Gas Safety Products. Installation, operating and maintenance. Merlin 1000S+i Gas & Electric Utility Controller. Rev: 03 Date:

Similar documents
Gas Safety Products. Installation, operating and maintenance. Merlin 1500S Gas Interlock System. Rev: 03 Date:

Gas Safety Products. Installation, operating and maintenance 11/18/2015. Merlin 1000S+ Gas Utility & Electrical Isolation Controller

Gas Safety Products. Installation, operating and maintenance. Merlin 1500S Gas Interlock System. American Gas Safety LLC 1 05/10/2016

Gas Safety Products. Installation, operating and maintenance. Merlin 1000VW+ Gas Interlock, Gas Proving, Electric & Water Isolation System

Gas Safety Products. Installation, operating and maintenance. Merlin 1000BH Gas Proving/Gas Detection System

Gas Safety Products. Installation, operating and maintenance 23/08/2016. Merlin 1000BH Gas Proving/Gas Detection System

Product Data Sheet. Merlin GDP2. Gas Safety Products. Merlin GDP2. Installation, operating and maintenance 23/08/2016. S&S Northern Ltd 1

Gas Safety Products. Installation, operating and maintenance 09/05/2016. Merlin CT1650+ Gas Interlock System. S&S Northern Ltd 1

Gas Safety Products. Installation, operating and maintenance 28/10/2015. Merlin CT1250 Gas Interlock System. S&S Northern Ltd 1

Gas Safety Products. Installation, operating and maintenance 11/26/2015. Merlin Gas Detectors. Merlin Gas Detectors. American Gas Safety LLC 1

Gas Safety Products. Installation, operating and maintenance 10/12/2017. Merlin Gas Detectors. Merlin Gas Detectors. American Gas Safety LLC 1

Gas Safety Products. Installation, operating and maintenance. Merlin Gas Detectors. Merlin Gas Detectors. Rev: 09 Date: Product Data Sheet

Gas Safety Products. Installation, operating and maintenance. Merlin CO2 Monitor 4500PPM. Merlin CO2 Monitor. Rev: 11 Date:

Gas Safety Products. Installation, operating and maintenance. Merlin CO2 Monitor 2800PPM. Merlin CO2 Monitor 2800ppm. American Gas Safety LLC 1

Gas Safety Products. Installation, operating and maintenance. Merlin Gas Detectors. Read these instructions carefully before operating or servicing.

Troubleshooting Guide

Troubleshooting Guide

Boiler Room Control THE MERLIN RANGE GAS DETECTION EQUIPMENT ENGINEERED TO DELIVER EXCEPTIONAL LEVELS OF SAFETY

UPON COMMENCMENT OF INSTALLATION IT IS OF PARAMOUNT IMPORTANCE THAT THE STEP BY STEP GUIDE (INCLUDED) IS FOLLOWED COMPLETELY

Please read this sheet as it contains important information

Installation and user manual for the FX range of fire panels. 1, 2, 4 and 8 zone panels

Installation Instructions. The SEC-L is a gas pressure proving system with water and electric isolation, gas detection and ventilation interlock.

FTEN1, FTEN2, & FTEN4 1, 2 & 4 ZONE FIRE DETECTION AND ALARM CONTROL PANELS

VGPS-evo V3.3. Installation Instructions. The VGPS-evo is a gas pressure proving system with ventilation interlock and optional CO2 detection.

GPPS-evo V3.3. Installation Instructions

Installation Instructions

Multi Function Control System for Boiler and Plant rooms SEC-B. The Home of Control & Automation in Ireland

BX444-Mc Gas Detector

GS100M Gas Detector. Technical Specification

Four Channel Gas Detection System AGDS 4. The Home of Control & Automation in Ireland

GS100M Gas Detection Controller

Water Leak Detector - Four Zone with open/short-circuit detection. Product overview

OPERATION AND INSTALLATION MANUAL

Installation and user manual for the CF5000, MF5000 and FXP5000 range of fire panels

