Astro 2 circulator models. Installation and operating instructions

Similar documents
E.2 series high efficiency circulator. Installation and operating instructions

Installation and operating instructions. E.2 Series high efficiency circulator

ASTRO 2 SERIES HOT WATER RE-CIRCULATION SYSTEM INSTALLATION AND OPERATING INSTRUCTIONS

COMPASS HIGH-EFFICIENCY WET-ROTOR CIRCULATORS

ASTRO 2 SERIES HOT WATER RE-CIRCULATION SYSTEM INSTALLATION AND OPERATING INSTRUCTIONS

Sequence of operation

Astro Express 2 - Hot Water Delivery System

ASTRO EXPRESS 2 HOT WATER DELIVERY SYSTEM

3750 Pulpress pressurisation unit. Installation and operating instructions

Condensing boiler plant (vp)

TIDALWAVE I/G POOL PUMP INSTRUCTION MANUAL

Series 4302 & FILE NO: 43d.12 DATE: June 1, 2004 SUPERSEDES: 43d.12 DATE: July 15, dualarm Vertical In-Line Pumps

dualarm Vertical In-Line Pumps

INSTALLATION & OPERATING INSTRUCTIONS

MAXI PUMP INSTRUCTION MANUAL NE6151B /NE6171B READ THIS MANUAL CAREFULLY BEFORE USING YOUR MAXI PUMP

2 SPEED PUMP INSTRUCTION MANUAL READ THIS MANUAL CAREFULLY BEFORE USING YOUR 2 SPEED PUMP

568X, 587X, 588X Series

HALLMARK INDUSTRIES INC. HALLMARK INDUSTRIES INC. Safety WARNING WARNING. Must reset the voltage! Shallow Well Jet Pumps

569, 570, 571, 572 Series

INSTRUCTION MANUAL DN0136 REVISION D

DualPak Series FILE NO: DATE: Feb. 15, 1999 SUPERSEDES: DATE: Sept. 28, DualPak 6900 Series Booster System

569, 570, 571, 572 Series

J SERIES. Technical Specifications. Centrifugal Pumps for J Series Condensate & Boiler Feed Pumps. Features

DISHWASHER. Models DW2432 and DW2432SS. Installation Manual. Write Serial Number (on inner door of unit) here:

Owner s Guide and Installation Manual

Installation Manual CARBONATOR With Plain-Water Booster

Patterson/AMT Inline Circulator Pump Refer to pump manual for General Operating and Safety Instructions.

instant hot water no waiting & no waste benefits Hot water recirculation solutions Astro hwr

Patterson/AMT Inline Circulator Pump Refer to pump manual for General Operating and Safety Instructions.

LC Series - Light Commercial Pump Station Installation and Operation Manual

Patterson/AMT Inline Circulator Pump Refer to pump manual for General Operating and Safety Instructions.

HIGH EFFICIENCY CIRCULATOR INSTRUCTION, INSTALLATION, MAINTENANCE AND REPAIR MANUAL

Pump - Owner s Manual

Food Waste Disposer Instruction Manual

CONTENTS CONSIDERATIONS. General Plumbing Component Connection ILLUSTRATION. Control System CONFIGURATION. Voltage Verification CONNECTION

Owner s Guide and Installation Manual

SMF PUMP OWNER S MANUAL

Owner s Guide and Installation Manual

OWNERS GUIDE TO INSTALLATION AND OPERATION

52 SAN LUCAS CEILING FAN

Oscillating Ceiling Fan

Pump WaterVISE, FloVISE

OPERATING AND MAINTENANCE MANUAL FOR PLATE HEAT EXCHANGER INDIRECT FIRED WATER HEATER. Electric Heater Company Base Model "BWXP"

Domestic Pump Vacuum and Boiler Feed Units Series VCMD TM INSTRUCTION MANUAL DN0137 REVISION F

SUBMERSIBLE DIRTY WATER PUMP

SM-909/SM /2" Sweat 3/4" Sweat 3 3/8" F.L. Max. Max. Line Weight Model No. HP Inlet/Outlet Volts Amps Fluid Temp. Pressure (Lbs.

48 TAYLOR CEILING FAN

INSTALLER: PLEASE LEAVE THIS MANUAL FOR THE OWNER S USE. Condensate Return Systems General Installation, Operation, & Service Instructions !

