FPA Australia submission to the review of the Ozone Protection and Synthetic Greenhouse Gas Management Act 1989 and associated legislation.

Similar documents
Ozone Protection and Synthetic Greenhouse Gas Management Regulations 1995

Fire Protection Accreditation Scheme (FPAS)

LIFE PROPERTY ENVIRONMENT ASSOCIATION PROFILE. Fire Protection Association Australia. Life. Property. Environment.

Queensland Building Plan (Licensing Reform) FPA Australia Submission

Fire Protection Industry Board (ODS & SGG) Risk Management Plan. A risk management plan for storing and disposing of fire extinguishing agents

Fire Protection in the Mining Industry. Garry Kwok Board Member

ASSEMBLY 37TH SESSION

Guidance Note EC Regulation No 842/2006 on Certain Fluorinated Greenhouse Gases. BFPSA Guidance for the Fire Protection Industry

Application Form. Qualified Accreditation

NATIONAL HALON MANAGEMENT STRATEGY

Guided Learning Hours (GLH) 4 Invigilated Assessment (IA) 1 Total Qualification Time (5)

CONSULTATION ON THE VICTORIAN GOVERNMENT S PROPOSAL TO BAN E-WASTE FROM LANDFILL

In this issue. RAC equipment use up/ refrigerant leaks down. Access Canberra Safety Alert 065 Gas Explosion

Official Journal of the European Union

Daikin s Policy. and Comprehensive Actions on the Environmental Impact of

Making equipment decisions

Policies and Measures for HCFCs in Japan

1 Status China ratified the Montreal Protocol and the London amendment on June 14, It is an Article 5 country.

Fire Safety Policy. Document Author: Director of Estates, Fleet & Facilities Management

Control of refrigerant gases during manufacture, installation, servicing

ODS & SGG Alternatives for the Fire Protection Industry 2018

Use of R1234yf, R744 (CO 2 ) and R134a in automotive air conditioning

OZONE LAYER PROTECTION ACT 1996

ARE YOU AN AUTHORISED REFRIGERATION GAS PRACTITIONER?

BETTER URBAN PLANNING

Fire Protection, Inspection and Testing Qualifications Forums. Jeremy Rose (Artibus Innovation) Chris Wyborn (FPA Australia)

ODS Licensing System. Information Document

International New Technology and Refrigerant Symposium

Alarm Signalling Equipment: Connection Requirements (Victoria) TAN 06. Technical Advisory Note. Version 1 October 2018

Council is committed to its groups working together, and to working closely with other relevant agencies, including the Queensland Police Service.

COMMISSION REGULATION (EU)

Q. Which hydrocarbons can be used as a refrigerant? The following hydrocarbons can be used as a refrigerant in cooling & heating applications:

PURPOSE OF THE PROCEDURE

Halon Special Permit (HSP) Update. A total of 35 companies have a current Halon Special Permit.

Managing our Landscapes Conversations for Change

Responsible Care Product Stewardship for Refrigerants

NFPA Marine Fire Protection Codes and Standards An Overview. Guy R. Colonna, P.E. National Fire Protection Association. Quincy, MA USA

Corporate Plan reference: 2. A Strong Community 2.1 Safe and healthy communities

Page 2 Draft Revision to the Australian Automotive Air Conditioning Code of Practice 2014

June 2017 (Updated 18 January 2018) Fire Safety Policy. Peter Webb, Project Manager Compliance First Choice Homes Oldham Limited

Audit Mapping Document

Health and Safety Policy. Version Author Revisions Made Date 1 Colin Campbell First Draft March 2014

NATURAL REFRIGERANTS FOR HEAT PUMPS AND AIR-CONDITIONING SYSTEMS. Bernard Thonon Greth

South Australian Regulatory Requirements

MINIMAX FIRE PRODUCTS WHITE PAPER THE COST-BENEFIT ADVANTAGES OF REPLACING HALON WITH 725 PSI MX 1230 CLEAN AGENT FIRE SUPPRESSION SYSTEMS

Transforming Library Services in the digital information environment

Information Guide Maintenance and Refrigerant Regulations. Issue 35

4: Leakage matters: for service and maintenance contractors

West Yorkshire Fire & Rescue Authority. Fire Protection Policy

Executive Summary. Direct Investigation into the Safety Regulation of Eco-friendly Refrigerants

GIS Data Exchange Committee. and the NFPA Standards Making System

Stakeholder Meeting Dublin, Ireland Update on the new F-Gas Rules Andrea Voigt, EPEE

Client Advisory Note June 2015:

FIRE SAFETY POLICY June 2014

Safety training for industry and government services

Developments in Australian Standard AS (Emergency Lighting)

EMLC Academy Trust. Fire Safety Policy 2017/19. Every child deserves to be the best they can be

UNCONTROLLED IF PRINTED. Issued with the authority of the Chief Commissioner and General Manager of Scouts Australia NSW

Baseline Data Required for AS

Creating a safer world!

