MECKLENBURG COUNTY FIRE MARSHAL S OFFICE

Similar documents
2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge.

SECTION 907 FIRE ALARM AND DETECTION SYSTEMS

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST FIRE ALARM SYSTEM INSTALLATION

Florida Building Code Chapter 9 Fire Protection Systems Advanced Course

MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION

Florida Building Code 2010

El Reno Fire Department Fire Alarm Plan Review Worksheet

SANTA CLARA COUNTY Winchester Blvd., Los Gatos, CA (408) (408) (fax)

NFPA Changes

Moreno Valley Fire Department Fire Prevention Bureau. New and Existing Fire Alarm & Signaling Systems Guideline

THE BASICS OF FIRE ALARM PLAN REVIEW

Fire Protection Coffee Break Training May 2016

Fire Alarm, Water Flow Alarm & Signaling Systems

Fire Alarm System Fundamentals

Overview of Fire Alarm Provisions Based on the 2012 IBC, IFC and NFPA 72, 2013 Edition

12/14/2013. Fire alarm and emergency power SPRINKLER HEAD

Type of Fire Alarm Control Panel: System is: Existing OR New If new, provide Electrical Permit Number:

rpsa FIRE PROTECTION ENGINEERS

TABLE OF CONTENTS GENERAL... 2 A. DEFINITIONS DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2

2018 NICET Code Transition Changes

Bold items are particular to the City of Euless

Residential Care Facilities Requirements

PROPOSED CHANGE TO THE 2012 BUILDING CODE O. REG. 332/12 AS AMENDED

Agency for Health Care Administration

SECTION FIRE ALARM STANDARDS REVISED CONSTRUCTION STANDARD

Fire Alarm Acceptance Testing & On-Going Maintenance with The Joint Comm. Standards / Reporting. Prepared Especially for : OSFM TEC 2016

Changes in NFPA

Riverside County Fire Department Office of the Fire Marshal Market St., Ste. 150, Riverside, CA Ph. (951) Fax (951)

Fire Alarm System Fundamentals Presented By: Shamim Rashid-Sumar, Vice President Middle East Operations Rolf Jensen and Associates, Inc.

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

Chapter 4: Fire Protection Systems

Rancho Cucamonga Fire Protection District Prevention Bureau Standard

THIS ORDINANCE ONLY AFFECTS EXISTING FIRE ALARM SYSTEMS.

MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry

2012 OBC Changes. Summary of key changes to Life Safety and Fire Protection Systems for CFAA January 22, 2014

M E M O R A N D U M. NFPA 5000 A2011 ROP Letter Ballot

Agency for Health Care Administration

CFAA Technical Seminar Ontario Building Code Updates to 2015

FIRE & LIFE SAFTEY STANDARD

Functional Performance Test

COMMERCIAL (IBC) FIRE ALARM SUBMITTAL GUIDE

5123: information. The graphic plan shall include, but may not be limited to: (a) A primary and secondary means of exit from each floor;

Residential Based Care Facility Guidelines

For additional information regarding R-3.1 residential care facilities please contact (951)

Date Issued: December 14, 2017 Revision: 2.1

Report to Adhoc Health Code change proposal regarding locking arrangements From John Woestman, BMHA

Balloting Version First Draft NFPA 101 Life Safety Code Proposed 2015 Edition

2012 International Building Code Errata (Portions of text and tables not shown are unaffected by the errata)

780 CMR: STATE BOARD OF BUILDING REGULATIONS AND STANDARDS 780 CMR: MASSACHUSETTS AMENDMENTS TO AND THE INTERNATIONAL BUILDING CODE 2009

M E M O R A N D U M. NFPA Technical Committee on Building Services and Fire Protection Equipment

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION CHECKLIST

Standard of Practice - Fire Alarm Systems. NOTE: Significant revisions or additions to the previous standards are highlighted in italics.

3.1 Introduction. 3.1 Introduction

Defend In Place 2012 IFC Overview of Institutional Occupancies

Agency for Health Care Administration

STANDARDS UPDATE NOTICE (SUN) ISSUED: February 5, 2018

Residential-based Care Facility R-4 Guideline

GROUP SR SPECIAL RESIDENCE (ASSISTED SELF-PRESERVATION) OCCUPANCIES

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU STANDARD

MD-DC-VA Automatic Fire Alarm Association, Inc. Interfacing Fire Alarm, Sprinkler and Elevator Systems In Maryland, DC and Virginia

2. HVAC and smoke control systems; fire, smoke, and combination fire/smoke dampers. 5. Central control and monitoring system.