LEAKSTOPPER MULTIZONE WATER LEAK DETECTION ALARM PANEL INSTALLATION AND OPERATION MANUAL

Reflective Optical Beam Smoke Detector User Guide

Installation and user manual for the BiWire / Conventional Repeater Panel

Sigma. K1000 Series 1, 2, 4 & 6 Zone Fire Control Panels. Operation and Maintenance Manual. Man-1048 Issue 05 October 2009

Multi Channel Gas Detection System AGDS MC. The Home of Control & Automation in Ireland

Door Release Power Supply

Installation, Operating and Maintenance Manual

LC1 & 2. Fire Alarm Panel 6\VWHPLQVWDOODWLRQRSHUDWLQJ PDLQWHQDQFH LQVWUXFWLRQV

TOTAL SOLUTIONS. Liquid Level Control Product Guide. MATELEC AUSTRALIA innovative by design

Centaur TM II Cube Slave Alarm Signalling Equipment INSTALLATION GUIDE

Fire-Cryer. Plus Application Guide APPLICATION GUIDE FIRE EXIT VIMPEX. Shaping Alarm Technology

Gasflag. Single Channel Control Panel Alarm Only Apparatus. Installation, operating and maintenance instructions, M07225.

100 Series Gas Ventilation Interlock System

GRUNDFOS INSTRUCTIONS LCD 108. Installation and operating instructions

MERLIN RANGE GAS DETECTION EQUIPMENT

La Marche Manufacturing Company Option 16 Series. Digital Combined Accessory Package. Installation and Operation Manual

Gas interlock system S & 100 CS

FR-4000 & FR-8000 Fire Alarm Monitor Installation Manual

ESP TECHNOLOGIES LIMITED

STATUS ALARM ALARM HISTORY POWER HISTORY RESET

NZ 400 AUTOMATIC FIRE ALARM SYSTEM OPERATORS MANUAL

BX444-M Gas Detector. Features. Application. Operation

EXAMPLES OF HOW TO ORDER

CaterSense 03 & ATSC-02-xx

GL-CO-RFG Channel Gas Leak Alarm System

EXAMPLES OF HOW TO ORDER

Carbon Monoxide Transmitter

TECHNICAL MANUAL EDITION 1.0 VANDAL RESISTANT AUDIO AND VIDEO DOOR ENTRY SYSTEMS

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel

TT /97. Features INSTALLATION INSTRUCTIONS. Horn. Lamps

21-light Remote Annunciator. Owner s Manual

WD-CS. Water leak detection cable. Technical Overview. Features. Page 1. Data Sheet Ref: Issue: 5.1.

ANALOX 5001 Carbon Dioxide Monitor. User Manual ANALOX Analox 5001 Carbon Dioxide Monitor User Manual

FIRE ALARM CONTROL EQUIPMENT. Addendum October 2006 Instructions for new style EN54-4 Power supply unit module

B-40/B-41 Modulating Temperature Controller

MASTER JOCKEY PUMP CONTROLLER. Model JPCE INSTRUCTION MANUAL. C 2018 Master Control Systems, Inc

PROPOINT PLUS ASPIRATING SMOKE DETECTION SYSTEM

STATUS ALARM ALARM HISTORY POWER HISTORY RESET

SYSTEM MANUAL FT1-SB. Single Zone Fire Alarm System

Hydrosense. Vimpex Limited. Star Lane. Great Wakering. Essex SS3 0PJ. Tel: +44 (0) Fax +44 (0)

LEAKMONITOR MULTIZONE WATER LEAK DETECTION ALARM PANEL INSTALLATION AND USER OPERATION MANUAL

PTE0705 Electric Fence Monitor

INSTALLATION AND OPERATING INSTRUCTIONS

RTD-10 Installation Instructions

FEC400 Series. Installation Manual

LeakSafe. solutions. WaterSwitch2. Installation Instructions

Beacon 110 Gas Monitor Operator s Manual

MINERVA MX. 800 Series Ancillary Equipment

Public Safety DAS Annunciator Panel

EXTINGUISHING AGENT RELEASE MODULE

KM300 Carbon Monoxide Detection System Installation Manual

Power Supply / Battery Charger Units, incorporating load switching relays for Smoke Dispersal, Bell Booster or other uses

USER MANUAL FOR OPERATING SYSTEM

SMART EVO 2 - User Manual ELECTRICAL PANEL FOR 2 MOTORS

Saffire User & Installation Manual. IMPORTANT This manual should be left with the panel after installation.

