig 8) and fix with M6 bolt (see, Fig 8). Repeat for other ceiling bracket. Step 6 To centralise unit over doorway, carefully slide air curtain left or right. Ensure air curtain is mounted horizontal level. Tighten all fixing bolts until the air curtain is safely hanging from the ceiling. OTE: Joining Kit is available to join two air curtains together. See separate instructions supplied with Joining Kit. WARIG: It is the sole responsibility of the installer to ensure that the fixing locations and suspension system used are suitable for the air curtain being installed. Fig 8 7. LPHW Models For LPHW models ensure that water isolation valves are fitted in the flow and return pipework adjacent to the air curtain connected correctly as shown in the diagram in Appendix. For the design of the water pipework system and pump, water flow rates and pressure drops for maximum heat output of the air curtain are given in Table below. Table Air Curtain Water Flow Rate Water Pressure Drop (l/min at 8/7 C) (kpa) C-000W, -row (6kW) 7.8. C-00W, -row (9kW).7.0 C-000W, -row (kw).6.0 C-00W, -row (kw) 9. 9.8 OTE: Water Pressure Drop is across the flow and return pipework to the air curtain and includes for the coil fitted inside the unit and the valve fitted in the heating pipework to the unit. Water flow rates and pressure drops at different water temperatures can be calculated using the Thermoscreens coil calculation programme. Visit the Thermoscreens website for details. The installer must connect the -port valve in the heating pipework as shown in Figure 9 below: mm pipe mm pipe wire valve to pcb inside air curtain A A/B B mm pipe mm pipe R E T U R F L O W Fig 9 T9900-- UK Page 8

8. ACCESS FOR ELECTRICAL COECTIO 8. How to access terminals To gain access to the air curtain for connection and commissioning, slide out both plastic end caps and hinge open bottom access panel as explained below. 8.. Remove plastic end caps Using a Pozi o screwdriver, unfasten single securing screw (see Fig 0) from each end cap. Fig 0 Carefully slide out plastic end cap from each side of the unit. All screws and end caps should be kept safe as they will be required later in the installation. 8.. Hinge open bottom access panel Fig Unfasten M6 securing bolts located on the top inside lip of access panel (see, Fig ). Fig Lift top edge of access panel upwards (see, Fig ) and hinge panel open (see Fig ). OTE: Above illustration detail wall mounted air curtain, but installation on site could just as well be ceiling mounted. Fig T9900-- UK Page 9

9. EXTERAL COTROLS 9. Remote switch contacts I0, I Terminals I0 and I on the Ecopower PCB inside the air curtain can be used to provide different control strategies using remote volt-free contacts (see Fig ). This could be to provide remote On/Off from a timer or BMS Digital/Output contact, to work with a door switch or for simple weather compensation control to disable heating when outdoor air temperatures become warmer. Table describes the different functions: Fig Table Function I0 otes Remote On/Off (IHIBIT) Unit operates normally in MAUAL Mode or AUTO Mode from the Remote Control Unit switches off after s, with fan run-on at Medium fan speed if DIP = OFF Use the Remote Control to set up unit and then hide it away if required. * On/Off is then done via I0 using a remote volt-free contact. Function I DIP I0 otes Door Switch Control Summer Winter After 0s the heating is disabled and the fan goes to low speed Unit operates normally in MAUAL Mode or AUTO Mode from the Remote Control COLD DAY Unit operates normally in MAUAL Mode or AUTO Mode from the Remote Control Heating is disabled straight away, Fan speeds operate normally from the Remote Control WARM DAY O OFF Door Open:- ormal Control Door Closed:- Heating Off Low Fan Speed Simple weather compensation control using an outdoor air thermostat with volt free contacts (see Section 9.) OTE: Wire volt-free, remote switch contacts to -way screw terminals I0 and I using -core cable. WARIG: Do not apply any voltage to terminals I0 and I as this will damage the Ecopower PCB inside the air curtain. * OTE: The Ecopower Remote Control must stay plugged-in for the air curtain to keep working. An optional plug-in EEPROM is available from Thermoscreens so the Remote Control can be unplugged and the air curtain stay working. Visit the Thermoscreens website for details. T9900-- UK Page 0

