Liebert Mini-Mate2 Air-Cooled Model

Similar documents
Liebert Prop Fan Condensing Unit

Liebert Mini-Mate2. 8-Ton (28kW) Capacity, Air, Water, Glycol, GLYCOOL, Chilled Water; 50 & 60 Hz. Technical Data Manual

Liebert Mini-Mate2 1 To 8 Tons

Liebert Mini-Mate2 1 To 8 Tons

Liebert Mini-Mate2 1 To 8 Tons

Liebert Small System MCD and PFH Condensers (1-5 Ton) Warranty Inspection Check Sheet

TECHNICAL GUIDE. Description SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS YD360, 480 & THRU 50 NOMINAL TONS YTG-B-0811

PACKAGE AIR CONDITIONER

VariCool VAV Engineering Guide

C13-Series Engineering Guide

Liebert Mini-Mate Thermal Management Systems

Condensing Unit Installation and Operating Instructions

Service Step by Step Trouble-Shooting Check-List

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 FEATURES B-0703

Guide Specifications for InRow Direct Expansion

Data Aire LCS TM (Large Ceiling System) R-410A. 6, 8, 10, and 13 ton. ISO 9001 Certified

Data Aire LCS TM (Large Ceiling System) R-407C. 6, 8, 10, and 13 ton. ISO 9001 Certified

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS. HA300, HB360, HB480 & HB thru 50 NOMINAL TONS (50 Hz)

INSTALLATION INSTRUCTIONS

Liebert OVERHEAD COOLING IN A VARIETY OF CAPACITIES AND CONFIGURATIONS. Mini-Mate2. 1 to 8 Tons. Provides Precision Cooling And Humidity Control

CoolSpot Engineering Guide

TECHNICAL MANUAL CX(E) SPLIT SYSTEMS. Tel: Fax:

B. Unit construction shall comply with ASHRAE 15 Safety Code, NEC, and ASME applicable codes (U.S.A. codes).

Data Aire Mini Ceiling Systems 1, 1.5, 2, and 2.5 ton capacities R-410A. ISO 9001 Certified

Condensing Unit Installation and Operating Instructions

CeilMate TM Series 3 and 4 tons of cooling capacity. Ceiling Mounted Systems. Air Handler with Remote Condensing Unit Air Handler designed for R-410A

Liebert. Mini-Mate2 1 To 8 Tons Overhead Precision Cooling And Humidity Control

VertiCool Aurora Engineering Guide

TECHNICAL GUIDE GENERAL SPECIFICATIONS COMMERCIAL SPLIT-SYSTEM COOLING UNITS FOUR PIPE SYSTEM OUTDOOR UNIT: INDOOR UNIT:

SPLIT-SYSTEM EVAPORATOR BLOWER DESCRIPTION FEATURES L4EU NOMINAL TONS

FULLY SELF-CONTAINED AIR CONDITIONING WITH INDUSTRIAL DURABILITY

VertiCool CLASSIC. Engineering Guide. Effective March Air-Cooled, Water-Cooled, Chilled Water and Water Source Heat Pump

Advance Release September 2009

Data Aire Mini Ceiling Systems 1, 1.5, 2, and 2.5 ton capacities R-410A. ISO 9001 Certified

INSTALLATION INSTRUCTIONS TXV Horizontal Slab Coils WLSH

K*ES120 DESCRIPTION TECHNICAL GUIDE SPLIT-SYSTEM EVAPORATOR BLOWERS 10 NOMINAL TONS EER 8.5 ACCESSORIES FIELD INSTALLED TABLE 1: ARI RATINGS*

EMBASSY SERIES SINGLE PACKAGE AIR CONDITIONERS (WATER-COOLED) C2ED060, 090, 120 & 180 5, 7-1/2, 10 & 15 Nominal Tons

Shelf Units R-407C. 2, 3, and 4 ton. ISO 9001 Certified

CHAMPION SPLIT-SYSTEM EVAPORATOR BLOWER DESCRIPTION FEATURES L2EU NOMINAL TONS

Installation, Start-Up and Service Instructions

TABLE OF CONTENTS. NOTE: Read the entire instruction manual before starting the installation. TROUBLESHOOTING... 13

Liebert CSU3000 Chiller

Technical Guide DESCRIPTION CHAMPION SPLIT-SYSTEM EVAPORATOR BLOWER L4EU240A 20 NOMINAL TONS (WORLD 50 HZ) FEATURES XTG-A-0307

Guide Specifications PART 1 GENERAL 1.01 SUMMARY

Liebert Challenger 3000/Liebert Challenger ITR with Liebert icom Control. Operation & Maintenance Manual - 50 & 60Hz

TECHNICAL GUIDE SPLIT-SYSTEM AIR-COOLED EVAPORATOR BLOWER 25, 30, 40 & 50 TON LA300, LB360, 480 & 600 (50 Hz) PROVEN PERFORMANCE GENERAL FEATURING

RTU. Roof Top Units 8 30 Ton. Maxi-Kool.

PARALLEL RACK SYSTEM INSTALLATION & OPERATIONS MANUAL With Master Rack Compressor Sequencer

ENGINEERING GUIDE. Water-Cooled Self-Contained Units C-Series, Vertical

SECTION COMPUTER ROOM AIR CONDITIONING SYSTEMS

INSTALLATION INSTRUCTIONS TXV Horizontal Duct Coils EHD

NOTE: Special care should be given to those areas where these symbols appear.

Liebert Datamate: R-407C Parts Manual

KCC Centrifugal Fan Air Cooled Condensers

CAS. Product Specifications. COMMERCIAL SPLIT SYSTEMS CONDENSING UNITS R 410A, 6 to 12.5 TONS BUILT TO LAST, EASY TO INSTALL AND SERVICE

DESIGN GUIDELINES SPLIT TYPE AIR TO AIR HEAT PUMPS PAGE 1 of 6

FALCON Rooftop Units ACPSE 50/60Hz Cooling Capacity : 36 to 1388 MBH (11 to 407 kw) Heating Capacity : 40 to 1298 MBH (12 to 380 kw)

Liebert PDX and PCW Thermal Management Systems

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS

User s Information and Installation Instructions

TECHNICAL GUIDE MODELS: H5CE090, H3CE120 & H1CE /2, 10, & 12-1/2 NOMINAL TONS EER DESCRIPTION

Brown University Revised August 3, 2012 Facilities Design & Construction Standards SECTION AIR HANDLING UNITS

Operation Manual SCT14B and SCT18B. Inspection. 3 General Description. 3 General Requirements. 3 Standard Features.

Commercial High-Efficiency Condensing Units

User s Information/Installation Instructions

ENVIRONMENTAL CONTROL UNIT (ECU) PART NUMBER OPERATIONS AND MAINTENANCE MANUAL

Modular Data Temp Systems Air Cooled Water/Glycol Cooled 8, 10 and 13 ton capacities R-410A. ISO 9001 Certified

Series 6, Vertical Floor-Mount Units

AIR COOLED LIEBERT CHALLENGER 3000 MODELS

VERTICOOL TECHNICAL DATA MANUAL. Vertical Air/Water Cooled 3-25 Tons

G Series. G Series Air Coils Installation ti Manual ENCASED/UNCASED AIR COILS. Geothermal/Water Source Heat Pumps R-410A Refrigerant 2-5 Ton

OPERATIONS AND MAINTENANCE MANUAL FOR THE 8-TON TURF CART ENVIRONMENTAL CONTROL UNIT (ECU) PART NUMBER

DRY CHARGE UNITS. 1.5 to 5 Tons AIR CONDITIONERS LCS13DC PRODUCT SPECIFICATIONS L C S 13 DC MODEL NUMBER IDENTIFICATION

INSTALLATION INSTRUCTIONS TXV Coils EDM, EDD, EDA

Liebert DSE Thermal Management System

Product Data. Features/Benefits. GEMINI 38AKS Commercial Air-Cooled Split Systems 50/60 Hz. 25 to 40 Nominal Tons (82.8 to 127.

Modular Data Temp Systems Air Cooled Water/Glycol Cooled R-407C. 8, 10 and 13 ton capacities. ISO 9001 Certified

SECTION FAN COIL UNITS

INSTALLATION AND OPERATING INSTRUCTIONS

INSTALLATION INSTRUCTIONS

DLCLRA. INSTALLATION INSTRUCTIONS Outdoor Unit Single Zone Ductless System Sizes 36 to 58 TABLE OF CONTENTS

Commercial High-Efficiency Condensing Units

SPLIT-SYSTEM HEAT PUMPS 50 AND 60 HZ DESCRIPTION

Installation, Start-Up and Service Instructions

Product Specifications. Vertical Floor Consoles By First Co.

