Water Regulations Tutorial # 7 Washroom

Similar documents
Water Regulations Tutorial # 6 Conservation

Designs of domestic bathrooms, guidance and advice from

Water Supply (Water Fittings) Regulations 1999

Installing, modifying and maintaining domestic plumbing systems. Water Supply (Water Fittings) Regulations 1999

The Water Regulations Solutions Specialist

Hamad bin Isa Al Khalifa King of The Kingdom of Bahrain

Installation Instructions / Operating & Maintenance Manual Ablution Plant Model BTHW-1

SENSELEC INFRA-RED CONTROLS

Oval Tap Range. Installation Instructions & User Guide. Please keep these instructions for future reference and request of replacement parts

This chapter investigates domestic

Approved. Document. Sanitation, hot water safety and water efficiency. The Building Regulations 2010

Target Monobloc Kitchen Mixer Chrome

WALLACE MAXIPUMP 3000, 5000, 6000 and HYDROJET 30P, 30C, 140 AND HJ400 INSTALLATION AND MAINTENANCE INSTRUCTIONS

Quadrato Tap Range. Installation Instructions & User Guide. Please keep these instructions for future reference and request of replacement parts

AIR ADMITTANCE VALVES FOR DOMESTIC PROPERTIES Guidance Notes

CHILDRENS TOILETS. Junior Series WC and Pan. Junior Series - Technical. Designer bathroom suites - miniaturized!

Domestic and Residential Fire Sprinklers Design Policy

Summer Works Scheme 2010

Trade of Plumbing. Module 2: Domestic Hot and Cold Water Service Unit 11: Sanitary Appliances Phase 2

REGISTRATION EXAMINATION, JUNE 2015 LICENSED PLUMBER QUESTION AND ANSWER BOOKLET. Time allowed THREE hours

Blitz Tap Range. Installation Instructions & User Guide. Please keep these instructions for future reference and request of replacement parts

Pear Kitchen Sink Tap

CRAFTSMAN EXAMINATION, JUNE 2007 PLUMBING QUESTION AND ANSWER BOOKLET. Time allowed THREE hours

REGISTRATION EXAMINATION, NOVEMBER 2011 CERTIFYING PLUMBER ANSWER SCHEDULE

RESOLUTION MSC.339(91) (adopted on 30 November 2012) AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS (FSS CODE)

Beeline Monobloc Kitchen Mixer Tap

Unvented Calorifier Range. Operating and Maintenance Manual. For Models & 500

TREVI BLEND SINGLE LEVER SHOWER VALVES. INSTALLER After installation pass to user for future reference

Trade of Plumbing. Module 2: Domestic Hot and Cold Water Service Unit 10: Hot Water Supply Phase 2

Issue 4 Oct Panamatic Top loading Maxi & Optima 3 Installation

HOME INSPECTION CHECKLIST

REGISTRATION EXAMINATION, NOVEMBER 2014 LICENSED PLUMBER ANSWER SCHEDULE

Helping you to understand your water use

ADVANCE ECB ELECTRIC COMBINATION BOILER

Accessories. 4in1 DVS Thermostatic Mixing Valve. TMV3 Thermostatic Mixing Valves. Specifications

AUTOMATIC TAPS. Infrared Taps. The perfect hygiene and water saving enhancement

PLEASE LEAVE THIS MANUAL WITH THE OSO UNIT AFTER INSTALLATION INSTALLATION MANUAL

Please also see 10 golden rules for correct Saniflo installation on

REGISTRATION EXAMINATION, NOVEMBER 2014 LICENSED PLUMBER QUESTION AND ANSWER BOOKLET. Time allowed THREE hours

Nero Tap Range. Fitting Instructions & Contents List

Zip Econoboil. On wall boiling water. Installation instructions & user manual. Model number: ,

Pipe Sizing Table. Hydraulic Load Served (fixture units)

ANNEX AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS (FSS CODE) CHAPTER 1 GENERAL

Installation Instructions Thermostatic Bar Shower Valve ALTO ECOTHERM

INSTALLATION MANUAL. Ecoline Geo RI HP PLEASE LEAVE THIS MANUAL WITH THE OSO UNIT AFTER INSTALLATION

PLEASE LEAVE THIS MANUAL WITH THE OSO UNIT AFTER INSTALLATION INSTALLATION MANUAL

Contents. Commissioning 6 Operation 6 Routine Preventative Maintenance 6 Fault Finding 7 Spares Parts 8 Technical Support 9

Master in Architecture. (Services in High Rise Buildings)

EVAC Commercial Marine Equipment TOILET TECHNICAL DATA EVAC 90, SQUATTING TOILET. To main vacuum line, connection Ø50.

