LOA44.252A27. Oil Burner Control. Building Technologies HVAC Products

Similar documents
LOA2... LOA3... Oil Burner Controls. Siemens Building Technologies HVAC Products

Oil Burner Controls LOA3... Building Technologies HVAC Products

Oil Burner Controls LMO24... LMO44...

Oil Burner Controls LMO24... LMO44...

LGA... Gas Burner Controls. Siemens Building Technologies HVAC Products

Oil Burner Controls LOA3... Building Technologies Division

LOA2... LOA3... Oil Burner Controls. Siemens Building Technologies Landis & Staefa Division

LGA... Gas Burner Controls. Building Technologies Division

LGA... Gas Burner Controls. Siemens Building Technologies Landis & Staefa Division

Flame Safeguards LFE10. Building Technologies HVAC Products

Flame Safeguards LFE10. Building Technologies HVAC Products

QRC1... Blue-flame Detectors. Siemens Building Technologies HVAC Products

Burner controls. Building Technologies HVAC Products

Infrared Flame Detectors

C Note! LGI16... Burner Controls. Building Technologies

Burner Controls. Building Technologies HVAC Products

Gas Burner Controls. Building Technologies HVAC Products

QRA4.U. Flame Detector. Siemens Building Technologies HVAC Products

LFE50. UV Flame Safeguard. Building Technologies Division DETACTOGYR

LAE10 LFE10. Use. Series 02

Use. The burner controls are certified to EN 230 and EN 298.

LFE50. UV Flame Safeguard. Siemens Building Technologies HVAC Products DETACTOGYR. Series 02

Flame detector. The QRA4.U is for use with the following types of burner control:

Use. Burner controls for use with forced draught gas or gas / oil burners of small to medium capacity in intermittent operation.

Infrared Flame Detectors

Flame detector. The QRA4.U is for use with the following types of burner control:

Burner Management System

QRA2... QRA10... QRA53... QRA55... Flame Detectors. Siemens Building Technologies HVAC Products

Flame detector. Building Technologies Division Infrastructure & Cities Sector

QRA10... QRA53... QRA55...

RAR... Photocell Detectors. Building Technologies Division

Building Technologies Division

UV Flame Supervision System

Burner Management System

Blue-flame Detectors

Basic unit with integrated air-fuel ratio control for forced draft burners

QRA10... QRA53... QRA55...

QRA10... QRA53... QRA55...

Burner Management System

Basic unit with integrated fuel-air ratio control for forced draft burners LMV Building Technologies Division

Building Technologies Division

Basic Unit with integrated Fuel / Air Ratio Control for Forced Draft Burners LMV Building Technologies

Program module for burner control LME71.000

Building Technologies

QRA10... QRA53... QRA55...

Heating Element. Building Technologies HVAC Products

EUROBOX SERIES TYPES CM... SM... MM...

EURO-OIL SERIES TYPES G.. G../. OR.. OR../. F.. FR..

EUROBOX SERIES TYPES CM...N SM...N MM...N

MANUAL OF - INSTALLATION - OPERATION - MAINTENANCE LIGHT OIL BURNERS G4 - G6 G10 - G18 SINGLE STAGE

LFL Series Burner Flame Safeguard Control

Product Range Overview

EUROFLAT SERIES TYPES C... S... M...

Main Features. Functions. with automatic ignition and control functions for the heating and domestic hot water circuit

MICROFLAT SERIES TYPES C.../U T X

TWO STAGE HEAVY OIL BURNERS

DKG 972. Gas Burner Safety Control. For 2-stage atmospheric gas burners

Forced draught gas burner

CORONA BURNER CONTROLLER INSTRUCTION MANUAL RCF15 EXCLUSIVE FOR FLAME ROD. Corona Corporation

QFM21... Siemens Building Technologies HVAC Products. Symaro Duct Sensors. for relative humidity and temperature

for relative humidity and temperature

Room Air Quality Sensors

Gas burner automatic safety control MMI / 811.1

MMG Gas burner safety control

DMG 970. Gas Burner Safety Control. For 2-stage forced draught and combi oil/gas burners

ELECTRONIC FLAME SUPERVISION MULTI-BURNER

DKO 974/976 DKO 974 N/976 N. Oil Burner Safety Control

QAF63.2 QAF63.6. Frost sensors for use on the air side. Building Technologies HVAC Products