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw

Liebert Air-Cooled Fin/Tube Condensers

SECTION AIR-COOLED SPLIT SYSTEM AIR CONDITIONING UNITS

Data Aire Series Air Cooled, Water/Glycol Cooled 6 through 30 Ton Dual Circuits R-407C

Series 6. Guide Specification 60 Hz. MISSION CRITICAL Air Conditioning Systems. ClimateWorx International Inc.

CS/CD/CP AIR COOLED CONDENSING UNITS (P/N E207120C R2)

Technical Guide SUNLINE 2000 DESCRIPTION ACCESSORIES FIELD INSTALLED SPLIT-SYSTEM EVAPORATOR BLOWER K4EU NOMINAL TONS (WORLD 50 HZ)

RHGN-H: COMMERCIAL AIR HANDLER WITH VARIABLE FREQUENCY DRIVE (VFD) NOMINAL 10 TONS R-410A REFRIGERANT 2-STAGE AIR-FLOW

Installation Instructions

Installation Instructions

1.1 This section applies to air handling units for HVAC Systems.

WineZone Ceiling Mount Ductless Split 15

TECHNICAL GUIDE DESCRIPTION EA090/FA090 SPLIT-SYSTEM HEAT PUMPS OUTDOOR UNIT INDOOR UNIT

INSTALLATION INSTRUCTIONS TXV Coils for Manufactured Housing EMA

SPLIT-SYSTEM EVAPORATOR BLOWERS K2EU060, K4EU090, K3EU120 & K1EU180 5 Thru 15 Nominal Tons DESCRIPTION ACCESSORIES FIELD INSTALLED

Transcription:

Liebert Products & Service World Headquarters United States 1050 Dearborn Drive, P.O. Box 29186 Columbus, Ohio 43229 Telephone: 614-888-0246 Facsimile: 614-841-6973 Europe Via Leonardo Da Vinci 8 Zona Industriale Tognana 35028 Piove Di Sacco Italy Telephone: 39-049-9719-111 Facsimile: 39-049-5841-257 Liebert Canada - Vancouver #108-7500 Winston St., Burnaby, B.C. V5A 4X5 Telephone: 604-420-8857 Facsimile: 604-420-8865 Liebert Mini-Mate2 Air-Cooled Model Job Name Model Quantity BLOOM AGRICULTURAL BLDG MMD24E7PJSDA / PFH027A-PL7 1 (One) /1 (One) Date December 4, 2013 Invoice # Purchaser FOR APPROVAL P.O. # A-120213 Tag # Submitted By ALPINE REFRIGERATION & AIR CONDITIONING FC-1/CU-1 Liebert Canada Mike Vinogradov PG1 Rev 10/10

Project Name: BLOOM AGRICULTURAL BLDG Date: December 4, 2013 Reference No.: Q01991984 Submitted By: Liebert Canada Mike Vinogradov Liebert Mini-Mate2 Ceiling-Mounted Precision Cooling Unit ENGINEERING SPECIFICATION SHEET Model Number: MMD24E7PJSDA Quantity: 1 Condensing Model Number: PFH027A-PL7 Quantity: 1 ELECTRICAL SUPPLY REQUIREMENTS Module: 208/230 Volts, 1 Phase, 60 Hz, 38.4 Full Load Amps, 48.0 Wire Sizing Amps, 50.0 Over-current Protection Device Condensing Module: 208/230 Volts, 1 Phase, 60 Hz, 13.4 Full Load Amps, 16.4 Wire Sizing, 25.0 OPD NET CAPACITY DATA 70ºF (21.1ºC) DB 58.4ºF (14.7ºC) WB 50 % RH Total - High Speed: 20,100 BTU/hr (5.9 kw) Sensible - High Speed: 17,900 BTU/hr (5.2 kw) EVAPORATOR FAN Direct Drive Motor, 0.5 HP (0.3 kw) Air Volume - High Speed: 885 CFM (1504 CMH) Air Volume - Low Speed: 800 CFM (1359 CMH) External Static Pressure: 0.3 Inches of Water (8 mm) REHEAT SECTION SCR Reheat: 19,100 BTU/hr (5.6 kw) Includes Fan Motor HUMIDIFIER SECTION Steam Generating Canister Capacity: 4.3 lbs/hr (1.5 kg/hr) 1.5 kw CONDENSING UNIT Design Ambient: 95ºF (35ºC) Outdoor Propeller Fan (Lee-Temp Head Pressure Control) Condensing Unit Hot Gas Bypass Capacity Control R-407C Refrigerant field supplied and charged by others ADDITIONAL EQUIPMENT Evaporator Non-Locking Disconnect Switch Filter Clog Indicator Remote Humidifier Contact Remote shutdown terminal Sweat Adapter Kit Condensate Pump Duct Kit with MERV 8 Filter IS-WEBADPT Card inside enclosure, wired to and mounted on rear panel of Mini-Mate - HTTP, SNMP, or BACnetIP Protocols; Qty: 1 (One) per Unit Standard Liebert 1 year parts only warranty + Startup by a Liebert service affiliate M-F, 8-5PM only. PG2 Rev 10/10

SMALL SYSTEMS 2-ton and 3-ton MINI-MATE2 DIRECT EXPANSION FAN/COIL MODULE STANDARD FEATURES EVAPORATOR COIL Constructed of copper tubes in a staggered tube pattern. Tubes are expanded into continuous high efficiency aluminum lance type fins. Coil is set in condensate drain pan, with float switch for unit shutdown. REFRIGERATION SYSTEM Single refrigeration circuit, includes a liquid line filter drier, externally equalized expansion valve, and a quick-connect female coupling on both the suction and liquid lines. Each female coupling is provided with an access valve connection. The module is precharged with refrigerant and sealed. FAN ASSEMBLY Centrifugal type, double width, double inlet, with a direct drive 2-speed fan motor mounted to the blower housing and includes lifetime lubricated bearings. CONTROLS Microprocessor based design includes 8 key membrane key pad for setpoint and program control, unit on/off, and fan speed mounted in a decorative wall box for remote mounting. CABINET AND CHASSIS Constructed of galvanized steel for strength and corrosion resistance with thermal/acoustical insulation to reduce sound levels and prevent condensation. Removable panels allow access to the electric panel or refrigeration components for service or maintenance. Vibration isolators are provided with the chassis for mounting. UNIT DISCONNECT SWITCH Consists of a non-locking type, non-automatic molded case circuit interrupter mounted inside the unit, with handle accessible outside cabinet. REV 09/11 DPN000186 REV 4

SMALL SYSTEMS 2-ton and 3-ton LIEBERT MINI-MATE2 DIRECT EXPANSION FAN/COIL MODULE ADDITIONAL FEATURES (Split DX Systems) ELECTRIC REHEAT Electric low watt density 304 stainless steel fin tubular reheat element provides one stage of reheat to maintain room dry bulb temperature. SCR ELECTRIC REHEAT includes integral controller and sensor to provide modulating electric reheat. STEAM GENERATING CANISTER HUMIDIFIER is housed in a steel enclosure and includes a replaceable canister with integral fill cup, fill and drain valves, and high water indicator. System automatically fills and drains as well as maintains the required water level based on conductivity. HIGH TEMPERATURE SENSOR is mounted in the unit with the sensing element in the return airflow. Upon activation, the high temperature stat will immediately shut down the entire unit. SMOKE DETECTOR the smoke detector senses the return air, shuts down the unit upon detection, and sends visual and audible alarm. This smoke detector is not intended to function as or replace any room smoke detection system that may be required by local or national codes. FILTER CLOG SWITCH activates the alarm system when the pressure drop has exceeded the customer-set level. FREE COOLING is factory piped with a control valve, free cooling coil is constructed of copper tubes and aluminum fins. Coil is designed for closed-loop applications using properly treated and circulated fluid. Refer to installation manual for further guidelines. Not available with SCR reheat option. SHIP LOOSE ACCESSORIES PRECHARGED REFRIGERANT LINE SETS consist of one pre-charged liquid line and one pre-charged insulated suction line of soft copper tubing. Each line is pre-charged with R-407C refrigerant. Each line has one male quick-connect coupling and one female quick-connect coupling with an access valve connection. Line sets are available in 15 ft. (4.6 m) and 30 ft. (9.1 m) lengths for interconnection of remote condensing units. Maximum recommended line-set distance is 45 ft. (13.7 m). FILTER BOX is constructed of galvanized steel, supplied with a nominal 16 (406mm) x 20 (508 mm) x 4 (102 mm) deep pleated MERV 8 filter (based on ASHRAE 52.2-2007). The box is provided with a ¾ (19 mm) duct flange. The filter is accessible via a hinged access door, without shutting the unit down. The filter box option also includes a ¾ (19 mm) discharge air duct collar. CONDENSATE PUMP has a capacity of 80 GPH (303 l/h) for 230 volt 60 Hz units and 74 GPH (279 l/h) for 208/277 volt 60 Hz units or 56 GPH (212 l/h) for 220 Volt 50 Hz units at 10 ft. (29 kpa) of head. Pump is complete with pump, motor assembly, reservoir, integral float switch, and auxiliary safety float switch to shut unit off in event of pump failure. Pump assembly is designed to mount on the right side of the evaporator (indoor) module, or other suitable means to allow condensate drainage into the reservoir. REMOTE TEMPERATURE AND HUMIDITY SENSORS include sensors mounted in an attractive case with 30 ft.(9m) of cable. SWEAT ADAPTER KIT Contains two suction and two liquid compatible fittings that allow field-supplied interconnecting refrigerant lines to be used. See installation, operation and maintenance manual for maximum recommended installed distances. AIR DISTRIBUTION PLENUM Easily installed, self-contained air distribution plenum provides air discharge in three directions. The plenum is supplied with a nominal 16 (406mm) x 25 (535mm) x 4 (102mm) deep pleated MERV 8 filter (based on ASHRAE 52.2-2007). SINGLE POINT POWER KIT Allows modules to be connected to a single power feed when the evaporator and condenser modules are closed coupled. OPTIONAL HIGH STATIC BLOWER ASSEMBLY Centrifugal type, double inlet, with a belt drive 1 speed fan motor mounted to an adjustable motor base, and includes ball bearings on both motor and blower. Higher duct static pressures are attainable up to 2.0 (51 mm) ESP down stream from unit. REV 07/11 DPN000187 REV 3