Guidance for Stationary Refrigeration & Air-Conditioning

Low GWP alternative refrigerants to R404A

Tackling the mounting e-waste problem

Fire suppression systems for server rooms and data centres

KISII UNIVERSITY INFORMATION COMMUNICATION AND TECHNOLOGY

Fire Safety Policy. Billy Hanafin H & S and Operations Officer. Fife Cultural Trust. Version 1.0 October 2013 Page 1

Published in March 2005 by the. Ministry for the Environment. PO Box , Wellington, New Zealand ISBN: X.

West Yorkshire Fire & Rescue Authority. Fire Protection Policy

Requirements for the Collection, Transportation, Storage and Treatment of Cooling and Freezing Appliances containing Hydrocarbons (HC)

Information Bulletin

DEMONSTRATION OF ADVANCED INTEGRATED HVAC&R SYSTEMS IN A LOBLAWS SUPERMARKET IN CANADA

ARKANSAS FIRE PROTECTION LICENSING BOARD ACT 743 OF 1977

LYHA Fire Safety Policy

Legislation & Standards

Today s world has more risk than ever. Today s G4S has more ways to protect you.

MANUFACTURER OF FIRE EXTINGUISHING AGENTS

FIRE SAFETY POLICY. Executive Management Team. Health, Safety and Fire Steering Group.

INSTALLED BANK OF REFRIGERANT

The Problem of Counterfeit Refrigerants

Describing the Integrated Land Management Approach

Lakanal House inquest: Statement from the Fire Sector Federation

Electrical Safety Policy and Management System

Transitioning to Alternatives and Challenges in Japan

Third Party Certification:

Fire Safety Policy SH HS 06. Version: 4. Summary:

How it may affect the future of your school. Michael France Director, Regulatory Affairs National Air Transportation Association

Draft FPA Australia Technical Specification for Public Comment FPAA101D DRAFT

The new fire regulations - more demands on the employer? The Regulatory Reform (Fire Safety) Order 2005

MCSCS Proposed Changes to Fire Service Regulations

LANDSCAPE INSTITUTE CORPORATE STRATEGY ISSUED 3RD APRIL Landscape Institute 107 Grays Inn Road London WC1X 8TZ United Kingdom

EXHIBIT G REFRIGERANT MANAGEMENT POLICY

An Overview of Extinguishing Systems for Computer Equipment

Securing Your World. Who we are. What we do

Meeting the Challenges of the EU HFC Phase-Down

IFLA Strategic Plan

Protocol between Local Housing Authorities and Fire and Rescue Authorities to improve fire safety

Fire Safety. A TUC guide for trade union activists

HALON ALTERNATIVE FIRE EXTINGUISHER 3

Australian Standard. Gaseous fire extinguishing systems AS (Incorporating Amendment No. 1) AS

Health & Safety Policy HSP 03 Fire Safety Version Status Date Title of Reviewer Purpose/Outcome

Transcription:

FPA Australia submission to the review of the Ozone Protection and Synthetic Greenhouse Gas Management Act 1989 and associated legislation 1 P a g e

Table of contents 1.0 About FPA Australia... 4 1.1 FPA Australia members 5 1.2 FPA Australia technical committees 6 2.0 Introduction... 8 3.0 Ozone Depleting Substances (ODS) and Synthetic Greenhouse Gas (SGG) extinguishing agents in the fire protection industry... 9 4.0 Domestic end use arrangements... 10 5.0 Complinace and Enforcement... 12 6.0 Why is maintenance of fire protection systems and equipment important... 13 7.0 Halon and the role of the National Halon Bank.. 15 8.0 Working with the Australian Government..... 16 9.0 Contacts 16 2 P a g e