Miscellaneous. TMV3 Mixing Valves. TMV3 Thermostatic Mixing Valves. Specifications. Temperature Readout. Features include:

NOT EVERYTHING IN LIFE IS COMPLICATED.

Capri Tap Range. Installation Instructions & User Guide. Please keep these instructions for future reference and request of replacement parts

Link-Up. Solid Fuel Association Guide to Central Heating.

SINKS AND HYGIENE EQUIPMENT

Level 3 Awards in Water Regulations & Hot Water Systems ( /30) June 2016 Version 1.5

Dual Control Concealed & Exposed Thermostatic Shower Valve

ENGINEERING STANDARD FOR SANITARY PIPEWORK ORIGINAL EDITION JAN. 1995

The POWERTANK. Range A PACKAGED SOLUTION FOR BOOSTING WATER. by Pedrollo Distribution. powertank.co.uk

STUDENT NOTES Plan, size and layout sanitary pipe work and fixtures

CRAFTSMAN EXAMINATION, NOVEMBER 2009 PLUMBING QUESTION AND ANSWER BOOKLET. Time allowed THREE hours

CPC-150-ANA. 150 litres, 535mm x 1300mm high. Pandora Heat Bank. 100kW Plate Heat Exchanger with 22mm Thermostatic Mixing Valve.

F & P Wholesale WE SIMPLY DELIVER MORE

Pressure Boosting Solutions

HORNE 15 and 20 thermostatic mixing valve specification manual 2009

Frequently Asked Questions

WATER DOMESTIC PROPERTIES REGULATIONS FOR. Information guide for your home

Vented systems explained Performance without compromise Vented System (Gravity Fed) Positive Head Systems

Draft FPA Australia Technical Specification for Public Comment FPAA101D DRAFT

Helping you understand your water usage

2. Sanitary Plumbing General Installation Requirements

Smile Tap Range. Installation Instructions & User Guide. Please keep these instructions for future reference and request of replacement parts

Understand and apply domestic hot water system installation, commissioning, service and maintenance techniques

RESOLUTION MSC.292(87) (adopted on 21 May 2010) ADOPTION OF AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS

Decade Tap Range. Installation Instructions & User Guide. Please keep these instructions for future reference and request of replacement parts

pump solutions Full technical data sheets are available to download: For further advice on selecting the correct pump call:

Pressurisation units & expansion vessels

Unvented Direct & Indirect Hot Water Cylinders (400L L)

MEGAFLO HE Iss 1

The easy solution for waste water removal

Unvented water heating

Atmos EasySolar. Installation Instructions for. Sloping roof and flat roof installation with evacuated tube collector

Pisa Tap Range. Installation Instructions & User Guide. Please keep these instructions for future reference and request of replacement parts

Space Saver. Installation and user manual SS3 SS5 SS7 SS9. Issue 001 September 2017 ENGLISH UK IRL SmithsEP.co.uk

UNIT 5 COLD WATER SUPPLY

Notice on the implementation of the amendments to the FSS Code in resolution MSC.339(91)

English Piping Guide Vacuum Piping Guide, Building :04

WC2 & WC3 Installation & Maintenance Instructions

There are several designs of toilets. These are close coupled, low level, high level, back to wall, and wall- hung.

CBU144. Compact Booster Unit - single pump To ensure the quality of potable water according to EN1717. Product specification sheet

All Valve Industries. General Product Overview. Distributed by All Valve Industries. Ph: Fax:

CONTENTS. Frequently asked questions: Usage Care and maintenance Safety Technical and installation. Settings

ZIP Varipoint III. Installation, Maintenance and User Instructions. Models VP303, VP503 VP803, VP953 direct unvented water heaters. Issued August 2008

Technical reference Reference & design

technical specifi cation residential sprinkler systems

Sanipack is a compact pump/macerator specially designed to take the waste from a wall hung or back to wall WC pan.

APP Environmental Services P/L.

