User Manual SF6 GASCHECK 6000

Similar documents
SF 6 -Leak Pointer Operating Manual (original version) Type-No.: R002

REFRIGERANT LEAK DETECTOR

Leak-Seeker I Refrigerant Leak Detector

CLI Refrigerant Gas Leak Detector. User s Guide

TEK-Mate. Refrigerant Leak Detector

GERMANY TEC 'LOGY leak-detect EXPERT

TEK-Mate. Refrigerant Leak Detector

Model C-380. Instruction Manual. Refrigerant Leak Detector. reedinstruments

D-TEK Select. Refrigerant Leak Detector

Instruction Manual Electronic Leak Detector. Bedienungsanleitung Elektronisches Lecksuchgerät. Mode d emploi Détecteur de fuites électronique

Refrigerant Leak Detector

actoolsupply.com User Guide Extech RD300 Air Conditioning AC Refrigerant Leak Detector Refrigerant Leakage Detector Model RD300 actoolsupply.

OPERATING INSTRUCTIONS

6-1 Installing Batteries 6-2 Automatic Circuit/Reset Feature 6-3 Feature Sensitivity Adjustment

RLD-H10P Refrigerant Leak Detector

Instruction Manual MSI Sensit HXG

Refrigerant / Combustibles Leak Detector

III. 99 Washington Street Melrose, MA Phone Toll Free Visit us at OPERATING INSTRUCTIONS

Unrivalled Detection.

Model: LD5 Dual Mode Refrigerant Gas Leak Detector. Operating Instructions

AIR CONDITIONNING 95 CODE 002

H-10PM. Refrigerant Leak Detector

LD920. User Manual. H2/N2 Tracer Gas Leak Detector. Detects 5% H2 in 95% Nitrogen Tracer Gas. Made in U.S.A. LeakDetectors-LD920-UserManual.

USER MANUAL MINITRACER PORTABLE SNIFFER

LD-5000 REFRIGERANT LEAK DETECTOR

99 Washington Street Melrose, MA Phone Toll Free Visit us at

RLD-H10G Refrigerant Leak Detectors

NGD8800 USER S MANUAL

YELLOW JACKET. H 2 Tracer Gas Leak Detector. Operations Manual. Detects 5% H 2 in 95% Nitrogen Tracer Gas. Model 69341

ATD-3698 Refrigerant Gas Leak Detector. Owner s Manual

SENSIT HXG-2. Instruction Manual For use with combustible gases Gas Leak Detector

LD910. User Manual. Combustible Gas Leak Detector. Detects all Hydrocarbon and other Combustible Gases. Made in U.S.A. MSHA Approved Intrinsic Safety

LD900. User Manual. Refrigerant Gas Leak Detector. Detects all HFO, HFC, HCFC, and CFC Refrigerants including blends. Made in U.S.A.

LEAK DETECTION INDUSTRY LEADING SENSITIVITY

II 2 G. SENSIT HXG-2d. Ex ib IIB T3 IP20. Suitable for combustible gases such as Methane, Butane, Propane and Natural Gas MADE IN USA

Model: LD7 Dual Mode Refrigerant Gas Leak Detector. Operating Instructions

Whisper. Ultrasonic Leak Detector

LD 5000 REFRIGERANT LEAK DETECTOR JB INDUSTRIES INC.

Model ATD Refrigerant Gas Leak Detector. User Manual. Detects all CFC, HFC, HCFC, HFO Refrigerants including blends

Macurco Single-Gas XL Series Monitor, CM-1XL Carbon Monoxide (CO), HS-1XL Hydrogen Sulfide (H2S) User Instructions

Model R9100. REED Instruments Instruction Manual. Ultrasonic Leak Detectortor

testo Leakage detector for refrigerants Bedienungsanleitung Instruction manual

testo Leakage detector for gas Instruction manual

EVac II Programmable Digital Vacuum Gauge

SENSIT HXG-2d Combustible Gas Detector INSTRUCTION MANUAL Read and understand Instructions before use. PENDING Ex. II3G Ex ic llb T3 IP20

Carbon Monoxide Meter Model CO15. User Manual. Additional User Manual Translations available at

GG-VL-R REFRIGERANT VENT LINE SENSOR. Installation and Operation Manual

Dräger X-am 7000 Multi-Gas Detection

Precision Infrared Thermometer. Users Manual

Operating Instructions. Model: LD3 Dual Mode Refrigerant Gas Leak Detector ROBINAIR.COM

SENSIT HXG-2d. SENSIT TECHNOLOGIES 851 Transport Drive Valparaiso, IN Phone: (219) Fax: (219)

Reacti-Therm I and III Heating Modules

Tru Pointe Refrigerant Leak Detector Instruction Operation & Maintenance Rev. 0 April 2003

SENSIT HXG-2d Combustible Gas Detector

For technical support call:

Instruction Manual for FORMALDEHYDE GAS DETECTOR MODEL FP-30/FP-40

RD99 REFRIGERANT GAS LEAK DETECTOR WARNING!