1.0 About FPA Australia Fire Protection Association Australia (FPA Australia) is the national peak body for fire safety that provides information, services and education to the fire protection industry and the community. FPA Australia is represented across Australia by active members employing over 18,000 individuals representing every aspect of the fire protection community manufacturers and suppliers of fire protection products and services, fire-fighters, building owners, insurers, designers and building surveyors, government and legislators, educators and anyone else working as part of the fire protection community to provide a safer environment for all Australians. The Association is a not-for-profit organisation employing over 35 employees with its national head office based in Melbourne with other fulltime resources positioned in other states. The Association s sole focus as a non for profit organisation is to continually develop the industry in all regards of fire protection and reinvest into the industry to achieve improved safety outcomes. Central to our vision is a focus on advocacy in order to influence change and deliver improved fire safety outcomes for the community with the following strategic goals: Our Vision To promote the protection of life, property and the environment from fire and related emergencies. Our Mission To work with our members, government, corporate and community organisations for the continuous improvement in legislation, standards, education, awareness, products and services for the protection of life, property and the environment from fire and related emergencies. Our Values Integrity: behaving ethically, acting with loyalty, honesty and transparency and being prepared to express our views. Independence: being prepared to establish relationships, build trust and foster cooperation without showing favour. Professionalism: being committed to the continuous professional development of our Association and industry. 3 P a g e

1.1 FPA Australia members FPA Australia members are involved throughout all phases of the fire protection industry as illustrated by figure 1 below. Figure 1 Phases of the Fire Protection Industry Some of the fire protection systems and equipment our members cover through these phases include: Fire detection and alarm systems Portable and mobile equipment Fire sprinkler and hydrant systems, tanks and fixed fire pumps Special hazard fire protection systems Passive fire protection Many of our members are fire protection companies that operate in the maintenance test and inspect area. Figure 2 FPA Australia membership Organisation 4% Individual 30% Corporate 66% 4 P a g e

1.2 FPA Australia Technical Committees FPA Australia contributes through its Technical Advisory Committees (TACs) and Special Interest Groups (SIGs) to the technical requirements for fire protection systems and equipment used in Australia. Over 300 industry subject matter experts contribute significantly to the technical committee process to support the work of the Association. These technical committees are made up of volunteers from the membership with an interest and expertise in particular areas of fire protection and a commitment to advance the industry. The TACs and SIGs are managed and coordinated by the FPA Australia Technical Department and the National Technical Advisory Committee (NTAC) under the authority of the FPA Australia Board, see figure 3. Figure 3 FPA Australia Technical Committee structure 5 P a g e

FPA Australia s TACs and SIGs contribute to a wide variety of organisations and documents including legislation (State, Territory and Commonwealth), Building and Plumbing Codes, Australian Standards, fire brigade documentation, industry guidelines and FPA Australia s own technical documents, see figure 4. Figure 4 FPA Australia Technical Committee input to technical requirements for fire protection systems and equipment 6 P a g e

2.0 Introduction FPA Australia believes the Ozone Protection and Synthetic Greenhouse Gas Management Act 1989 (the Act) and its associated legislation has been effective in ensuring Australia meets its legal obligations under the Montreal Protocol on Substances that Deplete the Ozone Layer and the Kyoto Protocol, created under the UN Framework Convention on Climate Change, to reduce greenhouse gas emissions. Australia continues to be a world leader in the phase out of ozone depleting substances and has made significant advances in the responsible management of halon. We also commend the Australian Government s recent actions to undertake a comprehensive review of the Act and its associated legislation to ensure a continued protection of the environment, while reducing regulatory burden on businesses and individuals operating under the legislation. Initially when implementing the provisions of the legislation, the Australian Government recognised that it needed to work in partnership with the fire protection industry. It therefore allowed for the establishment of the Fire Protection Industry (ODS & SGG) Board (the Board) to administer the Ozone Protection and Synthetic Greenhouse Gas Management Regulations 1995 (Cth) (the Regulations). As the fire protection industry permit scheme administered by the Board is now well established, FPA Australia believes more stringent adherence to the Regulations by the fire protection industry is expected. In this regard FPA Australia notes the requirement to use only licensed technicians when handling Ozone Depleting Substances (ODS) and Synthetic Greenhouse Gas (SGG) extinguishing agents provides a very important step within the fire protection industry to train and develop a competent workforce. FPA Australia strongly advocates the importance of ensuring technicians are appropriately trained and assessed to handle ODS and SGG extinguishing agents used in the fire protection industry. The Association is committed to continuing to work with the Australian Government to deliver a balanced regulatory environment that protects workers, the community and the environment while delivering a business environment that stimulates growth and innovation. 7 P a g e