CROWN WATER HEATERS CPU10 - CPU15 CPOS10 - CPOS15

257mm 181mm mm

Installation Manual. Instrucciones de instalación y manual de usuario 1

ADVANCE STAINLESS STEEL UNVENTED HOT WATER SYSTEMS

Transcription:

Arrow Valves Ltd Water Regulations Tutorial #7 Washroom Arrow Valves Tel 01442 823 123 Fax 01442 823 234 www.arrowvalves.co.uk Water Regulations Tutorial # 7 Washroom Updated 21/07/16 Two principal objectives of the Water Regulations are conservation and greater harmonisation with mainland Europe. One of the most significant changes in the UK since the introduction of the Water Regulations is the allowance of non-siphonic flushing apparatus for WCs. It is no longer necessary to flush WCs and urinals from flushing cisterns. It is permissible to flush from the mains supply pipe or domestic boosted cold water circuit providing the appropriate controls are fitted. This whole subject is covered in detail - complete with colour illustrations and diagrams - in chapter 9 of the Water Regulations Guide. WC FLUSH VOLUME Schedule 2, paragraph 25 (1) (d) requires any type of flushing device installed from 1 January 2001 to have a maximum flush volume of 6 litres to a WC pan. Dual flush cisterns were banned under the old byelaws but are now permitted again; providing the maximum flush volume is 6 litres and the lesser volume is a maximum of two thirds of the greater volume - i.e. 4 litres if the greater volume is 6 litres. The period from 1 July 1999 to 1 January 2001 was transitional and allowed the installation of either 7.5 or 6 litre cisterns. METHODS OF FLUSHING WC PANS Siphon - The original 1880 Thomas Crapper design remains the most popular method in the UK, since the siphon or valveless control is inherently reliable at not leaking. It does require a physical effort to operate and this is considered by some to be rather cumbersome and outdated. Mechanical Valves Outlet valves controlling the flow to the pan are now permitted. These are known as Drop or Flap valves. A mechanism is required to hold the valve open for the whole duration of the flush. This could be a solenoid valve with a nontouch electronic activation sensor. These mechanical sealing valves can leak and therefore waste a lot of water. Most cisterns fitted with this type of valve are manufactured with an internal overflow and an overflow condition may be relatively inconspicuous. Pressure Flushing Cisterns PFC s have a pressure vessel in the cistern that utilises mains water pressure to compress the gas during filling. This stored energy is released during the flush to increase the velocity of water. This is used in some American States but is unlikely to be used widely over here. Pressure Flushing Valves FV s allow the WC pan to be flushed without a cistern. The valve allows a predetermined quantity to be flushed. The flushing can be initiated manually or automatically providing the maximum consumption rates are observed. DC Pipe Interrupter (model DC257) for a urinal flush from the mains or cold boosted water without a cistern The water is supplied either directly from the mains or boosted supply pipe or from a storage cistern via a distributing pipe. In both cases suitable backflow protection is required. This method is likely to be

widely used in non-house buildings but flushing valves are not permitted in houses. (Note - Pressure Flushing Valves will be shortened to Flushing Valves in this tutorial). BACKFLOW PROTECTION The contents of a WC pan or urinal is Fluid Category 5 the highest category and therefore must be protected with either AUK1 interposed cistern arrangement (i.e. gravity supply) DC Pipe Interrupter e.g. model DC257. Type AB air gap (with booster pump) A conventional WC suite will consist of a 6 litre cistern, float valve (with type AG air gap) and overflow arrangement. This creates a type AUK1 interposed cistern. In other words, the cistern can be supplied from a supply pipe or storage cistern and no additional backflow protection is required. Remember a servicing valve is required e.g. model AFL. A WC pan with no cistern, i.e. flushed by a flushing valve, should be supplied through any of the three arrangements listed above. The WRAS guidance clause R25.2 allows an interposed cistern (type AUK1) to be used. This is a storage cistern (with type AG air gap), which supplies water under gravity to the WC pan, urinal or bidet. For WC flushing cisterns only, an alternative Fluid Category 3 backflow prevention arrangement may be accepted instead of the Type AG air gap please see below: Topic B58 states - Although a Type AUK1 air gap must incorporate a Type AG air gap the Regulators Specification (test code sheet 2212.3 Annex B) permits the installation of an alternative fluid category 3 backflow prevention arrangement for WC flushing cisterns only. In recognition of this, where an inlet feeding a WC flushing cistern fails to meet the requirements for a Type AG air gap (please refer to interpretation E04) water suppliers may be willing to accept an alternative fluid category 3 backflow prevention device in place of a Type AG air gap. This will however be dependent upon a risk assessment of the WC. Factors that will be taken into consideration will include, but are not restricted to whether:- The cistern incorporates an outlet control which ensures the pipework connecting the pan and cistern is completely evacuated between flushes; and If there is any risk of back pressure. A single distributing pipe (AKA down service) is acceptable according to G15.10 for flushing any number of WCs and urinals. This distributing pipe must not be used for washbasins or other applications. The same cistern may be used for the hand washbasins providing they are supplied from a separate distributing pipe from that cistern. BIDETS AND ABLUTION HOSES The Water Regulations identify ascending spray bidets and any hose used for toiletry purposes as Fluid Category 5, therefore requiring a suitable air gap arrangement. For hygiene reasons, bidets must be supplied with domestic water, meaning Fluid Category 1 (cold) or Fluid Category 2 (hot). In the case of a boosted system with the pump drawing water from a cistern with type AB air gap, this same cistern cannot be used for a bidet if it is already supplying the flushing valves to WC pans or urinals (assuming no DC Pipe Interrupters are used). This is because the cistern theoretically could be contaminated due to backflow from the WC pans and one would not want to wash one s private parts with that! Arrow Valves Ablution Plant (model BTHW) provides point of use Fluid Category 5 backflow protection and delivers warm water at the required safe temperature to a bidet or Ablution hose adjacent to a WC. This subject will be discussed further in tutorial 8. Ablution Plant (model BTHW) Delivers safe hot water with Fluid Category 5 backflow prevention