52 BAYTOWNE CEILING FAN

Crown Boiler Company

installation and operation manual for Hunter Ceiling Fans

52 BARSTOW CEILING FAN

FOOD WASTE DISPOSER OWNER S GUIDE

Owner s Guide and Installation Manual

Installation and Operation Manual For Hunter Ceiling Fans

C-IV 60 CEILING FAN READ AND SAVE THESE INSTRUCTIONS. FAN RATING AC 120V. 60Hz

owner s manual & parts list

52 CEILING FAN READ AND SAVE THESE INSTRUCTIONS FAN RATING AC 120V.

CEILING FAN OWNER'S MANUAL

Universal Fire Tube Boiler Wall Mount Models

SPA BLOWER OWNER'S MANUAL XXXX, XXXX, XXXX, XXXX, XXXX, XXXX fax

Plastic Housing Plastic Housing Stainless Housing SM /8" 3 3/8"

7 1/4" 3 3/8" Pump Max. Max. Line Weight Model No. HP Housing Inlet/Outlet Fluid Temp. Pressure (Lbs.)

52 BERKSHIRE CEILING FAN

Easy installation. EZ80N EZ Fit Ventilation Fan INSTALLATION GUIDE READ AND SAVE THESE INSTRUCTIONS. Table of Contents

installation and operation manual for Hunter Ceiling Fans

Water Distiller Service Manual

Owner s Guide and Installation Manual

CEILING FAN OWNER'S MANUAL

Summer Breeze Heater Service Manual

6. Cooling System XCITING 400i. This chapter covers the location and servicing of the cooling system components for the KYMCO XCITING 400i.

HD 525 S 06/03 A ! 5.960

CEILING FAN OWNER'S MANUAL

Installation, Operation and Maintenance Instructions Electric Flow Heater OM009

Elite Primer Baldor Series External Pond Pump

CHILLER. Operator s & Installation Manual

IMPORTANT SAFETY INFORMATION! WARNING ALWAYS keep electric cords, home furnishings, drapes, clothing, papers, or other combustibles at least 3 feet (0

INSTRUCTION AND REPAIR MANUAL

TQ Series. Electronic Control Pump Instruction Manual. 50Hz. ISO 9001 Certified Walrus Pump Co., Ltd.

Instruction Sheet 00 Variable Speed Delta T (00-VDT)

Installation and User Instructions HS10U, HS15U.

CEILING FAN OWNER'S MANUAL

DRAINMAKER INSTALLATION INSTRUCTIONS PREINSTALLATION CHECKLIST

Taco 00 Series Cartridge Circulators

Installation GUIDE VDWU524SS VDWU524WSSS FDWU524WS FDWU524 VDWU324SS FDWU324

Installation Instructions

Hanson LED C e i l i n g F a n

! The Caution Symbol (exclamation point) alerts you to a "CAUTION", a safety or

"S" SERIES IMMERSIBLE PUMP OWNER'S MANUAL INSTALLATION OPERATION PARTS Models S12 S16

CHAMPION PUMP OWNER S MANUAL

INSTALLATION & MAINTENANCE MANUAL FOR QuickDraw

Dishwasher Installation Manual

ECONO FLO 2.7HP VARIABLE SPEED PUMP OWNER S MANUAL

POWER SHOWERS Models 4500M 5002M 4500T 5002T

6000, 8000, & 15000

Instruction manual. Submersible sump pump. Safety instructions Application Electrical connection Installation Maintenance Technical data

Clean & Clear. Cartridge Filter System Owner s Manual IMPORTANT SAFETY INSTRUCTIONS READ AND FOLLOW ALL INSTRUCTIONS SAVE THESE INSTRUCTIONS

52 STRATHMERE CEILING FAN

READ AND SAVE THESE INSTRUCTIONS

Circulating Oil Temperature Control System

Transcription:

Astro 2 circulator models Installation and File No: 10.89 Date: august 05, 2013 Supersedes: 10.89 Date: june 26, 2013

contents 1.0 Introduction 4 2.0 Installing 4 2.1 Terminal box 4 2.2 Electrical wiring 5 3.0 Check valve removal (optional) 5 4.0 Start up 5 5.0 Installation troubleshooting guide 6 6.0 Spare parts 7