3.0 Ozone Depleting Substances (ODS) and Synthetic Greenhouse Gas (SGG) extinguishing agents in the fire protection industry FPA Australia commends the Australian Government for taking an outstanding international position in ensuring Australia meets its legal obligations under the Montreal Protocol on Substances that Deplete the Ozone Layer and the Kyoto Protocol, created under the UN Framework Convention on Climate Change, to reduce greenhouse gas emissions. The production of CFCs, carbon tetrachloride and halon has now stopped in Australia. The import of HCFCs is subject to a reducing quota. There are however, no restrictions on the import of HFCs and perfluorocarbons which were introduced principally as replacements for ozone depleting gases. Halons, which contain bromine, were significant firefighting chemicals and were targeted very early in the piece as substances containing bromine are estimated to be responsible for 25 per cent of the chemical destruction of ozone over Antarctica and 50 per cent over the Arctic. Halon is therefore now banned in Australia and many other countries except in certain approved areas. One approved area is aviation where the relatively low weight, low freezing point and other factors make it the most suitable extinguishing agent at high altitude. However, efforts worldwide are being made to develop replacements for halon. For example halon is also currently permitted in some military vehicles, but FPA Australia notes alternatives such as HFC227ea are now being used in vehicles such as the Australian designed Bushmaster armoured personnel carrier. Though HFC227ea has a zero ozone depleting potential it is 2900 times more greenhouse intensive than CO 2. Other applications were ODS & SGG extinguishing agents may be found include: Computer rooms Telecommunication switch stations and facilities Manufacturing facilities Data processing centres Industrial process control rooms Engine compartments Petro chemical facilities Chemical storage rooms Museums Libraries 8 P a g e

Figure 5 Relative impact of some common fire extinguishing agents compared to CO2 Figure 5 shows why halon has been banned in Australia and many other countries. However, it also shows that replacements such as HFC227ea (GWP 2900) still have a significant impact on the environment and the importance of domestic end use arrangements such as the current fire protection permit scheme. 4.0 Domestic end use arrangements FPA Australia supports a national licensing system enabling businesses and technicians throughout Australia using a single permit with one set of consistent standards when handling ODS and SGG extinguishing agents. FPA Australia notes the emphasis of undertaking maintenance in relation to fire protection systems and equipment is to ensure operational reliability and avoid or prevent system or equipment failure. Essentially maintenance of fire protection systems and equipment is about ensuring that the required, approved or established performance level of individual or integrated systems and equipment is continually achieved in order to demonstrate that systems and equipment are fit for purpose. It is therefore imperative to continue to have a competency-based licensing system ensuring technicians in the industry have the appropriate skills to undertake the installation, testing, maintenance, decommissioning, storage and disposal tasks safely with minimal impact on the environment. Working with ODS and SGG extinguishing agents in any activity where a discharge of the agent is possible as a consequence of the work being performed should continue to require the appropriate licence. 9 P a g e

We strongly believe the Board should also continue to provide information to the fire protection industry and the general public on its activities and purpose, thereby improving awareness and understanding of ODS and SGG legislative requirements and the need to reduce the use of controlled substances and the potential risk for accidental emissions of these controlled substances. Though we are of the view the end use controls have worked well and have been a success, they have not been reviewed for some time and so it is timely to assess and identify any opportunities for improvement. It is with this view that FPA Australia recommends the following areas for consideration: Increasing compliance and enforcement activities Issuing infringement notices for breaching licence conditions Reviewing all definitions and adding definitions such as reclaim, recover, recycle and accidental discharge (within definition of lawful discharge) Updating information on licence entitlements and units of competency within Table 322 of the Regulation Review currency of all standards specified in Table 326 of the Regulation Review timeframes for requirement to report quarterly usage by Halon Special Permit and Extinguishing Agent Trading Authorisation holders Requirement for re-used ODS and SGG extinguishing agents to be cleaned and restored back to manufacturers specification (consideration of recovery, recycling and reuse processes) Requirement to ensure all ODS and SGG extinguishing agents sold in the Australian market meet the required specification Requirement for system owners to undertake routine maintenance via the use of a licensed technician and the use of a log book Requirement for extinguishing agent discharges to be reported to the Board Requirement for end of life product stewardship for ODS and SGG extinguishing agents 10 P a g e

5.0 Compliance and Enforcement Compliance means following the law and FPA Australia firmly believes compliance is the responsibility of all businesses, organisations, governments and individuals. We commend the Fire Protection Industry (ODS & SGG) Board s work to provide ongoing information to the fire protection industry and the general public on its activities and purpose, thereby improving awareness and understanding of ODS and SGG legislative requirements and the need to reduce the use of controlled substances and the potential risk for accidental emissions of these controlled substances. FPA Australia emphasises education, raising awareness of impacts, obligations and duty of care has been effective in encouraging industry to comply. However, the Association believes there are some aspects which could be strengthened leading to higher levels of compliance in the fire protection or related industries. Such aspects include allowing for the publication of details of cancelled or suspended permits, greater enforcement activities, fines and expanding the scope of infringement notices. ODS and SGG extinguishing agent. 11 P a g e