EMERGENCY PLANNING AND PREPAREDNESS

University Design Standard Fire Alarm Systems

Michigan State University Construction Standards FIRE DETECTION AND ALARM PAGE

LOCAL AMENDMENTS TO THE INTERNATIONAL FIRE CODE 2006 EDITION

Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions.

British Columbia Building Code 2006 Division B Part 3 Fire Protection, Occupant Safety and Accessibility Section 3.2 Building Fire Safety

Interfacing Fire Alarm, Sprinkler and Elevator Systems

GENERAL AREAS OF INSPECTION

Large Family Daycare Guideline

Memphis Housing Authority High Rise Fire Alarm Upgrades. Questions from Contractors (Through Addendum #2) Communications Systems, Inc.

Smoke Detector Activation of any smoke detector shall start the alarm verification mode.

January 1, 2014 Mandatory Effective Date

SAF-BCF SECOND REVISIONS WITH STATEMENTS

ICC CODE CORNER 2015 International Fire Code

HCD DSA OSHPD 1 2 1/AC AC SS SS/CC

PART 1 GENERAL Quality Assurance A. Fire Alarm Contractor Qualifications:

GROUP SR SPECIAL (ASSISTED SELF-PRESERVATION) OCCUPANCIES

STATE OF MARYLAND DEPARTMENT OF STATE POLICE OFFICE OF THE STATE FIRE MARSHAL

Automatic Fire Alarm Association Webinar On Inspection, Testing, And Maintenance Of Fire Alarm Systems

Hinesville First United Methodist Church SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

FIRE SAFETY REQUIREMENTS FOR PRE RESIDENTIAL BUILDINGS OF THREE OR MORE STORIES (DOROTHY MAE ORDINANCE - NO. 158,963)

SECTION 915 CARBON MONOXIDE DETECTION

FIRE SAFETY UPGRADING CONSIDERATIONS for EXISTING SENIOR CITIZEN LODGES

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

Applying Performance-based Fire Alarm System Design Part 4

Clarification. Summary of Changes. Summary of Changes. Alan Cavers Area Manager Fire & Security Systems Group

Standard for the Installation of Carbon Monoxide (CO) Detection and Warning Equipment

FIRE PROTECTION SYSTEMS

FIRE ALARM SYSTEMS & 780 CMR. Dave LeBlanc, PE, FSFPE March 17, 2015

HIGH-RISE RETROFIT ORDINANCES - NO and NO

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION GUIDELINE RESIDENTIAL CARE FACILITIES 2007 CBC/CFC (R-3.1)

The 2013 National Fire Alarm and Signaling Code

2007 CBC & CFC Residential Care Facility Requirements (24 hour care only)

EMERGENCY PLANNING AND PREPAREDNESS

97 FCV 006 Page 2 of 16 EXPLANATORY MATERIAL

Unified Fire Authority - Fire Prevention Bureau

FIRE PROTECTION SYSTEMS

GROUP SR SPECIAL (ASSISTED SELF-PRESERVATION) OCCUPANCIES

FIRE PROTECTION SYSTEMS

Transcription:

Effective Date: 11/01/02 Purpose: MECKLENBURG COUNTY To establish a set of guidelines for performance testing of all newly installed or upgraded fire alarm systems in order to ensure that all devices and related equipment (i.e. additional fire suppression and extinguishing systems) meet the minimum requirements of NFPA 72. Policy: A. Plans and specifications, or shop drawings, for automatic and manual fire protective signaling systems shall be submitted and approved by the Mecklenburg County Fire Marshal s Office Plans Review Section prior to the installation of equipment and wiring. The shop drawings shall include at a minimum: 1. Floor plan(s). 2. Locations of all alarm initiation and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation equipment. 5. Power connection. 6. Battery calculations 7. Conductor types and sizes. 8. Voltage drops calculations. 9. Manufacturer, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. B. Upon installation of all fire alarm systems and any related equipment, the system(s) shall be subject to an acceptance test and witnessed by the Fire Marshal. C. Upon installation and testing of the system(s), test certificates meeting the minimum requirements of the applicable NFPA standards shall be provided to the inspector at his or her request. D. All systems and related fire suppression equipment shall be fully installed, tested and confirmed operable prior to a Certificate of Occupancy being issued. E. The following requirements are ones that meet the minimum requirements of NFPA 72 and the North Carolina Fire Code and are provided as a guide in conducting the required acceptance test(s):