installation & Astro 2 circulator models 4 warning Prior to installation, read these installation and. Installation and operation must comply with local regulations and accepted codes of good practice. The use of this product requires experience with and knowledge of the product. Only licensed or trained installers should install this product. For supply Connection, use wires acceptable for at least 90 c (194 f). Risk of shock: this pump has not been tested for use in swimming pools or marine areas. To reduce risk of electric shock: Unplug before servicing, see instructions for proper installation, connect to a properly grounded, grounding type receptacle only. For indoor use only. Use copper conductors only. Do not install with motor above or below pump body. Do no submerge. Do not run pump dry. These installation and are applicable to the following Astro 2 models. astro 2 models model astro 210ci electrical input rating 200w, 1.72a astro 210ss 200w, 1.72a astro 220ssu 33w, 0.29a astro 225ssu 83w, 0.69a astro 225bs ½" swt 75w, 0.64a astro 225bs O" swt 75w, 0.64a astro 230ss 97w, 0.81a astro 230ci 115v, 60hz 97w, 0.81a astro 230ci-r Single phase 97w, 0.81a astro 250ss 117w, 0.98a astro 250ci 117w, 0.98a astro 250ci-r 117w, 0.98a astro 280ci 218w, 1.9a astro 280ss 218w, 1.9a astro 290ci 218w, 1.9a astro 290ss 218w, 1.9a astro 280ci 230v 210w, 0.9a astro 280ss 230v 230v, 60hz 210w, 0.9a astro 286ci Single phase 370w, 1.6a astro 286ss 370w, 1.6a 1.0 introduction You are about to install a pump from the finest multi-speed wet rotor circulator line on the market today. The Armstrong Astro 2 circulators are designed for closed hydronic or potable water systems. Their intended use is for circulating water or glycol solutions. For pumping domestic water use non-ferrous lead free bronze or stainless steel body pump construction. The Astro 2 operates extremely quietly and is lubricated by the system liquid being pumped by the circulator. These circulators except Astro 286 are designed to work at temperatures and pressures up to 230 f (110 c) and 150 psi. Astro 286 is designed to work at temperature and pressure upto 150 f (65 c) and 150psi. For fluid temperature upto 185 f (85 c), operating current must not exceed 1.35a. For lead free bronze and stainless steel pumps used in potable water systems, it is recommended that the operating temperature of the fluid be kept as low as possible (i.e. below 150 f/65 c) to avoid precipitation of calcium. When unpacking the circulator, inspect for any damage that may have occurred during transit. Check for loose, missing or damaged parts. 2.0 installing We recommend that any soldering be done before the pump is actually installed. This will eliminate the possibility of solder dropping into the pump body. Thoroughly flush the system out before installing the circulator. Before Installing, check that the flow direction of the water through the pump body matches the arrow on the circulator body. The circulator is supplied for up discharge installation. Install the circulator in either the outlet or inlet line to the boiler or hot water heater. It is important to install these circulators with the split between the circulator body and the motor in a vertical position. This ensures efficient operation. See installation examples. correct installations incorrect installations

Astro 2 circulator models installation & 5 The circulator shaft must always be in a horizontal position. (The piping can be in a horizontal or vertical run.) Isolation valves should be installed on the discharge and suction side of the pump to facilitate service. 2.1 terminal box Always install the circulator with the terminal box above or beside the motor. If the terminal box is under the motor as initially mounted, remove the motor mounting screws and rotate the motor to the proper position. (See example.) Ensure the gasket is intact and seated before evenly retightening the mounting screw to 4.5-5.5 lb/ft (6-7.5 Nm). To ensure the rotor still spins freely, temporarily remove the plug (located in the middle of the nameplate), insert a flat head screwdriver into the slot in the end of the rotor shaft and turn. Retighten the plug to 1.5-2 lb/ft (2-2.7 Nm). Ensure no water leak at all sealing contacts. Wire shall be 14 to 16 gauge solid wire or 16 to 18 gauge stranded wire. To wire, loosen the screw from the terminal box cover and remove the screw and cover. Insert wires through supplied liquid-seal connector (installed) or included ½" npt adaptor or other strain relief connector (not provided). Strip ³/af" of insulation from the ends of the three wires to be connected. To insert the wires into the terminal strip, flip the terminal lever away from the wire opening and press down firmly. Insert the stripped wire into the opening and release the lever. Tug on the wire gently to ensure it is secured. Connect the hot wire to terminal 'l', the neutral wire to terminal 'n', and the ground wire to terminal f. Tighten the terminal box cover. 2 plug 1 3 The motor is thermally protected so overload protection is not necessary. All that is required is a fused plug or circuit breaker in the power line. Electrical information can be found on the nameplate of the motor. Do not hang items or articles of clothing on the pump as air must be able to circulate freely through the motor. Do not operate the circulator without the motor plug installed. 3.0 check valve removal (optional) Using a pair of needle-nose pliers, grip one of the flat wings of the check valve and gently pull the valve out vertically. 2.2 electrical wiring The electrical wiring must be installed strictly in accordance with national electrical codes, local codes and regulations. 1 Electrical installation should be conducted by a qualified electrician. 2 Always make sure electric power is disconnected before wiring the circulator. The motor is designed for 60 Hz, 1 phase, 115 or 230 volt power.