PRODUCT GUIDE. ionscience.com Unrivalled Gas Detection.

Using the MiniRAE 2000 & ppbrae PID

MetRad1 Handheld Metal/Gamma Detection Unit. Operation Manual. Berkeley Nucleonics Test, Measurement and Nuclear Instrumentation since 1963 BNC

Pioneer-R16 Gas Monitor Operator s Manual

NEW Restek Electronic Leak Detector

GASGUARD VENT LINE3. Ammonia Sensor OPERATING & INSTALLATION MANUAL

testo 316-EX gas leak detector Instruction manual

Dräger X-am 5600 Personal Monitor Multi-Gas Detection Device

Safe Operation Manual. Honeywell IQ Force Gas Detector

T.ex Single Gas Detector VISA

YELLOW JACKET. ACCUPROBE UV and ACCUPROBE II Refrigerant Leak Detector with Heated Sensor. Instruction and Operation Manual

GAS-Mate. Combustible Gas Leak Detector

OPERATING MANUAL. EchoThermJ DIGITAL HOT PLATE MODEL HP30 AND HP30A. DOCUMENT NUMBER HP30-03 Revised 10 December 2011

Models LBW-420-LEL (24 VDC powered) Ammonia Leak Detector

Combustible Gas Leak Detector Instruction Manual

LS1. Operator Manual. Kane International Ltd

Lutron GS-5800 ULTRASONIC GAS LEAKAGE DETECTOR

Wilcom. Model FR2 Fiber Ranger Optical Fault Locator OPERATING INSTRUCTIONS

GG-R REFRIGERANT SENSOR. Installation and Operation Manual

GASGUARD Cl 2. Chlorine Sensor OPERATING & INSTALLATION MANUAL

RAM GENE-1 ERK. Contamination & Radiation Meter. Operating Manual. Document #PRIR90N2.DOC Version 2.2 October 2009

INSTRUCTION MANUAL FOR RIKEN PORTABLE TOXIC GAS MONITOR

RAM GENE / RAM GENE-1

GASGUARD NH 3. Ammonia Sensor OPERATING & INSTALLATION MANUAL

Refrigerant / Combustibles Leak Detector

MODEL: SP12C7. (Portable 4 gas detector) Operating Manual

Confined Space Monitoring. Leak Investigation. Functions 4. Bar Hole Sampling. Line Purge Testing. Actual Size GX-2012

OPERATING MANUAL TORREY PINES SCIENTIFIC, INC. DIGITAL HPLC COLUMN HEATER MODEL CO20 DOCUMENT NUMBER CO20-00

HIGH VOLTAGE A.C. PROXIMITY DETECTOR HI-PROX

User Guide. Portable banknote counter AB300

275HVD NON-CONTACT, HIGH VOLTAGE DETECTOR DETECTOR DE ALTA TENSIÓN SIN CONTACTO

Self-contained and intrinsically safe wireless stand-alone multi-point gas detector.

Utopian Split A/C. Thank you for purchasing this quality Split A/C system!

Instruction Manual. Self-Leveling Combination Cross-Line Laser and Five-Beam Laser Dot Model No &

TAG MR VOLTAGE DETECTORS AND ACCESSORIES. Instruction & Operation Manual

Which Refrigerant Analyzer do I have? Ultima ID Model RI-2004HV Series

Instruction manual EN

UV Scanner. Model Specification. Introduction. 854 Instruction Manual

Eclipse 90 UV Scanner Model A Version 1

GASGUARD SO2 Sulfur Dioxide Sensor OPERATING & INSTALLATION MANUAL

Instruction Manual. Self-Leveling Combination Cross-Line Laser and Five-Beam Laser Dot Model No , &

GasAlert. Introduction. WWarning. Table 1. GasAlert Models. Gas Monitored

Leak Monitors and Leak Detectors

Transcription:

