A. Section includes Factory Packaged, Modular units, providing cooling and heating for air distribution systems.

Similar documents
AIR HANDLING UNITS Vibration Isolation Air Filtration Equipment Ductwork.

Brown University Revised August 3, 2012 Facilities Design & Construction Standards SECTION AIR HANDLING UNITS

SECTION AIR HANDLING UNIT

1.1 This section applies to air handling units for HVAC Systems.

UNIVERSITY OF MISSOURI Central Station Air-Handling Units March

SPECIFICATION DELETED SECTION CENTRIFUGAL HVAC FANS

SECTION SPLIT-SYSTEM AIR-CONDITIONERS

Guide Spec Summary. Option List. Date: 05/21/2001. EarthWise Modular Climate Changer Full Spec. Prepared by: Phone Number: Prepared for:

SECTION AIR COILS

DARTMOUTH COLLEGE DESIGN January 3, 2012 & CONSTRUCTION GUIDELINES

Construction Standards Page

A. American National Standards Institute (ANSI) : Establishes requirements applicable to certifying direct gas-fired heaters.

Complete HVAC Capability. Central Station Air Handling Units. Publication No. WT-CSX-0616A

A. This Section includes air-handling units with coils for indoor installations.

Construction Standards Page Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA

A. Codes and Standards that are Standard at the University:

SECTION PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS - CUSTOM

SECTION AIR-COOLED SPLIT SYSTEM AIR CONDITIONING UNITS

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS

SECTION AIR HANDLING UNITS WITH COILS. 1. Central Station Air Handling Units. 1. Section Basic Mechanical Requirements.

SECTION PACKAGED COMPRESSOR AND CONDENSER UNITS

UNIVERSITY OF ROCHESTER DESIGN STANDARDS NOVEMBER 1, 2013

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number:

SECTION SPLIT-SYSTEM AIR-CONDITIONERS

A. Air Handling Units shall be designed to the specific requirements of the application: Recirculation or 100% Makeup.

KINGS COUNTY JAIL EXPANSION PHASE III COUNTY OF KINGS SECTION

AIR HANDLER SPECIFICATION

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION EXHAUST FANS

University of Delaware

A. Section includes split-system air-conditioning units consisting of separate evaporator-fan and compressor-condenser components.

Modular Supply Make-Up Air Unit

SECTION WATER-SOURCE UNITARY HEAT PUMPS

A. Section includes factory-packaged units capable of supplying up to 100 percent outdoor air and providing cooling and heating.

HVAC REPAIR/REPLACEMENT 07/18/12 SECTION HVAC - MAJOR EQUIPMENT

SECTION FAN COIL UNITS

SECTION CUSTOM INDOOR CENTRAL-STATION AIR-HANDLING UNITS For large systems, 50,000 cfm or more.

.2 Section Waste Management and Disposal.

Internal ridged board 1" x 1.5 foil face installation shall be installed on roof, walls and base of casing.

Direct Fired Heater Model AD Specification

C. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1.

SECTION AIR COOLED WATER CHILLERS

SECTION (15833) - HVAC POWER VENTILATORS

High Plume Blowers Suggested Specification Section (Master Format 1996) Suggested Specification Section (Master Format 2004)

TYPICAL CPA SPECIFICATIONS

MIN. CCT. QTY RLA LRA HP FLA AMPACITY /1/ /3/

A. Air-conditioning and Refrigeration Institute (ARI) - Standard 550/590, latest edition, and ARI certification program.

Copyright 2003 and 2005 by The American Institute of Architects (AIA) Modified by MSU Physical Plant / Engineering and Architectural Services

Modular Heating & Ventilating Unit Model IGX-HV

Advance Release September 2009

C. Samples for Initial Selection: For units with factory-applied color finishes.

SECTION AIR COILS

A. General: Refer to paragraph entitled "SUBMITTAL" in Section Include the following data:

TECHNICAL GUIDE SPLIT-SYSTEM AIR-COOLED EVAPORATOR BLOWER 25, 30, 40 & 50 TON LA300, LB360, 480 & 600 (50 Hz) PROVEN PERFORMANCE GENERAL FEATURING

AIR HANDLING. B. Section Building Automation and Control System Guidelines. C. Section Air Cleaning Devices and Filters

A. Product Data: Include rated capacities, operating characteristics, furnished specialties, and accessories.

SECTION REFRIGERATION EQUIPMENT. A. Section Includes: Refrigeration equipment for insulated cold storage rooms including necessary accessories.

