LTS Liquid-to-Steam Humidifier. Installation, Operation and Maintenance Manual

Similar documents
STS Steam-to-Steam Humidifier

CRUV. Electric Humidifier. Installation, Operation, and Maintenance Manual

Vaporstream Electric Humidifier. Installation, Operation, and Maintenance Manual

Vapormist Electric Humidifier. Installation, Operation and Maintenance Manual

Vaporstream Electric Humidifier. Installation, Operation and Maintenance Manual

READ AND SAVE THESE INSTRUCTIONS STS. Steam-to-Steam Humidifier. Installation, Operation, and Maintenance Manual

XT Series Electrode Steam Humidifier. Installation, Operation, and Maintenance Manual

READ AND SAVE THESE INSTRUCTIONS HUMIDI-TECH. Electric Humidifier. Installation, Operation, and Maintenance Manual

GTS Gas-to-Steam Humidifier

GTS Gas-to-Steam Humidifier

DRI-STEEM MODEL STS and STS- DI

VAPORSTREAM. Electric-to-Steam Humidifier. With Vapor-logic controller Web-enabled access Interoperability via Modbus or optional BACnet or LonTalk

DRI-STEEM Models and LTS-DI

READ AND SAVE THESE INSTRUCTIONS VAPORMIST. Electric-to-Steam Humidifier. Installation, Operation, and Maintenance Manual

DRI-STEEM Models LTS and LTS-DI

GTS. Installation, Operation, and Maintenance Manual WARNING. Gas-to-Steam Humidifier

Ultra-sorb Models LV and LH

Steam Humidifier Models 1150 and 1160

VAPORSTREAM Models VLC and VLDI

READ AND SAVE THESE INSTRUCTIONS XTR. Electrode Steam Humidifier. Installation, Operation, and Maintenance Manual

READ AND SAVE THESE INSTRUCTIONS XT SERIES. Electrode Steam Humidifiers. Installation, Operation, and Maintenance Manual

XTR Electrode Steam Humidifier. Installation, Operation, and Maintenance Manual

Ultra-sorb Steam Dispersion Panels

READ AND SAVE THESE INSTRUCTIONS XT SERIES. Electrode Steam Humidifiers. Installation, Operation, and Maintenance Manual

XT SERIES. Electrode Steam Humidifiers. Easy to maintain Adaptable Comprehensive control with Vapor-logic option

Steam Injection Humidifiers for use with steam boilers PR0DUCT CATALOG

Steam Injection Humidifiers for use with steam boilers. Installation, Operation, and Maintenance Manual

Steam Injection Pressurized Steam Humidifiers. Installation, Operation, and Maintenance Manual

DRI-STEEM Models GTS and GTS-DI

Steam Injection Pressurized Steam Humidifiers. Installation, Operation, and Maintenance Manual

Steam Injection Humidifiers for use with steam boilers PRODUCT CATALOG

ULTRA-SORB STEAM DISPERSION TUBE HUMIDIFIER PANEL

Installation Instructions. For the 18 Built-In Dishwasher and Front Color Panels

DRI-STEEM Models GTS. and GTS -DI

ES Series Electric Humidifier

Ultra-sorb Steam Dispersion Tube Humidifier Panel

XT SERIES. Electrode Steam Humidifiers. Easy to maintain Adaptable Comprehensive control with Vapor-logic option

Installation Instructions. Operation and Maintenance Manual

Quick Start Installation Guide

.4 Section Ductwork Low Pressure Metallic to 500 Pa..3 ANSI/ARI 640 Commercial and Industrial Humidifiers.

"SXDDR" Series Steam Heat Exchanger Humidifiers

READ AND SAVE THESE INSTRUCTIONS DRANE-KOOLER. Water Tempering Device. Installation, Operation, and Maintenance Manual

CUFFED FAST-PAC EXTERNAL MOUNT MULTIPLE TUBE ASSEMBLY

XTR Electrode Steam Humidifier. Installation, Operation, and Maintenance Manual

VAPORSTREAM. Electric-to-Steam Humidifier. With Vapor-logic controller Web-enabled access I nteroperability via Modbus or optional BACnet or LonTalk

Standard and CELDEK Evaporative Cooler Modules Installation, Operation, and Maintenance Manual

Installation Instructions. Operation and Maintenance Manual

Installation Instructions

Steam Injection. Humidification system

Standard and CELDEK Evaporative Cooler Modules Installation, Operation, and Maintenance Manual

DRI-STEEM Models GTS

OPERATING AND MAINTENANCE MANUAL FOR PLATE HEAT EXCHANGER INDIRECT FIRED WATER HEATER. Electric Heater Company Base Model "BWXP"

CELDEK Evaporative Cooler Module Installation, Operation, and Maintenance Manual. CELDEK Evaporative Cooler

L A signature series TA T N E RE O, A L L A T S IN

Installation Instructions for. OmniFount

"ER" Series Electric Humidifier

DRI-STEEM CRU SERIES ELECTRIC STEAM HUMIDIFIERS

CLe-series Dishwashers

THE SIX STEPS OF HUMIDIFICATION DESIGN

TABLE OF CONTENTS. NOTE: Read the entire instruction manual before starting the installation. TROUBLESHOOTING... 13

ULTRA-SORB. Installation, Operation, and Maintenance Manual MODEL. Steam Dispersion Panel. For pressurized steam applications

HE360 Humidifier Installation Kit

Installation Instructions Owner s Manual

Residential Steam Humidifier

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

installation and start-up instructions HUMIDIFIERS AND HUMIDISTAT

B.C.S. Shop Heaters 26, 30 & 36 (36 shown)

VT Series. Service Kit Manual CAUTION

HE120, HE160 Humidifier Installation Kit

"ESDDR" Series Electric Humidifier

Installation. 15 W. Undercounter/Freestanding Ice Machine FGIM515 / CFGIM515 FPIM515 / CFPIM515

Electrical cable Water supply tube Fittings for tube Coupler Teflon tape. Hole saw min. 2½" bit

ULTRA-SORB. Installation, Operation, and Maintenance Manual MODEL. Steam Dispersion Panels

Installation Instructions

Read and save these instructions! DRANE-KOOLER. Water tempering device Installation, operation and maintenance manual

Installation Instructions for. CattleMaster Series Fountains

Armstrong J Series Float, Thermostatic Steam Traps, Condensate Controllers & Liquid Drainers Installation and Maintenance Manual

DISHWASHER. Models DW2432 and DW2432SS. Installation Manual. Write Serial Number (on inner door of unit) here:

TIDALWAVE I/G POOL PUMP INSTRUCTION MANUAL

INSTALLATION INSTRUCTIONS FOR 6532 SERIES PACKAGE HEAT PUMP

FLANGED CORR/GUARD CORR/GUARD INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS UNDERCOUNTER DISHWASHERS

SPECIFICATION DIVISION 23 SECTION DESCRIPTION DIVISION 23 HEATING, VENTILATING AND AIR CONDITIONING (HVAC) SECTION STEAM HUMIDIFIERS

INSTALLATION INSTRUCTIONS

HE220, HE260 Humidifier Installation Kit

CROWN. Boiler Co. Santa-Fe Series. Hydronic Air Handlers INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS

SAFETY AND INSTALLATION MANUAL MODEL 8100

Steam Humidification Light Commercial Applications. Better technology means better business.