installation & Astro 2 circulator models 6 4.0 start up These circulators are maintenance free. Self-lubricated by the system fluid, these circulators have no seals to leak or coupling to break. A proper installation practice recommends to thoroughly flush the system clean of all foreign materials prior to installing the circulator. Fill the system before starting. Speed setting of Astro 2 3-speed circulators: (Not applicable for Astro 286) The speed of these pumps can be adjusted with a 3-speed rotary switch. On speed setting 1, the pump operates at approximately half the performance of the speed setting 3 (maximum speed) and consumes about half the power of full speed operation. warning Never operate the circulator dry as permanent damage may occur. Never shut off the discharge or restrict suction flow while the circulator is operating. The venting of the rotor chamber may be done automatically. However, to assure proper and faster venting of this circulator, we recommend the manual venting procedure as follows 1 Place a container under the back of the circulator to catch any water that may run out. 2 Be sure power to the circulator is off at the fuse or circuit breaker. 3 Loosen plug on the back of the motor but do not remove. 4 Continue until water appears. 5 After a sufficient amount of water free of air bubbles has passed, retighten the plug. 6 The circulator can now be started. liquid temperature minimum inlet pressure 150 f (65 c) 3.0 ft (0.91 m) 167 f (75 c) 4.4 ft (1.34 m) 194 f (90 c) 9.2 ft (2.8 m) 230 f (110 c) 36.1 ft (11.0 m) 5.0 installation troubleshooting guide fault possible cause remedy Noise from radiator Excessive pressure passing the thermostatic valve. Reduce the speed setting. Flow decreases will reduce system pressure and eliminate the noise. The radiator is not giving off any heat Pump generates little or no output The thermostatic valve is jammed or blocked. The heating system is not balanced. Incorrect discharge direction. Turn pump 180 Dirty impeller Suction port blocked Outlet blocked Isolation valve closed Dirty strainer Air in the pump Pump at lowest/medium speed level Pump set point is too low Shut off all other radiators in the system, and set the pump at maximum speed. Once the blockage has been dislodged reopen the radiators and adjust pump to original speed setting. Re-assess the system. Fit new commissioning valves on all radiators (may be integrated in the thermostatic valves) to enable an even distribution of the flow. Open pump and clean impeller note: Close isolation valves if present Open pump and clean housing note: Close isolation valves if present Clean isolation valves Open isolation valves Clean strainer Switch off pump and open bleed screw to vent. Set pump to the next higher speed level. Increase set point on the pump or controller.

Astro 2 circulator models installation & 7 fault possible cause remedy Pump stopped, no power Pump stopped, power supply present Power supply interrupted Fuse tripped or circuit breaker opened Thermal switch has actuated Pump does not start Check the power supply. Attach external power control if necessary. Repair short-circuited wire. Repair loose contact. Check for the properly rated fuse. Check pump motor and lead. Reduce ambient temperature. Clean blocked or slow rotating pumps. Open air vent screw and unlock shaft. Clean pump. Increase speed/set point. Replace pump. Noises in system, thermostatic valves/pipes Pump output too high Reduce speed level. Open bypass/valve. Install circuit balancing valves to adjust flow. Check pump selection/system. Adjust pump. Check system /gauges. Replace pump. Noisy pump Air in pump Open bleed screw and vent pump. Vent and top up system with water. Check expansion tank. Install air separator. Cavitation sounds Resonance noises Knocking from foreign bodies in the pump/or on valve Increase inlet pressure. Reduce temperature. Throttle back pump. Reduce speed. Use sound insulation material between the pump and surface to reduce resonance noise. Install expansion joints. Install fixture to change system s natural frequency. Adjusts pump speed. Replace pump/motor. Clean impeller. Adjust valve pressure. Adjust valve spring. Turn valve around if installed incorrectly. Replace pump. 6.0 spare parts spare part item no. applicable models Check valve 1" 810223-104 Astro 220ssu, Astro 225ssu Check valve 1¼" 810223-105 Astro 210, Astro 230, Astro 250, Astro 280, Astro 286 Check valve 1½" Astro 290

toronto 23 bertrand avenue toronto, ontario canada m1l 2p3 +1 416 755 2291 buffalo 93 east avenue north tonawanda, new york u.s.a. 14120-6594 +1 716 693 8813 birmingham heywood wharf, mucklow hill halesowen, west midlands united kingdom b62 8dj +44 (0) 8444 145 145 manchester wolverton street manchester united kingdom m11 2et +44 (0) 8444 145 145 bangalore #59, first floor, 3rd main margosa road, malleswaram bangalore, india 560 003 +91 (0) 80 4906 3555 shanghai no. 1619 hu hang road, xi du township feng xian district, shanghai p.r.c. 201401 +86 21 3756 6696 armstrong fluid technology established 1934 armstrongfluidtechnology.com tm