SECTION ROTARY-SCREW WATER CHILLERS

PITTSBURG STATE UNIVERSITY. HVAC and BUILDING AUTOMATION SYSTEM STANDARDS

AIR HANDLERS. Central Station (CS3) Roof Mounted (RT) (Modular AL Frame AHU)

B. Unit construction shall comply with ASHRAE 15 Safety Code, NEC, and ASME applicable codes (U.S.A. codes).

Guide Spec Summary. Option List. Date: 05/21/2001. EarthWise T-Series AHU Full Spec. Prepared by: Phone Number: Prepared for: Acceptable Manufacturers

A. Section Common Motor Requirements for HVAC Equipment: Fan motors.

SECTION AIR DUCT ACCESSORIES

A. Air-conditioning and Refrigeration Institute (ARI) - Standard 550/590, latest edition, and ARI certification program.

XeteX, Inc. All Rights Reserved.

SECTION CENTRAL HVAC EQUIPMENT

DSV Model Air Cooled Self Contained Indoor Packaged Units 3-5 Tons Preliminary Application Data

1.03 RELATED SECTIONS: The following sections contain requirements that relate to this section.

1.2 REFERENCES - comply with the following codes and standards:

SECTION CONVECTION HEATING AND COOLING UNITS

Bulletin C6200 MAY Buffalo. Big Buffalo. Air Handling. Custom Applications

A. Product Data: Include rated capacities, operating characteristics, furnished specialties, and accessories.

DESIGN GUIDELINES SECTION HVAC

B. Unit shall be shipped as a single package unless the unit is too large to fit on a standard tractor-trailer.

VERTICAL STACK INNKEEPER GUIDE SPECIFICATION CGC Hybrid Heat Pump System

UNIFIED FACILITIES GUIDE SPECIFICATIONS

Stanford University Facilities Design Guidelines SECTION DECENTRALIZED UNITARY HVAC EQUIPMENT

MACH N-407 Heat Pump Air-Cooled Chiller

DARTMOUTH COLLEGE DESIGN March 15, 2003 & CONSTRUCTION GUIDELINES

SECTION COMPUTER ROOM AIR CONDITIONING SYSTEMS

Industrial Fans & Blowers

SECTION ROTARY SCREW WATER CHILLERS Vibration Isolation Pumping Equipment (HVAC) Induced Draft Cooling Tower

Turning Air Into Solutions. TUBEAXIAL PAINT SPRAY BOOTH EXHAUST FANS. Model TCBS

SPLIT-SYSTEM EVAPORATOR BLOWER DESCRIPTION FEATURES L4EU NOMINAL TONS

Chilled Water DOAS Fan Powered Terminal Units

SKYPAK II, 3 Ton Series, gives you a

SECTION CENTRIFUGAL WATER CHILLERS Vibration Isolation Pumping Equipment (HVAC) Induced Draft Cooling Tower

30GN FLOTRONIC II AIR-COOLED CHILLERS

Centeral Station Air Handling Unit

1. Product Data for Prerequisite EQ 1: Documentation indicating that units comply with ASHRAE 62.1, Section 5 - "Systems and Equipment.

DIVISION 15 MECHANICAL

30GT FLOTRONIC AIR-COOLED CHILLERS

FLD = Furnished by Trane U.S. Inc. / Installed by Equipment Submittal Page 3 of 13

Series PACKAGED ROOFTOP UNITS, HEAT PUMPS AND OUTDOOR AIR HANDLING UNITS. Features:

MAC N-407 Air-Cooled Chiller

SECTION ROOFTOP REPLACEMENT AIR UNITS

University of Houston Master Construction Specifications Insert Project Name

SSL / SBS Sales Guide BLOWER-COILS REDUCED-FOOTPRINT, VERTICAL

SECTION PACKAGED, OUTDOOR, CENTRAL-STATION AIR- HANDLING UNITS

Transcription:

15855 AIR HANDLING UNITS SPECIFIER: CSI MasterFormat 2004 number: 237313 PART 1 GENERAL 1.1 SUMMARY A. Section includes Factory Packaged, Modular units, providing cooling and heating for air distribution systems. B. Related Sections: 1. 15240 - Vibration Isolation. 2. 15885 - Air Filtration Equipment. 3. 15890 - Ductwork. 1.2 REFERENCES A. Air Moving and Conditioning Association (AMCA): Standard 611 Fan Performance Testing. B. American National Standards Institute (ANSI): ANSI 9 Roller Bearings, Load Rating, and Fatigue Life. C. National Fire Protection Association (NFPA): NFPA 90A Air- conditioning and Ventilating Systems. D. Air-conditioning and Refrigeration Institute: Standard 410 Air Cooling and Heating Coils. E. Florida Building Code (FBC) - Mechanical. F. Florida Building Code (FBC) - Energy Conservation. 1.3 SUBMITTALS: A. Shop Drawings, list of materials, cooling coil performance data, fan performance data, and fan curves. Performance data shall be certified by unit manufacturer. 1.4 QUALITY ASSURANCE A. Cooling coils shall meet ARI standard 410.l B. Air handlers shall be ARI 430 certified. 1.5 WARRANTY A. Provide all labor, materials and equipment necessary to repair and/or replace any air handling unit components and/or accessories that fail (except for items replaced under Project No. SPECIFICATION GUIDELINES 15855 1

