OPERATION INSTRUCTIONS ENERGY RECOVERY VENTILATOR WITH EXHAUST. For Use With Bard 2 Through 5 Ton QW*S Series

Similar documents
OPERATION INSTRUCTIONS ENERGY RECOVERY VENTILATOR WITH EXHAUST. For Use With Bard 2 Through 5 Ton QW*S Series

INSTALLATION INSTRUCTIONS WALL MOUNT ENERGY RECOVERY VENTILATOR WITH EXHAUST

INSTALLATION INSTRUCTIONS ENERGY RECOVERY VENTILATOR WITH EXHAUST MODELS: WGERV-A3A WGERV-C3A WGERV-A5A WGERV-C5A WGSERV-A5 WGSERV-C5

INSTALLATION INSTRUCTIONS ENERGY RECOVERY VENTILATOR WITH EXHAUST MODELS: WFERV. Bard Manufacturing Company, Inc.

INSTALLATION INSTRUCTIONS ERVR-A3D-X ERVR-C3D-X RETROFIT ENERGY RECOVERY VENTILATOR

INSTALLATION INSTRUCTIONS WALL MOUNT ENERGY RECOVERY VENTILATOR WITH EXHAUST

I-TEC ERV Economizer Ventilator System (Vent Code "E")

INSTALLATION INSTRUCTIONS WALL MOUNT ENERGY RECOVERY VENTILATOR WITH EXHAUST

INSTALLATION INSTRUCTIONS ENERGY RECOVERY VENTILATOR WITH EXHAUST

INSTALLATION INSTRUCTIONS WALL MOUNT ENERGY RECOVERY VENTILATOR WITH EXHAUST

INSTALLATION INSTRUCTIONS WALL MOUNT ENERGY RECOVERY VENTILATOR WITH EXHAUST

OPERATION INSTRUCTIONS ENERGY RECOVERY VENTILATOR WITH EXHAUST. For Use With Bard 2 Through 5 Ton QH Series Heat Pumps

Q-Tec TM QC-Series Chilled Water Air Conditioner

Q-TEC QC-Series Chilled Water Air Conditioner

THE WALL-MOUNT TM SIX TON AIR CONDITIONER

Q-TEC Q24H3-Q60H3 Air-to-Air Heat Pump 10 EER Units

Q-TEC Q24A-Q60A Air Conditioners

Bill McCullough. Director ERV Products. Dallas, TX

THE WALL-MOUNT Quiet Climate A/C 10.0 EER

Q/Tec TM QW-Series Water-to-Air Heat Pumps

BARD MANUFACTURING COMPANY, INC. WG3S-WG5S 2-Stage Cooling with Gas Heat Engineering Specification Guide

Q/Tec TM QH-Series 2 Air-to-Air Heat Pumps

Scholar III Unit Ventilator

THE WALL-MOUNT GAS/ELECTRIC Low NOx Certified Models

Green Refrigerant. THE WALL-MOUNT STEP CAPACITY AIR CONDITIONERS Integrated Part Load Value (IPLV) Efficiency Up To 15.3 BTU/WATT. Engineered Features

The Wall-Mount Step Capacity Gas/Electric - WG*S Series Integrated Part Load Value (IPLV) Efficiency Up to 15.6 BTU/WATT NOx Certified Models

THE WALL-MOUNT HEAT PUMPS EER, (60HZ)

BARD MANUFACTURING COMPANY, INC. W18AA-W72AB

THE WALL-MOUNT QUIET CLIMATE HEAT PUMPS

USER S GUIDE. For all Packaged Systems (Air Conditioners and Heat Pumps)

Wall Mounted Air Conditioners with Gas Heat Models AVGA

BARD MANUFACTURING COMPANY, INC. W24G-W60G Gas Heat/Electric Cooling Engineering Specification Guide

THE WALL-MOUNT 6-TON AIR CONDITIONERS

Q/Tec TM QA-Series Air Conditioners

Electric Heat Strips: Features an automatic limit and thermal cut-off safety control. Heater packages can be factory or field installed.

I-TEC I30A1D-I60A1D 2-Stage Compressor High Efficiency Air Source Air Conditioners w/dehumidification

LOW VOLTAGE CONTROL CIRCUIT WIRING

Electric Heat Strips: Features an automatic limit and thermal cut-off safety control. Heater packages can be factory or field installed.

