Air Conditioning Technical Data Low temperature hydrobox for VRV EEDEN3-204 HXY-A
Indoor Unit Low temperature hydrobox for VRV HXY-A TABLE OF CONTENTS HXY-A Features............................................................. 2 2 Specifications....................................................... 3 Technical Specifications............................................. 3 Electrical Specifications.............................................. 4 3 Options.............................................................. 5 Options............................................................... 5 4 Dimensional drawings............................................. 6 Dimensional Drawings............................................... 6 5 Piping diagrams.................................................... 7 Piping Diagrams..................................................... 7 6 Wiring diagrams.................................................... 8 Wiring Diagrams - Single Phase.................................... 8 7 External connection diagrams................................... 0 External Connection Diagrams...................................... 0 8 Hydraulic performance............................................ Static Pressure Drop Unit........................................... VRV Systems Indoor Unit
Indoor Unit Low temperature hydrobox for VRV HXY-A Highly efficient space heating/cooling Can be used with a variety of applications such as underfloor, AHU, low temperture radiators, VRV plug-and-play as all necessary components are integrated for quick installation Leaving water temperature range from 5ºC to 45ºC without electric heater Saves time on system design as all water-side components are fully integrated with direct control over leaving water temperature Saves space with contemporary wall hung design Super wide operating range for hot water production from -20 to +43ºC ambient outdoor temperature Requires no gas connection or oil tank Connectable to VRV IV heat pump Accurate temperature control, fresh air provision, Biddle air curtains and hot water production, all integrated in a single system requiring only one single point of contact at s rim en put m s ery tos A o - wdvy norx LIVH 2 Features VRV Systems Indoor Unit
2 Specifications Indoor Unit Low temperature hydrobox for VRV HXY-A 2- Technical Specifications HXY080A HXY25A Cooling capacity Nom. kw 8 () 2.5 () Heating capacity Nom. kw 9 (2) 4 (2) Casing Colour White Material Precoated sheet metal Dimensions Unit Height mm 890 Width mm 480 Depth mm 344 Packed unit Height mm 45 Width mm 650 Depth mm,06 Weight Unit kg 44 Packed unit kg 47 Packing Material Carton / EPS / PP (Straps) Carton / EPS / PP (Straps) Weight kg 2.8 Pump Type DC motor Nr of speeds Inverter controlled Nominal ESP unit Heating kpa 79 43 Cooling kpa 83 55 Power input W 0 35 Expansion vessel Volume l 0 Max. water pressure bar 3 Pre pressure bar Operation range Heating Ambient Min. ºC -20 Max. ºC 24 Water Min. ºC 25 side Max. ºC 45 Cooling Ambient Min. ºCDB 0 Max. ºCDB 43 Water Min. ºC 5 side Max. ºC 20 Refrigerant circuit Gas side diameter mm 5.9 Liquid side diameter mm 9.5 Water circuit Piping connections diameter inch G "/4 (female) Safety valve bar 3 Manometer Yes Drain valve / fill valve Yes Shut off valve Yes Flow switch Yes Air purge valve Yes Water side Heat Type Brazed plate exchanger Quantity Water flow rate Min. l/min 5.0 (6) Heating Nom. l/min 25.8 40. Cooling Nom. l/min 22.9 35.8 Insulation material Foamed synthetic elastomer Water filter Diameter perforations mm Material copper - brass - stainless steel PED Category Art3 3 3 2 VRV Systems Indoor Unit 3
2 Specifications Indoor Unit Low temperature hydrobox for VRV HXY-A 2 2-2 Electrical Specifications HXY080A HXY25A Power supply Phase ~ Frequency Hz 50 Voltage V 220-240 Voltage range Min. % -0 Max. % 0 Current Zmax List No requirements Recommended fuse A 6 ~6 Current - 50Hz Nominal running current A 2.5 Wiring connections Communication cable Quantity 2 Type of 0.75 ~.25 mm 2 (FF2) wires For connection with user interface Quantity 2 Type of 0.75 ~.25 mm 2 (PP2) wires For power supply Quantity 3G Type of wires wire type / size has to be selected according to applicable legislation Notes () Tamb 35ºC - LWE 8ºC (DT=5ºC) (2) DB/WB 7ºC/6ºC - LWC 35ºC (DT=5ºC) (3) PED unit category: Art3 3: excluded from scope of PED due to article, item 3.6 of 97/23/EC (4) The sound pressure level is measured via a microphone at a m distance from the unit. It is a relative value, depending on the distance and acoustic environment. (5) Value mentioned is connection after ball valves, Connection at unit is G-/4 FEMALE (6) Flow switch setting (7) Height difference between lowest and highest point in the water circuit has to be \<= 5 m (8) Combination restrictions of 3D079543 are effective to this unit. 4 VRV Systems Indoor Unit
Indoor Unit Low temperature hydrobox for VRV HXY-A 3 Options 3 - Options 3 3 VRV Systems Indoor Unit 5
Indoor Unit Low temperature hydrobox for VRV HXY-A 4 Dimensional drawings 4 - Dimensional Drawings 4 6 VRV Systems Indoor Unit
5 Piping diagrams Indoor Unit Low temperature hydrobox for VRV HXY-A 5 - Piping Diagrams 3 5 VRV Systems Indoor Unit 7
6 Wiring diagrams 6 - Wiring Diagrams - Single Phase Indoor Unit Low temperature hydrobox for VRV HXY-A 6 8 VRV Systems Indoor Unit
Indoor Unit Low temperature hydrobox for VRV HXY-A 6 Wiring diagrams 6 - Wiring Diagrams - Single Phase 3 6 VRV Systems Indoor Unit 9
Indoor Unit Low temperature hydrobox for VRV HXY-A 7 External connection diagrams 7 - External Connection Diagrams 7 0 VRV Systems Indoor Unit
Indoor Unit Low temperature hydrobox for VRV HXY-A 8 Hydraulic performance 8 - Static Pressure Drop Unit 3 8 VRV Systems Indoor Unit
8 Hydraulic performance 8 - Static Pressure Drop Unit Indoor Unit Low temperature hydrobox for VRV HXY-A 8 2 VRV Systems Indoor Unit
Daikin s unique position as a manufacturer of air conditioning equipment, compressors and refrigerants has led to its close involvement in environmental issues. For several years Daikin has had the intention to become a leader in the provision of products that have limited impact on the environment. This challenge demands the eco design and development of a wide range of products and an energy management system, resulting in energy conservation and a reduction of waste. These products are not within the scope of the Eurovent certification program Daikin Europe N.V. participates in the Eurovent Certification programme for Air conditioners (AC), Liquid Chilling Packages (LCP) and Fan coil units (FCU), Check ongoing validity of certificate online: www.eurovent-certification.com or using: www.certiflash.com The present leaflet is drawn up by way of information only and does not constitute an offer binding upon Daikin Europe N.V.. Daikin Europe N.V. has compiled the content of this leaflet to the best of its knowledge. No express or implied warranty is given for the completeness, accuracy, reliability or fitness for particular purpose of its content and the products and services presented therein. Specifications are subject to change without prior notice. Daikin Europe N.V. explicitly rejects any liability for any direct or indirect damage, in the broadest sense, arising from or related to the use and/or interpretation of this leaflet. All content is copyrighted by Daikin Europe N.V. BARCODE Daikin products are distributed by: Naamloze Vennootschap - Zandvoordestraat 300, B-8400 Oostende - Belgium - www.daikin.eu - BE 042 20 336 - RPR Oostende EEDEN3-204 09/2 Copyright Daikin The present publication supersedes EEDEN2-204