normal maintenance, such as belts), for a period of two (2) years from the date of substantial completion of the project. PART 2 PRODUCTS 2.1 MANUFACTURERS A. Air Handling Equipment: 1. Carrier. 2. Enviro-Tec. 3. McQuay. 4. Trane. 5. Temptrol. 6. York. 7. Krueger. B. Reheat Coils: 1. Heat Pipe Technology, Inc., Gainesville, FL. 2. Accepted equivalent by unit manufacturer. 2.2 FACTORY FABRICATED MODULAR AIR HANDLING UNIT A. Unit shall be of arrangement and type shown on Construction Documents with design capacities as scheduled. Design units for floor mounting. Central station air handler and components shall be ARI certified and complete with base frame fans, coils, motors, drives, belt guards where required, drains, filter sections, access doors and accessories as specified. B. Casing: 1. Exterior casing walls shall be fabricated of minimum 0.08" aluminum, continuous hot dipped galvanized steel, or black steel phosphatized and coated with baked enamel finish not lighter than 18 gage. Removable panels shall provide access to the interior of the unit. 2. Interior walls shall be fabricated so that solid metal, aluminum, minimum 0.063", or other approved metal, separates the airstream from fiberglass, ductliners, and internal insulation. Casing panels shall have a minimum R value of 13. 3. The removal of access panels or doors shall not affect the structural integrity of the unit. 4. Unit casing panels (roof, walls, floor) and doors shall be provided with a minimum thermal resistance (R-value) of 13 BTU Hr *FT2* F. 5. All doors downstream of the cooling coil shall be provided with a thermal break construction of door panel and door frame. 6. Gasketing shall be provided around the full perimeter of the doors to prevent leakage. 7. Handle hardware shall be designed to prevent unintended closure. 8. All drain pan threaded connections shall be visible external to the unit. Threaded connections under the unit floor shall not be accepted. C. Fan Section: Project No. SPECIFICATION GUIDELINES 15855 2

1. Fan section shall encase 1 double-inlet, double-width forward curved or backward inclined fan suitable for static pressures and air quantities indicated. a. Fan wheel shall be dynamically and statically balanced at factory. b. Maximum fan rpm shall be 25 percent less than the first critical speed. Fan wheel diameter shall be as indicated. c. Fan outlet velocity shall not exceed 2500 RPM. 2. Fan shaft shall be solid or hollow, ground and polished steel, and coated with rust inhibitor. a. V-belt driven fan shall have variable-pitch motor sheaves and drives shall be designed for 50% overload capacity. b. Drives shall be selected for the mean rpm of the drive to match the fan operating rpm at design fan rpm. 3. Fan bearings shall be grease lubricated, ball bearings, self-aligning type. Bearings shall be designed for an average life of 200,000 hours. Provide extended lubrication lines with external grease fittings. D. Coil Section: 1. Coil section shall encase cooling coils and drain pan. a. Arrange coils for horizontal airflow. b. Provide a minimum of 6 rows for chilled water service. c. Provide intermediate drain pans for multiple coil installations. d. Coil headers shall be completely enclosed within the insulated casing with only connections extended through the cabinet. 2. Drain pan shall be one of the following: a. Stainless steel, double pan construction with the inner pan covered with a heavy coat of mastic, and thermally isolated from the exterior casing with 1-inch thick fiberglass insulation. b. Welded heavy gage stainless steel, thermally isolated from the exterior casing with insulation of 1-1/2-inch-thick polystyrene or non-moving air space with the equivalent R value. c. Drain connections shall be of the same material as the drain pan and shall extend a minimum of 2-1/2 beyond the unit base. d. Drain pan threaded connections shall be visible, external to the unit floor are not acceptable. 3. Tubing for coils shall be copper 1/2" to 5/8" outside diameter. a. Fins shall be (aluminum) (copper) mechanically bonded by tubing expansion with a maximum spacing of 10 fins per inch unless noted otherwise. b. Coils shall have supply and return connections on the same end. 4. Refrigerant coils shall have venturi type refrigerant distributor arranged for down feed. Project No. SPECIFICATION GUIDELINES 15855 3

