Operating Instructions Heating Controllers RVL479, RVL480, RVL481, RVL482

Similar documents
Operating Instructions

Operating Instructions

RVL471. Heating controller. G2524en. Installation Instructions. 1 Installation. 2 Commissioning

G a

RVL470. Heating Controller. Use. Functions. Series B

RVL472. Heating Controller. Building Technologies HVAC Products. Series C. including d.h.w. heating

RVL47. Heating Controller. Installations Instructions. Installation

RVL471 Heating and Domestic Hot Water Controller Basic Documentation

RVL481. Heating Controller. including d.h.w. heating

RVL480. Heating Controller

Heating and D.h.w. Controller RVL482 Basic Documentation

District heating controller for two heating circuits and d.h.w. according to Siemens specifications:

QAA Room Unit for Boiler Control with OpenTherm Interface Basic Documentation. Siemens Building Technologies Landis & Staefa Division

RVP331. Heating Controller for 2 heating circuits, d.h.w. and boiler. Building Technologies HVAC Products

RVL479. Heating Controller. for use with a partner unit

RVP310. Heating Controller. Building Technologies HVAC Products

RVP340 Heating controller for 1 heating circuit RVP350 and RVP351 Heating controllers for 1 heating circuit and d.h.w. Basic Documentation

RVP360 and RVP361 Heating controllers for 2 heating circuits and d.h.w. Basic Documentation

Heating Controller for 2 heating circuits, d.h.w. and boiler, communicating

QAW70. Room Unit. Siemens Building Technologies HVAC Products. for use with heating controllers

Room Units and Sensors for Use in Heating Plants. Siemens Building Technologies HVAC Products SIGMAGYR. Type summary

Operating Instructions

QAW70. Room Unit. Building Technologies. for use with heating controllers

RVD120, RVD140 Controllers for district heating and d.h.w. Basic Documentation

INSTRUCTION FOR THE USER THC V E OIL BLU

1. COMMISSIONING OF THE BOILER en DESCRIPTION FUNCTION BUTTON DESCRIPTION SYMBOL DISPLAY

Room Unit. Building Technologies SYNERGYR

Synco 900 Operating instructions

Heating Controller SDC. District Heating Controller DHC 43 OPERATING INSTRUCTIONS

REA22 Room Temperature Controller

Landis & Gyr RAV 91 Operating Instructions

Operating instructions

PRELIMINARY EDITION

Synco 900 Operating Instructions. Edition 1.0 Controller series 1 CE1B2707en Building Technologies HVAC Products

Bosch. Gas Condensing Boiler. Applications Manual. 100, 151 Combi Boiler 57, 100, 131, 151 Heating Boiler

Operating instruction. Remote control station WCM-FS /

P20. ECL Comfort. User's Guide. Installer's Guide. ECL Comfort P20. User's Guide. Installer's Guide *VI7BD502* *087R8014* *087R8014* *VI7BD502*

ProCon Boiler Controller Commissioning Quick Reference Guide

COnDEnSInG BOIlERS TAU UNIT OIL USER parameters manual

1 DOCUMENT REVISION CONTROL ELEMENTS... 9

Safety. DANGER Indicates potentially fatal situations. WARNING Indicates possible danger to life and limb.

RVA /109. Heating Circuit ZONE Controller. Instructions for the INSTALLER

Use. Functions. Key function. Other functions

G2484. Installation. - Control panel (in the panel front, on the inner wall, or on a DIN rail)

Self-learning Room Temperature Controller

HMC300. Control unit. Operating Instructions. EMS plus (2014/10) O

M116 / M450 USER AND MAINTENANCE MANUAL FOR MODULATING-CONTROL BOILER WITH GAS BURNER EQUIPPED FOR NATURAL GAS. Type : B23 ATLANTIC 2000

Synco living Operating Instructions. Edition 3.0 Controller series C CE1B2707en Building Technologies

R. Room temperature controller with solar control FR 120. Operating instructions for the user (2012/02)

ProCon 16, 31, 47 & 75. RVA 63 Boiler and Circuit Controller Commissioning Data.