DMWD 1 to 4 Zone Water Detection Alarm with Distance to Leak Measurement Installation and Operation Manual

LD1000 ARCHITECT AND ENGINEER SPECIFICATIONS. RLE TECHNOLOGIES Rev

Intelligent Security & Fire Ltd

MASTER PRESSRE MAINTANENCE CONTROLLER. Models PMCE INSTRUCTION MANUAL. C 2018 Master Control Systems, Inc

R Series Remote Annunciators and Expander Installation and Operation Guide

AquiTron. AT-LDM Liquid Detection Module INSTALLATION INSTRUCTIONS

OPERATION & INSTALLATION MANUAL FOR ALARM PANEL M2AP01

ED820-24V MODEL INSTRUCTION MANUAL. fire DETECTOR

Ç Consilium Consilium US, Inc. 59 Porter Rd Littleton, MA USA

QA16 Addressable System

Flopurge TS. Operation Manual

Transcription:

Gas Safety Products Merlin 1000S+i Gas & Electric Utility Controller Installation, operating and maintenance Rev: 03 Date: 14-08-18 1

Table of contents 1 General information... 3 2 Installation... 3 2.1 Panel Mounting.... 3 2.2 Power Supply.... 3 2.3 Gas solenoid valve.... 3 2.4 Electric Contactor.... 3 2.5 BMS Connections.... 3 2.6 Timeout Facility.... 3 2.7 Remote emergency shut off buttons.... 3 2.8 Gas Detector.... 3 2.9 FS 123.... 3 2.10 CO2 Monitor.... 3 2.11 12v DC.... 3 2.12 Internal Buzzer.... 3 3 Operation Instructions... 4 3.1 How to turn the system on and off... 4 3.2 Explanation of LED status... 4 3.2.1 Power LED... 4 3.2.2 Gas on LED... 4 3.2.3 Electric on LED... 4 3.2.4 Timeout LED... 4 3.2.5 EM Stop LED... 4 3.2.6 Gas Detected LED... 5 3.2.7 CO2 High... 5 3.3 Using the emergency shut off... 5 3.4 BMS integration... 5 3.5 Fire alarm integration... 5 3.6 Fan switch integration... 5 3.7 Auto reset... 6 1000S+i Wiring Diagram... 6 Rev: 03 Date: 14-08-18 2