Submittal Data Performance Data Electrical Data

THE WALL-MOUNT ONE TON AIR CONDITIONER GREEN REFRIGERANT R-410A. 10,800 Btuh 9.00 EER Right Side Control Panel. Engineered Features

GreenPac & GreenPac HGR Heat Pumps & Air Conditioners Models AVP

Energy Recovery with Cooling and Heating Model ERCH

KINGS COUNTY JAIL EXPANSION PHASE III COUNTY OF KINGS SECTION

INSTALLATION INSTRUCTIONS WALL MOUNTED PACKAGE AIR CONDITIONERS WA121

OWNER S MANUAL. High-Wall Fan Coil Unit CONTENTS

Put the V back in HVAC

USER GUIDE MODELS ERV CONSTRUCTO 1.5 QUATTRO ERV CONSTRUCTO 2.0 QUATTRO READ AND SAVE THESE INSTRUCTIONS FOR RESIDENTIAL USE ONLY rev.

SAFETY AND INSTALLATION MANUAL MODEL 8100

50TM COMBINATION HEATING/COOLING UNITS

THE WALL-MOUNT ONE TON AIR CONDITIONER. Green Refrigerant. 12,000 Btuh EER Right Side Control Panel. Engineered Features

SKYPAK II, 3 Ton Series, gives you a

Owner s Manual Super-Slim Four-Way Cassette

Heat Recovery Ventilators models:

GREEN REFRIGERANT R-410A

CHAPTER 4. HVAC DELIVERY SYSTEMS

Operation Manual SCT14B and SCT18B. Inspection. 3 General Description. 3 General Requirements. 3 Standard Features.

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 FEATURES B-0703

48TM GAS HEATING/ELECTRIC COOLING UNITS

SKYPAK II, 3 Ton Series, gives you a

GREEN REFRIGERANT R-410A

Using the Remote Control Unit

Tech to Tech May 07 HRV s & ERV s

Rooftop Ventilator. Models RV and RVE. with Packaged Cooling & Heating

Utopian Split A/C. Thank you for purchasing this quality Split A/C system!

INSTALLATION INSTRUCTIONS TEC40 ELECTRONIC CONTROLLER

MiniCore Ventilator (500, 1000) Series Engineering Guide

CATALOG. SKYPAK Self-Contained Heating/Cooling Units

maintenance should only be performed by a trained, qualified person. Consumer service is recommended only for filter replacement.

Installation, Operation and Maintenance Manual

User Manual HEAT RECOVERY VENTILATORS 1000 HE HE HE HE HE HE COMPACT 5585 COMPACT READ AND SAVE THESE INSTRUCTIONS.

FLOOR CONSOLE/ UNDER CEILING DUAL TYPE. ABT Series FUJITSU GENERAL LIMITED AIR CONDITIONER OPERATING MANUAL P/N

Electric Heat Strips: Features an automatic limit and thermal cut-off safety control. Heater packages can be factory or field installed.

Energy Recovery Ventilation

OPERATING MANUAL AIR CONDITIONER CASSETTE TYPE. AUT Series KEEP THIS MANUAL FOR FUTURE REFERENCE FUJITSU GENERAL LIMITED P/N

UNDERCOUNTER LABORATORY REFRIGERATORS and FREEZERS Installation, Operation and Maintenance Instructions

Energy Recovery Ventilators

Advance Product Data. Features/Benefits. 42WKN Hydronic Fan Coil Units

USER S INFORMATION MANUAL

CAS. Product Specifications. COMMERCIAL SPLIT SYSTEMS CONDENSING UNITS R 410A, 6 to 12.5 TONS BUILT TO LAST, EASY TO INSTALL AND SERVICE

WALL-MOUNT HEAT PUMPS - (60HZ)

DES CHAMPS PRODUCTS 85% 4,400 CFM

Outside Air Requirements... SOLVED!

Indholdsfortegnelse. Danvent Air Handling Units SERVICE MANUAL

50TM TFF COMBINATION HEATING/COOLING UNITS

48TF GAS HEATING/ ELECTRIC COOLING UNITS

Application Data. Fig. 1 39M Unit with Energy Recovery Section

Benefits Offered by Passive Dehumidification Wheel Speed Control

Contents. How to choose Recovery Ventilation type?...3. How do HRV, ERV and TRV Systems work?...4. Types of installations...5. VUT 200 H mini...