REGULATOR S SPECIFICATION Clause G25.11 states, All WC Pans and all flushing devices for WC pans should conform to a specification approved by the Regulator. This means a flushing arrangement and pan should be tested and approved as a suite rather than individually. This requirement does not apply to urinal bowls. DESIGNER S CHOICE Consulting engineers generally design mains or boosted hot and cold water systems and gravity storage cisterns are rarely used these days for many good reasons. In this instance WC pans flushed with a flushing valve should be flushed from a dedicated cistern with type AB air gap. A booster pump will be required to restore pressure. A compact unit is available as Boost-A-Break model BTAB. The duration of the flush should be controlled with a flushing valve. In view of the Regulator s Specification, high flow demand, lack of flushing valves / large DC Pipe Interrupters, means few consulting engineers are using this technology for WC pans at present. This situation is quite different for urinals, where there are suitable approved fittings and cisternless urinals are being installed. Section of Arrow Valves DC Pipe Interrupter (model DC257). One device is used per urinal bowl. Supply - mains or boosted water DC PIPE INTERRUPTERS A DC Pipe Interrupter is a non-mechanical arrangement that provides Fluid Category 5 protection against backsiphonage (vacuum on the supply). It is not suitable for backpressure. It has a nozzle, which creates a jet. Downstream of this nozzle are several radial holes to atmosphere. It is clear that negligible restriction can t exist downstream - otherwise water would simply come out the vent holes. No control valves are permitted downstream. Previously, the DC Pipe Interrupter needed to be fitted 300 mm above the spillover level of a WC pan or urinal. This has now been amended to 150 mm, please see below: Topic B39 states - In the case of Type DC arrangements the WRAS Technical Committee has agreed that a reduction in the distance between the lowest point of the air aperture and the free discharge point or spillover level of an appliance from 300 mm to 150 mm, in alignment with the requirements specified in the British Standard and European norm, is acceptable. All other installation requirements remain unaltered. Boost-A-Break Break tank and pump set with Type AB air gap (model BTAB) for Fluid Category 5. Flush WCs or urinals without additional backflow protection. Supplied as complete unit DC Pipe Interrupters must therefore be fitted to vertical pipes with the flow in a vertical downward direction. Where larger DC Pipe Interrupters for WC pans are to be used, care should be taken with the design to avoid leakage from these devices. For large buildings, supplying water from a dedicated boosted circuit drawing water from a cistern with a type AB air gap is likely to be a better solution. Arrow Valves Boost-A-Break model BTAB Break Tank and Booster set meets the requirements with the minimum amount of space. URINAL FLUSHING The conventional method for flushing urinals using a flushing cistern is still acceptable. There is now a second method flushing without a cistern from a supply pipe via a DC Pipe Interrupter. Clause G25.9 states Urinals may be flushed with either: a. manual or automatically operated cistern; or b. a pressure flushing valve directly connected to a supply or distributing pipe which is designed to flush the urinal, either directly manually or automatically, provided that the flushing arrangement