1. Manual Fire Alarm Boxes a. Manual fire alarm boxes shall be located not more than 5 feet from the entrance to each exit. Additional manual fire alarm boxes shall be located so that travel distance to the nearest box does not exceed 200 feet measured horizontally on the same floor. Exception: Manual fire alarm boxes shall not be required in Group E occupancies where the building is equipped throughout with an approved automatic sprinkler system, the notification appliances will activate on sprinkler water flow and manual activation is provided from a normally occupied location. b. The height of the manual fire alarm boxes shall be a minimum of 42 inches and a maximum of 48 inches measured vertically, from the floor level to the activating handle or lever of the box. c. Manual fire alarm boxes shall be red in color. d. Where fire alarm systems are not monitored by a supervising station, an approved permanent sign on or beside the box shall be installed that reads: WHEN ALARM SOUNDS - CALL FIRE DEPARTMENT. e. The fire official can require the installation of listed manual fire alarm box protective covers to prevent malicious false alarms or to provide protection from physical damage. 2. Power Supply and Wiring a. Primary and secondary power supply and wiring shall comply with the requirements of the ICC Electrical Code and NFPA 72. 3. Zones a. Each floor shall be zoned separately and a zone shall not exceed 22, square feet. The length of any zone shall not exceed 300 feet in any direction. Exception: Automatic sprinkler system zones shall not exceed the area permitted by NFPA 13. b. A zoning indicator panel and the associated controls shall be provided in an approved location. The visual zone indication shall lock in until the system is reset and shall not be canceled by the operation of an audible-alarm silencing switch. c. The primary purpose of the fire alarm system annunciation is to enable responding personnel to identify the location of a fire quickly and accurately and to indicate the status of emergency equipment or fire safety functions that might affect the safety of occupants in a fire situation. All required annunciation means shall be readily accessible to responding personnel and shall be located as required by the fire official to facilitate an efficient response to the fire situation.

d. In buildings that have floors located more than 75 feet above the lowest level of fire department vehicle access that are occupied for human occupancy, a separate zone by floor shall be provided for all of the following types of alarm-initiating devices where provided: Smoke detectors. Sprinkler water flow devices. Manual fire alarm boxes. Other types of automatic fire detection devices or suppression systems. 4. Alarm Notification Appliances. a. Visible alarm notification appliances shall be provided in public and common areas. b. Group I-1 and R-1 sleeping accommodations shall be provided with a visible alarm notification appliance, activated by both the in-room smoke alarm and the building fire alarm system. c. Wall-mounted appliances shall have their tops above the finished floors at heights of not less than 90 inches and below the finished ceilings at heights of not less than 6 inches. Wall-mounted appliances shall be mounted such that the entire lens is not less than 80 inches and not greater than 96 inches above the finished floor. d. Visible notification appliances shall be located not more than 15 feet from the end of the corridor with a separation not greater than 100 feet between appliances. If there is an interruption of the concentrated viewing path, such as a fire door, an elevation change, or any other obstruction, the area shall be treated as a separate corridor. e. In corridors where there are more than two visible notification appliances in any field of view, they shall be spaced a minimum of 55 feet from each other or they shall flash in synchronization. 5. Audible Alarms a. Audible alarm notification appliances shall be provided and sound a distinctive sound that is not to be used for any purpose other than that of a fire alarm. The use of the distinctive three-pulse temporal pattern fire alarm evacuation signal required by NFPA 72 became effective July 1, 1996, for new systems installed after that date. The audible alarm notification appliances shall provide a sound pressure level of 15 decibels (dba) above the average ambient sound level or 5 dba above the maximum sound level having a duration of at least 60 seconds, whichever is greater, in every occupied space within the building. The minimum sound pressure levels