9. Overheat safety cut-out indication For electric heated air curtains the Ecopower PCB includes a fault indication signal for if the overheat safety cut-out on the electric heater operates. Volt free changeover contacts (6A 0VAC 0VDC) can be wired via the -way screw terminal HEALTHY (see Fig ). Refer to Section.: Overheat Safety cut out, for how to reset a overheat safety cut-out situation. Fig O HEALTHY C C ALARM! 9. Weather compensation control (Summer/Winter) To save heating energy on warmer days a simple weather compensation (Summer/Winter) heat control strategy can be used. Fit an outdoor air thermostat with volt-free contacts (supplied by the installer) to a north facing wall. Use a -core cable to connect the outdoor air thermostat to -way terminal I on the Ecopower PCB (see Fig 6) On the Ecopower PCB, set DIP to OFF as per Table, (see Section 9.: Remote switch contacts I0, I). Fig 6 Switch Contact Closed = Heating Enabled (cold day) Switch Contact Open = Heating Disabled (warm day) Outdoor Air Thermostat WARIG: Do not apply any voltage to terminal I as this will damage the Ecopower PCB. OTE: To promote increased energy saving a more advanced weather compensation control strategy is available from Thermoscreens. Using a heating curve, the discharge air temperature of the airstream coming from the air curtain is controlled against the outside air temperature. Visit the Thermoscreens website for details. 0. MULTIPLE AIR CURTAI SYSTEMS For master/slave control, plug and connect units together with Thermoscreen RJ extension cables (not supplied) as per Figure 7 below. Each air curtain must have its own electrical supply. maximum 8 units Fig 7 T9900-- UK Page

. SYSTEM COFIGURATIO. Optional features WARIG: Isolate and disconnect air curtain from the power source before making any changes. DIP switches on the air curtain Ecopower PCB (see Fig 8) provide the following optional features, as explained below: Fan heat interlock Disable fan run-on Thermostat master (for master/slave installations) Weather compensation heat control (Summer/Winter) Door switch control Fig 8 Feature DIP setting Default otes Fan heat interlock Allows fan speed to govern heat output on electric heated units. If low or medium fan speed is selected, a lower heat output results. High heat operates only on high fan speed. Disable fan run-on The minute fan run-on after switch off is enabled or disabled on electric heated air curtains. Thermostat master For master/slave installations. Only the air sensor in the thermostat master air curtain is used to measure air temperature. Set DIP to O in the air curtain that will be the master unit. Weather compensation control or Door switch control Simple weather compensation control to save heating energy. or Door switch control. DIP O DIP O DIP O DIP O O Heat output is governed by fan speed. OFF Fan run-on at medium speed enabled. OFF Air curtains in master/slave systems all act independently. OFF I Weather compensation O I Door switch This feature is only used with electric heated air curtains to limit very high air temperatures. Set DIP to OFF if unit is water heated or ambient. Must only be used for water heated or ambient air curtains. Each air curtain must have DIP set to O for no fan run-on. Air sensor thermistors in all slave air curtains will be ignored. Stops some units blowing cold air and others blowing warm air in master/slave systems on larger doorways. See Section 9. Remote Switch Contacts I0 and I for details Weather compensation control is the same as Summer/Winter control OTE: rectangle is moveable head of DIP switch. OTE: A range of advanced factory fitted and plug-in control options are available from Thermoscreens to enhance the performance of the Ecopower PCB controller inside the air curtain. These include advanced weather compensation control using a heating curve, outlet air temperature control, ECObus Modbus BMS control, modulating heater outputs and EEPROMs for non-standard control strategies. Visit the Thermoscreens website for details. T9900-- UK Page

. FA SPEED SELECTIO Factory settings for the fan speeds are shown in Table below: (refer also to wiring diagrams in Appendix ) Table Fan Speed HIGH (black wire) MEDIUM (blue wire) LOW (red wire) Maximum air velocity at outlet grille (m/s) 9.0 Maximum air curtain mounting height (m).0 (.m exposed) 7.0.0 Sound Pressure Level of air curtain [db(a) at m] C-000-0 C-00-0 C-000 - C-00 - C-000-8 C-00-8 C-000-9 C-00-0 C-000-6 C-00-6 C-000-7 C-00-8 Air Volume Flow Rate (m /h) [for E & A] 0 800 00 00 0 60 7 77 0 7 00 00 Sound pressure levels db(a) at m distance are for a single air curtain mounted at its maximum mounting height, operating in a room with average acoustic characteristics as defined in CIBSE Guide B (reverberation time 0.7s at khz) and a room size equivalent to 8 air changes per hour (ac/h). Care needs to be taken when selecting air curtains for an installation as noise levels can be several db higher if the mounting height is reduced, if the room is more live (i.e. hard surfaces, no furnishings or absorbent materials), if the room is smaller than 8 ac/h equivalent or a combination of these factors. oise levels will also increase if more than one air curtain is installed at the same doorway (e.g. +db(a) for equal point sources: direct field). T9900-- UK Page