incorporates a backflow arrangement or device appropriate to fluid category 5 (see Schedule 2: Paragraph15). Clause G25.13 states Where manually or automatically operated pressure flushing valves are used for flushing urinals, the flushing valve should deliver a flush volume not exceeding 1.5 litres per bowl per position each time the device is operated. Note supply pipe means mains water (typically 2 4 bar at ground level). Distributing pipe is the down pipe from a storage cistern (10 m head = 1 bar). The boosted cold water circuit can be used to fill or flush WCs and urinals, providing appropriate backflow protection is provided see backflow prevention. FLUSHING WITHOUT A CISTERN (USING A FLUSHING VALVE) This new method has several advantages compared with flushing cisterns. The operation is as follows - water is supplied from a supply pipe (mains) or the boosted cold water circuit. A low voltage solenoid valve controls the flow and backflow protection is afforded by a DC Pipe Interrupter. A large bore braided flexible hose links the pipe to the urinal sparge outlet. An active Infra-red sensor is located above each bowl in the false wall (or in the ceiling), which senses a person. The sensor must see the user for 10 seconds - this prevents false operation when someone walks past. The controller will then operate the solenoid for the selected. One litre (1.5 legal max.) is a typical flush volume. FLUSHING URINALS FROM A CISTERN This conventional arrangement consists of a cistern mounted above a single or group of urinals. Water gradually fills the cistern either at a continuous slow rate (through a pet cock ) or modulated (turned on or off) at a higher flow rate. The cistern flushes once the water level reaches the self-siphon level. AUTOMATIC URINAL FILLING RATE Schedule 2, paragraph 25 states the legal requirements for WCs and urinals. This is repeated and reinforced by the two guidance clauses reproduced below - Clause G25.12 states An automatically operated flushing cistern serving urinals should be filled with water at a rate not exceeding: a. 10 litres per hour per urinal bowl for a cistern serving a single urinal; or b. b. 7.5 litres per hour per urinal bowl or position or, as the case may be, for each 700 mm width of urinal slab for a cistern serving two or more urinals. Clause G25.10 states Unless a urinal cistern is manually operated, or fills and flushes by a device operated by an electronic sensor, pressure pad or no less suitable device which ensures that the urinal is only flushed after it is used, the inlet to the flushing cistern is to be controlled by a time switch opening an inlet valve or some other equally effective automatic device which regulates the periods during which the cistern may fill. There are three acceptable methods for preventing flushing when the urinals are not being used Time switch and pet cock this is a crude arrangement with many inherent limitations. Hydraulic impulse device (original Cistermiser) these devices rely on a man washing his hands after using the urinal. Providing the washbasin tap is taken off the same circuit as the device it should initiate a mechanical timer. If the user does not wash his hands or uses the hot tap the device will not work. Reliability is impaired with high calcium carbonate in the water. Electronic sensors are much better.

Water Regulations Tutorial #7 Washroom Arrow Valves Electronic movement detectors this method is technically superior to others. They can be battery operated (often providing more than 2 years life) or mains operated. Devices are available for controlling conventional flushing cisterns or flushing valves (no cistern required). WATER COSTS It has been common practice to flush a group of three urinal bowls simultaneously from one cistern. Possibly only one may have been used. The following example compares water charges with different control methods. The table below illustrates the annual water cost for a typical building based on the following. A bank of 3 urinals is used to serve a building with 25 men, who use the facility twice during a day. The working hours are 8 hours a day, 5 days a week, 48 weeks per year. The combined water and sewerage charge is based on 1.52 per cubic metre. The maximum permitted volumes of 7.5 litres/urinal/hour for the flushing cistern and 1.5 litres per flush for the flushing valve are used (IRN R075). Description Annual Cost Comment Flushing cistern serving 3 bowls with no control Flushing cistern serving 3 bowls with Cistern Flush Valve - CFV No cistern. 3 Flushing Valves controlled by Urinal Flushing Valve controller 300 No control - contravenes Regulations. This is a typical 9 litre cistern flushing every 24 minutes day and night. 66 Electronic controller (e.g. CFV) isolates cistern when not used. With 50 users/day it is assumed there is unlikely to be a period of more than 30 minutes of no use during the working day. 27 This is the total cost for 3 bowls! The primary reason for the Urinal Flush Valve saving is that it flushes only the bowl that has just been used, whereas the Cistern Flush Valve flushes 3 bowls simultaneously (irrespective of use). In practice a smaller flush volume is often used, e.g. 1 litre or less providing further savings. INDIVIDUAL URINAL FLUSHING (USING FLUSHING VALVE) This new method of flushing an individual bowl after use with a flushing valve (no cistern required) has the following advantages Maximum water saving individually flushed Minimum smell flushes automatically immediately after each use No bulky cistern or large pipes pipes are 15 mm and normally concealed No overflow required Flush volume and flow rate easily altered at any time No small pet cocks or small orifices to block No planned maintenance Reliable (individual isolation if maintenance is required) Hygienic and visually impressive OVERFLOWS / WARNING PIPES The ¾" nominal (22 mm OD) overflow pipe from a flushing cistern is generally described as a warning pipe. Clause G25.6 states- Cistern Flush Valve (model CFVWW) Except for pressure flushing cisterns, all WC flushing cisterns should be provided with a connection for a warning pipe, the outlet of which is to discharge in a prominent position, or other equally effective device. However, WRAS topic WC01 states that the use of internal warning pipes (standing overflows) in WC flushing cisterns, such that overflowing water is discharged into the back of the WC pan, is accepted as an equally effective device to an external warning pipe. Consequently, many WC cisterns now have an internal overflow, which discharge down the pan. The acceptance is conditional upon measures to reduce the likelihood of the internal overflow being used. A