1 General information The Merlin 1000S+i is a gas isolation, gas detection & electrical isolation utility controller. The Merlin 1000S+i can receive connections from remote emergency shut-off buttons, gas detectors and a CO2 monitor. It can also be integrated with a BMS and fire alarm. It is recommended that the user reads this guide before using the system. Please do NOT attempt to operate the unit until the contents of this document have been read and are thoroughly understood. 2 Installation 2.1 Panel Mounting The control panel is designed for surface mounting using 4 mounting screws. Removing the cover on the panel gives access to the circuit board. The PCB should be removed before drilling entry holes into the case. 2.2 Power Supply A 110-120VAC electrical supply should be supplied to the panel. This should be externally fused at 3 Amps using a fused spur and should be connected to the terminals marked LNE Power IN 2.3 Gas solenoid valve The gas solenoid valve should be powered using the terminals on the Merlin 1000S+i marked LNE to VALVE. 2.4 Electric Contactor An electrical output will be supplied to an electrical contactor. This will be internally fused at 3 Amps and should be connected to the terminals marked LNE Electric Contactor. 2.5 BMS Connections Terminal connections are available on the circuit board for connections to Building Management systems etc. Detailed on the circuit board as BMS OUT N/C, COM and N/O these are volt free connections. 2.6 Timeout Facility The Merlin 1000S+i has a built-in Auto-shut down feature and it will turn itself off after predefined time. Auto-shut down timeout is selectable. There are two dip-switches located on the inside facia of the Merlin 1000S+i labelled Time1 and Time2. They are factory set in the off position for a 2 hour timeout. On installation, they can be switched to the on position to select required timeout. Time1 Off, Time2 Off 2 hours Time1 On, Time2 Off 4 hours Time1 Off, Time2 On 8 hours Time1 On, Time2 On no timeout (auto-shut down disabled) On Auto-shut down gas supply will be turned off. 2.7 Remote emergency shut off buttons The terminal for remote emergency shut-off buttons is detailed on the circuit board as EM Remote. These connections are linked out as a factory setting. Remote emergency shut-off buttons should be volt free and wired to the Merlin 1000S+i using two-core cable. 2.8 Gas Detector The terminals detailed on the circuit board as Gas Detector. These connections are +,- and these can be wired to a Merlin Natural gas, Carbon monoxide or LPG detector. If no detector is being used leave the link in between the. Other detector types are available. 2.9 FS 123 This terminal switches when the key is turned on and off. This can be linked to a fan switch (panel supplied separately) which can provide power to the fans when the control panel is switched on. 2.10 CO2 Monitor This terminal can be wired to CO2 monitor to shut off the system in the event of High CO2 levels. If no CO2 monitor is supplied leave the terminal link in. 2.11 12v DC This is a permanent 12v DC output when there is power at the panel. 2.12 Internal Buzzer Operates at 65dB measured 30cm from closed panel. Rev: 03 Date: 14-08-18 3

Note: all low voltage connections should be made using a screened cable. To avoid electrical interference this should not be in the same conduit as mains cable as per the low voltage directive. 3 Operation Instructions 3.1 How to turn the system on and off Turn the key switch to on position. Gas and electric will flash for 10 seconds. Press relevant service button to turn required utility on. Turn the key switch to the off position to turn the panel off. Please Note: All services can be turned on or off only within 10 seconds of the key switch being turned on. After 10 seconds, all utility buttons will be disabled. The user must turn the key off and back on to adjust any services. 3.2 Explanation of LED status 3.2.1 Power LED When the system is connected to the mains supply, the Red LED of the AGS Logo located in the bottom right corner of the panel will illuminate. When no power is present, this LED will not light up. RED = OK OFF = No power to 1000S+i, a loose ribbon connection or the fuse may not be intact. 3.2.2 Gas on LED When the key switch is turned on, the gas valve will open and the green Gas On LED will illuminate. GREEN = Gas On OFF = Gas Off AMBER = Fault detected. 3.2.3 Electric on LED When Electric service is turned on, the Electric LED will illuminate BLUE. BLUE = Electric On FLASHING = Electric Off, Electric button enabled OFF = Electric Off, Electric button disabled 3.2.4 Timeout LED Under normal working conditions this LED is off. This LED will illuminate AMBER when auto-shut down has occurred. AMBER = auto-shut down 3.2.5 EM Stop LED If an emergency shut off button (either remote or on the panel) is pressed, the LED will illuminate AMBER and the gas will be turned off. The EM Stop button must be re-set before restarting the system. AMBER = EM Stop button pressed Rev: 03 Date: 14-08-18 4