User Manual SF6 GASCHECK 6000

V1.01 SF6 GASCHECK 6000 Page 2 Contents 1 Remarks... 3 1.1 Target group... 3 1.2 Correct use... 3 2 General Specification... 4 3 Features... 5 4 Operation Features... 6 5 Serarching for leaks... 7 6 Operating tips... 8 7 Maintenance... 9 8 Specifications... 10 9 Warranty & Repair Policy... 11

V1.01 SF6 GASCHECK 6000 Page 3 1 Remarks 1.1 Target group This is intended for operators who perform operationspecific settings on the SF6 GASCHECK 6000. Safety instructions Before you use the instrument, please read and comply with these instructions: Keep the in a safe place. Only ISM employees may open the instrument or parts of it. There are no components in the instrument that require maintenance. Protect the instrument from moisture. Use the instrument only in dry places. Only use earthed systems that are without current. 1.2 Correct use The SF6 GASCHECK 6000 leak detectors are intended only for detecting leaks and making measurements on components filled with SF 6. Any other use is considered as incorrect.

V1.01 SF6 GASCHECK 6000 Page 4 2 General Specification The SF6 GASCHECK 6000 is the world s first truly automatic electronic leak detector requiring absolutely no operation intervention during the leak search process. Controlled by an exclusive POWERSHIFT software, the SF6 GASCHECK 6000 continuously and automatically adjusts critical sensitivity related functions providing optimal leak searching results. If your application requires a higher sensitivity and a calibrated measurement in [g/year], [ppm], or [cc/s] consider the SF6 LEAKCHECK P1:p leakdetector. For more information visit

V1.01 SF6 GASCHECK 6000 Page 5 3 Features The world s 1st truly automatic electronic leak detector for SF6 Patented microprocessor controlled circuitry Exclusive POWERSHIFT software New state of the art Cold Cathode Diode (CCD) sensor Superior resistance to background contaminants Exclusive TACHOMETER style LED leak indicators Rugged, ergonomically correct housing fits comfortably in your hand Up to 75 hours or more of battery life with auto off feature Includes hard case, spare CCD sensor and 3 size C alkaline batteries

V1.01 SF6 GASCHECK 6000 Page 6 4 Operation Features TURNING THE INSTRUMENT ON Click the START button once to turn the unit ON. RESETTING THE INSTRUMENT At any time during operation, clicking the START button resets the instrument to its highest sensitivity level and balances it to ambient conditions. SWITCHING AUDIBLE ALARMS The SF6 GASCHECK 6000 incorporates two user selectable audible alarm sounds. At any time during operation, simply double click the START button to toggle between the two audible alarm options. The instrument will store the current alarm setting when turned OFF, thus becoming the operation alarm the next time the instrument is powered up. TURNING THE INSTRUMENT OFF At any time during operation, press and hold down the START button until the LED display turns OFF. This indicates that the unit has been shut down. SENSOR STATUS INDICATOR If the sensor is damaged, every other one of the tachometer LED s will light up visibly notifying the user of the problem, and then the instrument turns itself OFF. LOW BATTERY INDICATOR When the batteries reach approximately 10% of capacity, the rightmost tachometer LED will stay lit above the LO BAT legend. CONTROL Single momentary push-button operates all functions of the unit: With the instrument OFF, click the START button once to turn it ON. The instrument is automatically calibrated and ready to search for leaks. With the instrument ON, holding the button down for 3 seconds turns the instrument OFF. Audible alarm setting is remembered. With the instrument ON, double clicking the button changes the audible alarm from high to low intensity and vice versa. With the instrument ON, clicking the button once resets the instrument to maximum sensitivity and nulls out any ambient contamination.

V1.01 SF6 GASCHECK 6000 Page 7 5 Serarching for leaks The SF6 GASCHECK 6000 is fully automatic and need only be turned on to begin a leak search. All necessary sensitivity and calibration settings are automatically selected by the unit s advanced POWERSHIFT software providing optimal leak searching performance under any conditions. 1. Take care not to contaminate the detector probe tip if the part being tested is contaminated. If the part is particularly dirty, or condensate (moisture) is present, it should be wiped off with a dry shop towel or blown off with shop air. No cleaners or solvents should be used, since the detector may be sensitive to their ingredients. 2. Visually trace the entire SF6 GASCHECK 6000 containing system paying particular attention to all mechanical and welded joints. Each questionable area should be carefully checked with the detector. Always follow the SF6 containing system around in a continuous path so that no areas of potential leaks are missed. If a leak is found, always continue to test the remainder of the system. 4. At each area checked, the probe should be moved around the location at a rate no more than 1-2 in/s (25 to 50mm/s), and no more than.2 (5mm) from the surface, completely around the position. Slower and closer movement of the probe greatly improves the likelihood of finding a leak. 5. An apparent leak shall be verified at least once by blowing shop air into the area of the suspected leak, if necessary, and repeating the check of the area. In cases of very large leaks, blowing out the area with shop air often helps locate the exact position of the leak. 6. Following any service to the SF6 system, and any other service that disturbs the SF6 system, a leak test of the repair and of the service ports of the SF6 system should be done.