LIEBERT MINI-MATE2 1-3 TON SYSTEMS WALL MOUNTED MICROPROCESSOR CONTROL AND MONITOR GENERAL BUTTON CONTROL allows full function modification of all running parameters. The 8 key membrane keypad includes on/off, fan speed, menu, alarm silence, increase, decrease, escape & enter. DISPLAY A 2 line x 16 character LCD which displays all monitoring, control, alarm, and diagnostic information. ALARMS are displayed on the LCD display with audible alarm. COMMON ALARM connections are provided at unit-mounted interface board for remote annunciation of unit alarms (compatible with SITE SCAN). STANDARD ALARMS TEMPERATURE high and low thresholds are programmable between 35 F and 95 F (1.6 C and 32.2 C). The alarm indicates excessive high or low room air temperature. HUMIDITY high and low thresholds are programmable between 15% RH and 85% RH. The alarm indicates excessive high or low room air humidity. HIGH HEAD Indicates a head pressure above factory preset point, and provides compressor cutout. SHORT CYCLE ALARM Indicates the compressor has turned off-on-off at least 10 times in a one hour period. LOSS OF POWER Indicates that a power interruption has occurred. HIGH WATER ALARM Indicates high water level in condensate pan, and shuts down unit. ADDITIONAL ALARMS The following alarms are available when the appropriate options are included with the unit. A maximum of two(2) alarms from the list below. Change Filters Indicates that the pressure drop across the filters has exceeded the pre-set level. Humidifier Problem Indicates excessive high water levels in the humidifier canister. Water Detected Indicates that water has been detected at a customer specified location. Smoke Detected Indicates that smoke has been detected, and unit shutdown. Alarm does not function as or replace any room smoke detection system that may be required by local or national codes. FEATURES OF THE MONITOR MONITOR Room conditions, operating status, alarms. SET-UP Password protected programming of various time delays and unit configurations. SETPOINT Password protected programming of operational setpoints/alarms. 5 DAY/ 2 DAY PROGRAMMABILITY 2 changes per day for temperature and humidity control setpoints. TEMPERATURE AND HUMIDITY SENSOR CALIBRATION can be adjusted from ±5 F/±10% RH to match local measuring device. DPN000178 REV 7/11 REV 3

SMALL SYSTEMS 2 & 3 TON MINI-MATE2 FAN/COIL MODULE DIMENSIONAL DATA AIR, WATER/GLYCOL & CHILLED WATER WITH DIRECT DRIVE BLOWER 3 7/8" (98mm) 1" (25.4mm) 11" (279mm) 18" (457mm) DUCT FLANGE 20" (508mm) 18" (457mm) 3/4" (19mm) 15" (381mm) CUSTOMER SUPPLIED THREADED RODS FOR MODULE SUPORT FROM CEILING (TYP. 4) 11 1/8" (283mm) 19 7/8" (505mm) 1" (25.4mm) (OPTIONAL) FILTER BOX COVER PLATE SUPPLIED WITH PLENUM. 24" (610mm) CABINET DIMENSION 1 7/16" (37mm) 18" (457mm) HANGING BRACKET 27 13/16" (706mm) THREADED ROD CENTERS 14" (356mm) CABINET OUTLINE 30" (762mm) CABINET DIMENSION 11 5/8" (295mm) SHADED AREA INDICATES A RECOMMENDED CLEARANCE OF 30" (762mm) BE PROVIDED FOR COMPONENT ACCESS AND REMOVAL 18" (457mm) REMOVABLE ACCESS 1 7/16" PANELS (37mm) 7/8" (22mm) HOLES FOR MODULE RIGGING (TYP. 2 EACH END). CABINET DIMENSIONS SAME AS ABOVE. 14" (356mm) 10 7/8" (276mm) 54" (1372mm) CABINET 57 13/16" DIMENSION (1468mm) OVERALL 55 13/16" DIMENSION (1418mm) THREADED ROD CENTERS (OPTIONAL) DISCHARGE AIR DUCT FLANGE SUPPLIED WHEN (OPTONAL) FILTER BOX IS ORDERED. 14" (356mm) 18" (457mm) SHADED AREA INDICATES A RECOMMENDED CLEARANCE OF 30" (762mm) BE PROVIDED FOR ACCESS AND FILTER REMOVAL NOTE: UNIT IS SPACED EVENLY IN REFERENCE TO THREADED ROD CENTERS MODULE DIMENSIONAL DATA UNIT NET WEIGHT MODEL # 60 HZ 50 HZ LBS (KG) MM*24E NA 225 (102) MM*36E MM*35E 225 (102) MM*40C MM*39C 230 (104) REMOVABLE PANEL ON SIDE OF PLENUM. MINIMUM CLEARANCE 30" (762mm) FOR FLTER ACCESS AND REMOVAL. 6" (152mm) 5" (127mm) AIR DISCHARGE OUT SIDES OF PLENUM. 48" (1219mm) OVERALL DIMENSION 24" (610mm) OVERALL DIMENSION AIR DISCHARGE OUT SIDES OF PLENUM. 3.25" (83mm) AIR INLET THROUGH GRILL IN CENTER OF PLENUM. (OPTIONAL) AIR DISTRIBUTION PLENUM ALL PIPING & ELECTRICAL FIELD CONNECTIONS ARE THE SAME REV 04/11 DPN000193 REV 3

SMALL SYSTEMS 2 & 3 TON MINI-MATE2 UNIT PIPING DATA AIR, WATER/GLYCOL & CHILLED WATER Entrance For Customer High Volt Connections. Entrance For Customer High Volt Connections With (SPPK) Single Point Power Kit. FRONT OF UNIT DPN000192 Entrance For Customer Low Volt Connections 7/8" (22.2mm) Dia. Entrance For Low Voltage Connection to Condensing Unit (if applicable) Optional 1/4" O. D. compression Fitting. Use Copper Lines For Humidifer Supply Line Evaporator Air Inlet on Ducted Version. Filter Clog Switch Option Connection Point Hot Water Reheat 5/8" (15.9mm) OD CU or Free Cooling Outlet 7/8" (22.2mm) OD CU. Extends 3-1/2" (88.9mm) beyond panel exterior. Hot Water Reheat 5/8" (15.9mm) OD CU or Free Cooling Inlet 7/8" (22.2mm) OD CU. Extends 3-1/2" (88.9mm) beyond panel exterior. Evaporator Air Outlet on Ducted Version NOTE: ROUTE SUPPLY LINE TO CLEAR HANGING RODS. 7/8" Dia. (22.2mm) Electrical Entrance for Condensate Pump Connection. Suction Refrigerant Line Quick Connect Female Coupling with Access Valve Power Supply from Electric Service Power Block in Fan/Coil Module. Fan/Coil Unit Condensate Pump Support Brace Condensate Drain Evaporator Air Outlet For Plenum Version Air Outlet Duct Condensate Pump 3/4" Hose Barb Supplied on Pump Tank Flexible Rubber Tubing 3/4" FPT Customer Connection Field Supplied Rigid Piping (Support as Required) CONDENSATE PUMP (FIELD INSTALLED) ON UNIT WITH AIR OUTLET DUCTWORK Drain Line (Field Supplied) 3/4" NPT Female Condensate Drain connection. Drain is Trapped Internally And Must Not betrapped Outside of The Module. Chilled Water Supply Line(IN) 7/8" (22.2mm) OD CU Extends 3-1/2" (88.9mm) beyond panel exterior. Chilled Water Return Line(OUT) 7/8" (22.2mm) OD CU Extends 3-1/2" (88.9mm) beyond panel exterior. Liquid Refrigerant Line Quick Connect Female Coupling with Access Valve Fan/Coil Unit Condensate Pump Condensate Drain Note: 3/4" (19.1mm) Flexible Rubber Tubing Assembly (Supplied with Pump Kit) must be installed on pump end of rigid piping (Support as Required.) Evaporator Air Inlet For Plenum Version Single Point Power Kit (SPPK) Harness Connection From Condensing Unit BACK OF UNIT Drain Line (Field Supplied Power Supply from Electric Service Power Block in 3/4" Hose Barb Fan/Coil Supplied on Module Pump Tank Flexible Rubber Tubing 3/4" FPT Customer Connection Condensate Field Supplied Pump Support Brace Rigid Piping (Support as Required) CONDENSATE PUMP (FIELD INSTALLED) ON UNIT WITH AIR DISTRIBUTION PLENUM REV 09/09 REV 1