READ AND SAVE THESE INSTRUCTIONS SEISMIC. Cer tification Option. Installation Manual

RECOMMENDED LOCATION STEP BY STEP INSTALLATION. MODEL S 200P, 800BP and 97 POWER HUMIDIFIERS

INSTALLATION MANUAL. Manufactured by AQUA-AIR MANUFACTURING. (801) or (800) FAX (801)

User s Information Manual

Installation Instructions

WineZone Ceiling Mount Ductless Split 15

INSTALLATION, OPERATION AND MAINTENANCE MANUAL

INSTY-PAC EXTERNAL MOUNT MULTIPLE TUBE ASSEMBLY

INSTALLATION INSTRUCTIONS GEO PRIME TANK. (Patent Pending) GPC

Installation Electric Dryers Instructions 01

Vapor-logic 3 to Vapor-logic4

Installation Guide. 15 W. Undercounter/Freestanding Nugget Ice Machine U L. Viking Range, LLC. 111 Front Street

Transcription:

LTS Liquid-to-Steam Humidifier Installation, Operation and Maintenance Manual

Overview LTS models....3 Dimensions....4 Output capacities....6 Weights, connections and heated water properties.... 7 Installation Selecting a location....8 Clearance recommendations....9 Mounting Mounting methods....10 Trapeze hanger....11 Support legs....12 H-legs....12 Wall brackets....13 Outdoor Enclosure....14 Piping Overview....22 Drain....24 Alternative water seal and drain valve....25 Water supply....26 Wiring....28 Dispersion General instructions....31 Interconnecting piping requirements....32 Drip tee installation....34 Single and Multiple dispersion tubes....35 Rapid-sorb....39 Operation Start-up procedures....46 Start-up LW417 control....47 LW417 automatic drain and flush...48 LW417 variable skim times...49 LW417 end-of-season drain....49 LW417 Onboard diagnostics......................... 49 Maintenance Standard water models....50 DI water models....54 Troubleshooting LTS and LTS-DI....56 LW417....57 Outdoor Enclosure replacement parts....59 Replacement parts Humidifier tank....60 Control cabinet....62 Warranty....Back cover

Overview Figure 3-1: LTS standard water model Modulating valve Hot liquid return Hot liquid supply Figure 3-2: LTS DI/RO water model Modulating valve Hot liquid return Steam outlet Water seal Steam outlet Float valve Manual drain or optional motorized drain valve Air gap Open drain Heat exchanger Manual drain valve LTS-OM-8 Heat exchanger Standard water models (LTS) Standard water LTS humidifiers heat potable or softened fill water into steam for humidification. A conductivity probe controls water level, requiring water conductivity to be at least 100 μs/cm (2 grains/gallon) to operate properly. Therefore, standard water LTS models will not operate with demineralized water. For demineralized water operation (using deionized or reverse osmosis treated water), use LTS-DI model humidifiers (described below). Deionized water models (LTS-DI) LTS-DI humidifiers heat deionized (DI) or reverse osmosis (RO) fill water into steam for humidification. LTS-DI models control water levels using a float valve. Notes: not covered by your DRI-STEEM warranty. converted in the field for use with deionized/reverse osmosis (DI/RO) water. LTS-DI models can be converted in the field for use with potable or softened water. 212 F (100 C) water. provided by installer. Hot liquid supply Water seal Air gap Open drain LTS-OM-09

Overview Figure 4-1: Dimensions, LTS models 25C and 100C (one heat exchanger) Front view Side view K L H J A 5/16" dia. (M8) mounting holes D E F C B OM-931 OM-932 Table 4-1: LTS dimensions LTS model number Description 25C 100C inches mm inches mm A Overall height* 19.50 495 19.50 495 B Face width 14.75 375 19.25 490 C Face length 23.83 605 39.65 1007 D E F Distance from bottom to return outlet of heat exchanger Distance from bottom to supply inlet of heat exchanger Distance from side to heat exchanger 6.67 169 6.67 169 3.67 93 3.67 93 3.20 80 3.20 80 H Hot liquid return outlet 1.00 25 1.00 25 J Hot liquid supply inlet 1.00 25 1.00 25 K Distance from side to steam outlet 7.38 187 10.75 273 L Distance from front to steam outlet 2.50 64 2.75 70 Notes: * Add 23.5" (597 mm) to overall height when LTS is mounted on optional support legs. C = Copper heat exchanger with nickel coating

Overview Figure 5-1: Dimensions, LTS models 400C (two heat exchangers) Front view Side view K L H A J D E F G B C LTS-OM-03 Table 5-1: LTS dimensions LTS model Description 400C inches mm A Overall height* 19.50 495 B Face width 30.25 768 C Face length 55.15 1401 D Distance from bottom to return outlets of heat exchangers 6.67 169 E Distance from bottom to supply inlets of heat exchangers 3.67 93 F Distance from side to first heat exchanger 4.20 107 G Distance from side to second heat exchanger 16.50 419 H Hot liquid return outlet 1.00 25 J Hot liquid supply inlet 1.00 25 K Distance from side to steam outlet 15.13 384 L Distance from front to steam outlet 3.75 95 Notes: * Add 22.5" (572 mm) for total height with H-legs. C = Copper heat exchanger with nickel coating

Overview Table 6-1: LTS output capacities using hot water Output (lbs/hr and kg/h) LTS model number Flow Hot water supply temperature 240 F 116 C 250 F 121 C 260 F 127 C 280 F 138 C Pressure drop through heat exchanger gpm L/m lbs/hr kg/h lbs/hr kg/h lbs/hr kg/h lbs/hr kg/h psi kpa 8 30 25 11 45 20 65 29 100 45 1.5 10 10 38 32 15 53 24 74 34 116 53 1.8 12 25C 12 45 40 18 60 27 85 39 135 61 2.0 14 15 57 50 23 75 34 105 48 160 73 2.5 17 17 64 60 27 90 41 120 54 170 77 3.0 21 8 30 50 23 70 32 95 43 150 68 2.4 17 10 38 60 27 80 36 108 49 172 78 3.2 22 100C 12 45 70 32 90 41 120 54 195 88 4.0 28 15 57 85 39 110 50 140 64 230 104 6.0 41 17 64 95 43 125 57 155 70 250 113 8.0 55 20 76 150 68 205 93 265 120 420 191 5.0 34.5 400C* 24 91 190 86 250 113 310 141 470 213 6.0 41 30 114 240 109 300 136 350 159 510 231 8.0 55 34 129 260 118 320 145 380 172 540 245 10.0 69 Notes: * Two heat exchangers and two valves C = Copper heat exchanger with nickel coating The LTS is not ASME-certified.