occupancies. MECKLENBURG COUNTY shall be: 70 dba in occupancies in Groups R and I-1; 90 dba in mechanical equipment rooms; and 60 dba in other occupancies. The maximum sound pressure level for audible alarm notification appliances shall be 120 dba at the minimum hearing distance from the audible appliance. Where the average ambient noise is greater than 105 dba, visible alarm notification appliances shall be provided in accordance with NFPA72 and audible alarm notification appliances shall not be required. Exception: Visible alarm notification appliances shall be allowed in lieu of audible alarm notification appliances in critical care areas of Group I-2 b. Where audible appliances are installed to provide signals for sleeping areas, they shall have a sound level of at least 15 dba above the average ambient sound level or 5 dba above the maximum sound level having a duration of at least 60 seconds or a sound level of at least 70 dba, whichever is greater, measured at the pillow level in the occupiable area. If any barrier, such as a door, curtain, or retractable partition, is located between the notification appliance and the pillow, the sound pressure level shall be measured with the barrier placed between the appliance and the pillow. c. Actuation of alarm notification appliances or emergency voice communications and annunciation at the protected premises shall occur within 10 seconds after the activation of an initiating device. d. Trouble signals required to indicate at the protected premises shall be indicated by distinctive audible signals. These trouble signals shall be distinctive from alarm signals and shall be located in an area where it is likely to be heard. 6. Smoke Detectors. a. Spot-type smoke detectors shall be located on the ceiling not less than 4 inches from a sidewall to the near edge or, if on a sidewall, between 4 and 12 inches down from the ceiling to the top of the detector. b. On smooth ceilings, spacing of 30 feet shall be permitted. c. Smoke detectors shall not be located directly in the air stream of supply registers. In spaces served by air-handling systems, detectors shall not be located where airflow prevents operation of the detectors. d. An approved, single-station smoke alarm shall be installed in every guest room and every living area and sleeping room within a guest suite in new hotels and dormitories, in every sleeping room in lodges or rooming houses, and inside and outside every sleeping area in the immediate vicinity of the bedrooms and on all levels of the dwelling unit including basements in new apartment buildings.

Exception: In apartment buildings protected throughout by an approved supervised automatic sprinkler system, the smoke alarms are not required inside the sleeping rooms. e. In new construction where two or more smoke alarms are required within a living unit, suite of rooms, or similar area, they shall be arranged so that operation of any smoke alarm shall cause the alarm in all smoke alarms within the living unit, suite of rooms or similar area to sound. f. The alarms shall sound only within an individual living unit, suite of rooms or similar area and shall not actuate the building fire alarm system. g. Duct smoke detectors shall be connected to the building s fire alarm control panel when a fire alarm system is provided. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location. Exceptions: The supervisory signal at a constantly attended location is not required where duct smoke detectors activate the building s alarm notification appliances. In occupancies not required to be equipped with a fire alarm system, actuation of a smoke detector shall activate a visible and an audible signal in an approved location. Smoke detector trouble conditions shall activate a visible or audible signal in an approved location and shall be identified as air duct detector trouble. h. System-type smoke detectors or other automatic fire detection located in elevator lobbies, elevator hoist ways and elevator machine rooms used to initiate fire fighter s service recall shall be connected to the building fire alarm system. A lobby smoke detector shall be located on the ceiling within 21 feet of the centerline of each elevator door within the elevator bank under control of the detector. i. Smoke detectors shall not be installed in elevator hoist ways. Exception: Where the top of the elevator hoist way is protected by automatic sprinklers or where a smoke detector is installed to activate the elevator hoist way smoke relief equipment 7. Door Release Service and Unlocking Devices. a. Magnetic door holders that allow doors to close upon loss of operating power shall not be required to have a secondary power source. b. Any device or system intended to actuate the locking or unlocking of exits shall be connected to the fire alarm system serving the protected premises. c. All exits connected shall unlock upon receipt of any fire alarm signal by means of the fire alarm system serving the protected premises and shall also unlock upon loss of the primary power. 8. Fire-Extinguishing Systems.

a. Automatic fire-extinguishing systems or suppression systems shall be connected to the building fire alarm system where a fire alarm system is required. 9. Alarm Signals and Monitoring. a. Fire alarm systems and automatic sprinkler systems shall be monitored by an approved supervising station in accordance with NFPA 72. Exceptions: Single and multiple-station smoke alarms required by IBC - Section 907.2.10. Smoke detectors in Group I-3 occupancies. Supervising service is not required for automatic sprinkler systems in one- and two-family dwellings. Limited area sprinkler systems serving fewer than 20 sprinklers. b. Manual fire alarms, automatic fire extinguishing systems, and emergency alarm systems in Group H occupancies shall be monitored by an approved supervising station. Exception: When approved by the building official, on-site monitoring at a constantly attended location shall be permitted provided that notifications to the fire department will be equal to those provided by an approved supervising station. c. Water flow detecting devices shall initiate an alarm no more than 90 seconds after a sustained flow of at least 10 gpm. d. Upon activation of the initiating device(s), receipt of the correct initiating device signal at the supervising central station until the initiation of retransmission to the public fire service communications center should take a maximum of 90 seconds. e. A minimum of two separate means of interconnection shall be provided between the primary and remote communications center receiving equipment. This interconnection shall be dedicated and shall not be used for any other purpose. Revised Date: 11/01/09