IRRAD - PHASE II RADIANT COOLING - DESIGNING FOR FLEXIBLE PARTITION OF SPACE

Similar documents
7. MECHANICAL SYSTEM DESIGN

DESCRIPTION OF TECHNOLOGY

UFAD and Displacement Ventilation. Dan Int-Hout, FASHRAE Chief Engineer Krueger Richardson, Texas

NEW AR-L AR-C AND HIGH-CAPACITY LINEAR COOLING PANELS. Higher energy efficiency. Increased thermal comfort

Underfloor Air Distribution:

KLIMA Active Chilled Beams

Mechanical System Redesign. Dedicated Outdoor Air System. Design Criteria

Chilled beam technology overview John Woollett 1, Jonas Åkesson 2 Swegon AB 1,2

Energy Savings Potential of Passive Chilled Beam System as a Retrofit Option for Commercial Buildings in Different Climates

Radiant Exchange in Stratified Environments: Considerations and Challenges for Hourly Energy Simulation of UFAD, DV, and Radiant Cooling Systems

Element Z General Design Requirements Existing Facilities Information

UNDERFLOOR PRODUCTS E3

Underfloor Air Conditioning in North America David Arnold Troup Bywaters + Anders/ Director and Regional Chair ASHRAE Region at Large

Library stacks and records storage 150 LB/SF live load

FIRE INSPECTORS GUIDELINES FOR PLAN REVIEWS AND INSPECTIONS OF NEW CONSTRUCTION / ADDITIONS AND CHANGE OF OCCUPANCY

Chilled Beams. Getting a Warmer Reception

Modular Active. Chilled. Beams

C o o l i n g a n d h e a t i n g s y s t e m s

State of the art building simulation software... Frenger Radiant chilled beam performance at 1 Shelly St - Sydney

Element Z General Design Requirements Existing Facilities Information

Case Study: Furman University Charles H. Townes Center for Science. Michael K. Mantai, PE, CCP President System WorCx

maximize displacement ventilation Opportunities

UNDERFLOOR HEATING GUIDE

Cooling and heating systems. Static cooling ceiling system SKS-5/3 for visible installation

FAST AND ROBUST BUILDING SIMULATION SOFTWARE. Chilled Beam Performance: 1 Shelly Street, Sydney

Architectural Engineering Senior Thesis Mechanical System Redesign

HAP e-help. Modeling Induction Beams in HAP v4.8 QB TIP 001

Chilled beams. TRACE 700 incorporates two chilled beam strategies: passive and active.

Halton CPT Passive Chilled Beam

MECHANICAL SERVICES 101. Ian White

ENGINEERING BULLETIN. Overview of Chilled Beam Technology. Purpose. Summary. Theory

Jim Aswegan Chief Engineer

Chilled Ceilings / Beams Working Principles & Applications

Senior Thesis Centre Community Hospital East Wing Addition - Proposal Keith Beidel Mechanical Option 12/05/02 1

UFAD Underfloor air distribution system

RADIANT HEAT. Construction Automotive Industry

FR-A180 FR-A360. Occupancy detector. Use

Dates of Construction Construction Start 2/28/1999 Date of Completion 4/2000 Occupancy 5/2000

COOLING and DE-HUMIDIFICATION WITHOUT USING REFRIGERANTS

Pharmaceutical Facility Design

Life Safety Damper Installation ASHRAE St Louis Chapter Feb. 9,2015. Peter McDonnell, PE, LEED AP BD+C McClure Engineering

Displacement Ventilation

WARM WATER UNDERFLOOR HEATING SYSTEMS. Guidance Notes

RADIANT COOLING SYSTEMS OPPORTUNITIES FOR RADIANT COOLING IN NORTH AMERICAN CONSTRUCTION DALE HANSCOMB, REHAU Sales Manager Building Technology

RADIANT PANELS COMMERCIAL BUILDINGS INNOVATIVE VENTILATION & HEATING

REHAU Radiant Heating Systems. A warm welcome

Raised Access Floor - (AE Breadth Area)

The Residences at Christina Landing Wilmington, DE

BALANCING ENERGY EFFICIENCY & INDOOR THERMAL COMFORT

Taming the Health Care Building Codes NFPA vs. The International and Chicago Building Codes JENSEN & HALSTEAD LTD.