6.0 Why is maintenance of fire protection systems and equipment important? FPA Australia believes that if maintenance is not undertaken by a licensed technician, the risk of system or equipment failure increases over time. Figure 6 below simply illustrates this relationship between performance level, maintenance and increased risk exposure. Minimising this risk is the objective and importance of maintenance and key objectives which form part of the fire protection industry permit scheme. Figure 6 Performance level, maintenance and risk exposure With maintenance Without maintenance Level of Performance Increased risk of system / equipment failure addressed by maintenance Time It is true that in some instances regardless of whether maintenance has been undertaken by a licensed technician, systems and equipment will reach the end of their design lifetime and will require replacement. However, routine inspection, testing and preventative maintenance activities would be expected to identify this and ensure the need for replacement is identified and acted upon. 12 P a g e

Figure 7 below illustrates that in order to capitalise on the investment made to incorporate fire protection systems and equipment via the design and installation phases, it is important for a licensed technician to undertake routine maintenance to ensure these systems and equipment remain fit for purpose or inuse phase. Figure 7 Achieving fire safety objectives Significant investment throughout design and construction phase Ongoing maintenance during in-use phase is essential to realise return on design & construction phase investment Only investment in design, construction and maintenance of fire protection systems & equipment achieves fire safety objectives The domestic end use arrangements prescribe the requirement for a licenced technician to undertake the installation, testing, maintenance and decommissioning of a gaseous fire extinguishing system. However, amendments to the legislation are required for requirements for system owners to undertake routine maintenance, repair, rectification or resolution via the use of a licensed technician. 13 P a g e

7.0 Halon and the role of the National Halon Bank Originally introduced as a fire fighting agent in Australia in the early 1970s, halons quickly replaced many previously accepted firefighting products because of their superior firefighting characteristics and ease of use. Because of the very aggressive way halons deplete ozone, they were banned from sale in developed countries from January 1, 1994 (except for a very restricted number of essential uses). This ban is an important policy element of the international treaty which enforces the ban the Montreal Protocol on Substances that Deplete the Ozone Layer. Today halon is only used in very limited quantities domestically. Currently, halon is only allowed to be used for commercial and private aviation, maritime (including foreign flag vessels operating in or through Australian waters) and certain defence applications. In 1993, the Australian Government established the National Halon Bank (NHB) to store decommissioned halon for destruction or reclamation to meet essential uses until an alternative was found for all current uses. The NHB was the first facility in the world solely dedicated to the storage, decanting, recycling and destruction of ozone depleting substances. FPA Australia notes the vital component the NHB continues plays in Australia s Halon Management Strategy which in turn helps Australia meet our obligations under the Montreal Protocol. The continuing ongoing support of the fire protection industry around Australia by accepting halon to transfer for disposal is equally important in achieving the goals of the Halon Management Strategy. Significantly the Board continues to promote awareness of the environmental dangers posed by discharges of halon and other ODS and SGG extinguishing agents through the domestic end use arrangements. 14 P a g e

8.0 Working with the Australian Government FPA Australia was first appointed to provide the services of the Fire Protection Industry (ODS & SGG) Board (the Board) in accordance with regulation 311(1) of the Regulations on 6 June 2005. The Association will continue to take a leadership position in achieving substantial reductions in the emissions of ozone depleting and synthetic greenhouse gases while actively promoting compliance with all provisions of the legislation. We look forward to continuing our successful partnership with the Australian Government while actively promoting industry's products, services and knowledge. The cooperation between FPA Australia and the Australian Government serves as a valuable model for cooperative partnerships between the fire protection industry and government. This partnership serves to highlight the achievements that are possible by adopting and industry collaborative approach. We strongly advocate the overriding objective to identify options to prevent the unnecessary discharge of any scheduled ODS and SGG extinguishing agents and improve awareness of the safety risks. In addition to the comments provided above, the Association is committed to working collaboratively with the Australian Government through representation on the technical working group and provide any support to the review of the Act and its associated legislation. 9.0 Contact details Scott Williams Chief Executive Officer Fire Protection Association Australia Building 2, 31-47 Joseph St Blackburn North VIC 3130 PO Box 1049, BOX HILL VIC 3128 Phone: 03 8892 3131 or 1300 731 922 Email: Web: scott.williams@fpaa.com.au www.fpaa.com.au 15 P a g e