Room Temperature. for 2-pipe fan coil units for compressors in DX type equipment

MAKING MODERN LIVING POSSIBLE. TP7001 Range Electronic 7 Day Programmable Room Thermostat. User Guide. Danfoss Heating

Heating Controller SDC Remote Heating Controller DHC

MAKING MODERN LIVING POSSIBLE. CP715Si. Electronic 2-Channel Common Timebase Programmer for Heating and Hot Water. User Guide.

ProCon 16, 31, 47, 75, 77 & HT. RVA 46. Zone Controller Commissioning Data.

MC200. Users Instructions. HEATING DIVISION Hort Bridge Ilminster, Somerset TA19 9PS Tel: Fax:

For the owner and the heating engineer. Operating and Installation Manual VRC 400. Programmable weather compensator with separat HW time control

Room thermostat with 24-hour time switch and large LCD

Type UCG/UDG. English...1 Français...7 Español Up button. OK button. Down button

ECL Comfort 210 / 296 / 310

R. Boiler Energy Management System FW 200. Operating Instructions for the User (2010/05)

1 DOCUMENT REVISION SOFTWARE VERSION BASIC DESCRIPTION BASIC OVERVIEW OF HYDRAULIC DIAGRAMS HYDRAULIC DIAGRAMS...

User s Manual

District heating controller

RVS46.. AVS75.. AVS37.. QAA75.. QAA78.. QAA55.. Albatros 2 Zone controller User Manual. Building Technologies HVAC Products

AUTO CM CM USER GUIDE

Self-learning Room Temperature Controller

VR 90 Remote control unit

District heating controller

Albatros2 Boiler Controllers User Manual RVS13.. RVS53.. Siemens Schweiz AG HVAC Products. Edition 1.0 Controller series A CE1P2383en

Operating instructions

RVS13... RVS53... AVS75... AVS37... QAA75... QAA78... QAA55... Albatros2 Boiler controllers User Manual. Building Technologies HVAC Products

3 Channel Multi-Purpose Programmer User Instructions

Operating Instructions Model : HC HC-N

- Data Brochure Universal Reset Module 422

RVS43.. RVS63.. AVS75.. AVS37.. QAA75.. QAA78.. QAA55.. Albatros2 Boiler controller User Manual. Building Technologies HVAC Products

- Data Brochure Universal Reset Module 423

RF ELECTRONIC PROGRAMMABLE ROOM THERMOSTAT, 7 DAY

Drayton Digistat +3RF

RVA Heating Circuit or Primary Controller Basic Documentation. Siemens Building Technologies Landis & Staefa Division

RVS43.. RVS63.. AVS75.. AVS37.. QAA75.. QAA78.. QAA55.. Albatros2 Boiler controllers User manual. Building Technologies HVAC Products

CentaurStat 7 User Operating Instructions Central Heating Programmable Room ThermoStat

DAY/TIME Button: Selects hour, minute and day setting.

Contents. Box contents: JGSTAT2B (Black) Fixing screws (White) Icons used in this manual:

Boiler controller Lambdatronic S 3200

RF Programmable Room Thermostat User Instructions

Linea HE. High efficiency combi boiler. Users Instructions THESE INSTRUCTIONS TO BE RETAINED BY USER

BM Programming Module. For the heating engineer Installation instructions

CM707. Programmable Room Thermostat with Optimum Start, Optimum Stop and Delayed Start. User Guide

Installation, service and operating instruction Cetetherm Midi Compact SR144 DHWC

Control solutions Biofloor

Residential Gas Condensing Boiler Greenstar ZBR16/21/28/35/42-3A... ZWB28/35/42-3A...

District Heating Controller

- Brochure D 542. Introduction. Features. tekmarnet 4 Thermostat /05. 5 Data Brochure Control settings wiring instructions

DAY/TIME Button: Selects hour, minute and day setting.