Temperature Control and Zoning of UFAD Systems

Swegon PACIFIC. Integrated chilled beam PACIFIC CHILLED BEAM KEY FIGURES

AGENDA. 1. Call to Order. 2. Approval of Minutes. 3. Approval of Invoices and Commitments. 4. Review Updated Site Analysis and Permitting

RADIANT PANELS COMMERCIAL BUILDINGS INNOVATIVE VENTILATION & HEATING

Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 1. Contextual Reminder

By: Russell Bainbridge March 18th, 2016 FPE 596

SPACE TYPE: JUDICIAL CHAMBER

Kawasaki centrifugal chiller using water as a refrigerant. Sep 26 th 2017 Kawasaki Heavy Industries, Ltd. Machinery Division Hayato Sakamoto

4 August Islington Fire Protection Transpower NZ Limited

Active & Passive Beams

MANDATORY MEASURES MANDATORY LIGHTING CONTROLS (a) Area Controls: Manual controls that control lighting in each area separately

Chilled Beam and Radiant Cooling Basics. Salt Lake City, UT ASHRAE Chapter December 2013 Nick Searle

Eco-enerdigm was built on the technology of Samyang System Group that was founded in Since 2003, Eco-enerdigm has been testing and researching

seasons in regions with hot, humid climates. For this reason, a dehumidification system with a radiant panel system needs to be developed. In a former

SCO # 1 & 2 PUNCLH LIST Project Name: VANCLEAVE UPPER ELEMENTARY CLA#: 13003

Integrated Solution PARTNERS

Comparison of radiant and convective cooling of office room: effect of workstation layout

MANDATORY MEASURES INDOOR LIGHTING CONTROLS. (Reference: Sub-Chapter 4, Section 130)

To describe human body heat transfer, the concept. Thermal comfort with radiant and convective cooling systems. Articles. REHVA Journal June

The Code of Practice for Fire Safety in Buildings 2011 It comprises 7 parts and 1 annex:

Smoke Master SMIA Compact pressurisation and smoke exhaust system

Next Generation Passivhaus Archives

COST-EFFECTIVE FIRE-SAFETY RETROFITS FOR CANADIAN GOVERNMENT OFFICE BUILDINGS

NOVEMBER 2012 THE EUROPEAN EXPERIENCE

BTBa. FLUSHLINE Ventilated chilled beam for cooling, heating and ventilation. BTBa

VENTILATION SYSTEM COMPONENTS. Product Overview

Integrated Solution PARTNERS

CEE 243. Week 2 HVAC systems at Y2E2

EMBEDDED PIPE SYSTEMS. SURFACE HEATING AND COOLING Heat transfer coefficient COOLING CAPACITY. Max. heating-cooling-capacity

Drawing 1: Pumping Layout (A Abu Saleh /5) Scale:

APPLICATION GUIDE BEAMS

Building & Fire Code Academy. Building Better With Our Greatest Resource Education. Welcome!

MANDATORY MEASURES INDOOR LIGHTING CONTROLS. (Reference: Sub-Chapter 4, Section 130.1)

Life cycle cost comparison of TABS vs. other HVAC (UK) TECHNICAL BROCHURE

Experimental Study on Crawl-Space Heating with Thermal Storage using Heat Pump

IES Whole-Building Energy Model Baseline Energy Model Input/ Output Report. East Liberty Presbyterian Church East Liberty Presbyterian Church

Displacement Ventilation in Classrooms

ELECTRICAL Seminar. B A L A Consulting Engineers, Inc. Edward J. Lynch, PE Vice President, Electrical Department Manager.

CAPILLARY SAMPLING INTRODUCTION. Page 1 CAPILLARY SAMPLING

Research on fire protection methods and a case study "Futurum"

Halton Rex for Vario R6O - Variable air volume chilled beam

RADIANT COOLING RESEARCH SCOPING STUDY

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST FIRE ALARM SYSTEM INSTALLATION

SPACE CONDITIONING IN COMMERCIAL BUILDINGS Overview

IAAI/USFA Abandoned Building Project

PSC-ID-x-CM Series Ceiling Mount Occupancy Sensor

Residential HVAC System Design

Construction standards and qualities

Full Service Central Station Fire Alarm Listing Evaluation

Feasibility of Controlling Heat and Enthalpy Wheel Effectiveness to Achieve Optimal Closed DOAS Operation

Transcription:

IRRAD - PHASE II RADIANT COOLING - DESIGNING FOR FLEXIBLE PARTITION OF SPACE

Cooling System

RADIANT COOLING PIPING LAYOUT Proposal for the REHAU core temperature control (CCTC) pipe size: RAUTHERM S 20x2,0mm pipe spacing: 15cm, pipe mounted on the lower reinforcement This piping layout of the CCTC is a first proposal, it has to be clarified: - occupied areas - distances to structural walls and beams - distances to ducts and air outlets - flow rate - position of the manifolds, in this proposal: manifold in the suspended ceiling below the chilled slab - pipe position in the concreted slab SECTION OF THE SLAB: pipes near the manifold with a spacing of less than 15cm and pipes outside the chilled slab led in corrugated pipe The position and size of the space for air conditioning or air outlets has to be checked

REFELECTED CEILING PLAN The planning of the structural system, external windows, placement of lights and fans in the slab and other services is such that each sub-divided space continues to receive: Radiant cooling for the RCC slab. Fresh Air Supply Daylight from the windows Artificial lighting Ceiling Fan Sprinkler system Fire Detector

COLUMN PLACEMENT AND VERTICAL DUCT LOCATIONS

COLUMN PLACEMENT AND VERTICAL DUCT LOCATIONS

DUCTING LAYOUT AND AIR FLOW Chilled and desiccated fresh air is released into the condition space near the floor. Fresh Air Supply grille AHU Fresh Air Supply system takes care of latent load, whereas Radiant Cooling from the ceiling and the floor takes care of the sensible load

DISPLACEMENT VENTILATION Chilled fresh air supply close of the floor will pick up heat at the people and machine occupation and rise up to the ceiling to be returned to the AHU. AHU ADVANTAGES: Air can be supplied at 18 o C to 20 o C as against 12 o C to 15 o C in conventional upper level air supply systems. Therefore, Cooling energy is saved. Fresh Air distribution is more effective. Due to circulation of air through the space being partially supported by natural buoyancy, less air circulation power is needed.

Partition Layout

PARTITIONS The structural and the Air distribution system permits flexibility in partitioning of the office space. Each sub-divided space continues to receive: Radiant cooling for the RCC slab. Fresh Air Supply Daylight from the windows Artificial lighting Ceiling Fan Sprinkler system Fire Detector Ground Floor

PARTITIONS The structural and the Air distribution system permits flexibility in partitioning of the office space. Each sub-divided space continues to receive: Radiant cooling for the RCC slab. Fresh Air Supply Daylight from the windows Artificial lighting Ceiling Fan Sprinkler system Fire Detector First and Second Floor

PARTITIONS The structural and the Air distribution system permits flexibility in partitioning of the office space. Each sub-divided space continues to receive: Radiant cooling for the RCC slab. Fresh Air Supply Daylight from the windows Artificial lighting Ceiling Fan Sprinkler system Fire Detector Third Floor

Results

INTERIORS AND TEMPERATURE ANALYSIS : FIRST FLOOR 20.3 20.1 28.2 22.2 20.9 27.9 21 20.3 28.2 22 20.4 20.3 Surface temperature of Wall, Floor and Ceiling Air temperature

INTERIORS AND TEMPERATURE ANALYSIS : SECOND FLOOR 20.3 20.7 28.3 23.2 21.4 28 21.8 20.7 28.5 23.4 20.9 20.9 Surface temperature of Wall, Floor and Ceiling Air temperature

INTERIORS AND TEMPERATURE ANALYSIS : THIRD FLOOR 21.7 21.8 23.9 28.7 28.4 22.1 21 21 Surface temperature of Wall, Floor and Ceiling Air temperature

INTERIORS AND TEMPERATURE ANALYSIS : FOURTH FLOOR 24.9 26 26.7 29 40.6 29.9 30.4 34.2 25 26.6 Conference Room Corridor Outdoor NOTE : The cooling system on this floor ( Top Floor ) had not been turned on Surface temperature of Wall, Floor and Ceiling Air temperature

CONCLUSION Occupants on all floors except fourth floor (which is not occupied), have expressed high degree of satisfaction with thermal comfort. It is seen that the Air temperature is considerably higher than surface temperatures. This shows that the perception of thermal comfort is strongly affected by Radiant temperatures of surrounding surfaces. Design of office spaces that require flexibility of space sub-division overtime, require a planning grid of services. Design of office spaces with Radiant Cooling through chilled slabs require careful planning of services. The service plans need to be such that space sub-division of different sizes of office cabins is managed with the use of suspended ceilings. The combination of Radiant Cooling from the ceiling slab and desiccated fresh air input close to the floor works best. This combination gives a high degree of satisfaction for thermal comfort and also ideal fresh air ventilation.