Overview Table 7-1: LTS connection sizes Description Water makeup (fill) Drain Steam outlet Condensate return Hot liquid supply inlet and return outlet Connection size ¼" pipe thread (DN8), except in Europe where it is DN10 ¾" (DN20) for models 25C and 100C 1" (DN25) for models 400C Varies with capacity and dispersion type. To determine outlet size, see Dri-calc or the Maximum steam carrying capacity of interconnecting hose, tubing, or pipe table in the DRI-STEEM Design Guide. ¾" pipe thread (DN20) See dimensions tables. Table 7-2: LTS weights LTS model number Shipping weight Operating weight lbs kg lbs kg 25C 95 43 175 79 100C 105 48 350 158 400C 262 119 900 409 Table 7-3: Properties of water 212 F to 340 F (100 C to 171 C) * Temperature Pressure F C psia kpa 212 100 14.7 101.3 220 104 17.2 118.4 230 110 20.8 143.2 240 116 25.0 172.0 250 121 29.8 205.5 260 127 35.4 244.1 270 132 41.9 288.4 280 138 49.2 339.0 290 143 57.6 396.6 300 149 67.0 461.7 310 154 77.7 535.2 320 160 89.7 617.8 330 166 103.1 710.1 340 171 118.0 813.1 Note: * Valves supplied by DRI-STEEM have a maximum inlet water temperature of 280 F (138 C).

Installation Locating the humidifier When selecting a location for the humidifier, consider the following: primarily top, left side, and front (see clearance recommendations hose, tubing, or piping optional equipment condensate return piping such as power distribution transformers and high horsepower motors controlled by variable frequency drives.

Installation Figure 9-1: LTS clearance recommendations For recommended service and maintenance purposes, maintain the following clearances: Left side with control cabinet mounted: 36" (914 mm) Left side: 24" (610 mm) for access to cleanout plate Top: 18" (457 mm) Rear: 6" (152 mm) Angle iron support leg Front: 36" (914 mm) Right side: 6" (152 mm) Bottom: 24" (610 mm) LTS-OM-04

Installation Table 10-1: Mounting options by model Mounting method Trapeze H-legs Support legs Wall brackets LTS/LTS-DI models 25C, 100C 400C Standard Optional Standard Optional X X X X Mounting methods To ensure that the water level control system works properly, the tank must be mounted level side to side and front to back. water damage. Support legs, trapeze hanger, and wall brackets are not available for LTS/LTS-DI models 400. These models must use H-legs. The mounting methods described in this manual are the only options available to maintain compliance to the UL 998 standard; alternate mounting methods will compromise the humidifier s CE, ETL, and C-ETL approvals. IMPORTANT: Installation must comply with governing codes.

Installation Trapeze hanger (LTS/LTS-DI models 25 and 100 only) Secure threaded rod to an overhead structure that is strong enough to support the operating weight of the LTS/LTS-DI humidifier and field installed piping, plus the weight of the control cabinet if it is mounted on the humidifier. Adjust the mounting so that the tank sets level side to side and front to back. Verify level after the tank is filled and is at operating weight. Figure 11-1: Trapeze hanger (LTS models 25C and 100C only) Secure rods to overhead construction Overhead installation Do not install water piping and humidifiers above expensive apparatus or equipment. A broken water pipe, leaking valve gland, condensation or other water leaks can occur causing serious damage and costly repairs to the equipment below. If this type of installation cannot be avoided, install a drip tray constructed of galvanized sheet metal under the humidifier, valve, etc., to catch potential water drips (see Figure 11-1). Pipe the overflow from the LTS directly to a floor drain do not drain the LTS into the drip pan. Terminate the drip pan and the LTS overflow drains above an open floor drain. Provide 18" (457 mm) minimum clearance above cover 1¼" (DN32) minimum Drip pan recommended in overhead installations (by installer) to prevent possible water damage 3/8" (M10) threaded rod of length required Angle or channel sized to properly support humidifier Humidifier drain to appropriate building waste. Do not drain humidifier directly into drip pan. Install water seal as shown on Pages 24 and 25. 25% larger than humidifier DC-1453 IMPORTANT: Installation must comply with governing codes.

Installation Figure 12-1: Support legs (LTS models 25C and 100C only) Optional set of four legs and hardware OM-933 Figure 12-2: H-legs (required for LTS models 400C) Support legs (LTS/LTS-DI models 25 and 100 only) Use enclosed bolts, nuts, and washers to fasten legs to tank. Shim or adjust so the tank sets level side to side and front to back. Verify level after the tank is filled and is at operating weight. H-legs (LTS/LTS-DI models 400 only) While the LTS and LTS-DI tank is securely held in the air, be accomplished by having the bolts slightly loose as the tank is lowered to the floor. Then tighten them after the unit is place. Adjust the mounting so the tank sets level side to side and front to back. Verify the tank is level after it is filled and at operating weight. LTS-OM-05 IMPORTANT: Installation must comply with governing codes.

Installation Wall brackets (LTS/LTS-DI models 25 and 100 only) W minimum fasteners as described below. Mounting the LTS/LTS-DI on concrete or block walls: Position the wall brackets so that when fastened they will be flush with the inside of the front and back flanges of the LTS/ LTS-DI tank. humidifier. Shim or adjust so the tank sets level side to side and front to back. Verify level after the tank is filled and at operating weight. Mounting Model LTS/LTS-DI 25 on a wood stud wall: center. Position the wall brackets so that when fastened they will be flush with the inside of the front and back flanges of the LTS/ LTS-DI tank, and fasten to the horizontal timbers. Shim or adjust so the tank sets level side to side and front to back. Verify level after the tank is filled and at operating weight. Mounting Model LTS/LTS-DI 100 on a wood stud wall: center. Position the wall brackets so they are flush with the inside of the front and back flanges of the LTS/LTS-DI tank, and fasten to the horizontal timbers. Shim or adjust so the tank sets level side to side and front to back. Verify level after the tank is filled and at operating weight. Mounting the LTS/LTS-DI on metal stud walls: backside of the wall. Run a bolt with a washer through the face IMPORTANT: Installation must comply with governing codes. Figure 13-1: Wall brackets (LTS models 25C and 100C only) A DRI-STEEM optional wall brackets (two required) LTS model A B in. mm in. mm 25C 15.5 394 24 610 100C 21 533 30 762 B DC-1454

Figure 14-1: LTS Outdoor Enclosure with standard or optional steam outlet, elevation view Standard steam outlet K Ventilation fans Optional steam outlet LTS humidifier A Power block See Note 2 below 6.5" Knockouts, 4" (102 mm) on center Enclosure drain 1½" pipe thread (DN40) with male nipple L Pipe chase G DC-1476 Notes: 1. The Outdoor Enclosure has two available steam distribution configurations. The standard configuration has a steam outlet on the right side of the Outdoor Enclosure for connecting to steam dispersion unit piping. The optional internal steam distribution configuration routes steam within the Outdoor Enclosure and down through the enclosure pipe chase into a building. 2. There are four knockouts located on the right and left side of the enclosure. Knockout sizes are 1½" (hole dia. 50 mm) for LTS models 25-100, and 2" (hole dia. 63.5 mm) for LTS models 200-800. Run the electrical power into the enclosure at these knockouts. 3. All piping from the LTS unit to the steam outlet is stainless steel pipe. Depending on the application, interconnecting piping from the steam outlet to the dispersion assembly can be tubing, pipe or DRI-STEEM vapor hose. 4. The preferred location for the LTS hot liquid valve is inside the Outdoor Enclosure. If one of these valves must be located inside the building, it must be located within 6' (1.8 m) of the humidifier to reduce pressure drop. 5. See the dimensions table on the next page.