. COMMISSIOIG THE SYSTEM. Verify system operation To commission the system, verify the following conditions are met: All fans are working. Fans operate at Low, Medium and High speeds. There is no excessive mechanical noise coming from the fans. When heating is selected, the air stream from the discharge grille warms up across the whole length of the air curtain. When set to manual with fans set to high speed, heating increases as higher heat is selected. Warm air reaches across the doorway with door open or closed. Ecopower Remote Control operates correctly in both manual and auto modes. OTE: To restrict heat output for standard C-000E and C-00E air curtains, disconnect second stage heating by removing push-on terminals K, K and K7 from Ecopower PCB. To convert three phase electric heated models to single phase please visit the Thermoscreens website.. Instruct customer and hand over Before leaving site, hand over the installation to the customer/end user or their representative. Explain that any person operating the air curtain must be given supervision and instruction by the person responsible for their safety, concerning the safe use of the unit and to understand any hazards involved. Children and those with reduced physical, sensory or mental capabilities should not operate the air curtain. Recommend that the doorway should be closed whenever possible but that during times of high pedestrian use it will become an open doorway. The air curtain then serves an essential purpose by saving energy and providing comfort to occupants. Explain that the inlet grilles must be cleaned regularly and the unit serviced at schedule intervals see Section 6: Service & Maintenance. OTE: Leave these instructions with the customer/end user or their representative!!. SIG OFF Complete the following once commissioning is completed: Installer signature Installer name Installer company Date Customer signature Customer name Customer company Date T9900-- UK Page

. FAULT CODITIOS. Overheat Safety cut-out An overheat fault in electric heated units may cause the overheat safety cut-out(s) to operate. This is indicated by flashing LEDs on the Remote Control and a red status LED on the Ecopower PCB inside the air curtain. Before resetting ensure there is adequate air flow from the air curtain and the unit has been commissioned as per Section. To reset a overheat safety cut-out: Step Step Step Step Switch off the electrical supply to the air curtain. Allow time for the air curtain to cool down, typically 0 minutes. Switch on the electrical supply to the air curtain. Press the Auto button on the Ecopower remote control times. Air curtain heaters will then operate and after 0 seconds the LEDs on the remote control will stop flashing and the status LED on the Ecopower PCB in the air curtain will flash green.. Fuses In the event of an electrical fault internal electrical fuses may operate. There are two internal fuses located on the Ecopower PCB inside the air curtain: Fuse 6.A(T) supplies the fan motors within the air curtain Fuse 00mA(F) controls the circuitry of the Ecopower PCB. Ecopower PCB status indication There is a status LED on the Ecopower PCB inside the air curtain (See LED shown on Wiring Diagrams in the Appendix). This indicates the status of the Ecopower Control system as follows:. LED flashing green operation normal. LED flashing red low supply voltage, remote control not plugged in or RJ cable fault. LED permanently red overheat safety cut-out(s) open circuit from an overheat situation (see Section : Fault Conditions for how to reset) T9900-- UK Page

6. SERVICE & MAITEACE WARIG: Failure to adequately maintain the unit and provide a suitable cleaning schedule will result in a loss of performance and reduced life expectancy of the air-curtain and possible overheating and fire risk with electric heated units. 6. Every week OTE: Weekly maintenance can be carried out by the Cleaner or Janitor. Turn off the air curtain to prevent dust entry and then clean top face of the air inlet using a vacuum cleaner with an extension tube and brush. 6. Every months WARIG: Before servicing, isolate and disconnect the air curtain from the electrical power. WARIG: The following servicing and maintenance must be carried out by a competent electrician or a Thermoscreens appointed technician. Clean and inspect the inside of the air curtain as follows: Step Step Step From each plastic end cap unfasten securing screw and carefully slide out the end caps. Unfasten M6 bolts from top of access panel (see Fig, Section 8..). Lift top of access panel upwards and hinge open. Clean and remove any build-up of dust and dirt within the air-curtain (inlet/outlet grilles, electric heaters, fan impellers, housings and motors) using a vacuum cleaner and soft brush. OTE: Build-up of dirt on fan impellers can cause vibration, noise and excessive wear on the motor bearings. Step Check within the unit to ensure all electrical connections and crimped terminals are tight and that all cables are in good condition. Hinge and close access panel and refit end caps after servicing. Reconnect electrical supply and test to ensure correct operation (see Section : Commissioning). T9900-- UK Page 6