Submittal Data PERFORMANCE DATA CERTIFIED DIMENSION PRINTS CERTIFIED ROOF CURB DIMENSION PRINTS SERVICE OPTION DIMENSION PRINTS

BRONZE MODELS 90H* 190H READ AND SAVE THESE INSTRUCTIONS

READ AND SAVE THESE INSTRUCTIONS

Product Specifications. Vertical Floor Consoles By First Co.

Product Release Summary

UNIVERSITY OF ROCHESTER DESIGN STANDARDS NOVEMBER 1, 2013

DUCTED AIR CONDITIONER. Owner s Manual. KD Series KD24. Kaden Owner s Manual 1

AIR CLEANER A GUIDE TO OPERATING AND MAINTAINING YOUR ELECTRONIC. NOTE TO INSTALLER: This manual should be left with the equipment owner.

KSD-35 DR11 KUE-35 DVN11

INSTALLATION INSTRUCTIONS

user s information manual

Classic 13 Heat Pumps High Efficiency Vertical Packaged Heat Pumps Models HVPA and HVPSA

Transcription:

OPERATION INSTRUCTIONS ENERGY RECOVERY VENTILATOR WITH EXHAUST Models: 90-007 QWSERV 90-08 QWSERV with Intelligent Defrost For Use With Bard Through 5 Ton QW*S Series Bard Manufacturing Company, Inc. Bryan, Ohio 506 Since 9...Moving ahead, just as planned. Manual: 00-5E Supersedes: 00-5D File: Volume II, Tab Date: 0-- Manual 00-5E Page of

CONTENTS Electrical Specifications... General Description... 90-007 & -08 with Intelligent Defrost... Control Requirements... Recommended Control Sequences... Control Wiring... Ventilation Airflow... Performance & Application Data... 5 & 6 Energy Recovery Ventilator Maintenance... 6 & 7 Figures Figure Speed Adjustment... Figure Belt Replacement... 8 Figure Hub Assembly with Ball Bearings... 9 Figure Configuring 80-067 CO Control... Wiring Diagram Wiring Diagram for 90-007 QWSERV... 0 Wiring Diagram for 90-08 QWSERV w/i.d... Tables Table Ventilation Air (CFM)... Table Summer Cooling Performance... 5 Table Winter Heating Performance... 6 Maintenance Procedures... 7 BARD MANUFACTURING COMPANY, INC. BRYAN, OHIO USA 506 Manual 00-5E Page of

ELECTRICAL SPECIFICATIONS Model Voltage Amps 90-007 90-08 Control Voltage 0 / 08. V Model 90-007 90-08 For Use with the Following Units QWS-A, -B, -C QWS-A, -B, -C QWS-A, -B, -C QW5S-A, -B, -C GENERAL DESCRIPTION The Energy Recovery Ventilator was designed to provide energy efficient, cost effective ventilation to meet I. A. Q. (Indoor Air Quality) requirements while still maintaining good indoor comfort and humidity control for a variety of applications such as schools, classrooms, lounges, conference rooms, beauty salons and others. It provides a constant supply of fresh air for control of airborne pollutants including CO, smoke, radon, formaldehyde, excess moisture, virus and bacteria. The ventilator incorporates patented rotary heat exchange state-of-the-art technology to remove both heat & moisture and provides required ventilation to meet the requirements of ASHRAE 6. standard. It is designed as a single package which is factory installed. The package consists of a unique rotary Energy Recovery that can be easily removed for cleaning or maintenance. It has two 5-inch diameter heat transfer wheels for efficient heat transfer. The heat transfer wheels use a permanently bonded dry desiccant coating for total heat recovery. Ventilation is accomplished with blower/motor assemblies each consisting of a drive motor and dual blowers for maximum ventilation at low sound levels. speeds can be adjusted so that air is exhausted at the same rate that fresh air is brought into the structure thus not pressuring the building. The rotating energy wheels provide the heat transfer effectively during both summer and winter conditions. NOTE: Operation is not recommended below 5 F outdoor temperature because freezing of moisture in the heat transfer wheel can occur. 90-08 WITH INTELLIGENT DEFROST This model is equipped with a thermostat which is sensing the intake ventilation air. It is factory set to initiate a defrost sequence when operations are below 0 F. This defrost time is set for a -minute defrost for every minutes of ERV operation. This control circuit controls the intake damper assembly allowing the ERV to operate with zero intake air to allow conditioned room air to defrost the cassette wheels. CONTROL REQUIREMENTS. Indoor blower motor must be run whenever the ERV is run.. Select the correct motor speed on the ERV. Using Table of the ERV Installation Instructions determine the motor speed needed to get the desired amount of ventilation air needed. For instance, do not use the high speed tap on a ERV if only 00 CFM of ventilation air is needed. Use the low speed tap. Using the high speed tap would serve no useful purpose and would effect the overall efficiency of the heat pump system. System operation costs would also increase.. Run the ERV only during periods when the conditioned space is occupied. Running the ERV during unoccupied periods wastes energy, decreases the expected life of the ERV, and can result in a large moisture buildup in the structure. The ERV can remove up to 60 to 70% of the moisture in the incoming air, not 00% of it. Running the ERV when the structure is unoccupied allows moisture to build up in the structure because there is little or no cooling load. Thus, the air conditioner is not running enough to remove the excess moisture being brought in. Use a control system that in some way can control the system based on occupancy. NOTE: The Energy Recovery Ventilator is NOT a dehumidifier. IMPORTANT Operating the ERV during unoccupied periods can result in a build up of moisture in the classroom. Manual 00-5E Page of