Figure 15-1: LTS Outdoor Enclosure, top view Valve access door: Optional steam outlet (exits enclosure through pipe chase) C J E Valve access door Pipe chase extending 1" (25 mm) above enclosure floor D H F Valve section heater Intake ventilation fan Enclosure drain Standard steam outlet (exits enclosure here) LTS humidifier Control panel Control panel heater Electrical and cleanout access door Intake ventilation fan B Table 15-1: LTS Outdoor Enclosure dimensions* LTS or LTS-DI model number Item Description 25-100 200-800 inches mm inches mm A Enclosure height 56.00 1422 66.00 1676 B Enclosure width 36.00 914 46.00 1168 C 4.50 114 4.50 114 Pipe chase position D 2.00 57 3.50 89 E 20.00 508 32.00 312 Pipe chase size F 8.00 203 10.00 254 G 6.00 152 8.50 216 H 18.63 473 22.00 559 Steam pipe position J 14.50 368 20.50 521 K 12.25 311 11.00 279 L Enclosure length 60.00 1524 78.00 1981 Note: * See drawings on this and the previous page.

Specifications using an Outdoor Enclosure with a heater package. using an Outdoor Enclosure without a heater package. Note: The Outdoor Enclosure is only available in the United States and Canada. Table 16-1: LTS Outdoor Enclosure weights LTS or LTS-DI model number Outdoor Enclosure shipping weight* Table 16-2: LTS Outdoor Enclosure connection sizes Outdoor Enclosure operating weight* lbs kg lbs kg LTS-25 600 272 680 308 LTS-100 625 284 850 386 LTS-400 1050 476 1700 771 Note: * Includes humidifier Description LTS or LTS-DI model number 25-100 200-800 Water makeup (fill) ¼ pipe thread (DN8) ¼ pipe thread (DN8) Drain ¾ (DN20) 1 (DN25) Condensate return ¾ pipe thread (DN20) ¾ pipe thread (DN20) Steam outlet See the LTS catalog

Figure 17-1: Outdoor enclosure installation detail Normally closed fill valve (by factory) Make-up water supply piping (by installer) (See Note 2) Open to drain Vent with check valve (by installer) Humidifier Disconnect (by installer); see Detail A 120 V supply 120 V from unit disconnect or other source (See Note 1) Roof decking Drain line, min. 1½" electric valve (See Note 3) 120 V N Detail A Normally closed (fail closed) min 3/8" electric valve (by installer) Optional water seal (P-trap) drain line, min. 1½" (DN40) (See Note 3) Normally open (fail open) min ½" electric valve (by installer) Disconnect box Domestic water, 80 psig (582 kpa) maximum Open drain (See Note 4) Open drain (See Note 4) Heated building interior To valves (by installer) (See Note 1) To LTS humidifier OM-7558 Piping notes: 1. Insulate supply water piping to avoid dripping from condensation. To ensure that water does not remain in the fill line and freeze if there is a loss of power, DRI-STEEM recommends field installing additional valves upstream of the fill valve in a conditioned space. Power these valves on the same circuit as the LTS; if the power goes off, water drains out of the fill line to prevent freezing (see Figure 17-1). Supply power for these valves from the same circuit that supplies the LTS. 2. Ensure that water lines are protected from freezing conditions. thermostat with a remote sensor on the fill line to cut power to the LTS and safety valves to stop fill water to the LTS and drain the fill piping when the temperature is below freezing. 3. DRI-STEEM recommends copper or iron drain piping for outdoor enclosures. On a loss of power the tank water will drain, but not be cooled by the Drane-kooler because of the field supplied safety shut-off valves. If it is critical to keep the Drane-kooler functional in the case of a power loss, disconnect the Drane-kooler and relocate it down inside the conditioned space of the building. Pipe the supply water for the Drane-kooler before the safety shut-off valves. 4. If copper or iron piping is used for both the fill and drain piping, these drains may be tied together. Locate 1" air gap only in spaces with adequate temperature and air movement to absorb flash steam; otherwise, condensation may form on nearby surfaces. Refer to governing codes for drain pipe size and maximum discharge water temperature.

Figure 18-1: Outdoor Enclosure mounting options Flush Curb 14" (356 mm) Legs (LTS 25-100) 14" (356 mm) DC-1110 OM-1095 OM-1096 Outdoor Enclosure mounting enough clearance for opening the access doors. support the unit and that support structure dimensions coincide with unit dimensions. fan outlets, gasoline storage, or other contaminants that could potentially cause dangerous situations. The use and storage of gasoline or other flammable vapors and liquids in open containers in the vicinity of this appliance is hazardous. intake of snow or splashed rain. Locate the Outdoor Enclosure so that prevailing winds do not blow into the air intakes. to installing the unit. may have become loosened. Check that all nuts are tightened. enclosure. It is recommended that the electrical power is run into the enclosure at these knockouts. In both cases it must be lifted from the bottom base using a method that holds it level, and keeps it from tipping, falling, or twisting. If the unit is severely twisted during handling, permanent damage may occur. It is the installer s responsibility to verify the handling equipment s capability to safely handle the unit. across the entire unit could cause tipping resulting in unsafe conditions or damage to the unit. base frame and/or special lifting lug hooks installed on the unit. All lifting operations must be accomplished with a load spreader of sufficient width to ensure that the lifting cables clear the side of the unit. If this type of spreader is not available, wood strips should be inserted between the cables and unit where necessary. All four lifting points must be used and will be marked lift here on the unit.

configurations. The standard configuration has a steam outlet on one side of the Outdoor Enclosure for connecting to steam dispersion unit piping. The optional internal steam distribution configuration routes steam within the Outdoor Enclosure and down through the pipe chase into a building. See drawings on Page 15. pipe chase is provided to maintain proper pressure within the enclosure in the event that this opening is not utilized. However, it is recommended that this pipe chase be used for both the supply water piping and drain piping, in which case the pipe proper enclosure pressure. cannot be used, the supply water and drain piping can be run through the knockouts, although preferably on the opposite side from the utility connections. controlled heaters are provided: one strip heater is located in the control cabinet section, and one strip heater is located in the front section to keep the enclosure at a constant minimum temperature. drain from the enclosure through this drain. Outdoor Enclosure. The keypad must not come in contact with the strip heaters or block the intake ventilation hood. located in a severe climate, a remote mount keypad should are available as an option for this mounting configuration transporting to the roof. Curbs are manufactured of 16-gauge galvanized steel and shipped with all hardware for bolt-together assembly. All holes are matched before leaving the factory. Curb curb gasket with adhesive on one side is supplied with hardware. The gasket must be installed between the top of the curb and the base surface of the Outdoor Enclosure to prevent moisture from leaking into the building from either driving rain or melting snow. An installation drawing is also included. Important note about Outdoor Enclosure installation hot liquid valve is inside the Outdoor Enclosure. If one of these valves must be located inside the building, it must be located within 6' (1.8 m) of the humidifier to reduce pressure drop. Figure 19-1: Outdoor Enclosure clearances Left side: 36" (914 mm) Front: 36" (914 mm) Top: Keep open for access Back: 12" (305 mm) OM-955 Right side: 24" (610 mm)