7. WARRATY All units are covered by a two year warranty. Failure to adequately maintain the unit may void the warranty. If any problems are encountered, please contact your installer/supplier. Failing this please contact the Thermoscreens warranty department. Care has been taken in compiling these instructions to ensure they are correct. Thermoscreens Ltd. disclaims all liability for damage resulting from any inaccuracies and/or deficiencies in this documentation. Thermoscreens Ltd. retain the right to change the specifications stated in these instructions. Thermoscreens Ltd Email: sales@thermoscreens.com St. Mary s Road uneaton Tel: + (0) 768 66 Warwickshire England Fax: + (0) 768 878 CV AU www.thermoscreens.com T9900-- UK Page 7

C AIR I 00 (min). C min 9 70 09 AIR OUT 6 0 0 9 mm Entry points for electrical supply and controls C-00 68 8 8 C-000 96 89 87 C-00 66 89 7 C-000 8 866 700 A A B C Cmin 9 DETAIL A D Rp /in. BSP LPHW connections Remote control connection interface B APPEDIX A Dimensions of C Air Curtain Wall Mounted 0 90 0 00 00 900 D 68 86 8 T9900-- UK Page 8

C 00 (min). C min AIR I 6 6 70 09 9 AIR OUT 9 Entry points for electrical supply and controls mm C-00 C-000 C-00 66 96 68 89 89 8 7 87 8 00 00 900 A DETAIL A 9 0 D Rp /in. BSP LPHW connections Remote control connection interface C-000 8 866 700 A B C Cmin D 68 86 8 APPEDIX B Dimensions of C Air Curtain Ceiling Mounted B 9 T9900-- UK Page 9

TERMIAL BLOCK 00V / ph / 0Hz Grey L L L E L L L E 8 C Auto Thermal Trip Healthy m -.8 kw (x).m -.8 kw (x) m -.6 kw (x).m -.6 kw (x) Alarm Summer/Winter or Door Contact J To Slave Air Curtain F = F00mA F = T6.A J C C O F F LED I I0 R 0-0V J Master/Slave Cable J6 Th J9 ph ph O REMOTE COTROL J0 Second Stage Heating (top elements) First Stage Heating (bottom elements) EEPROM J L J rectangle is moveable head of DIP switch J L 6 High speed Med speed Low speed 0V 7 Grey 8 L High speed Med speed Low speed 0V Fan Fan 9 J6 0 J7 ECO-Power CVR008-9 ~ (COMMO) (Low) (Med) (High) Capacitor 0 m - µf.m - µf APPEDIX A WIRIG DIAGRAM C-000E and C-00E T9900-- UK Page 0

ph.8 kw (x).8 kw (x) ph Second Stage Heating (top elements) TERMIAL BLOCK 00V / ph / 0Hz Grey L L L E L L L E 8 C Auto Thermal Trip Healthy Alarm Summer/Winter or Door Contact.6 kw (x) J To Slave Air Curtain F = F00mA F = T6.A J C C O F F LED I I0 R 0-0V J Master/Slave Cable J6 Th J9 ph O REMOTE COTROL J0 EEPROM J L J rectangle is moveable head of DIP switch.6 kw (x) J L High speed Med speed Low speed 0V 6 7 ph Grey 8 L High speed Med speed Low speed 0V Fan Fan 9 J6 0 J7 ECO-Power CVR008-9 First Stage Heating (bottom elements) ~ (COMMO) (Low) (Med) (High) Capacitor 0 µf Fan Motor ~ Fan Motor (COMMO) (Low) (Med) (High) Capacitor µf 0 APPEDIX B WIRIG DIAGRAM C-000E T9900-- UK Page