RECOMMENDED CONTROL SEQUENCES Several possible control scenarios are listed below:. Use a programmable electronic thermostat with auxiliary terminal to control the ERV based on daily programmed occupancy periods. Bard markets and recommends Bard Part No. 80-060 programmable electronic thermostat for heat pump applications.. Use a motion sensor in conjunction with a mechanical thermostat to determine occupancy in the classroom. Bard markets the CS000A for this use.. Use a DDC control system to control the ERV based on a room occupancy schedule.. Tie the operation of the ERV into the light switch. The lights in a room are usually on only when occupied. 5. Use a manual timer that the occupants turn to energize the ERV for a specific number of hours. 6. Use a programmable mechanical timer to energize the ERV and indoor blower during occupied periods of the day. 7. Use Bard Part No. 80-056 CO controller for ondemand ventilation. CONTROL WIRING The QWSERV comes wired in the low voltage control circuit from the factory. With the X Remote Thermostat Option, it is default wired into the A terminal, which drives the vent to operate only during occupied periods when using a Bard 80-060 or CS9B Series thermostats. If you prefer for the QWSERV to operate anytime the blower is operational, you will need to install a jumper wire from G to A. If you prefer to use Bard 80-067 CO controller to make the ventilation on-demand, there is a connection adjacent to the thermostat connections in the unit upper right-hand corner, and is marked to match CO controller connections. Furthermore, you will need to field set the CO sensor jumpers per Figure. With the D Door Mounted Thermostat Option, the thermostat is already connected and programmed to operate the QWSERV only during occupied periods. VENTILATION AIRFLOW The ERV is equipped with a -speed motor to provide the capability of adjusting the ventilation rates to the requirements of the specific application by simply changing motor speeds. CFM TABLE VENTILATION AIR (CFM) High Speed () Medium Speed (Blue) The ERV units are wired from the factory on medium intake and low exhaust speeds. The ERV is equipped with independently controlled -speed motor to provide the capability of adjusting the ventilation rates to the requirements of the specific application and to be able to provide positive pressure in the structure. This is accomplished by setting the intake blower on a higher speed than the exhaust blower. WARNING Open disconnect to shut all power OFF before doing this. Failure to do so could result in injury or death due to electrical shock. Moving the speed taps located in the control panel can change the blower speed of the intake and exhaust. See Figure. FIGURE BLOWER SPEED ADJUSTMENT Low Speed (Red) 50 75 00 With the H Door Mounted Thermostat and CO controller, the unit is ready to go with on-demand ventilation as controlled by the CO controller. Manual 00-5E Page of