Note: If your LTS humidifier uses a LW417 controller, the aquastat option must be purchased to provide freeze protection. are provided with all the necessary hardware for elevating stand legs should be securely mounted to the grade by the installing contractor. To prevent the outdoor environment from penetrating the enclosure, close-off provisions must be made between the stand legs. steel pipe. Depending on the application, interconnecting piping from the steam outlet to the dispersion assembly can be tubing, pipe or DRI-STEEM vapor hose. Enclosure is recommended. Insulated or heat taping of water piping is recommended. Figure 20-1: Typical rooftop installation overview Flue Humidifier in Outdoor Enclosure Roof surface Electrical connections Steam piping Remote Vapor-logic3 keypad Drain piping Water piping Curb DC-1210M

Operation When power is applied to the Outdoor Enclosure: humidifier is not allowed to operate unless the temperature The strip heaters will power down when the temperature inside humidifier will allow the humidifier to continue operating until to cool the electronic components. greater, a high limit switch powers down the humidifier. The ventilation fans will continue to run and, once the enclosure automatically resume normal operation. Maintenance Outdoor Enclosure electrical service door. annually. CAUTION: Always shut off electrical service disconnect prior to working on the humidifier.

Installation Figure 22-1: Field piping overview for LTS models 25C and 100C (models with one heat exchanger) ¾" pipe thread (DN20) dispersion unit condensate return inlet Water supply shut-off valve, by installer Water supply line; water pressure range 25 psi to 80 psi (172 kpa to 582 kpa); water conductivity minimum 2 grains/gallon (100 μs/cm) Shock arrester recommended to reduce water hammer, by installer Steam vapor outlet Install level Optional condensate return piping from dispersion unit Unions, by installer Air vent tube Modulating valve Install level Manual or electric drain valve LTS-OM-01 6" (152 mm) minimum H2: Air vent height must be equal to or greater than H2 (see table below) Hot liquid return Hot liquid supply ¾" (DN20) minimum condensate drain piping rated for 212 F (100 C) See valve detail drawing on Page 23 H1 Pitch 1/8"/ft (1%) ¾" (DN20) minimum drain, skim and overflow piping rated for 212 F (100 C) Overflow line Water seal line If run is over 10' (3 m), increase pipe to 1¼" (DN32) Water seal line MUST be below drain valve to ensure humidifier drains correctly 1" (25 mm) air gap Open floor drain. Refer to governing codes for drain pipe size and maximum temperature requirements Table 22-1: Heights required to overcome humidifier internal pressure (H1, H2) Unit output Water seal height (H1) Air vent height (H2) lbs/hr kg/h inches mm inches mm 138 62 12 305 27 686 139 183 63 83 15 381 30 762 > 183 > 83 18 457 33 838 Figure 22-1 notes: recommended for constant system flow. If variable system flow is desired, a two-way valve located in the hot liquid return line is recommended. rising into the humidifier. skim/overflow port, eliminating the possibility of backflow or required; however, governing codes prevail. of entrained air. DRI-STEEM warranty.

Installation Figure 23-1: Field piping overview for LTS-DI 400C (DI model with two heat exchangers) Steam vapor outlet ¾" pipe thread (DN20) dispersion unit condensate return inlet Water supply line; water pressure range 25 psi to 80 psi (172 kpa to 582 kpa); first 3' (1 m) is recommended to be stainless steel tubing with a 2" (50 mm) water seal or loop in the supply line to isolate steam during DI/RO water system maintenance Install level Optional condensate return piping from dispersion unit Strainer, by installer Air vent tube Modulating valve Hot liquid return Install level Hot liquid supply Manual or electric drain valve 6" (152 mm) minimum Air vent height must be equal to or greater than H2 (see table on Page 22) ¾" (DN20) minimum condensate drain piping rated for 212 F (100 C) See valve detail below Unions, by installer H1 Overflow line Pitch 1/8"/ft (1%) 1" (DN25) minimum drain and overflow piping rated for 212 F (100 C) Water seal line If run is over 10' (3 m), increase pipe to 1¼" (DN32) Water seal line MUST be below drain valve to ensure that humidifier drains correctly 1" (25 mm) air gap Open floor drain. Refer to governing codes for drain pipe size and maximum temperature requirements LTS-OM-13 Figure 23-1 notes: for constant system flow. If variable system flow is desired, a twoway valve located in the hot liquid return line is recommended. rising into the humidifier. overflow port, eliminating the possibility of backflow or siphoning however, governing codes prevail. of entrained air. DRI-STEEM warranty. standard water system or for piping a system with one heat Figure 23-2: Three-way valve detail AB B Hot liquid return From heat exchanger To heat exchanger Hot liquid supply When the three-way valve is retracted (in the up position), flow is from B to AB, bypassing the heat exchanger. LTS-OM-21 A

Installation Figure 24-1: Drane-kooler water tempering device Drain piping The drain line piped from the humidifier must be run to an approved sanitary waste or suitable drain. If nonmetallic pipe continuous operating temperature. DRI-STEEM's Drane-kooler, shown mounted to a typical humidifier, tempers discharged water temperature. For other Drane-kooler mounting options or for more information, contact DRI-STEEM or view the Drane-kooler product data sheet in the literature section at www.dristeem.com OM-951a and drain water dumped into the floor drain will cause flash steam. This steam will rise and saturate electrical components, adversely affecting component life and performance. skim water from the humidifier be tempered before it is discharged into the building drain piping. The Drane-kooler option will To allow normal operation and prevent steam from escaping through the drain line, the installer must provide a water seal of a sufficient height to contain the pressure developed in the humidifier system. See the table on Page 22 for water seal heights. Drain piping after the water seal must be pitched a minimum of pitch. water to be lifted by a pump, DRI-STEEM offers a condensate pump option. A check valve is required on the discharge of the pump. Electrical power for the pump is independent of the humidifier. Plug the pump into a wall outlet; an integral float switch turns the pump on and off.

Installation Drain piping (continued) LTS humidifier should place a union directly after the factory drain fitting, provide mount the humidifier closer to the floor, use the Alternate water seal and drain valve piping diagram shown on this page. The installer needs to rework the factory piping that connects the drain valve to the skim/overflow fitting, cut out the elbow, and repipe per the diagram. The LTS-DI humidifier has a pipe thread fitting on the drain valve and on the overflow fitting. Prior to dumping into a drain, the installer needs to connect the drain and overflow, provide a water the humidifier closer to the floor, use the Alternate water seal and drain valve piping diagram shown on this page. Alternate water seal and drain valve piping Typically, the water seal height dictates the minimum dimension the bottom of the humidifier can be above the floor. The alternate water seal reduces the water seal piping below the humidifier up to Figure 25-1: Alternate water seal and drain valve piping Skimmer outlet Top of water seal must be below skimmer outlet H1 (see table on Page 22) Drain connection Air gap Open drain OM-945 Notes: drain connection, such as when the humidifier is mounted near the floor.