Water Regulations Tutorial #7 Washroom Arrow Valves strainer should be incorporated or fitted upstream of the float valve. Clearly it is desirable to have a strainer that can be cleaned without dismantling the valve or pipe. The AFL Valve with a 180 micron strainer is ideal, since this also complies with the requirement for a servicing valve - Schedule 2, paragraph 16 (2). The allowance of internal overflows and non-siphonic flushing apparatus is a retrograde step in terms of water conservation. There are concerns that users will not observe, not realise there is a fault or choose to ignore the trickle down the pan. There are alternatives to the internal overflow including Automatic Flow Limiting (AFL) Valve. Quarter turn Servicing Valve with a ball capable of accepting an Automatic Flow Limiting and / or Strainer cartridge. Visible warning tundish, sight glass, mechanical or electrical indicator Audible signal A mechanical device, which disables the flush, thereby indicating to the user there is a fault A device that detects when the water level rises above the maximum operating level and closes the water supply to the float valve. HAND BASINS Water supplied to the cold tap should be wholesome (Fluid Category 1) so it is suitable for drinking. Taps not suitable for drinking (e.g. Hose Union taps) should be labelled in accordance with the below clause G27.4. Clause G27.4 states Except in a house, all taps that are supplied with cold water that is non wholesome should be labelled Not Drinking Water. The industry guidance for this clause states that it is also equally acceptable to label the other way, known as safe condition, i.e. wholesome water taps labelled Drinking Water. Assuming no plugs are provided, self-closing taps should be used G28.1 (see tutorial 6). A servicing valve with an automatic flow limiter is ideal for conserving water and preventing splashing - model AFL. HOSE UNION TAP The hose union tap in a washroom is likely to be risk assessed as Fluid Category 5 and must be supplied from a break tank with Fluid Category 5 protection such as type AB air gap e.g. Break Tank and Booster Set Boost-A-Break model BTAB. Diagram R15.12.2a allows the same cistern used for WC or urinal flushing valves to be used for a Hose Union tap in the toilet vicinity. Compact surface mounted stainless steel box, with spherical valve and hose connection. (model HUTB) Where a gravity system is used, the supply to the hose union tap can be from a distributing pipe (R15.12.2), either dedicated or one serving WC & Urinal flushing valves. Clearly this tap is not suitable for drinking. It should be labelled in accordance with clause G27.4 Not Drinking Water. Furthermore it would be wise to use a lockable tap. A solution is offered with the Arrow Valves secure hose tap housed in a lockable stainless steel box model HUTB. A new alternative solution is a removable wall mounted HU tap ( Detach-A-Tap model HUD). A push-fit connection allows the tap outlet to be removed when not in use, preventing unauthorised use and someone inadvertently drinking see below.

SUMMARY 1. It is a legal requirement to use some form of device to prevent flushing of urinals when not used. 2. Urinals can now by flushed from a supply pipe without a cistern - providing a DC Pipe Interrupter and flushing valve are used. 3. Instead of DC Pipe Interrupters, a booster pump drawing water from a cistern with type AB air gap may be used. This cistern can supply WC pans, urinals and a hose union tap in the toilet area. 4. Internal overflows from WC cisterns are permitted. 5. A servicing valve should be provided for every cistern and flushing valve a valve incorporating a serviceable strainer is recommended. Thank you for your interest