PERFORMANCE AND APPLICATION DATA Ambient O.D. VENTILATION RATE 50 CFM 65% EFFICIENCY TABLE SUMMER COOLING PERFORMANCE (INDOOR DESIGN CONDITIONS 75 DB/6 WB) VENTILATION RATE 75 CFM 66% EFFICIENCY VENTILATION RATE 00 CFM 67% EFFICIENCY DB/WB F VLT VLS VLL HRT HRS HRL VLT VLS VLL HRT HRS HRL VLT VLS VLL HRT HRS HRL 75 65 580 688 95 977 75 7887 50 577 805 808 786 0 970 590 9587 65 075 05 70 580 580 0 977 977 0 50 50 0 808 808 0 970 970 0 65 65 0 65 580 580 0 977 977 0 50 50 0 808 808 0 970 970 0 65 65 0 80 590 50 90 05 7897 65 65 05 600 77 668 069 060 800 960 0 57 868 75 65 50 9 95 7897 605 7887 05 776 805 668 5 0 800 60 9587 57 60 00 70 5 50 0 809 7897 09 05 68 679 668 85 800 5 557 57 90 65 50 50 0 7897 7897 0 05 05 0 668 668 0 800 800 0 57 57 0 60 50 50 0 7897 7897 0 05 05 0 668 668 0 800 800 0 57 57 0 80 590 970 870 05 68 5 65 800 85 77 55 08 060 680 580 0 9768 75 65 970 7 95 68 76 7887 800 9787 805 55 659 0 680 780 9587 56 95 70 5 970 6 809 68 7 09 800 9 679 55 7 85 680 755 557 75 65 970 970 0 68 68 0 800 800 0 55 55 0 680 680 0 0 60 970 970 0 68 68 0 800 800 0 55 55 0 680 680 0 0 80 590 790 00 05 78 579 65 6075 050 77 009 65 060 860 600 0 56 085 75 65 790 75 95 78 9 7887 6075 8 805 009 7796 0 860 950 9587 56 6 90 70 5 790 506 809 78 90 09 6075 8 679 009 78 85 860 75 557 56 6 65 790 790 0 78 78 0 6075 6075 0 009 009 0 860 860 0 56 56 0 60 790 790 0 78 78 0 6075 6075 0 009 009 0 860 860 0 56 56 0 80 590 860 670 05 59 77 65 050 75 77 67 70 060 0 780 0 70 99 75 65 860 6605 95 59 079 7887 050 87 805 67 9 0 0 070 9587 70 76 85 70 5 860 79 809 59 870 09 050 6 679 67 0 85 0 995 557 70 6 65 860 860 0 59 59 0 050 050 0 67 67 0 0 0 0 70 70 0 60 860 860 0 59 59 0 050 050 0 67 67 0 0 0 0 70 70 0 75 65 0 905 95 579 7 7887 05 586 805 6 069 0 60 690 9587 085 850 80 70 5 0 99 809 579 69 09 05 868 679 6 557 85 60 665 557 085 65 5 0 8 76 579 8 5 05 58 8 6 00 85 60 5 899 085 8 60 0 0 0 579 579 0 05 05 0 6 6 0 60 60 0 085 085 0 70 5 0 5 809 0 809 09 0 09 679 0 679 85 0 85 557 0 557 75 65 5 0 5 76 0 76 5 0 5 8 0 8 85 0 85 899 0 899 60 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 LEGEND VLT = Ventilation Load Total HRT = Heat Recovery Total VLS = Ventilation Load Sensible HRS = Heat Recovery Sensible VLL = Ventilation Load Latent HRL = Heat Recovery Latent Manual 00-5E Page 5 of