SMALL SYSTEMS 2 & 3 TON MINI-MATE2 GENERAL ARRANGEMENT DIAGRAM SPLIT SYSTEMS AIR & CHILLED WATER FAN COIL Condenser Coil Scroll Compressor High Pressure Switch AIR COOLED (Split System) Liquid Injection Valve Bulb Suction Line Male Quick Connect Coupling Suction Line Female Quick Connect Coupling * Sensing Bulb Hot Gas Bypass Solenoid Valve 3 - Way Head Pressure Relief Valve Hot Gas Bypass Control Valve Check Valve 3/8" SAE 45 Male Flare (MCD) or Atmospheric (PFH) Pressure Relief Valve Sight Glass External Equalizer Liquid Injection Valve Service Access Ports Filter Drier Expansion Valve Liquid Line Solenoid Valve * Liquid Line Male Quick Connect Coupling Liquid Line Female Quick Connect Coupling Receiver Heater Pressure Limiting Switch Lee - Temp Receiver Pressure Balancing Valve Evaporator Coil Bleed Valve CHILLED WATER Chilled Water Return Chilled Water Supply Chilled Water Control Valve Chilled Water Coil 3 - Way Chilled Water Control Valve (Optional) ** Shut - Off Valves ** Hose Bibs * Use Liebert sweat adapter kit with field hard piping or use Liebert pre-charged line set. Close-coupling option available with MCD. FIELD PIPING ** Components are not supplied by FACTORY PIPING Liebert but are recommended for proper circuit operation and maintenance. REV 12/09 DPN000191 REV 2

SMALL SYSTEMS 2 & 3 TON MINI-MATE2 ELECTRICAL FIELD CONNECTIONS Site monitoring connection. Terminals TB4-1(+) TB4-2(-) are for connection of a 2 wire. twisted pair, communication cable (available from Liebert or others) to optional sitescan. Remote Control Panel Connection to TB3-1,2,3,4 connected with field supplied Thermostat wire (22ga, shielded/ jacketed: available from Liebert or others). Unit Control Board terminals marked GND, +5V, T-, T+ must be connected to corresponding terminals on Remote Control Wall Box. Common alarm connection. Field supplied 24V. Class 2 wiring to common alarm conn TB1-6 & TB1-7. Customer remote alarm connection field supplied 24V. Class 2 wiring to conn TB1-1, TB1-2 & TB1-3. Remote unit shutdown. Replace existing jumper between terminals TB1-4 & TB1-5 with normally closed switch having a minimum 75VA rating. use field supplied 24V class 1 wire. Field supplied unit disconnect switch when factory unit disconnect switch is not supplied Electric service not by Liebert (Optional) condensate pump aux float switch connection to term TB1-8 & TB1-9. Factory installed disconnect switch. Earth ground connection Connection terminal for field supplied earth grounding wire. Heat rejection connection. Field supplied 24V NEC class 2 wiring. See note 2. For remote air cooled units from terminals TB2-1, 2, 3 & 4 in the Fan/Coil module to wires 1, 2, 3 & 4 in the condensing module: 1. 24V GND 2. 24V Supply 3. High Pressure Alarm (OPT) 4. Hot Gas Bypass Connection High Volt Power Connections. Electric service connection terminals. Entrance for customer low volt connections. Remote Humidifier Contact Field Supplied 24V class 2 wiring to terminals 11 & 12, located in field wire compartment. Entrance For Customer High Volt Connections. Electrical entrance for optional condensate pump Drycooler/Circulating pump control circuit TB70-71. Optional w/econ-o-cycle models. Use field supplied 24V class 2 wire. Field supplied, field wired thermostat wire to remote wall box Entrance For Customer Low Voltage Connections NOTES: 1.Refer to specification sheet for full load amp and wire size amp ratings. 2.Control voltage wiring must be a minimum of 16GA (1.3mm) for up to 75' (23m) or not to exceed 1 volt drop in control line. Field supplied 24V (NEC class 2 wiring) to condensing module. (if applicable) REV 12/09 DPN000195 REV 2

LIEBERT INTELLISLOT WEB/485 CARD WITH ADAPTER Product Specification/Installation Sheet Description The Liebert IntelliSlot Web/485 Card with Adapter (P/N IS-WEBADPT) provides 10/100baseT Ethernet network and Modbus connectivity for your Liebert equipment. Operating status is monitored and alarms are communicated via the network using SNMP, BACnet IP (for Liebert DataMate and Liebert Mini-Mate) and/or HTTP protocols and over RS-485 using the Modbus protocol. Additional Features SNMP v1, v2c with MIB-II support HTTP Telnet BootP, DHCP per RFC2131 Remote firmware updates via HTTP BACnet IP (for Liebert DataMate and Liebert Mini-Mate) Compatibility With Other Emerson Network Power Products Precision Cooling Unit (Controller see selected codes*) Liebert Challenger 3000 (L00, L15, LSM, LAM) Liebert DataMate (L0B) Liebert Deluxe System/3 (L10, L15, LSM, LAM) Liebert Himod (LAM) Liebert ICS (L10, LSM, LAM) Liebert Mini-Mate (L0B) Liebert Mini-Mate2 (MM2) Liebert Mini-Mate2 8 Ton (L8T) Large UPS *Controller Codes Liebert Npower L00: L0B: L10: L15: LSM: LAM: Level 00 Level 0B Level 10 Level 15 Standard Microprocessor Advanced Microprocessor Hiross Microface IGMnet Liebert Atlas PEC, Liebert Atlas Air, Liebert LECS15, Liebert CEMS 100 Liebert Series 300 Liebert Series 600 /610 (Single Module) Liebert Series 610 System Control Cabinet (Multi-Module) Hiross 7200 (EMEA) Hiross HiPulse (EMEA) Power Management Liebert Datawave Liebert FPC Liebert PPC Liebert Static Transfer Switches: Liebert STS Liebert STS2 (3 pole) Liebert STS2/PDU Overall and Mounting Dimensions 0.6" (15.3mm) 2.8" (71.1mm) 7" (177.8mm) 3.4" (86.4mm) 0.8" (20.3mm) Six holes, each 0.156" diameter 2.4" (61mm) 4" (101.6mm) 0.4" (10.2mm) 0.2" (5mm) 3.2" (81.3mm) 1