Installation Water supply piping general instructions air gap to prevent back siphoning into a potable water system. However, some governing codes may require additional protection such as a vacuum breaker or backflow preventer. The supply water pressure range must be 25 psi to 80 psi (172 kpa LTS model (standard water) water supply piping The water supply assembly includes a strainer, needle valve, and fill Since the primary component of the water supply assembly is a solenoid valve, there may be noise issues that surface during a fill cycle. During a fill cycle, the supply water drops the water temperature in the tank and may collapse the steam, which can cause a low rolling sound. To diminish this, adjust the needle valve to decrease the water fill rate and/or use hot supply water. In cases where water hammer occurs when the fill solenoid closes, a shock arrester is recommended. Reducing the supply water may diminish the noise, but installing a shock arrester is the best solution. The minimum water conductivity for the LTS standard water

Installation Water supply piping (continued) LTS-DI model water supply piping drain option, a solenoid valve is added on the inlet of the float valve. The end-of-season feature shuts off the fill water supply and drains the tank when there is no demand for humidity for 72 hours. (This length of time is a default setting and is user-adjustable if your system has a Vapor-logic3 controller. See the Vapor-logic3 Installation and Operation Manual Note: Damage caused by chloride corrosion is not covered by your DRI-STEEM warranty. When using nonmetallic tubing for supply water, it must be rated of noninsulated stainless steel pipe directly off the humidifier prior to connecting to the nonmetallic tubing. When using nonmetallic water seal/loop in the supply line to isolate steam during DI/RO water system maintenance. DRI-STEEM recommends installing a strainer in the water supply line to prevent clogging of the float valve orifice. A strainer is highly recommended when the humidifier has the end-of-season drain option. The strainer will prevent particulate from collecting at the solenoid valve seat. If the LTS-DI humidifier is supplied with tap water, the float valve assembly will become clogged and the humidifier will operate without water.

Installation CAUTION: Only qualified electrical personnel should perform installation procedures. Where to find wiring diagrams interconnection requirements. devices: airflow proving switches, high limits, transmitters, or humidistats. All wiring must be in accordance with all governing codes and with LTS wiring diagrams. CAUTION: When drilling holes in the control cabinet, make sure the unit is powered off, protect all internal components from debris, and vacuum out the control cabinet when finished. Failure to comply with this directive can damage sensitive electronic components and void your DRI-STEEM warranty. Electrical installation Wiring and branch circuit protection is provided by the installer LTS humidifiers have a 120-volt, single phase electrical supply and capacity requirements against those listed on the name plate. Wiring requirements The length of wire from the control cabinet to the humidifier must the controller is the LW417, the length of wire from the control The top portion of the control cabinet contains control circuitry; the bottom portion of the control cabinet contains power circuitry. Place conduit connection holes in the control cabinet so that the control and power wire routing is limited to their respective sides of the control cabinet. Control wiring and power wiring must be run in dedicated or separated earthed metal conduit, cable trays, or trunking. The control cabinet should be mounted in a location convenient for door. The installer is responsible for making electrical connections at the power terminals.

Installation Control wiring wiring should minimize electrical noise problems: wiring must be minimum 18-gauge (1 mm 2 grounding. (1 mm 2 can be wired using minimum 18-gauge (1 mm 2 grounding. transmitter end. be minimum 18-gauge stranded wire run in a separate conduit 2 18-gauge (1 mm 2 wire with a bare drain wire for grounding. CAUTION: When drilling holes in the control cabinet, make sure the unit is powered off, protect all internal components from debris, and vacuum out the control cabinet when finished. Failure to comply with this directive can damage sensitive electronic components and void your DRI-STEEM warranty. IMPORTANT: Do not use shielded (screened) cable for water level control devices.

Installation IMPORTANT: Failure to follow these wiring procedures can result in erratic operation or failure. This product has been tested at the factory for proper operation. Product failures resulting from faulty handling, incorrect wiring, or shorting of wires together on external components are not covered under your DRI-STEEM warranty. Review information and diagrams before proceeding. Grounding requirements The approved earth ground must be made with solid metal-tometal connections and must be a good conductor of radio Ground wire should be the same AWG (mm 2 When the control cabinet is mounted remotely from the humidifier, a ground wire is necessary from the machine ground lug on the humidifier to the machine ground lug in the control cabinet. The bonding machine ground wire should be no less than 14-gauge AWG (mm 2 requirements. Figure 30-1: Humidifiers with Vapor-logic3 control Brown or black, top probe rod (full water condition) Orange or white, middle probe rod (refill water condition) Violet or red, bottom probe rod (low water condition on standard water models) OM-VL3-11 Figure 30-2: Humidifiers with LW417 control To humidifier probe head on tank Brown, top probe rod (full water condition) Orange, middle probe rod (refill water condition) Violet, bottom probe rod (low water condition ) Probe wiring V O BR OM-829a

Installation Selecting the dispersion assembly location the water vapor being discharged is carried off with the airstream and does not cause condensation or dripping from the duct. air can most readily absorb the moisture being added without causing condensation at or after the unit. This normally will be after the heating coil or where the air temperature is highest. high efficiency filter. The filter can remove the visible moisture and become waterlogged. impinge on a metal surface. impinge on fire or smoke detection devices. duct. The unit can put more moisture in one branch than the other. DRI-STEEM's Humidification System Design Guide available at www.dristeem.com. Note: Most DRI-STEEM literature is available for downloading and printing from our website, www.dristeem.com Where to find specific installation instructions by product about interconnecting piping and drip tee installation Ultra-sorb LV and LH Installation, Operation and Maintenance manual. instructions, see Pages 35-38.

Installation IMPORTANT: Failure to follow the recommendations in this section can result in excessive back pressures on the humidifier. This will result in unacceptable humidification system performance such as leaking gaskets, blown water seals, erratic water level control, and spitting condensate from the dispersion tube(s). Connecting humidifier to dispersion assembly with vapor hose that can affect humidifier system performance adversely. Using hose from alternative manufacturers increases the possibility of discharge at the dispersion assembly. aging, causing the vapor hose to become hard and susceptible to failure due to cracks. smaller than the humidifier steam outlet. use the recommend installation as shown on Page 34. chart on Page 35. Connecting humidifier to dispersion assembly with tubing or pipe adapters convert a tubing outlet on the humidifier to threaded pipe, allowing a pipe connection. apart. heavy wall pipe.