3.2.6 Gas Detected LED Under normal working conditions this LED is off. If the external Merlin detector connected detects gas this will show RED and the Gas valve will turn off. RED = Gas detected. 3.2.7 CO2 High Under normal working conditions this LED is off. If the concentration of CO2 in the air is at alarm level (relevant detector required), the LED will show RED and the Gas valve will turn off. RED = the concentration of CO2 is at alarm level. 3.3 Using the Emergency Shut Off The Emergency shut off button is located on the front of the panel. There is also a facility for remote shut off buttons to be wired in series. The Emergency shut off button(s) will cut off the gas supply when activated. To reinstate the system, the Emergency shut off button(s) will need to be reset and the panel restarted. 3.4 BMS Integration The Merlin 1000S+i can be integrated with a BMS to make or break a circuit on gas on/gas off, (valve open or valve closed). This will tell the BMS whether or not power is being sent to the solenoid. There is a dip-switch located on the inside facia of the Merlin 1000S+i labelled BMS Selection. This is factory set in the off position which signals the BMS on gas on/gas off. When switched to the on position, the 1000S+i will only signal the BMS on a fault, i.e. CO2 high level detected, gas detected, EM Stop pressed, etc. 3.5 Fire Alarm Integration The Merlin 1000S+i can be integrated with a fire alarm to close the gas supply automatically in the event of a fire. The volt free fire alarm signal can be wired in series with any remote emergency shut off buttons. If there is no remote emergency stop buttons installed wire this directly to the terminal marked EM REMOTE. 3.6 Fan Switch Integration There is the facility to connect a Fan Switch (FS1 or FS2 sold separately). The Fan Switch provides the facility to turn on the fan(s) when the key switch on the Merlin 1000S+i is in the on position and turn the power off to the fan(s) when the key switch on the Merlin 1000S+i is in the off position. There is a dip-switch located inside the facia of the Merlin 1000S+i labelled EM Selection. This is factory set in the off position which instructs the system to shut down the fan(s) and gas supply on activation of the emergency shut off button(s). On installation, this can be switched to the on position if required. This will instruct the system to leave the fans on and only shut off the gas supply on activation of the emergency shut off button(s). Note: This option is not available if Fan Switch is not installed. Rev: 03 Date: 14-08-18 5

3.7 Auto reset The Merlin 1000S+i has a built-in auto reset feature. There is a dip-switch located on the inside facia of the Merlin 1000S+i labelled Auto Reset. This is factory set in the off position. When the power is restored after the power cut, the panel has to be restarted manually. On installation, this can be switched to the on position if required. This will instruct the system to restart automatically when power is restored after the power cut. 1000S+i Wiring Diagram 1 2 3 4 5 6 7 8 9 10 11 12 13 L N E Gas Detector CO2 Monitor Gas Valve L N E EM Stop 1. Mains Input 110-120VAC Single Phase. 2. Gas Solenoid Valve Power Output, 110-120VAC, Max 3A. 3. Electric Contactor Power Output, 110-120VAC, Max 3A. 4. Water Valve, this is disabled on this system. 5. Supply Fan PD Switches terminal, this is disabled on this system. 6. Extract Fan PD Switches terminal, this is disabled on this system. 7. BMS output contacts. Normally Closed, Common and Normally Open. Max.1A @ 110-120VAC. 8. Gas pressure transducer, this is disabled on this system. 9. Remote EM Stop buttons and Fire Alarm input wired in series (purchased separately). VOLT FREE INPUT 10. Methane, CO or LPG Detector, power supply and volt free input (purchased separately). 11. Fan Switch output (purchased separately). For wiring instruction see Fan Switch user manual. 12. CO2 Monitor (purchased separately). VOLT FREE INPUT 13. Permanent 12VDC output when there is power at the panel. 50mA max Please note, Mains wires and low voltage wires should not be run in the same conduit as per the LOW VOLTAGE DIRECTIVE Rev: 03 Date: 14-08-18 6

INFORMATION ON WASTE DISPOSAL FOR CONSUMERS OF ELECTRICAL & ELECTRONIC EQUIPMENT When this product has reached the end of its life it must be treated as Waste Electrical & Electronics Equipment (WEEE). Any WEEE marked products must not be mixed with general household waste, but kept separate for the treatment, recovery and recycling of the materials used. Please contact your supplier or local authority for details of recycling schemes in your area. CONTACT US: AGS Head Office Tel: (727) 608-4375 Fax: (727) 538-4237 info@americangassafety.com American Gas Safety is the owner of this document and reserves all rights of modification without prior notice. Rev: 03 Date: 14-08-18 7