4 in 1 Digital Thermostat Control

Model: RT510RF. Installation Manual

C37. ECL Comfort. User's Guide. Installer's Guide. ECL Comfort C37. User's Guide. Installer's Guide *VI7CE602* *087R8070* *087R8070* *VI7CE602*

User Instructions For TopTronic RS-30

Room Unit for Boiler Control QAA User manual. Building Technologies. With OpenTherm Interface

Transcription:

Operating Instructions Heating Controllers RVL479, RVL480, RVL481, RVL482 Content Overview, display, and symbols... 4 Info button... 7 Operating modes... 8 Switching the heating ON... 9 D.h.w. heating... 10 Room temperature is not correct... 12 Departing from the heating program... 14 Querying and readjusting the setting values... 15 Selecting the room temperature setpoints... 16 Changing the heating program... 17 Entering the holidays... 20 Querying or readjusting the d.h.w. temperature... 21 Changing switching program 2... 22 Setting the clock... 24 Tips... 25 Faults and manual operation... 27 Siemens Building Technologies CE1B2540en 74 319 0616 0 b 18.07.2008 3/32

1 2540Z05 2 4 3 5 6 7 A B C 11 8 9 10 Siemens Building Technologies CE1B2540en 74 319 0616 0 b 18.07.2008 4/32

Overview what is where? 1 Operating mode buttons. The button indicating the current operating mode is lit 2 Button for d.h.w. heating ON / OFF (only RVL481, RVL482) 3 Info button 4 Display 5 Buttons for programming the setting values 6 Adjustment of heating curve 7 Buttons for manual operation: A = manual operation ON (LED lit) For buttons B and C, refer to page 29 8 LED for actuator OPENS or 1st burner stage ON 9 LED for actuator CLOSES or 2nd burner stage ON 10 LED for pump ON 11 Knob for room temperature readjustments Siemens Building Technologies CE1B2540en 74 319 0616 0 b 18.07.2008 5/32

Meaning of symbols on the display ECO BUS NORMAL heating REDUCED heating No heating required according to the prevailing outdoor temperature Holiday mode Heating OFF (frost protection ensured) Solar d.h.w. charging (only RVL481, RVL482) Fault in the plant One of the maximum limitations is active One of the minimum limitations is active Controller connected to the data bus Siemens Building Technologies CE1B2540en 74 319 0616 0 b 18.07.2008 6/32

You want to obtain information Press several times to display the: Time of day Outdoor temperature Room temperature (only if a sensor is used) Flow or boiler temperature The marking indicates the displayed variable. The info selected last is permanently displayed! Siemens Building Technologies CE1B2540en 74 319 0616 0 b 18.07.2008 7/32

The different operating modes Heating OFF Automatic heating up and setback according to the heating program / Heating automatically OFF during the holiday period entered / Heating automatically OFF if permitted by the prevailing outdoor temperature (ECO function) Continuously REDUCED heating Continuously NORMAL heating Frost protection ensured in all operating modes Remote operation with a room unit is only possible in AUTO mode. If the button flashes, the room unit overrides the controller's heating program. In AUTO mode, the controller operates fully automatically throughout the year. Siemens Building Technologies CE1B2540en 74 319 0616 0 b 18.07.2008 8/32

You want to switch the heating ON Is the heating plant ready to operate? Check position of the mains isolator Press button several times until the display shows the weekday and the time of day. Make corrections, if necessary Check date and time. Make corrections, if necessary Press for AUTO mode Activate the d.h.w. heating (only RVL481, RVL482) Practice-oriented and proven values were entered by your heating engineer when the controller was commissioned! Siemens Building Technologies CE1B2540en 74 319 0616 0 b 18.07.2008 9/32

You want d.h.w. heating (Only RVL481, RVL482) Press to switch d.h.w. heating ON (button lit) and OFF (button extinguished). When the button is lit, the controller provides d.h.w. heating at the following times, depending on the settings made by your heating engineer: According to switching program 2 According to the heating program 24 hours per day ( Mark with a cross whichever applies) Siemens Building Technologies CE1B2540en 74 319 0616 0 b 18.07.2008 10/32