QFM21... Duct Sensors. Building Technologies HVAC Products. Symaro. for relative humidity and temperature

QAF64.2-J QAF64.6-J. Frost detector. for use on the air side

Room Sensors. Building Technologies HVAC Products ... Symaro. for relative humidity (high accuracy) and temperature

DMG 973. Gas Burner Safety Control. For 2-stage forced draught and combi oil/gas burners, facility to connect an air damper unit

Duct Sensors. Siemens Building Technologies HVAC Products. Symaro. for relative humitidy (high accuracy) and temperature

DMG 973. Gas Burner Safety Control. For 2-stage forced draught and combi oil/gas burners, facility to connect an air damper unit

MMI (40-34) Gas burner safty control

for relative humidity and temperature

for relative humidity and temperature with calibration certificates

Eclipse Trilogy Flame Safeguard Modulating Sequences

Room Temperature Controller

QFM21... Duct Sensors. Siemens Building Technologies HVAC Products

Immersion Temperature Controller

PRELIMINARY EDITION

AUTOMATIC BURNER CONTROL SYSTEM SAFETY INFORMATION CONFORMITY

MANUAL OF - INSTALLATION - OPERATION - MAINTENANCE HEAVY OIL BURNERS

BC-R10 Series. Burner Controllers

OF INSTALLATION - USE - MAINTENANCE

Old documentation - Only for your information! Product is not available anymore!

FIREYE M4RT1 FLAME SAFEGUARD CONTROLS DESCRIPTION

LME75... Burner controls. Building Technologies

ISOMETER IR425. Insulation monitoring device for unearthed AC/DC control circuits (IT systems)

QXA2100. Condensation monitor QXA2101. Monitor to prevent damage caused by condensation on chilled ceilings and HVAC plants with AC/DC 24 V power.

UV - flame detector dual fuel burners for intermittent burner operations

Forced draught gas burner

Duct Temperature Sensors

RVP331. Heating Controller for 2 heating circuits, d.h.w. and boiler. Building Technologies HVAC Products

SERIES VAC Microprocessor-Based Intermittent Pilot Ignition Control FEATURES APPLICATIONS SPECIFICATIONS DESCRIPTION

Light oil burners. One stage operation

Dipl.-Ing. W. Bender GmbH & Co. KG Londorfer Str Grünberg Tel.: Fax:

Monitoring Devices 11/1

SERIES VAC Microprocessor-Based Hot Surface Ignition Control FEATURES APPLICATIONS SPECIFICATIONS DESCRIPTION AGENCY CERTIFICATIONS

Transcription:

Distribuitor: FLAME POWER SRL 021-3121727 ; 0744-340566 contact@arzatoare.ro ; www.arzatoare.ro 7 128 Oil Burner Control LOA44.252A27 Oil burner control for the supervision, startup and control of 1- or 2-stage forced draft oil burners, burners of direct-fired air heaters and burners having an oil throughput of more than 30 kg/h in intermittent operation. The LOA44.252A27 and this Data Sheet are intended for use by OEMs which integrate the burner controls in their products. Use, features Use General features The LOA44.252A27 is used for the supervision, startup and control of 1- or 2-stage forced draft oil burners in intermittent operation. Yellow-burning flames are supervised with photoresistive detectors QRB, blue-burning flames with blue-flame detectors QRC - Forced draft oil burners conforming to EN 267 - For use with stationary direct-fired air heaters - Oil burner controls for oil atomization burners in monoblock design conforming to EN 230 - Undervoltage detection - Bridging contact for oil preheater - Electrical remote reset facility 20.05.2004 HVAC Products