Customer Wiring Input power (input to TB3) Pin 1(+) Pin 2(-) Pin 3 (NC) Network port for NMS and Web access Modbus output for BMS (output from TB2) Specifications AC Inputs 18-24 VAC; 50/60 Hz Power Requirements DC Inputs 12-36VDC Power Consumption 6VA maximum Dimensions - W x D x H: in. (mm) 7 x 4 x 1.5 (178 x 102 x 38) Weight Net - oz. (kg) 7 (0.2) Shipping - lb. (kg) 1.3 (0.6) Ambient Operating Environment, F ( C) 32 to 104 (0 to 40); 10% to 90% RH (non-condensing) Ambient Storage Temperature, F ( C) -4 to 140 (-20 to 60) Protection SELV Isolated User Connections, Watchdog Timer Circuitry Communication Ports Wiring Specifications Service Terminal (RS-232) Unit Input Communications Modbus (RS-485) Ethernet Communications DB9F, DTE TB1, 2-Position Terminal Block P1, 20-PIN Vertical Header with Ejection Latches (for some UPS models) TB2, 2-Position Terminal Block RJ45 Connection Supported Wire Types Maximum Wire Length TB1 (RS-422) TB2 (RS-485) TB1: Pin 1 (+), Pin 2 (-) TB2: Pin 1 (+), Pin 2 (-) IGMnet or Liebert SiteScan Comms from unit (input to TB1 or P1) Refer to user manual for details 18-22 AWG Stranded & Shielded; 18 AWG* recommended Non Plenum - Belden 9461; Plenum - Belden 88761 18-22 AWG Stranded & Shielded; 18 AWG* recommended Non Plenum - Belden 9461; Plenum - Belden 88761 DTE serial port for configuration (requires null-modem connection) 1000 ft. (300m) 3000 ft. (915m) TB3 (Power Input) 18-22 AWG Stranded & Shielded; 18 AWG* recommended Non Plenum - Belden 8770; Plenum - Belden 88770 20 ft. (6m) DB9F Connector DTE Null Modem Cable 50 ft. (15m) RJ45 Connector Standard Category 5 Cable 328 ft. (100m) Liebert Corporation 1050 Dearborn Drive P.O. Box 29186 Columbus, OH 43229 Telephone: 1-800-877-9222 Facsimile: 1-614-841-6022 www.liebert.com 2007 Liebert Corporation All rights reserved throughout the world. Specifications subject to change without notice. Liebert is a registered trademark of Liebert Corporation. All names referred to are trademarks or registered trademarks of their respective owners. SL-29105_REV4_09-11 2

8 7 6 5 4 3 2 1 REVISIONS D H METAL MACHINE SCREW SEE NOTE 8. H PLATED THROUGH HOLE SEE NOTE 8. SMALL CIRCUIT CARD SEE NOTE 8. REV. DESCRIPTION 3 REDRAWN ON NEW BORDER; CHANGED P/N DESCRIPTION FOR 163769G5, G6, G7 AND G8. 4 1) UPDATE BORDER. 2) MODIFIED DRAWING TO SHOW NEW ENCLOSURE DESIGN. DATE APPROVED A. MEYER 6-28-07 K. STEPHENS 6-28-07 7/01/2010 M. VALESKY 7/01/2010 S. CRUMP D C LARGE CIRCUIT CARD SEE NOTE 8. C C B H ALUMINUM STANDOFF SEE NOTE 8. DETAIL C INSTALL NIC ADAPTER B NOTE. A 8. ADAPTER INSTALLATION - STEP 1 - REMOVE SMALL CIRCUIT CARD FROM LARGE CIRCUIT CARD. THIS IS DONE BY REMOVING TWO NYLON SCREWS AND UNPLUGGING ONE END OF SMALL RIBBON CABLE. STEP 2 - POSITION LARGE CIRCUIT CARD ONTO STANDOFFS BY ALIGNING PLATED THROUGH MOUNTING HOLE TO THE METAL STANDOFF. USE THE PROVIDED METAL MACHINE SCREW TO SECURE. NYLON SCREWS ARE USED TO SECURE THE BOARD TO THE REMAINING STANDOFFS. STEP 3 - ONCE LARGE CARD IS MOUNTED, REPLACE SMALL CIRCUIT BOARD, USING TWO SCREWS REMOVED IN STEP 1 AND RE-ATTACH RIBBON CABLE. SINGLE CARD VERSION SHOWN FOR ILLUSTRATION, SECOND CARD MOUNTED SAME MANNER. 18 SEE NOTE 9. (TEXT) A 9. EXTERNAL SERIAL LABEL APPLICATION - CLEAN AREA OF ENCLOSURE BASE WITH ALCOHOL. APPLY EXTERNAL SERIAL LABEL AS SHOWN. APPLY EXTERNAL SERIAL LABEL SIZE B 163769 3/4 4 DRAWING NUMBER SHEET REV. 8 FORM NO. 177106 REV 7 7 6 5 4 3 2 1

PROP FAN CONDENSING MODULES STANDARD FEATURES COMPRESSOR The 1½ - 8 ton PFH condensing units shall have a compliant scroll compressor with a suction gas cooled motor, vibration isolators, thermal overloads, internal centrifugal oil pump for forced feed lubrication, a maximum operating speed of 3500 RPM @ 60 HZ (2900 @ 50 HZ). The 1 ton PFH condensing unit shall have a reciprocating hermetic compressor. The 8 ton PFH is a dual compressor design with 3 ton and 5 ton compressors. CONDENSER COIL Constructed of copper tubes in a staggered tube pattern. Tubes are expanded into continuous high efficiency aluminum plate type fins. Coil is set in a drain pan for condenser coil washdown. REFRIGERATION SYSTEM Single refrigeration circuit, includes, suction and liquid line quick connect male couplings. The module is precharged with refrigerant and sealed. The 8 ton PFH includes two refrigeration circuits. HOT GAS BYPASS Factory piped hot gas solenoid valve and pressure regulating valve work in conjunction with a thermostatic liquid injection valve. This system allows operation down to zero load on the evaporating (indoor) module. Both circuits on the 8 ton model receive HGBP. FAN ASSEMBLY Consists of propeller type blades, constructed of zinc plated steel or aluminum, secured to the motor shaft by a heavy duty hub with set screws. Direct drive fan motors are provided with rain slingers, lifetime lubricated bearings, and internal overload protection. CABINET AND CHASSIS Designed for outdoor use with either roof or ground level mounting. The condensing module is constructed of galvanized and galvaneal painted steel for corrosion resistance. Both inlet and outlet air grilles are heavy duty steel with a durable P.V.C. coating. Removable exterior panels allow access to the electric panel or refrigeration components for service or maintenance. HEAD PRESSURE CONTROL A Liebert Lee-Temp control system is furnished with each refrigeration circuit and consists of an insulated heated refrigerant receiver with sightglass, pressure relief valve, pressure balancing valve, check valve, and head pressure operated 3-way valve. This system allows operation at ambient conditions as low as -30 F (-34 C). ADDITIONAL FEATURES QUIET LINE Oversized cabinet, low speed 6-pole motor, and Liebert fan blade design combine to achieve the quietest unit available(8 to 10 db(a) below standard models). Not available on 8 ton PFH. HIGH AMBIENT Oversized condenser coil with high efficiency aluminum plate type fins and increased airflow. Designed for operation at ambient conditions of 105 F (40 C) with no reduction in evaporator rated performance. Not available on 8 ton PFH. REV 04/11 DPN000128 REV 3

CABINET AND FLOOR PLANNING DIMENSIONAL DATA PROP FAN CONDENSING MODULES HORIZONTAL AIR DISCHARGE Fan Rotation CCW (left side) A REMOVABLE (RIGHT) PANEL FOR ACCESS TO REFRIGERATION COMPONENT. RIGHT AIR DISCHARGE LEFT AIR INTAKE B SHADED AREA INDICATES A MINIMUM CLEARANCE OF 18" (457mm) BE PROVIDED FOR PROPER AIR FLOW. SHADED AREA INDICATES A MINIMUM CLEARANCE OF 18" (457mm) BE PROVIDED FOR PROPER AIR FLOW. C REMOVABLE (FRONT) PANEL FOR ACCESS TO HIGH VOLTAGE & LOW VOLTAGE CONNECTIONS, AND REFRIGERATION COMPONENTS. SHADED AREA INDICATES A RECOMMENDED CLEARANCE OF 24" (610mm) BE PROVIDED FOR COMPONENT ACCESS AND REMOVAL. MODEL NUMBERS DIMENSIONAL DATA IN. (mm) MODULE WEIGHT 60 HZ 50HZ A B C lbs. (kg) net. PFH014A-L NA PFH020A-L NA 40 (1016) 23 1/2 (597) 18 (457) 200 (91) PFH027A-L NA PFH027A-H NA PFHZ27A-L NA PFH037A-L PFH036A-L 48 (1219) 31 (787) 18 (457) 241 (109) PFH042A-L PFH041A-L PFH037A-H PFH036A-H PFHZ37A-L PFHZ36A-L PFH042A-H PFH041A-H 53 (1343) 36 1/4 (918) 18 (457) 351 (159) PFHZ42A-L PFHZ41A-L PFH067A-L PFH066A-L REV 04/11 DPN000130 REV 1