For plants with d.h.w. storage tank, press until the button flashes to charge it manually (not possible in plants where d.h.w. is heated electrically). The d.h.w. is heated with a solar collector provided that your plant is equipped accordingly. The symbol indicates that solar d.h.w. is heated. D.h.w. heating is independent of the controller's operating mode. During the holiday period, d.h.w. is not heated. Siemens Building Technologies CE1B2540en 74 319 0616 0 b 18.07.2008 11/32

Room temperature is not correct If the room temperature is never correct, neither in mild nor in cold weather, make a room temperature readjustment with the setting knob: Room temperature too low: Turn the knob toward + Room temperature too high: Turn the knob toward 2540Z07 The setting knob's scale gives the room temperature readjustment in C. If the room temperature is not correct in mild weather only or in cold weather only, make the readjustment with the heating curve. For that purpose, there are three setting choices available, depending on the entries made by your heating engineer. To make a readjustment, proceed as follows: Siemens Building Technologies CE1B2540en 74 319 0616 0 b 18.07.2008 12/32

Setting choice Analog Room temperature not correct in mild weather Use slider on the left and readjust by about 5 C Room temperature not correct in cold weather Use slider on the right and readjust by about 5 C Digital Readjust line by Readjust line by about 5 C about 5 C Via data Contact plant operator Contact plant operator bus ( Mark with a cross whichever applies) After having made a readjustment, wait two days the room temperature requires a certain time to adapt! Siemens Building Technologies CE1B2540en 74 319 0616 0 b 18.07.2008 13/32

You don't want to heat according to the heating program No setback: Press to select NORMAL mode Reduced heating: Press to select REDUCED mode Don't forget to return to the normal heating program! The controller operates according to the heating program only when in AUTO mode. Siemens Building Technologies CE1B2540en 74 319 0616 0 b 18.07.2008 14/32

How to query or readjust setting values Press or to access the setting level The settings are assigned to several lines: Select next line below Select next line above Readjustment of values: Decrease Increase The value is adopted by selecting the next line or by leaving the setting level Leaving the setting level: Press button of the required operating mode, or the info button, or automatically after 30 minutes For list of lines, refer to the last page of these instructions. If you wish to practice, reset the time of day (refer to page 24). Siemens Building Technologies CE1B2540en 74 319 0616 0 b 18.07.2008 15/32

You want to select other room temperature setpoints To select lines: Press and To readjust values: Press and On line, change the setpoint of NORMAL heating (display ). Standard setting: 20 C On line, change the setting of REDUCED heating (display ). Standard setting: 14 C On line, change the setpoint of protection and holiday mode (display ). Standard setting: 10 C To leave the setting level: Select the required operating mode. Don't forget temperature-sensitive objects like plants! Siemens Building Technologies CE1B2540en 74 319 0616 0 b 18.07.2008 16/32

You want to change the heating program To select lines: Press and To readjust values: Press and For the daily heating up and setback, the controller comes with the following standard heating program: Daily from 06:00 to 22:00: NORMAL heating Daily from 22:00 to 06:00: REDUCED heating 2541Z04 You can enter a maximum of three heating periods per day. For each heating period, the following times need to be entered: Start of NORMAL heating End of NORMAL heating Siemens Building Technologies CE1B2540en 74 319 0616 0 b 18.07.2008 17/32

Procedure: 1. On line, select the weekday whose times you want to change: 1 = Monday, 2 = Tuesday, etc. 1-7 = all weekdays 2. On line, set the time for the start of NORMAL heating. 3. On line, set the time for the end of NORMAL heating. If additional daily heating periods are required: 4. On lines and, set the times required for the start and the end of the 2nd heating period. 5. On lines and, set the times required for the start and the end of the 3rd heating period. To cancel a heating period, change line, or until --:-- appears. To leave the setting level: Select the required operating mode. Siemens Building Technologies CE1B2540en 74 319 0616 0 b 18.07.2008 18/32