TABLE WINTER HEATING PERFORMANCE (INDOOR DESIGN CONDITIONS 70 F DB) Ambient O.D. 50 CFM 80% EFFICIENCY VENTILATION RATE 75 CFM 8% EFFICIENCY 00 CFM 8% EFFICIENCY DB/ F VLT HRS VLS VLT HRS VLS VLT HRS VLS 65 0 9 86 05 60 85 60 8 9 60 860 888 97 050 80 770 0 656 58 55 790 58 58 6075 90 5 860 985 875 50 970 7776 9 800 656 59 680 5 66 5 50 970 0 05 80 9 800 66 58 0 580 66 96 50 98 09 970 7970 750 5 700 608 0 75 8 69 0 998 0 0 90 555 888 600 078 960 067 5 870 796 7 85 76 6 580 955 6 0 00 90 860 050 60 88 600 8 96 5 670 8 56 75 80 780 6 08 0 960 8 58 00 968 67 90 59 99 5 590 57 68 65 500 060 769 79 0 00 76 680 850 96 587 680 8598 08-5 650 960 790 075 60 577 00 996 7-0 8880 0 7776 00 6 656 590 5 666 NOTE: Sensible performance only is shown for winter application. LEGEND VLT = Ventilation Load Total HRS = Heat Recovery Sensible VLS = Ventilation Load Sensible ENERGY RECOVERY VENTILATOR MAINTENANCE GENERAL INFORMATION The ability to clean exposed surfaces within air moving systems is an important design consideration for the maintenance of system performance and air quality. The need for periodic cleaning will be a function of operating schedule, climate, and contaminants in the indoor air being exhausted and in the outdoor air being supplied to the building. All components exposed to the airstream, including energy recovery wheels, may require cleaning in most applications. Rotary counterflow heat exchangers (heat wheels) with laminar airflow are self-cleaning with respect to dry particles. Smaller particles pass through; larger particles land on the surface and are blow clear as the flow direction is reversed. For this reason the primary need for cleaning is to remove films of oil based aerosols that have condensed on energy transfer surfaces. Buildup of material over time may eventually reduce airflow. Most importantly, in the case of desiccant coated (enthalpy) wheels, such films can close off micron sized pores at the surface of the desiccant material, reducing the efficiency with which the desiccant can absorb and exude moisture. FREQUENCY In a reasonably clean indoor environment such as a school, office building, or home, experience shows that reductions of airflow or loss of sensible (temperature) effectiveness may not occur for ten or more years. However, experience also shows that measurable changes in latent energy (water vapor) transfer can occur in shorter periods of time in commercial, institutional and residential applications experiencing moderate occupant smoking or with cooking facilities. In applications experiencing unusually high levels of occupant smoking, such as smoking lounges, nightclubs, bars and restaurants, washing of energy transfer surfaces, as frequently as every six months, may be necessary to maintain latent transfer efficiency. Similar washing cycles may also be appropriate for industrial applications involving the ventilation of high levels of smoke or oil based aerosols such as those found in welding or machining operations, for example. In these applications, latent efficiency losses of as much as 0% or more may develop over a period of one to three years. Manual 00-5E Page 6 of

CLEANABILITY AND PERFORMANCE In order to maintain energy recovery ventilation systems, energy transfer surfaces must be accessible for washing to remove oils, grease, tars and dirt that can impede performance or generate odors. Washing of the desiccant surfaces is required to remove contaminate buildups that can reduce adsorption of water molecules. The continued ability of an enthalpy wheel to transfer latent energy depends upon the permanence of the bond between the desiccant and the energy transfer surfaces. Bard wheels feature silica gel desiccant permanently bonded to the heat exchange surface without adhesives; the desiccant will not be lost in the washing process. Proper cleaning of the Bard energy recovery wheel will restore latent effectiveness to near original performance. MAINTENANCE PROCEDURES NOTE: Local conditions can vary and affect the required time between routine maintenance procedures, therefore all sites (or specific units at a site) may not have the same schedule to maintain acceptable performance. The following timetables are recommended and can be altered based on local experience. QUARTERLY MAINTENANCE. Inspect mist eliminator/prefilter and clean if necessary. This filter is located in the wall sleeve and can be accessed by either removing the exterior louver grille, the vent package from inside the unit, or by disconnecting the unit from the wall brackets, and rolling the unit away from the sleeve on its integral wheel system. The filter is an aluminum mesh filter and can be cleaned with water and any detergent not harmful to aluminum.. Inspect the ERV exhaust air pre-filter and clean if necessary. This filter is located behind the return air grille on the unit (accessible by swinging up the hinged filter/access front service door).. Inspect the comfort air filter and clean or replace as necessary. This filter is located behind the fronthinged service door.. Inspect energy recovery ventilator for proper wheel rotation and dirt buildup. This can be done in conjunction with Item above. Energize the energy recovery ventilator after inspecting the filter and observe for proper rotation and/or dirt buildup. 5. Recommended energy recovery wheel cleaning procedures follow: Disconnect all power to the unit. Open the front-hinged service door to the unit. 6. Remove the front cassette retaining panel from the front of the ERV. Unplug the amp connectors to the cassette drive motor. Slide energy recovery cassette out of the ventilator. 7. Use a shop vacuum with brush attachment to clean both sides of the energy recovery wheels. 8. Reverse shop vacuum to use as a blower and blow out any residual dry debris from the wheel. NOTE: Discoloration and staining of the wheel does not affect its performance. Only excessive buildup of foreign material needs to be removed. 9. If any belt chirping or squealing noise is present, apply a small amount of LPS- or equivalent dry film lubricant to the belt. ANNUAL MAINTENANCE. Inspect and conduct the same procedures as outlined under Quarterly Maintenance.. To maintain peak latent (moisture) removal capacity, it is recommended that the energy recovery wheels be sprayed with a diluted nonacid based evaporator coil cleaner or alkaline detergent solution such as 09. NOTE: Do not use acid based cleaners, aromatic solvents, temperatures in excess of 70 F or steam. Damage to the wheel may result. Do not disassemble and immerse the entire heat wheel in a soaking solution, as bearing and other damage may result.. Rinse wheel thoroughly after application of the cleaning solution, and allow to drain before reinstalling.. No re-lubrication is required to heat wheel bearings of the drive motor, or to the intake and exhaust blower motors. 5. If any belt chirping or squealing noise is present, apply a small amount of LPS- or equivalent dry film lubricant to the belt. Manual 00-5E Page 7 of