PIPING AND ELECTRICAL CONNECTIONS HORIZONTAL AIR DISCHARGE Liquid Line Quick Connect (Male Coupling). A Suction Line Quick Connect (Male Coupling). Except as noted G F Electrical Entrance for High Voltage Connection. B C Electrical Entrance for Low Voltage Connection. D E MODEL NUMBERS 60 HZ 50 HZ PFH014A- L NA PFH020A- L NA PFH027A- L NA PFH027A- H PFHZ27A- L PFH037A- L PFH042A- L PFH037A- H PFHZ37A- L PFH042A- H PFHZ42A- L PFH067A- L NA NA PFH036A- L PFH041A- L PFH036A- H PFHZ36A- L PFH041A- H PFHZ41A- L PFH066A- L ELECTRICAL CONNECTIONS IN. (mm) A B C 2 1/4 (57) 2 (51) 2 (51) 5 1/4 (133) 5 3/4 (146) 6 (152) 7 3/4 (197) 8 1/2 (216) 8 1/2 (216) D 8 3/4 (222) 4 3/4 (121) 4 3/4 (121) PIPING CONNECTIONS IN. (mm) E F G - 6 3/4 (171) 7 3/4 (197) 5 (127) - - 7 1/4 (184) 8 1/2 (216) 8 1/2 (216) DPN000132 REV 04/11 REV 1

GENERAL PIPING ARRANGEMENT PROP FAN CONDENSING MODULE SINGLE CIRCUIT = 1-5 Tons DUAL CIRCUIT = 8 Tons Condenser Coil High Pressure Switch Compressor * Liquid Injection Valve Bulb Hot Gas Bypass Solenoid Valve Suction Line Male Quick Connect Coupling Hot Gas Bypass Control Valve 3 - Way Head Pressure Control Valve Check Valve Atmospheric Pressure Relief Valve Sight Glass Liquid Injection Valve Liquid Line Male Quick Connect Coupling Liquid Line Solenoid Valve Receiver Heater Pressure Limiting Switch Lee - Temp Receiver Pressure Balancing Valve * Reciprocating compressor 1 Ton. Scroll compressor 1 1/2-8 Tons. SINGLE CIRCUIT SHOWN REV 04/11 DPN000129 REV 3

ELECTRICAL FIELD CONNECTIONS 1 5 TON PROP FAN CONDENSING MODULE Field supplied unit disconnect switch. Single or three phase electric service not provided by Liebert. Single or three phase electric service not provided by Liebert. Field supplied unit disconnect switch. Field supplied 24V NEC class 2 wiring to evaporator module. Field supplied 24V NEC class 2 wiring to evaporator module. Horizontal Air Discharge Models Top Air Discharge Models (5 ton High Ambient or 5 ton Quiet-Line) Electric service connection to contactor or terminal block. Factory wired to components on electric panel. Single or three phase electric service not provided by Liebert. High voltage electric power supply entrance. Low voltage electric power supply entrance. Earth ground connection terminal for field wiring. Heat rejection connection. Field supplied 24V NEC class 2 wiring. Wire connections from evaporator module: 1 24V GND 2 24V Supply 3 High Pressure Alarm 4 Hot Gas Bypass Connection NOTE: Refer to specification sheet for full load amp. and wire size amp. ratings REV 01/09 DPN000134 REV 1

Installation 2.0 INSTALLATION Read this entire installation section before starting installation. This section details dimensional, electrical and piping information and specifications that affect the placement of the PFH unit in relation the connected evaporator unit, other outside units, barriers and walls. Be particularly mindful of service and airflow clearances and maximum equivalent piping distances and in elevation differences between PFH and connected evaporator unit. Consult and confirm applications with your Emerson Network Power representative when applications exceed any of these specifications. 2.1 Equipment Inspection When the unit arrives, inspect all items for any visible or concealed damage. Report any damage to the carrier immediately and file a damage claim; send a copy of the claim to Emerson Network Power or your local Emerson sales representative. If possible, maintain equipment and packaging until it is at the installation location. 2.2 Location Considerations To ensure an adequate air supply, locate all condensing units in a clean-air area, away from loose dirt and debris that can clog the coil. Avoid ground-level sites with public access or areas that are exposed to heavy snow accumulation. Locate unit to allow maximum security and maintenance accessibility. Do not locate condensing units near steam, hot air or fume exhausts. Do locate units at least 18 in. (457mm) from walls, obstructions or adjacent units. For multiple unit installations, space unit so that the hot condenser exhaust air is not directed toward the condenser air inlet of an adjacent unit. Install a solid base at least 2 in. (51mm) higher than the surrounding grade and 2 in. (51mm) larger than condensing unit base dimensions and capable of supporting the condenser s weight. 2

2.5 Piping Considerations Installation The Liebert Mini-Mate2, Liebert DataMate and the 3-ton Liebert Challenger 3000 split system units are designed with quick-connect fittings and are factory-charged to proper refrigerant levels. This permits connecting units without brazing inside critical spaces. These split systems require two refrigerant lines an insulated copper suction line and a copper liquid line between the evaporator and condensing units. The 8-ton Liebert Mini-Mate2 split system units will require four refrigerant lines between the evaporator and condensing units. Each refrigeration circuit will need one insulated copper suction line and one copper liquid line. Two methods exist for installing the copper suction and liquid lines: Using optional pre-charged line sets (for 1- to 3.5-ton R-407C model units only). Using optional Sweat Adapter Kit(s) and hard piping between units. NOTICE Risk of improper handling of refrigerant. Can cause environmental damage and violation of environmental regulations. Refrigerant must handled in accordance with all national, regional and local codes. NOTE Proper safety equipment and proper refrigeration tools are required in working with R-407C refrigerant. Check unit serial tag for correct refrigerant type before topping off or recharging a system. NOTE Refrigerant R-407C uses a POE (polyol ester) lubricant. The R-407C refrigerant must be introduced and charged from the cylinder only as a liquid. NOTE When installing field piping, care must be taken to protect all refrigerant lines from the atmosphere, especially when using refrigerants with POE oils. Do not allow the piping to stand open to air for more than 15 minutes. Units designed for R-407C have a compressor which contains POE oil that is very hygroscopic; that is, it quickly absorbs water from the air. The longer the compressor piping is left open to air, the harder it will be to fully evacuate. If left open too long, the POE oil may need to be replaced before achieving the required vacuum level. NOTE Complete all piping and evacuate lines before connecting quick connects when using an optional sweat adapter kit and field installed hard piping. Follow all proper brazing practices including a dry nitrogen purge to maintain system cleanliness. 2.5.1 Piping for Elevation Differences between PFH and Evaporator System sizes affect the maximum equivalent piping lengths and maximum relative elevation differences between evaporator and condensing unit mounting locations. See Table 5 for requirements. Traps in refrigerant piping are required when elevation differences exist between evaporator and condensing unit mounting locations. See Figure 12 for requirements. Table 6 should be used when traps are required with field-fabricated piping assemblies, to calculate equivalent pipe lengths to determine if installation will comply with Table 5 requirements. 14

Installation Figure 12 Refrigerant piping diagram Evaporator Suction Line Piping Condensing Unit Below Evaporator Pitch down 1/2" (13mm) per 10 ft. (3m) NOTE When NOTE installing remote condensing units below the evaporator, When installing the remote suction condensing gas line should units below trapped the with evaporator, an inverted the suction trap to gas the line height should of the be trapped evaporator. with This an inverted prevents trap refrigerant to the height migration of the evaporator to the compressors during off cycles. Maximum recommended verti-. This cal prevents level drop refrigerant to condensing migration to unit the is compressors 15 ft. (4.6m). during off cycles. Maximum recommended vertical level drop to condensing unit is 15 ft. (4.6m). Condensing Unit Evaporator Condensing Unit See Table 5 for maximum vertical rise recommendation above evaporator. Suction Line Piping Condensing Unit Above Evaporator Traps recommended at the base of riser exceeding 5 ft (1.5m) and every 20 feet (6m) of vertical rise. Table 5 Nominal System Size Tons Pipe length and condenser elevation relative to evaporator Max. Equiv. Pipe Length ft. (m) Maximum PFH Level Above Evaporator, ft. (m) Maximum PFH Level Below Evaporator, ft. (m) 1, 1.5, 2 150 (45) 40 (12) 15 (4.6) 3, 3.5, 5, 8 150 (45) 50 (15) 15 (4.6) Table 6 Copper Pipe OD, in. Equivalent lengths for various pipe fittings, ft (m) 90 Degree Elbow Copper 90 Degree Elbow Cast 45 Degree Elbow Tee Gate Valve Globe Valve Angle Valve 1/2 0.8 (0.24) 1.3 (0.39) 0.4 (0.12) 2.5 (0.76) 0.26 (0.07) 7.0 (2.13) 4.0 (1.21) 5/8 0.9 (0.27) 1.4 (0.42) 0.5 (0.15) 2.5 (0.76) 0.28 (0.08) 9.5 (2.89) 5.0 (1.52) 3/4 1.0 (0.3) 1.5 (0.45) 0.6 (0.18) 2.5 (0.76) 0.3 (0.09) 12.0 (3.65) 6.5 (1.98) 7/8 1.45 (0.44) 1.8 (0.54) 0.8 (0.24) 3.6 (1.09) 0.36 (0.1) 17.2 (5.24) 9.5 (2.89) 1-1/8 1.85 (0.56) 2.2 (0.67) 1.0 (0.3) 4.6 (1.4) 0.48 (0.14) 22.5 (6.85) 12.0 (3.65) 1-3/8 2.4 (0.73) 2.9 (0.88) 1.3 (0.39) 6.4 (1.95) 0.65 (0.19) 32.0 (9.75) 16.0 (4.87) 1-5/8 2.9 (0.88) 3.5 (1.06) 1.6 (0.48) 7.2 (2.19) 0.72 (0.21) 36.0 (10.97) 19.5 (5.94) Refrigerant trap = Four times equivalent length of pipe per this table 15