Warning notes To avoid injury to persons, damage to property or the environment, the following warning notes should be observed! Do not open, interfere with or modify the unit! All activities (mounting, installation and service work, etc.) must be performed by qualified staff Before performing any wiring changes in the connection area of the LOA44.252A27, completely isolate the unit from the mains supply (all-polar disconnection) Ensure protection against electric shock hazard by providing adequate protection for the burner control s connection terminals Check to ensure that wiring is in an orderly state Press the lockout reset button / operating button only manually (applying a force of no more than 60 N), without using any tools or pointed objects Fall or shock can adversely affect the safety functions. Such units must not be put into operation, even if they do not exhibit any damage Mounting notes Ensure that the relevant national safety regulations are complied with Installation notes Always run high-voltage ignition cables separately while observing the greatest possible distance to the unit and to other cables Do not mix up live and neutral conductors When using the electrical remote reset facility, the lockout reset button must be integrated such that terminal 9 will be connected to the neutral conductor Electrical connection of the flame detectors It is important to achieve practically disturbance- and loss-free signal transmission: Never run the detector cable together with other cables Line capacitance reduces the magnitude of the flame signal Use a separate cable Observe the permissible lengths of the flame detector cables (refer to Data Sheets N7714 (QRB ) and N7716 (QRC )) Commissioning notes Prior to commissioning, check to ensure that wiring is in an orderly state When commissioning the plant or when carrying out maintenance work, make the following safety checks: Safety check Anticipated response a) Burner startup with flame detector darkened Lockout at the end of «TSA» b) Burner startup with flame detector exposed to extraneous light Lockout after approx. 40 seconds c) Simulation of loss of flame during operation. For that purpose, darken the flame detector during operation and maintain that state Repetition followed by lockout at the end of «TSA» 2/8

Standards Conformity to EEC directives Electromagnetic compatibility EMC (immunity) Low-voltage directive 89 / 336 EEC 73 / 23 EEC ISO 9001: 2000 Cert. 00739 ISO 14001: 1996 Cert. 38233 Service notes Each time a unit has been replaced, check wiring to ensure that it is in an orderly state and make the safety checks as indicated in «Commissioning notes» Do not press the lockout reset button «EK» for more than 10 seconds Use the KF test adapters for short periods of time only Disposal notes The unit contains electrical and electronic components and must not be disposed of together with household waste. Local and currently valid legislation must be observed. Mechanical design The housing is made of impact-proof, heat-resistant and flame-retarding plastic. It is of plug-in design and engages audibly in its base. The housing accommodates the - electronic sequence control and the load control relays - flame signal amplifier with the flame relay - lockout reset button with its integrated fault indication lamp Type summary The type reference given below applies to the burner control without base and without flame detector. Type reference Mains voltage Undervoltage detection t1 t3 TSA t3n t4 max. LOA44.252A27 AC 220...240 V X 25 s 25 s 5 s 2 s 5 s Legend t1 t3 t3n t4 TSA Prepurge time Preignition time Postignition time, depending on the time of flame establishment Interval from establishment of flame to the release of «BV2» Ignition safety time 3/8

Ordering Oil burner control without plug-in base refer to «Type summary» Connection accessories for burner controls of small capacity refer to Data Sheet 7201 - Plug-in base AGK11... - Cable holders AGK65..., AGK66, AGK67... - Cable strain relief elements for AGK67... Connection accessories for burner controls of small capacity refer to Data Sheet 7203 - Plug-in base AGK13 - Plug-in housing AGK56 - Cover AGK68 Flame detectors - Photoresistive detectors QRB1... refer to Data Sheet 7714 - Blue-flame detectors QRC1... refer to Data Sheet 7716 Demo case - For showing the functioning of burner controls - Refer to Operating Instructions B7989 Test adapter - For testing the functioning of burner controls on the burner - With switch for manual startup of burner - With switch for simulating the oil preheater s release contact - With 2 pairs of jacks for measuring the flame detector current - Refer to Operating Instructions B7986 Pedestal (empty housing) - To increase the overall height of the LOA44.252A27 to that of the LAB KF8891 KF8885 AGK21 Adapter - For replacing LAB15.1 / LAB16.3 by LOA44.252A27 - No rewiring of plug-in base required Test adapter - For testing the functioning of burner controls on the burner - With signal lamps for program indication - With 2 jacks for measuring the flame detector current Test adapter - For testing the functioning of burner controls on the burner - With signal lamps for program indication - With switch for simulating the flame signal - With holes for checking the voltages at the tabs of the burner control - With 2 jacks for measuring the flame detector s resistance KF8819 KF8833 KF8840 4/8