Installation Connecting humidifier to dispersion assembly with tubing or pipe (continued) condensation. lubricants used to thread the pipe. This will minimize the possibility of tank foaming. Denatured alcohol or mineral spirits work best for removing lubricant. use the recommend installation as shown on Page 34. Table 33-1: Maximum steam carrying capacity and length of interconnecting vapor hose, tubing, and pipe* Vapor hose Copper or stainless steel tubing and Schedule 40 steel pipe Hose I.D. Maximum capacity Maximum length** Tube or pipe size*** Maximum capacity Maximum developed length inches DN lbs/hr kg/h ft m inches DN lbs/hr kg/h ft m 1½ 40 150 68 10 3 1½ 40 150 68 20 6 2 50 250 113 10 3 2 50 220 100 30 9 3 80 450 204 80 24 4 100 750 340 100 30 5 125 1400 635 100 30 6 150 2300 1043 100 30 * Based on total maximum pressure drop in hose, tubing, or pipe of 5" wc (1244 Pa) ** Maximum recommended length for vapor hose is 10' (3 m). Longer distances can cause kinking or low spots. *** To minimize loss of capacity and efficiency, insulate tubing and pipe. Developed length equals measured length plus 50% of measured length to account for pipe fittings. Requires flange connection When using vapor hose, use DRI-STEEM vapor hose for best results. Field-supplied hose may have shorter life and may cause foaming in the evaporating chamber resulting in condensate discharge at the dispersion assembly. Do not use vapor hose for outdoor applications.

Installation Install a drip tee as show below when the humidifier is mounted higher than the dispersion assembly, when interconnecting hose or piping needs to go over an obstruction, or when interconnecting piping runs are long. IMPORTANT: Vapor hose must be supported to prevent sagging or low spots. Figure 34-1: Drip tee installation (piping over an obstruction) 90 long sweep or two 45 elbows Pitch Obstruction Insulate tubing and hard pipe to reduce steam loss LTS humidifier To dispersion assembly 6" (150 mm) minimum 8" (200 mm) minimum Tubing or pipe drip tee, by installer ¾" (DN20) Notes: 1" (25 mm) air gap Funnel or floor drain DC-1470

Installation Installation installing Single and Multiple dispersion tube assemblies tube applications Dispersion tube mounting point up. Condensate drain piping IMPORTANT: Failure to follow the recommendations in this section can result in excessive back pressures on the humidifier. This will result in unacceptable humidification system performance such as leaking gaskets, blown water seals, erratic water level control, and spitting condensate from the dispersion tube(s). Table 35-1: Hose kit sizing by capacity Maximum humidifier capacity Hose kit lbs/hr kg/h 56.8 25.8 1½" (DN40) with drain 85.2 38.6 2" (DN50) with drain > 85.2 >38.6 These models require Multiple dispersion tube assemblies and cannot use a hose kit. Table 35-2: Pitch of dispersion tube(s) and interconnecting piping for Single or Multiple dispersion tubes evaporative units* Condensate drain Type of interconnecting piping Diameter of dispersion tube and interconnecting piping Pitch of interconnecting piping Pitch of dispersion tube(s) Pitch of condensate drain Without drain Vapor hose Tubing or pipe 1½" (DN40) 2"/ft (15%) toward 2" (DN50) humidifier 1½" (DN40) 1/8"/ft (1%) toward humidifier 2" (DN50) 2"/ft (15%) toward humidifier No drain With drain Vapor hose Tubing or pipe 1½" (DN40) 2"/ft (15%) toward 2" (DN50) humidifier 1½" (DN40) ½"/ft (5%) toward humidifier ¼"/ft (2%) 2" (DN50) toward humidifier Note: When piping over an obstruction, see the drip tee installation illustration on the previous page. 1/8"/ft (1%) toward condensate drain ¼"/ft (2%) toward floor drain or toward humidifier if humidifier is below dispersion unit

Installation Figure 36-1: Single dispersion tube with condensate wasted to floor drain Vapor hose, tubing or pipe Duct Maximum capacity of dispersion tube: (25.8 kg/h) (38.6 kg/h) 90 long sweep or two 45 elbows Pitch* 3/8" (M10) mounting nut LTS humidifier 6" (152 mm) recommended ¼" (DN8) pipe thread Pitch tube toward drain 1/8"/ft (1%) Water seal 5" (127 mm) 1" (25 mm) air gap Notes: * Pitch vapor hose, tubing or pipe toward humidifier: 2"/ft (15%) when using vapor hose ½"/ft (5%) when using 1½" tubing or pipe ¼"/ft (2%) when using 2" tubing or pipe Condensate drain tube, by installer, minimum ¾" (DN20); must be suitable for 212 F (100 C) water Open drain. Refer to governing codes for drain pipe size and maximum temperature requirements. ½" (DN15) O.D. condensate drain tube; pitch ¼"/ft (2%) DC-1473a Figure 36-2: Dispersion tube escutcheon plates Figure 36-3: Single dispersion tube with condensate drain Dispersion tube plate 2.5" (64 mm) 3.25" (83 mm) Condensate drain plate 3.25" (83 mm) Thermal-resin tubelets (steam orifice inserts) Mounting bracket 1.5" (38 mm) 3.25" (83 mm) 3.25" (83 mm) OM-351c ¼" (DN8) pipe thread end Movable escutcheon plate. Plate can be mounted within limits of 2.5" (64 mm). ½" O.D. (DN15) copper tubing condensate drain OM-351b

Installation Figure 37-1: Single dispersion tube with condensate returned to humidifier Vapor hose, tubing, or pipe Duct Single dispersion tube with condensate drain 90% long sweep or two 45 elbows Pitch* Mounting nut, 3/8" (M10) ½" (13 mm) air vent 6" (152 mm) minimum 6" (152 mm) minimum ¼" pipe thread (DN8) 5" (127 mm) water seal Pitch tube toward drain 1/8"/ft (1%) ½" (DN15) O.D. condensate drain tube, pitch ¼"/ft (2%) LTS humidifier ¾" (DN20) condensate return connection (on face plate) Notes: * Pitch vapor hose, tubing or pipe toward humidifier: 2"/ft (15%) when using vapor hose ½"/ft (5%) when using 1½" tubing or pipe ¼"/ft (2%) when using 2" tubing or pipe H2 (see table, Page 22) Condensate drain tube, by installer, ¾" DN20 minimum. Return line piping material must be suitable for 212 F (100 C) water. DC-1473b

Installation Figure 38-1: Multiple dispersion tube with condensate wasted to floor Duct Multiple dispersion tube Vapor hose, tubing, or pipe 90 long sweep or two 45 elbows LTS humidifier Pitch* Water seal 5" (127 mm) 1" (25 mm) air gap 6" (152 mm) ¼" (DN8) pipe thread Open drain Mounting nut, 3/8" (M10) Pitch tube toward drain 1/8"/ft (1%) ½" (DN15) O.D. condensate drain tube, pitch ¼"/ft (2%) Condensate drain tube provided by installer, ¾" (DN20) minimum Notes: * Pitch vapor hose, tubing or pipe toward humidifier: 2"/ft (15%) when using vapor hose ½"/ft (5%) when using 1½" tubing or pipe ¼"/ft (2%) when using 2" tubing or pipe DC-1048a

Installation General Rapid-sorb installation instructions this manual. of all Rapid-sorb components with packing list. Report any shortages to DRI-STEEM factory immediately. provides necessary access in and around the ductwork or air handler. duct, or is installed across the face of a coil in an air handler. handler wall. duct or air handler wall. an additional hole in the center of the L-bracket. duct or air handler, refer to ALL pitch requirements for the The size, quantity, and location of penetrations are determined by the specific dimensions and configuration of the Rapid-sorb assembly you received. Note: The hardware for mounting the L-bracket to the duct or air handler wall and the hardware for the header support bracket is not provided. with Rapid-sorb header either inside or outside the duct. Contact your representative/distributor or DRI-STEEM for installation instructions for air handler or vertical airflow applications. IMPORTANT: Failure to follow the recommendations in this section can result in excessive back pressures on the humidifier. This will result in unacceptable humidification system performance such as leaking gaskets, blown water seals, erratic water level control, and spitting condensate from the dispersion tube(s).