2.5.2 Pre-Charged Line Sets Liebert pre-charged line sets are available in 15 ft. (4.5m) and 30 ft. (9m) lengths (see Table 7). NOTICE Table 7 Line Size, in. 3/8 liquid 5/8 or 7/8 suction Installation Risk of improper handling and installation of pre-charged lines. Can cause kinks and similar damage to lines. Care must be taken to prevent kinking the pre-charged lines for 1-ton and 3.5-ton units. Use tube benders and make all bends before making connections to either end of the precharged pipes. Coil any excess tubing in a horizontal plane with the slope of the tubing toward the condensing unit. Use a soft, flexible material to pack around the tubes when sealing openings in walls to prevent tube damage and to reduce vibration transmission. 2.5.3 Field-Fabricated Line Sets Refrigerant charge in Liebert pre-charged R-407C line sets Length, ft. (m) Charge R-407C, lb-oz (kg) 15 (4.5) 0-5 (0.14) 30 (9) 0-10 (0.28) 15 (4.5) 0-5 (0.14) 30 (9) 0-10 (0.28) All field-fabricated refrigeration piping should be copper piping, brazed using a brazing alloy with a minimum temperature of 1350 F (732 C), such as Sil-Fos. Use a flow of dry nitrogen through the piping during brazing to prevent formation of copper oxide scale inside the piping. Avoid soft solders such as 50/50 or 95/5. Use the sweat adapter kits to terminate the piping at each unit end. Consult factory representatives to obtain the proper sweat adapter kit. Table 8 has PFH unit connection sizes. Use Table 9 for recommended line sizes. Prevailing good refrigeration practices should be employed for piping supports, leak testing, evacuation, dehydration and charging of the refrigeration circuits. The refrigeration piping should be isolated from the building by the use of vibration-isolating supports. Use a soft, flexible material to pack around the tubes when sealing openings in walls to prevent tube damage and to reduce vibration transmission. Before connecting units together with field-fabricated piping, check for leaks and dehydrate the field piping as follows: 1. Pressurize the field piping to 150 psig (1034 kpa) using dry nitrogen with a trace of refrigerant. Check system for leaks with a suitable leak detector. 2. After completion of leak testing, release the test pressure (per local code) and triple evacuate the field piping to 250 microns or lower, breaking the vacuum between the first two evacuations with dry nitrogen. 3. After the third evacuation, verify 250 microns is maintained for at least one minute after the piping is isolated from the vacuum pump by a shutoff valve. Field piping is now ready to be installed between evaporator and condensing units. 16

Table 8 Liebert PFH unit charge levels and coupling size Model Numbers R-407C Charge Coupling Size 60 Hz 50 Hz lb-oz (kg) Liquid Suction 95 F (35 C) Standard Sound PFH014A-_L7 PFH020A-_L7 8-6 (3.80) #6 #11 PFH027A-_L7 PFH037A-_L7 PFH036A-_L7 PFH042A-_L7 PFH041A-_L7 13-5 (6.04) #6 #11 PFH067A-_L7 PFH066A-_L7 26-10 (12.08) #10 #12 PFH096A-_L7 PFH095A-_L7 3-ton Circuit 3-ton Circuit 22-9 (10.23) #6 #11 5-Ton Circuit 5-Ton Circuit 36-5 (16.47) #10 #12 105 F (41 C) High Ambient PFH027A-_H7 13-5 (6.04) #6 #11 PFH037A-_H7 PFH036A-_H7 PFH042A-_H7 PFH041A-_H7 26-10 (12.08) #6 #11 PFH067A-_H7 PFH066A-_H7 51-11 (23.45) #10 #12 Quiet-Line PFHZ27A-_L7 13-5 (6.04) #6 #11 PFHZ37A-_L7 PFHZ36A-_L7 PFHZ42A-_L7 PFHZ41A-_L7 26-10 (12.08) #6 #11 PFHZ67A-_L7 PFHZ66A-_L7 51-11 (23.45) #10 #12 Table 9 Equiv. ft. (m) Recommended line sizes, OD Cu PFH_14A PFH_20A PFH_27A PFH_36A PFH_37A 3-ton circuit of 8-ton model PFH_42A PFH_41A Installation PFH_67A PFH_66A 5-ton circuit of 8-ton model Suction Liquid Suction Liquid Suction Liquid Suction Liquid Suction Liquid Suction Liquid 50 (15.2) 5/8" 3/8" 5/8" 3/8" 7/8" 3/8" 7/8" 3/8" 7/8" 1/2" 1-1/8" 1/2" 75 (22.9) 5/8" 3/8" 7/8" 3/8" 7/8" 3/8" 7/8" 1/2" 7/8" 1/2" 1-1/8" 5/8" 100 (30.5) 7/8" 3/8" 7/8" 3/8" 7/8" 1/2" 1-1/8" 2 1/2" 1-1/8" 1/2" 1-1/8" 5/8" 125 (38.1) 7/8" 3/8" 7/8" 1/2" 7/8" 1/2" 1-1/8" 2 1/2" 1-1/8" 1/2" 1-3/8" 5/8" 150 (45.7) 7/8" 3/8" 7/8" 1/2" 7/8" 1/2" 1-1/8" 2 1/2" 1-1/8" 5/8" 1-3/8" 5/8" 1. Suction and liquid line sizing based on < 3 psi pressure drop in each, minimum horizontal suction line velocity > 700FPM (3.6m/s). 2. Suction size should be reduced one pipe size for vertical riser sections to maintain suction line velocity > 1000FPM (5.1m/s) for proper oil return. 17

2.5.4 Installation of Piping to Units NOTE When using hard piping, complete all piping and evacuate the lines before connecting quick-connects. Installation NOTE Liebert Challenger 5-ton evaporator includes a nitrogen holding charge only. This holding charge must be evacuated and unit placed in a 250 micron vacuum prior to connecting piping. See Table 12 for field charge required. Use caution when connecting the quick-connect fittings. Read through the following steps before making the connections. 1. Remove protector caps and plugs. 2. Carefully wipe coupling seats and threaded surfaces with a clean cloth. 3. Lubricate the male diaphragm and synthetic rubber seal with refrigeration grade oil. 4. Thread the coupling halves together by hand to ensure that the threads mate properly. 5. Tighten the coupling body hex nut and union nut with the proper sized wrench until the coupling bodies bottom out or until you feel a definite resistance. 6. Using a marker or pen, make a line lengthwise from the coupling union nut to the bulkhead. 7. Tighten the nuts an additional quarter turn; the misalignment of the lines shows how much the coupling has been tightened. This final quarter turn is necessary to ensure that the joint will not leak. Refer to Table 10 for torque requirements. 8. Add liquid refrigerant charge for any field-fabricated piping (refer to Table 11) and the 5-ton Liebert Challenger evaporator if used (refer to Table 12). Table 10 Piping connection sizes and torque Line Size, OD Cu Coupling Size Torque, lb-ft. (N-m) 1/4 or 3/8 #6 10-12 (145-175) 5/8 thru 7/8 #10 or #11 35-45 (510-655) 1-1/8 #12 50-65 (730-950) Table 11 Line Size, O.D., in. Line charges - refrigerant per 100 ft. (30m) of Type L copper tube R-407C, lb/100 ft. (kg/30m) Liquid Line Suction Line 3/8 3.7 (1.7) 1/2 6.9 (3.1) 5/8 11.0 (5.0 0.4 (0.2) 3/4 15.7 (7.1) 0.6 (0.3) 7/8 23.0 (10.4) 1.0 (0.4) 1-1/8 1.7 (0.7) 1-3/8 2.7 (1.1) 2.5.5 R-407C PFH Installed as a Replacement Condensing Unit in an R-22 System When replacing the condensing unit of an existing Liebert split system containing R-22 and mineral oil, the following should be considered. 1. Check for proper operation of the system prior to replacing the outdoor unit. If this is not possible, at minimum perform a leak check to ensure that the components that remain (line set, evaporator) are leak tight. 2. Check for acid or contaminants in the mineral oil. 18