Example of a 24-hour program with three heating periods: 2541Z05 NORMAL heating from 07:00 to 12:00, from 14:00 to 18:00, and from 19:00 to 23:00 If the settings for the weekend differ from the other weekdays, first enter the times for the entire week (1-7); then, change weekdays 6 and 7. Siemens Building Technologies CE1B2540en 74 319 0616 0 b 18.07.2008 19/32

You want to enter your holidays To select lines: Press and To readjust values: Press and The data for a maximum of eight holiday periods can be entered. To enter the data for one period, proceed as follows: 1. Line : Enter the number of the holiday period. 2. Line : Enter the date of the first day. 3. Line : Enter the date of the last day (possible only when an entry on line has been made). To cancel an entry, change line until --.-- appears on the display. When a holiday period has elapsed, its data will be cancelled. To leave the setting level: Select the required operating mode. No d.h.w. heating during the holiday period (only RVL481, 482). Before making any entries, prepare a holiday plan. Siemens Building Technologies CE1B2540en 74 319 0616 0 b 18.07.2008 20/32

You want to query the d.h.w. temperature or readjust the d.h.w. setpoint (Only RVL481, RVL482) To select lines: Press and To readjust values: Press and Set the NORMAL d.h.w. temperature setpoint on line. The standard setting is 55 C Query the current d.h.w. temperature on line Set the REDUCED d.h.w. temperature setpoint on line. This setpoint is used during the OFF periods of the selected program. The standard setting is 40 C To leave the setting level: Select the required operating mode. Excessive d.h.w. temperatures increase the risk of scalding and produce more scale! Siemens Building Technologies CE1B2540en 74 319 0616 0 b 18.07.2008 21/32

You want to change switching program 2 (Only RVL481, RVL482) In addition to the switching program for the heating periods, the controller has a second switching program. In your plant, your heating engineer has assigned it to... The factory settings are as follows: Daily from 05:00 to 22:00: ON Daily from 22:00 to 05:00: OFF Each day can accommodate a maximum of three ON periods. The following time settings are required for each ON period: Start of ON period End of ON period If you want to make changes, proceed as follows (analogous to the switching program for the heating periods): Siemens Building Technologies CE1B2540en 74 319 0616 0 b 18.07.2008 22/32

To select lines: Press and To readjust values: Press and 1. On line, select the weekday whose times you want to change: 1 = Monday, 2 = Tuesday, etc. 1-7 = all weekdays 2. On lines and, set the times required for the start and the end of the 1st ON period. 3. On lines and, set the times required for the start and the end of the 2nd ON period. 4. On lines and, set the times required for the start and the end of the 3rd ON period. To cancel an ON period, change line, or until --:-- appears. To leave the setting level: Select the required operating mode. Siemens Building Technologies CE1B2540en 74 319 0616 0 b 18.07.2008 23/32

You want to set the clock To select lines: Press and To readjust values: Press and 1. To set the time of day: select line 2. The weekday on line (1 = Monday, 2 = Tuesday, etc.) is set automatically with the date 3. Use the same procedure just as for the time of day: the date (day and month) on line the year on line To leave the setting level: Select the required operating mode. The change from wintertime to summertime, and vice versa, is made automatically. Siemens Building Technologies CE1B2540en 74 319 0616 0 b 18.07.2008 24/32

Savings tips without sacrificing comfort During the day, make certain that room temperatures of 21 C will not be exceeded. Every degree above that level will increase heating costs by 6 to 7 % Renew the air in the house quickly, with windows fully open Set the thermostatic radiator valves in unoccupied rooms to their frost protection position Radiators should not be covered by curtains, furniture, etc., as these reduce heat emissions Closed window shutters, blinds, etc., reduce heat losses to the environment Check heating energy consumption at regular intervals Make certain that the d.h.w. temperature setting is not unnecessarily high (only RVL481, RVL482) Siemens Building Technologies CE1B2540en 74 319 0616 0 b 18.07.2008 25/32