Installation IMPORTANT: Failure to follow the recommendations in this section can result in excessive back pressures on the humidifier. This will result in unacceptable humidification system performance such as leaking gaskets, blown water seals, erratic water level control, and spitting condensate from the dispersion tube(s). Rapid-sorb pitch requirements airflow duct, consider the following pitch issues: accomplished in the length of the hose cuffs used to connect the tubes to the header. pitch requirements. Table 40-1: Pitch of interconnecting piping, dispersion tubes, and headers for Rapid-sorb evaporative dispersion units Airflow Type of interconnecting piping Diameter of interconnecting piping Pitch of interconnecting piping Pitch of dispersion tubes Pitch of header Horizontal Vapor hose Tubing or pipe 1½" (DN40), 2" (DN50) 1½" (DN40), 2" (DN50), 3" (DN80), 4" (DN100), 5" (DN125), 6" (DN150) 2"/ft (15%) toward Rapid-sorb 1/8"/ft (1%) toward Rapid-sorb Vertically plumb 1/8"/ft (1%) toward condensate drain Vertical Vapor hose Tubing or pipe 1½" (DN40), 2" (DN50) 1½" (DN40), 2" (DN50), 3" (DN80), 4" (DN100), 5" (DN125), 6" (DN150) 2"/ft (15%) toward Rapid-sorb 1/8"/ft (1%) toward Rapid-sorb 2"/ft toward header 1/8"/ft (1%) toward condensate drain

Installation Figure 41-1: Rapid-sorb installed in a horizontal airflow with header outside the duct L-bracket Dispersion tube Airflow Tubelets (steam orifices) Duct 90 long sweep or two 45 elbows Slip coupling or hose cuff Pitch: 1/8"/ft (1%) Support bracket Vapor hose, tubing, or piping Header ¾" pipe thread (DN20) condensate drain ¾" (DN20) copper 1" (25 mm) air gap 5" (127 mm) 6" (152 mm) Open drain LTS humidifier DC-1471 Assembly and installation instructions for a Rapid-sorb installed with header outside the duct (horizontal airflow) 1. Locate and cut the holes in the ductwork for the dispersion tubes. Use the L-bracket as a template to locate the holes on the duct floor. 2. Temporarily, loosely suspend or support the header below the tube length dictates where the header should be suspended or supported temporarily. 3. Mount the dispersion tubes to the header with the provided connector, either a slip coupling or a hose cuff. take care not to shear the O-rings. the O-ring is resting on the face of the tubing. lubricant. 4. Position the flange of the L-bracket so it is upstream of the tubes

Installation Note: See Page 45 for steam supply and condensate drain line connection instructions. Assembly and installation instructions for a Rapid-sorb installed with header outside the duct (continued) L-bracket to the end of the dispersion tubes with the provided bolt, lock washer, and flat washer. 5. Before tightening the L-bracket bolts to the dispersion tubes follow these instructions: The dispersion tube will rotate in the slip coupling. Verify that the dispersion tube orifices are directed perpendicular to the airflow. The dispersion tube and slip coupling must be fully engaged on to the header stub for the O-rings to provide a seal. Before securing the hose cuff in place with the hose clamps on the dispersion tube and the header stub, verify that the dispersion tube orifices are directed perpendicular to the airflow. 6. Slide the assembly up until the L-bracket aligns with the mounting holes in the duct. The header pitch is duplicated in the L-bracket. The dispersion tube and slip coupling must be fully engaged on to the header stub for the O-rings to provide a seal. The high end of the L-bracket can be fastened tight to the duct or air handler. On the low end of the L-bracket, the fastener must be long enough to compensate for the pitch, and a nut should be provided and secured on both sides of the L-bracket and the duct or air handler for stability. cuffs to compensate for the pitch of the header. Before securing the hose cuff in place with the hose clamps on the dispersion tube and the header stub, verify that the 7. Permanently secure both ends of the header and verify that the 8. Verify that all fasteners are secure: 9. Secure and seal the dispersion tube escutcheon plate and condensate drain tube escutcheon plate around the respective tubes, if applicable.

Installation Figure 43-1: Rapid-sorb installed in a horizontal airflow with header inside the duct L-bracket Dispersion tube Tubelets (steam orifices) Airflow 90 long sweep or two 45 elbows Slip coupling or hose cuff Pitch: 1/8"/ft (1%) Duct Support bracket Vapor hose, tubing, or piping Header ¾" pipe thread (DN20) condensate drain ¾" (DN20) copper 5" (127 mm) 6" (152 mm) 1" (25 mm) air gap Open drain LTS humidifier DC-1472 Assembly and installation instructions for a Rapid-sorb installed with header inside the duct (horizontal airflow) 1. Locate and cut the holes in ductwork or air handler for steam header penetration, condensate drain piping, and header support support bracket when you drill the hole for the header support bracket fastener. 2. Loosely fasten the header in place. the duct. piping requirements, the header can be set on the floor of the air handler, assembled in the vertical position, and then raised and mounted in place. 4. Mount the dispersion tubes on the header with the slip couplings or hose cuffs. tubes, take care not to shear the O-rings. the O-ring is resting on the face of the tubing.

Installation Assembly and installation instructions for a Rapid-sorb installed with header inside the duct (continued) lubricant. 5. Allow the dispersion tubes to rest against the bottom of the duct. 6. Position the flange of the L-bracket so it is upstream of the tubes to the end of the dispersion tubes with the provided bolt, lock washer, and flat washer. 7. Rotate the assembly up until the L-bracket aligns with the mounting holes in the duct or air handler. The header pitch is duplicated in the L-bracket. The dispersion tube and slip coupling must be fully engaged on to the header stub for the O-rings to provide a seal. The high end of the L-bracket can be fastened tight to the duct or air handler. On the low end of the L-bracket, the fastener must be long enough to compensate for the pitch, and a nut should be provided and secured on both sides of the L-bracket and the duct or air handler for stability. use the hose cuffs to compensate for the pitch of the header. Before securing the hose cuff in place, with the hose clamps on the dispersion tube and the header stub, verify that the dispersion tube orifices are directed perpendicular to the airflow. 8. Verify that all fasteners are secure: 9. Secure and seal the header escutcheon plate around the header. 10. See Page 45 for steam supply and condensate drain line connection instructions.