TERMIAL BLOCK 00V / ph / 0Hz Grey L L L E L L L E 8 C Auto Thermal Trip Healthy Alarm Summer/Winter or Door Contact A O J J To Slave Air Curtain COTACTOR 0V AC Coil F = F00mA F = T6.A J C C O F F LED I I0 R 0-0V Master/Slave Cable J6 A O 6 Th J9 O REMOTE COTROL J0 EEPROM J L J rectangle is moveable head of DIP switch J L 6 High speed Med speed Low speed 0V 7 Grey 8 L High speed Med speed Low speed 0V Fan Fan 9 ph J6 0 J7 ECO-Power CVR008-9.m -.8 kw (x) m -.8 kw (x) ph.m -.6 kw (x) m -.6 kw (x) ~ (COMMO) (Low) (Med) (High) Capacitor 0 Fan Motor.m Fan - µf ~ Fan Motor (COMMO) (Low) (Med) (High) ph ph Capacitor 0 m Fan - µf Second Stage Heating (top elements) First Stage Heating (bottom elements) APPEDIX C WIRIG DIAGRAM C-00E T9900-- UK Page

TERMIAL BLOCK 0V / ph / 0Hz L L E E PORT VALVE Summer/Winter or Door Contact J F = F00mA F = T6.A J LED I I0 R 0-0V J To Slave Air Curtain C C O F F Master/Slave Cable Grey Green/ E J6 Th J9 O REMOTE COTROL J0 EEPROM J L J rectangle is moveable head of DIP switch J L High speed Med speed Low speed 6 0V 7 8 L Fan Fan High speed Med speed Low speed 9 0V J6 0 J7 ECO-Power CVR008-9 ~ (COMMO) (Low) (Med) (High) Capacitor 0 Fan Motor m - µf.m - µf ~ (COMMO) (Low) (Med) (High) Fan Motor (m &.m only) Capacitor µf 0 APPEDIX D WIRIG DIAGRAM C-000W, C-00W, C-000W and C-00W T9900-- UK Page

Low speed Medium speed High speed 8 7 6 0V / ph / 0Hz E L TERMIAL BLOCK E L F (A) Capacitor m - µf.m - µf 0 (COMMO) (Low) (Med) (High) ~ Fan Motor Fan Speed On/Off Remote Control Switch Capacitor µf 0 (COMMO) (Low) (Med) (High) ~ Fan Motor (m &.m only) 0 APPEDIX E WIRIG DIAGRAM C-000A, C-00A, C-000A and C-00A I T9900-- UK Page

8. DECLARATIO OF COFORMITY Thermoscreens Ltd. St. Mary s Road uneaton Warwickshire CV AU United Kingdom Telephone: + (0) 768 66 www.thermoscreens.com EC DECLARATIO OF COFORMITY as defined by the EC Council Directive on Machinery 006//EC, the Low Voltage Directive 0//EU, Electromagnetic Compatibility Directive 0/0/EU, the Energy related Products Directive 009//EC Herewith we declare that the air movement equipment designated below, on the basis of its design and construction in the form brought onto the market by us in accordance with the relevant safety, health and performance requirements of the Machinery. If alterations are made to the machinery without prior consultations with us, this declaration becomes invalid. Designation of Equipment: Series Type: Relevant EC Council Directives: AIR CURTAIS C-000A; C-000E; C-000W; C-00A; C-00E; C-00W; C-000A; C-000E; C-000W; C-00A; C-00E; C-00W (in Casing Styles: Surface Mount) the Machinery Directive (006//EC) the Low Voltage Directive (0//EU) the Electromagnetic Compatibility Directive (0/0/EU) the Energy related Products Directive (009//EC) Applied Harmonised Machinery - BS E ISO 00:00, BS E ISO 87:008 Standards: LVD - E 60-:0+A:0, E 60--0:009+A:0 EMC - E 6000-6-:007, E 6000-6-:007+A:0, E 6000--:0, E 6000--:0 ErP - Commission Regulation (EU) o.7/0, ISO 80:007, ISO 79:00 Basis of Self Attestation: Quality Assurance to BS E ISO 900: 008 B.S.I. Registered Firm Certificate umber FM 8 SGS Test Report ELS009//R/DC/; SGS Test Report EMC009/ CE Marking Association Test Report 6799, 6800, 7 and 78 Responsible Person: Mr. J.Rogers, Managing Director, Thermoscreens Ltd. Date: March 06 Signed: T9900-- UK Page