Tips to follow if something seems wrong The heating does not work: Check the display. If ECO (economy) is shown, no heating is currently required due to high outdoor temperatures! The heating always maintains the same room temperature: Check the operating mode used (only AUTO mode provides setback and heats up again) The control has a room unit, but it cannot be operated: Check controller's operating mode. To enable the controller to be operated from the room unit, it must be in AUTO mode The required room temperature is reached either too early or too late: Change the heating program If the building is well insulated, you can expect long cooling down times Siemens Building Technologies CE1B2540en 74 319 0616 0 b 18.07.2008 26/32

Faults and manual operation If you are uncertain: Is the plant switched ON? Are all plant fuses in order? Is sufficient fuel in the tank? Has the controller been readjusted by unauthorized persons? (Time of day, setpoints, etc.) Check the display. If is shown, line displays an error code: 10 = fault outside sensor 11 = fault solar sensor 12 = fault wind sensor 20 = fault boiler temperature sensor 30 = fault flow temperature sensor 40 = fault return temperature sensor 42 = fault return temperature sensor 50 = fault storage tank temperature sensor/control thermostat 1 Siemens Building Technologies CE1B2540en 74 319 0616 0 b 18.07.2008 27/32

52 = fault storage tank temperature sensor/control thermostat 2 54 = fault d.h.w. flow temperature sensor 60 = fault room temperature sensor 61 = fault room unit 62 = wrong room unit connected 73 = fault collector sensor 81 = short-circuit on the bus 82 = same bus address assigned several times 100 = two clock masters on the bus 120 = flow alarm 140 = inadmissible bus address or plant type 142 = no partner unit on the data bus These error codes are very useful for service staff. Siemens Building Technologies CE1B2540en 74 319 0616 0 b 18.07.2008 28/32

If the controller uses a room temperature sensor (room unit): Is the sensor affected by drafts, direct solar radiation, etc.? Is the sensor affected by heat gains, such as people, machines, lighting, etc.? Is the sensor covered by furniture, curtains, etc.? Are all thermostatic radiator valves in the "sensor's room" in the fully open position? The control no longer works: If the heat source and the heating circuit pumps still operate: Press button A to switch to manual operation: Heating plant with a valve: The valve can be operated manually by pressing button B (OPENING) or C (CLOSING) Heating plant with no valve: The burner runs continuously. With two-stage burners, Siemens Building Technologies CE1B2540en 74 319 0616 0 b 18.07.2008 29/32 2540Z06

the second stage can be switched ON and OFF by pressing button C. In the case of modulating burners, modulation can be changed by pressing button B (OPEN) or C (CLOSE) (only with RVL482) D.h.w. heating (only with RVL481, RVL482): The pumps used for d.h.w. heating run continuously. If the d.h.w. plant uses a mixing valve, you can drive it manually to the required position. In plants with a changeover valve, d.h.w. heating is not possible. Switch manual operation OFF again: Press button A or select the required operating mode. The heat source no longer works: The burner has gone to lockout: Press the reset button! The heating circuit pump and / or the boiler pump do not operate: Check the fuses! Siemens Building Technologies CE1B2540en 74 319 0616 0 b 18.07.2008 30/32

The coupling mechanism between actuator and valve is disengaged: Engage it! If you cannot correct the problem, call in your heating engineer. Address and phone no. of your heating engineer: Siemens Building Technologies CE1B2540en 74 319 0616 0 b 18.07.2008 31/32

Setpoint of NORMAL heating Setpoint of REDUCED heating Setpoint of holiday period / protection mode Weekday (1 to 7), for entering the heating program to Entry of heating phases for the heating program Number of the holiday period (1 to 8) First day of the holiday period (day.month) Last day of the holiday period (day.month) Heating curve, flow temperature at +15 C Heating curve, flow temperature at 5 C NORMAL d.h.w. temperature setpoint Actual value of the d.h.w. temperature REDUCED d.h.w. temperature setpoint to Entries for switching program 2 to Settings the yearly clock (time, weekday, date and year) Display of faults (refer to page 27) Displays depend on controller and plant type. Siemens Building Technologies CE1B2540en 74 319 0616 0 b 18.07.2008 32/32