FIGURE BELT REPLACEMENT INSTRUCTIONS Route () replacement belt in top groove of pulley. Belt Replacement Instructions Route () replacement belt in bottom groove of pulley. If belts "squeak" or "chirp" lubricate lightly with LPS- or equivalent "dry film" lubricant. MIS-66 Manual 00-5E Page 8 of

FIGURE HUB ASSEMBLY WITH BALL BEARINGS Manual 00-5E Page 9 of

WIRING DIAGRAM FOR 90-007 QWSERV! *ELECTRICAL SHOCK HAZARD *DISCONNECT POWER BEFORE SERVICING. Note: See Control Wiring Section of Installation Inst. for Wiring Energy Recovery to Unit Power Plug Control Plug 7 5 6 7 8 9 0 COM 08 0 80 5 8 (High Speed) Blue (Med. Speed) Red (Low Speed) 6 5 5 5 5 8 8 8 8 Speed Plug 0 V Term. Block Speed Plug Speed Plug To Unit High Voltage 0/08-60- 0 V Damper Damper 6 6 6 6 9 0 9 Control Relay Brown/ Green! (High Speed) Blue (Med. Speed) Red (Low Speed) Transformer Red Red WARNING USE COPPER CONDUCTORS Brown/ ONLY SUITABLE FOR AT LEAST Red/ 75 C. Speed Plug Control Relay Brown Green Yellow Brown Blk/Red DANGER Power Plug Ground Com 80V Transformer Control Relay Yellow 08V Brown/ Red Red/ Brown/ Component /70 /50 Green DISCONNECT ORANGE WIRE FROM TERMINAL BLOCK AND CONNECT RED WIRE FOR 08V OPERATION 8 7 6 5 Note: See Control Wiring Section of Installation Inst. for Wiring Energy Recovery to Unit -00 B Manual 00-5E Page 0 of

WIRING DIAGRAM FOR 90-08 QWSERV WITH INTELLIGENT DEFROST! *ELECTRICAL SHOCK HAZARD *DISCONNECT POWER BEFORE SERVICING. Note: See Control Wiring Section of Installation Inst. for Wiring Energy Recovery to Unit Power Plug Control Plug 7 5 6 7 8 9 0 COM 08 0 80 (High Speed) Blue (Med. Speed) Red (Low Speed) (High Speed) Blue (Med. Speed) Red (Low Speed) 0 V T Blue T6 Timer T Term. Block Green! Brown Green Brown Transformer Red Red Control Relay T T6 T Damper Blk/Red DANGER WARNING USE COPPER CONDUCTORS ONLY SUITABLE FOR AT LEAST 75 C. 5 Damper Yellow Gray Yellow Green Power Plug To Unit High Voltage 0/08-60- Ground Control Relay Speed Plug Com 0 V Yellow Note: See Control Wiring Section of Installation Inst. for Wiring Energy Recovery to Unit 08V Speed Plug Brown/ Red/ 80V Transformer Brown/ Red 8 6 5 5 5 5 8 8 8 8 Speed Plug T-Stat 0 DISCONNECT ORANGE WIRE FROM TERMINAL BLOCK AND CONNECT RED WIRE FOR 08V OPERATION 7 0 T-Stat Speed Plug Timer 0 9 8 7 6 0 6 6 6 6 Red/ Brown/ 5 Control Relay Component /70 /50 7-0 A Manual 00-5E Page of

FIGURE CONFIGURING 80-067 CO CONTROL VOLTAGE OUTPUT SET JUMPER PJ5 AS SHOWN C V SET JUMPER PJ TO VOLTAGE AS SHOWN VOLTAGE OUTPUT TO 0 V TO 0 ma C V SET JUMPER PJ TO CURRENT AS SHOWN MIS-75 Manual 00-5E Page of