Technical data General unit data Mains voltage AC 220 V 15 %...AC 240 V +10 % Mains frequency 50...60 Hz ±6 % External primary fuse (Si) max. 10 A, slow Power consumption approx. 3 VA Mounting position optional Weight approx. 140 g Degree of protection IP40, must be ensured through mounting Safety class I Input current to - terminal 1 max. 5 A - terminal 3 5 A (excl. current draw of burner motor and oil preheater) Perm. current at cos 0.6 Terminal 4 Terminal 5 Terminal 6 Terminal 8 Terminal 10 LOA44.252A27 Max. 2 A Max. 2 A Max. 2 A Max. 5 A Max. 1 A Environmental conditions Storage DIN EN 60721-3-1 Climatic conditions class 1K3 Mechanical conditions class 1M2 Temperature range -20...+60 C Humidity < 95 % r.h. Transport DIN EN 60 721-3-2 Climatic conditions class 2K2 Mechanical conditions class 2M2 Temperature range -50...+60 C Humidity < 95 % r.h. Operation DIN EN 60 721-3-3 Climatic conditions class 3K5 Mechanical conditions class 3M2 Temperature range at UN - AC 187...242 V - AC 242...264 V -20...+60 C -20...+40 C Humidity < 95 % r.h. Condensation, formation of ice and ingress of water are not permitted! 5/8

Technical data (cont d) Flame supervision with QRB... and QRC... For detector cable lengths, refer to Data Sheets 7714 (QRB...) and 7716 (QRC...). Type reference Detector current required (with flame) Perm. detector current (without flame) QRB... / QRC... Min. 58 µa Max. 5.5 µa The data given above only apply under the following conditions: - Mains voltage AC 230 V ±3 V - Temperature 23 C ±5 C - Detector cable length < 5 m The highest possible intensity of illumination is indicated by a slight increase of the detector current. Measuring circuit for detector current QRB... 11 12 LOA44... bl sw + µa DC QRB... 7128v01/0304 QRC... 11 12 1 LOA44... 7128v02/0304 bl sw br + µa DC QRC1... Legend µa DC DC microammeter with an internal resistance of Ri = max. 5 k bl Blue sw Black br Brown Function Preconditions for startup Burner control is reset Contacts in the line are closed No undervoltage Flame detector is darkened, no extraneous light Undervoltage detection Control sequence in the event of fault An additional electronic circuit ensures that, if mains voltage drops below approximately AC 160 V, burner operation will be prevented. Whenever lockout occurs, the outputs for the fuel valves, the burner motor, oil preheater and ignition equipment will immediately be deactivated (< 1 second). The lockout indication lamp changes to red and voltage is fed to terminal 10 («AL») for remote lockout indication. This state is also maintained in the event of mains voltage failure. Cause Mains voltage failure Extraneous light during «t1» No flame at the end of «TSA» Loss of flame during operation Loss of flame during «t3n» Response Restart on restoration of mains supply Lockout Lockout Repetition Lockout after approx. 2.5 s Reset After lockout, the burner control can be reset after 120 seconds. Indication Lockout position The lockout position is indicated by the lamp integrated in the lockout reset button. 6/8

Connection diagram and internal diagram Control sequence SB R/W 1 br b a fr2 fr1 BR LOA44... b a FR V ar2 ar1 AR L N EK1 hr1 b a t1,tsa, t4 2 9 10 8 3 6 7 4 5 11 12 OW QRB Si H 7128d01/0602 Z BV1 BV2 AL OH N M EK2 HR QRC bl sw 1 br 7128i01/0304 Legend AL Alarm device OH Oil preheater AR Main relay with contacts «ar...» QRB... Photoresistive detector BR Lockout relay with contacts «br...» QRC... Blue-flame detector BV... Fuel valve bl = blue, br = brown, sw = black EK... Lockout reset button R Control thermostat or pressurestat FR Flame relay with contacts «fr...» SB Safety limit thermostat FS Flame signal Si External primary fuse HR Auxiliary relay with contacts «hr...» W Limit thermostat or pressure switch M Burner motor V Flame signal amplifier OW Release contact of oil preheater Z Ignition transformer t1 Prepurge time t4 Interval between establishment of flame t3 Preignition time and release of «BV2» t3n Postignition time TSA Ignition safety time tw Waiting time A Beginning of startup sequence with burners using an C Operating position oil preheater A Beginning of startup sequence with burners using no C-D Burner operation oil preheater B Time of flame establishment D Controlled shutdown by «R» Control signals of the LOA44.252A27 Required input signals Permissible input signals 7/8

Dimensions Dimensions in mm LOA44.252A27 22 5,5 Plug-in base AGK11... / AGK13... 62,5 88 91 41,5 47 62,5 9 7128m04/0405 Distribuitor: FLAME POWER SRL 021-3121727 ; 0744-340566 contact@arzatoare.ro ; www.arzatoare.ro 8/8 2005 Siemens HVAC Production GmbH Subject to alteration!