Installation Remove Existing Condensing Unit 1. Recover refrigerant in system using proper refrigeration practices. 2. Oil removal: The majority of the oil will be in the old condensing unit (compressor, condenser and receiver), which will be replaced with the new unit. 3. Remove high-voltage and low-voltage wiring. NOTE Wiring should be removed by a licensed electrician. Existing low-voltage wiring may have a 3-wire lead. A 4-wire lead is required for hot gas bypass control on the new condensing unit. 4. Cut the line set before the Aeroquip fittings entering the condensing unit. 5. Remove the existing filter drier in evaporator unit and discard. The filter drier may contain contaminants that can be released out of the drier because of the POE oil. Filter Drier Selection and Installation Recommended 1. Install a replaceable-core filter drier approved for POE oil. The existing drier must be removed. The replaceable core drier will not fit in the same location as the existing drier. 2. Ensure there is enough clearance for replacing cores when choosing a location. 3. Replace core a week after startup and inspect the removed replaceable core for contaminants to determine if another replacement is needed. (If the system experienced a burnout, shorter interval replacements will be needed.) Optional Install a new filter drier approved for POE oil in place of the existing one. Install the New Condensing Unit 1. Install a stub tube kit on the existing line set connecting to the new condensing unit. This kit is available from Emerson or your local Emerson representative. 2. Evacuate the evaporator-piping system twice to a minimum 250 microns, breaking the vacuum with dry nitrogen each time. 3. Evacuate a third time to 250 microns and verify the above levels are maintained for at least one minute after the unit is isolated from the vacuum pump by a shutoff valve. 4. Connect the condensing unit with the evaporator and piping (see 2.5.4 - Installation of Piping to Units). 5. Add enough R-407C refrigerant for the evaporator unit and line set. See Table 11 for line set charges required and Table 12 for standard evaporator units. If a non-standard evaporator was used, refer to evaporator unit serial tag for charge amounts and use 1 oz. (0.0283kg) R-407C for every 1 oz. (0.0283kg) R-22 used in old evaporator and piping. 19

2.5.6 General System Charge Requirements Installation Liebert split system units are designed with quick-connect fittings and are factory-charged to proper levels. Due to the wide range of operating ambients and sensitivity of the system components to charge level, the system charge must be maintained at recommended levels. If there is any doubt that the system has the correct refrigerant charge level, the correct procedure is to remove the entire system charge, evacuate the system and weigh in the recommended factory charge total for both units and any line sets or field piping. Tables 7, 8, 11 and 12 are included for field piping allowances, condensing unit charges, line sets and evaporator charges. Total refrigerant charge = evaporator + lines + condensing unit NOTE All condensing units and most evaporator units are fully charged with refrigerant. Some evaporator units are shipped from the factory with a nitrogen holding charge only. (Refer to evaporator serial tags.) If field-supplied refrigerant piping is installed, refrigerant must be added to the system. Refer to Figure 12 for field-supplied piping guidelines. Table 12 Evaporator Charge Levels Evaporator Models Charge R-407C oz (kg) Indoor Unit MMD12E 3 (0.085) MMD18E 4 (0.113) Liebert Mini-Mate2 MMD24E 7 (0.198) MMD35/36E 7 (0.198) MMD59/60E 4 (0.113) MMD95/96E 7 (0.198) each circuit DME020E 4 (0.113) Liebert DataMate DME027E 5 (0.141) DME037E 6.5 (0.184) Liebert Challenger 3000 BF/BU036E 9 (0.255) BF/BU060E* 13 (0.368) * Evaporator is charged with nitrogen at the factory 20

2.6 Electrical Connections Installation Each unit is shipped from the factory with all internal wiring completed. All power, control wiring and ground connections must be made in accordance with the National Electrical Code and local codes. Refer to equipment nameplate regarding wire size and circuit protection requirements. Refer to Figures 5, 7 and 8 and electrical schematic (reference Figures 9 through 11) when making connections. A manual electrical disconnect switch should be installed within 5 feet (1.6m) of the unit in accordance with codes.! WARNING Risk of electric shock. Can cause injury or death. Disconnect all local and remote electric power supplies before working within. Use a voltmeter to be sure power is turned off before making any electrical connections. NOTICE Risk of incorrect phase sequencing. Can cause equipment damage. Three-phase power must be connected to the unit line voltage terminals in proper sequence so that the scroll compressor rotates in the correct direction. The three-phase scroll compressor requires proper phasing to ensure correct motor rotation. The component connections have been phase synchronized at the factory. Power phasing should be changed only at the line voltage supply to the unit. To change phasing, switch any two power leads to the unit. Observe system pressures to determine whether the unit is operating properly. NOTICE Risk of compressor slugging. Can cause equipment damage. Apply power to condenser 8 hours before operating the system. This time is required to allow liquid refrigerant to be driven out of the compressor. This is especially important at low ambient temperatures. The compressor crankcase heater is energized as long as power is supplied to the unit. Table 13 Design refrigerant pressures Suction Discharge (At Design Ambient) High-Pressure Cutout Table 14 Application limits 53-95 PSIG (365 to 655 kpa) 280 psig (1930 kpa) 400 psig (2760 kpa) Input voltage Dry Bulb Air Temperature at Condenser Minimum Maximum Minimum Maximum 115 F (46 C) Std -10% Ambient & Quiet-Line +10% -30 F (-34 C) -5% 208/230V 125 F (52 C) single-phase High Ambient Models 2.6.1 Low-Voltage Control Wire Connections Field-supplied four-wire control connection (10-wire on 8-ton units) is required between the outdoor condensing unit and the evaporator. Refer to Figures 5, 7 and 8 and to unit electrical schematic and Figures 9 through 11. 21

4.4 Field Charge Verification Maintenance An integral sight glass is provided with the receiver to assist in field charge verification. During charge verification set the control temperature down to keep the system running. If the system is equipped with hot gas bypass, de-energize it by removing power from the hot gas solenoid valve coil. To remove power, disconnect the solenoid leads from the unit contactor in the electric box (refer to specific unit schematic; reference Figures 7 through 10). When charge verification has been completed, replace and secure all wire connections and covers. During operation at design ambients (95 or 105 F; 35 or 41 C) the charge level will be above the sight glass in the receiver. If levels are below the sight glass an undercharge condition is likely. If levels are above the sight glass and higher discharge pressures than normal are observed an overcharge condition may be likely. However, verify that other high discharge pressure causes such as dirty coil and restricted airflow are not responsible before removing charge. At temperatures below design ambient, refrigerant backs into the condenser coil and the level in the receiver will drop below the sightglass. If you are trying to verify charge level at lower ambients, block the condenser coil to maintain 230psig (1585kPa) discharge pressure to ensure the head pressure control valve is closed. At these conditions the charge level should be above the sight glass in the receiver. NOTE The 5-ton high ambient, 5-ton Quiet-Line and 8-ton models consist of two condenser coils and two receivers. When restricting airflow on these units, the coils should be blocked off proportionally. If one coil is restricted significantly more than the other, liquid can remain in the restricted coil causing lower levels in the receivers. The receiver liquid level should be above the sight glasses in both receivers. There may be some variation in charge level between the two receiver sight glasses due to piping and assembly variations. When adding charge, determine which receiver level is lower and use that sight glass to gauge charge level. NOTE If no level is visible in the sight glass, add charge until the level is in the middle of the sightglass. Check the discharge pressure during this procedure and adjust coil restrictions to maintain 230 psig (1585 kpa). Once the charge is in the middle of the sightglass, add additional system charge per Table 22. After charging, unblock the coil and allow the unit to operate normally. After conditions have stabilized, restrict the coil if required to maintain 230psig (1585kPa) discharge pressure and verify that the charge level is above the sight glass. Table 22 Field verification charge Model Numbers R-407C 60Hz 50Hz oz (kg) PFH014A-_L PFH020A-_L 4 (0.11) PFH027A-_L PFH027A-_H PFHZ27A-_L PFH037A-_L PFH036A-_L 18 (0.51) PFH042A-_L PFH041A-_L PFH037A-_H PFH036A-_H PFHZ37A-_L PFHZ36A-_L PFH042A-_H PFH041A-_H 8 (0.23) PFHZ42A-_L PFHZ41A-_L PFH067A-_L PFH066A-_L 18 (0.51) PFH067A-_H PFH066A-_H PFHZ67A-_L PFHZ66A-_L 50 (1.42) PFH096A-_L 3-ton circuit 5-ton circuit PFH095A-_L 3-ton circuit 5-ton circuit 18 (0.51) 18 (0.51) 29