a. Proof test coils at 450 psig and leak tested at 300 psig air pressure under water, cleaned, dehydrated and sealed with a dry nitrogen charge. b. Coils shall be suitable for a working pressure of up to 300 psig. NOTE TO SPECIFIER: DX cooling coils shall only be used in a constant Volume system unless provisions are made to control the compressor loading to prevent freezing. DX refrigerant systems shall be installed with all the required devices and safeties and shall have the compressor and evaporator fan interlocked for simultaneous operation. c. Units with both a DX refrigerant and chilled water coils shall have a separate section for each. 5. Chilled water coils: E. Filters: a. Provide a minimum of 6 rows. b. Coils shall be tested by subjecting each coil to a minimum air pressure of 350 psig with the coil submerged in water. 1. As specified under Section 15885 - Air Filtration Equipment. NOTE TO SPECIFIER: Roof mounted equipment requires acceptance by M-DCPS on a per condition basis. 2.3 PENTHOUSE AIR HANDLERS AND OUTSIDE AIR HANDLING UNITS A. Units shall be of arrangement and type shown on Construction Documents with design capacities as scheduled. Units and components shall be ARI certified and complete with fans, coils, motors, drains, filter sections, and accessories as specified. B. Casing: 1. Design casing for indoor or outdoor installation as required and leak tight against 2- inch negative static pressure. 2. Casing walls shall be fabricated of minimum 0.08" aluminum or continuous hot dipped galvanized steel, or black steel phosphatized and coated with baked enamel finish not lighter than 18 gage. Removable panels shall provide access to the interior of the unit. Casing shall be bolted or welded to a galvanized steel base channel designed for curb mounting. 3. Interior walls shall be fabricated so that solid metal, aluminum (min 0.063") or other approved metal, separates the airstream from fiberglass, ductliners, and internal insulation. Casing panels shall have a minimum R value of 13. 4. Seams shall be welded or bolted and sealed to prevent leaks. 5. If outdoor installation, cover external vertical seams with a "U" clip, welded in place, for additional weather protection. 6. If outdoor installation, aluminum and galvanized steel unit roofs shall be flanged on all four edges, pitched for drainage, and to overlap all 4 sides of units. Project No. SPECIFICATION GUIDELINES 15855 4

7. Roof shall be gasketed and secured to side panel flanges with stainless steel or selftapping zinc coated screws. 8. Door sizes shall allow access to fan motor, coil, and inlet section. C. Fan Section: 1. Multi-blade, forward curved or backward inclined fans shall be double width, double inlet. 2. Fans shall be statically and dynamically balanced as an assembly with motor. 3. Fan housings shall be constructed of die-formed, streamlined inlets and side sheets. 4. Fan bearings shall be grease lubricated ball bearings. 5. Flexible boots shall be installed between the fans and unit casings. 6. Fans and motor assemblies shall be isolated from unit casings. Isolators shall be of spring type. D. Coil Section: 1. Coils shall have galvanized steel casings and be mounted in the coil casing with the same end connections accessible for service for coil removal from the unit through the roof or through the piping enclosure. 2. Tubing: a. Coils shall be copper 1/2" to 5/8" outside diameter. b. Fins shall be (aluminum) (copper) mechanically bonded by tubing expansion with a maximum spacing of 10 fins per inch unless noted otherwise. c. Coils shall have supply and return connections on the same end. 3. Refrigerant Coils: a. Provide with venturi type refrigerant distributor arranged for down feed. b. Coils shall be proof tested at 450 psig and leak tested at 300 psig air pressure under water. c. Clean, dehydrate, and seal with a dry nitrogen charge. d. Coils shall be suitable for a working pressure of up to 300 psig. 4. Chilled Water Coils: E. Dampers: a. Provide a minimum of 6 rows. b. Coils shall be tested by subjecting each coil to a minimum air pressure of 350 psig with the coil submerged in water. 1. Return air, fresh air shall be aluminum parallel blade type and rotated on rustproof nylon bushings encased in a non-ferrous housing. 2. Damper motor mounting brackets shall be provided inside the unit casing for center driving of the damper sets. F. Filters: As specified under Section 15885 - Air Filtration Equipment. Project No. SPECIFICATION GUIDELINES 15855 5

G. Penthouse air handlers shall have maximum dimensions as indicated. H. Penthouse air handlers shall have roof curbs as indicated. 2.4 REHEAT COILS A. Coordinate reheat coil installation with air handler manufacturer. PART 3 EXECUTION 3.1 INSTALLATION A. Equipment shall be installed according to manufacturer's recommendation. B. Casing seams shall be airtight. C. Condensate drains shall prevent any accumulation of condensate inside air handlers. P- trap on condensate drain on unit shall have a vertical leg equal to the maximum static pressure of the air handler. D. Seal coils at perimeter to prevent air bypass. Coils shall be installed to be completely drainable through header drains. E. Rigidly anchor units to roof slab to withstand wind velocities pressures as determined by FBC - American Society of Civil Engineers (ASCE) 7. F. Comply with calculations, signed and sealed by a Florida registered professional engineer, establishing wind velocity pressure values for the specific project according to FBC - ASCE 7. END OF SECTION Project No. SPECIFICATION GUIDELINES 15855 6