V1.01 SF6 GASCHECK 6000 Page 8 6 Operating tips WINDY CONDITIONS: Locating leaks under windy conditions may severely impede the leak searching process. Even very large leaks may be impossible to find as the escaping gas is quickly dissipated into the atmosphere. If necessary, fabricate a gas trap using aluminum foil around joints or fittings or otherwise shield the search area from the wind. WHEN TO RESET THE UNIT: It is necessary to reset the SF6 GASCHECK 6000 during a leak search if the unit becomes fully saturated, multiple leaks are present or during the leak verification process. LEAK VERIFICATION: If a suspected leak is indicated, verify several times by moving the sensor away from the leak area, resetting the unit and then back to the suspected leak. If the instrument indicates a leak three consecutive times, then you have found a leak.

V1.01 SF6 GASCHECK 6000 Page 9 7 Maintenance The SF6 GASCHECK 6000 Leak Detector is designed to required a minimal amount of field maintenance. Periodic replacement of the unit s sensor and batteries are the only maintenance needs. LOW BATTERY CONDITION: When the batteries reach approximately 10% of capacity, the rightmost LED of the tachometer indicator (above the LO BAT symbol) will energize. The other seven LEDs will continue to function as indicators of the leak s relative size. CHANGING THE CCD SENSOR: The CCD sensor assembly consists of metal and plastic components. Do not attempt to remove one component from the other. Do not use solvents or cleaning solutions for cleaning the sensor. It should be replaced when air vents become clogged. Eventually, the sensor will need to be replaced. This condition is usually indicated by abnormal or erratic performance. With the unit OFF, install the new sensor.

V1.01 SF6 GASCHECK 6000 Page 10 8 Specifications SENSOR: State of the art Cold Cathode Discharge Diode. TYPES OF GASES: SF6. SENSITIVITY: Fully automatic sensitivity selection with 6 visible LED range indicators. Maximum sensitivity allows detection of a 0.10 oz/yr (3 g/yr) leak of SF6. LEAK INDICATION AUDIBLE ALARMS: Two user selectable audible alarm options (High and low intensity alarm tones). VISUAL ALARMS: TACHOMETER bar graph display. Eight high intensity LEDs are arranged in a Tachometer-like display indicating leak intensity perthe sensitivity range. GEARSHIFT display is arranged in a gearshift pattern. Seven LEDs indicate the current sensitivity range of the unit and subsequent leak size as follows: GEAR LEAK SIZE N No Leak 1 & 2 Small 3 & 4 Medium 5 & 6 Large OPERATING TEMPERATURE: -18 to 60 C POWER: Three size C alkaline batteries Continuous Operating battery life at 77 F (25 C): High intensity alarm: 55 hrs Low intensity alarm: 75 hrs Because the instrument turns itself off after 10 min. of inactivity, the actual useful battery life may be longer than stated. See Maintenance section for LO BAT conditions. DIMENSIONS: Instrument (Lx W xh): 10 x 2.3 x 2 254mm x 59mm x 51mm. PROBE: 14 (36.5cm) long,.25 (6.4mm) diameter, metal flex probe. WEIGHT: 1 lbs. 2 oz. (500 grams)

V1.01 SF6 GASCHECK 6000 Page 11 9 Warranty & Repair Policy ISM Deutschland GmbH guarantees that all products are free of manufacturing and material defects for two years. If the equipment should fail during the guarantee period it will be repaired or replaced (at our option) at no charge. This guarantee does not apply to equipment that has been altered, misused, or returned solely in need of field service maintenance. This repair policy does not include equipment that is determined to be beyond economical repair. All products being returned for warranty repair must be accompanied by an original bill of sale and customer contact information. Address: ISM Deutschland GmbH Laubach 30 40822 Mettmann Germany Phone: 0049 2104 1448 0 Fax: 0049 2104 1448 25 Mail: info@ism-d.de web: