Not to be distributed outside offmapprovals and its affiliates except by Customer

Similar documents
Not to be distributed outside of FM Approvals and its affiliates except by Customer APPROVAL REPORT. BU-110 and BV-110 Loop Based Displays

Approval Standard for Radiant Energy-Sensing Fire Detectors for Automatic Fire Alarm Signaling

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH SHP-PRO CONTROL PANEL

TECHNICAL DATA. Humidity: 85% Relative Humidity (non-condensing) at 90 F (32 C) maximum.

MODEL ZAC ZONE ANNUNCIATOR/CONTROLLER DESIGNED FOR ZONE ANNUNCIATION AND MONITORING

TECHNICAL DATA. multi-hazard. model vfr400. Release Control Panel 290a. January 16, 2014

Bold items are particular to the City of Euless

TECHNICAL DATA OBSOLETE

DATA SHEET CYBERCAT 254 INTELLIGENT FIRE ALARM CONTROL SYSTEM DESCRIPTION APPROVALS: SYSTEM OPERATION. Form No. D

30.45 Electric Release PDRP-2001

CHEETAH XI INTELLIGENT SUPPRESSION CONTROL SYSTEM

Functional Performance Test

FireSystem 2000 Commercial and Light Industrial Fire Alarm Control Panel

Commercial and Light Industrial Fire Alarm Control Panel

SPECIFICATION FOR A TOTAL FLOOD ECARO-25 TM CLEAN AGENT FIRE SUPPRESSION SYSTEM FOR USE WITH THE CHEETAH Xi 50 CONTROL PANEL SYSTEM

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH CHEETAH Xi 50 CONTROL PANEL

Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions.

Installation, Operating and Maintenance Manual

SPECIFICATION FOR A TOTAL FLOOD ECARO-25 TM CLEAN AGENT FIRE SUPPRESSION SYSTEM FOR USE WITH THE SHP PRO CONTROL PANEL SYSTEM

APPROVAL REPORT. J.l. 3ZOA9.AX

ACC-25/50ZST. Zoned System Voice with Telephone Evacuation Control Panel

DATA SHEET CHEETAH XI 50 INTELLIGENT SUPPRESSION CONTROL SYSTEM DESCRIPTION APPROVALS: SYSTEM OPERATION. Form No. D

Certificate of Compliance

ECC-50/100C. Emergency Command Center

Model 3300 Technical Support and Installation Manual

Conventional Releasing Control Panel

SPECIFICATION FIKE CLEAN AGENT FIRE SUPPRESSION SYSTEM WITH IMPUSLE VALVE, Fike FK AGENT & SHP PRO CONTROL PANEL

SECTION AUTOMATIC TRANSFER SWITCHES

SECTION TOTAL FLOODING ECARO-25 CLEAN AGENT FIRE EXTINGUISHING SYSTEM

Syncro Matrix Analogue Addressable Fire Alarm Mimic Panel Product Manual

Specification/ Data Sheet

Model 17A00 Expansion Enclosure

SPECIFICATION FIKE CLEAN AGENT FIRE SUPPRESSION SYSTEM WITH IMPULSE VALVE, FK AGENT & CHEETAH Xi 50 CONTROL PANEL

FEC400 Series. Installation Manual

ECC-50/100(E) Emergency Command Center. General. Features. Emergency Voice Evacuation TYPICAL APPLICATIONS

SPECIFICATION FIKE CLEAN AGENT FIRE SUPPRESSION SYSTEM WITH IMPULSE VALVE, FK AGENT & CHEETAH Xi CONTROL PANEL

NFPA 72 Code Changes vs 2013

MS-4012/4024 and CMS-4012/4024. Instruction Manual for the. Fire Alarm Control Panels

RED1. Technical Support And Installation Manual. Models ST, E1, E2, E3, E4, and 420. Approved

Report No EC. 1 Windsor Dials, Windsor, Berkshire, UK. SL4 1RS ATEX CERTIFICATION REPORT. Electronstandart-pribor

Not to be distributed outside of FM Approvals and its affiliates except by Customer APPROVAL REPORT

Data Sheet Fire Safety & Security Products. System Overview. Initiating Circuits SXL-EX FACP 7906

CERTIFICATION BULLETIN

TECHNICAL DATA SHEET CONVENTIONAL FIRE ALARM SYSTEMS Conventional Fire Alarm Control Panel

Application, Installation, Operation & Maintenance Manual

NetworX Series NX-870E Fire Supervision Module Installation and Startup

Rancho Cucamonga Fire Protection District Prevention Bureau Standard

FIRE ALARM CONTROL EQUIPMENT. Addendum October 2006 Instructions for new style EN54-4 Power supply unit module

www. ElectricalPartManuals. com GADD MKIII Ground Fault Indication System Instruction Manual Ground Fault Protection

Across-the-Line SERIES MP300 Combined Manual and Automatic

RPSMLR2 RPSMLR2BB. Panic Device Power Controller Installation Guide LISTED. Rev

PWGSC Ontario MULTIPLEX FIRE ALARM SYSTEM Sect Region Project Page 1 Number R

EXTINGUISHING AGENT RELEASE MODULE

4100U City and Relay Cards Installation Instructions

Multi-Spectral, Digital, Infrared Electro-Optical. FSC Model No. s. Unitized, Two Stage, Quick Response Flame Detectors.

The following information shall become and form part of the contract documents.

Features. Omni2 Door Warning Sign Alarm Annunciator DATASHEET. Model C1190B Door Warning Sign

FIREFORCE 8 NOTIFICATION APPLIANCE CIRCUIT EXPANDER INSTALLATION & OPERATION MANUAL

AEGIS FEATURES DESCRIPTION. Conventional Fire Alarm-Suppression Control Unit. Effective: March Programmable Relays

July 14, 1999 DF C-100.

Event Detection System (EDS)

MR-2602 Two Zone Fire Alarm Control Panel

SECTION (13730) - INTRUSION DETECTION

DIESEL Engine Fire Pump Controllers Features

SP-1000X. Panic Device Power Controller Installation Guide. Rev

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel

GENERAL STANDARD FEATURES. ISO-9001 Engineering and Manufacturing Quality System Certified to International Standard ISO-9001 PATENT PENDING

RAPID RESPONSE Model RCP-1 Residential Control Panel 1 or 1-1/2 Inch (DN25 or DN40), 175 psi (12,1 bar) General Description.

RELEASE DEVICE CONTROLS

ECC-50/100(E) Emergency Command Center

ANNUNCIATOR FIXED MODULE

/9308 External Battery Chargers Installation Instructions

Variable Frequency Drive SERIES MP800 VFD

MODUL-R FIRE ALARM CONTROL PANELS. MR-2900/MR-2920 Addressable Fire Alarm Control Panels MEA. Features. Description

Report on First Revision November 2013 NFPA 731

Operating & Maintenance Manual. Alert-4 Ethernet LCD Master Alarm

MODEL B2 INSTALLATION MANUAL

RE 102 RE Fire Alarm Control Panel. Installation, Commissioning & Operating Manual

RAPID RESPONSE Model RCP-1 Residential Control Panel 1 or 1-1/2 Inch (DN25 or DN40), 175 psi (12,1 bar) General Description

LifeAlarm Fire Alarm Control Panels

DS7400Xi Addressable Control/ Communicator

MADE IN THE U.S.A. ADVANCE FIRE CONTROL MODEL LM21-AFC MANUAL RELEASE DEVICES TEST WEEKLY TO ASSURE PROPER OPERATION OF RELEASE DEVICE/CONTROL PANEL

Matrix2000. User Guide - CPD Advanced Analog Fire Alarm Control Panel 4 24 Zones. Version: 2.0 Revision: 1

FIREFLY II PLUS RELEASE DEVICES INSTALLATION MANUAL

INSTALLATION GUIDE XR5FC AND XR5SL COMMERCIAL FIRE PANELS

Unified Fire Authority - Fire Prevention Bureau

OSU PROJECT NO PAGE 1 02 NOV 2006 SECTION FIRE ALARM SYSTEM

Soft Start Series MP700 Solid State, Reduced Voltage

PSN-1000 & PSN 1000(E) Installation Manual

TECHNICAL MANUAL UNIT, INTERMEDIATE DIRECT SUPPORT AND INTERMEDIATE GENERAL SUPPORT MAINTENANCE MANUAL (INCLUDING REPAIR PARTS AND SPECIAL TOOLS LIST)

Fire Safety. Installation Instructions Model SMB-2 Main Control Board OPERATION INSTALLATION

Cautions and Warnings. Introduction 4009 NAC POWER EXTENDER

good things in small packages

OJD ITB No Attachment E Duress Alarm Equipment Specifications

This wiring diagram describes circuit connections for all models of the Series Quaestor-SZU Releasing Fire Control

Approval Standard for Electric Equipment for use in Hazardous (Classified) Locations General Requirements

www. ElectricalPartManuals. com GADP Ground Fault Indication System Instruction Manual Ground Fault Protection

Installation Guide for AL600ULM. Multi-Output Access Control Power Supply Charger. Rev

PEGAsys. Multi-Loop Intelligent Suppression Control System FEATURES DESCRIPTION. Effective: March 2007 K

Architect s Project Number of 12 Fire Alarm/Smoke Detection Systems District Master Specs 2013 Edition

Transcription:

Not to be distributed outside offmapprovals and its affiliates except by Customer APPROVAL REPORT MODELS CC-7000 Spark Extinguishing System and Modifieations to FM 1/8 and FM 3/8 Spark Deteetors Prepared for: FAGUS-GRECON GRETEN GmbH & CO, Ine. 0-3220 Alfeld/Hannover P.O. Box 1530 Federal Republic of Germany Projeet ID: 3021347 Class: 3260 Date of Approval: Authorized by: FM Approvals 1151 Boston-Providence Tumpike PO Box 9102? Norwood, MA 02062 Page 1 of 11 Enterprise

Model CC 7000 Spark Extinguishing System and Modifieations to FM 1/8 and FM 3/8 Spark Oeteetor from FAGUS-GRECON GRETEN GmbH & CO, Ine. 0-3220 Alfeld/Hannover P.O. Box 1530 Federal Republie af Germany I INTRODUCTION 1.1 Fagus-Grecon requested an Approval examination of the new Model CC7000 programmable spark extinguishing controller. This report covers the control console, il' s enclosure, detectors and extinguishing assemblies. The controller, detectors and extinguishing set as a system are suitable for use as a water spray extinguishing system for pneumatic material handling systems. 1.2 Approval is limited to the Model CC-7000 controller when used with application software version 1.4. 1.3 This report covers the new generation control console (cc70xx) and replaces the previously Approved BS 7 series detailed in Approval Report OT1A2.AY (November 18, 1992). 1.4 In addition, this report supplements the previous examinations of the series 8 detectors and extinguishing set covered in Approval Report OX7A2.Ay (August 26, 1994). Detector form, fit and function remain identical to previous, but components have been updated to surface mount components vs. the old through-hole design. 1.5 This Report may be freely reproduced only in its entirety and without modification. 1.6 Standards: Title Class Number Date National Fire Alarm Code ANSIINFPA 72 2002 Radiant Energy Flame Detectors ANSIIFM 3260 2004 1.7 Listing: The product will appear in the Approval Guide, a publication offm Approvals: WATER SPRAY EXTINGUISHING SYSTEM for Pneumatic Material Handling Systems Page 2 af 11

Type BS-7000 spark extinguishing system with operating software version 1.4. Each system consists of a CC-7004, 7020 or 7036 control console suitable for use -10 to 40 C (14 to 104 P). Each enclosure contains a Local Alphanumeric Display, intemal Master Module and power supplies with (7, 120r 24AH) battery supply suitable for at least four hours of standby operation. Common system Alarm and Trouble contacts are provided for connection to local alarm systems. Each enclosure can support either 4, 20 or a maximum of 29 Line Modules that power four separate zones of protection via FM 1/8 or FM 3/8 spark detectors with the KK 1/8 junction box and extinguishing set as described below. The FM 1/8 and FM 3/8 detectors, KK 1/8 and KK9/1 junction box are suitable for use -40 to 160 0 P (-40 to 70 C). Remote fiber optic viewers (1M and 2M) for use with the FM 3/8 detectors are rated for -40 to 660 0 P (-40 to 350 C). Each system will include one or more extinguishing assemblies (designated as LS-1, -2 or -3) suitable for 32 to 130 0 P (0 to 55 C) consisting ofbuchjost 849xxxx series valve marked 3511, 4163, 4164, 4165, 4166 plus a 12 or 24 V dc Herion solenoid marked 0200 or a 24 V dc Buschjost Solenoid 9332.02400 and brass or stainless steel nozzles marked k24, k30, k45 and k66. The system is suitable for use in ducts from 200 to 1200 mm (8 to 48 in.) in dia., with air velocities from 1 to 50 mps (200 to 10,000 fpm). A water supply capable of providing at least 70 L/min. (18 gpm) at a residual pressure of 4 bars (60 psi) is required for each nozzle. Time for establishment of water spray is fixed at 0.2 sec after initial spark recognition. The duration of water spray activated by each spark is adjustable from 3 to 99 sec. The detectors are responsive in the 0.8 to 1.1 micron range. FM 1/8, FM 3/8 and KK 1/8 are rated IP65. The control panel has provision for a max of 4, 20 or 116 zones of detection dependant on panel size. 1.8 Except as described in this report, components and applications described in the manual and literature are not covered by this Approval. The environmental ratings of the enclosure have only been evaluated for general electrical safety and interior use applications. Any other claims have not been verified by FM Approvals. II DESCRIPTION 2.1 This section briefly describes the features and functions of the Model BS 7000 spark extinguishing system. A more detailed description may be found in the Instruction Manual, Document No. 600473 02 O. Portions ofthat manual are attached to this report. 2.2 This CC 70xx, or control console is integral to the BS 7000 family of controis. The BS 70xx controller is of modular construction and available in configuration from 4 to 116 zones of sensor (detection) points. 2.3 The CC-70xx is a modular microprocessor based control consisting of an enclosure with integral local alpha-numeric annunciator display and user interface. The intemal (UPS) power supply and battery charger are independent of an internal DIN rack system used to mount all other modules. 2.4 Enclosure - The CC-70xx enclosure, available in three different configurations, referred to as cc7004, cc7020 and cc7036. A painted, 14 gauge metal enclosure {400mm (16in) x 600mm (24in.) x 250mm (10in), 800mm (32in) x 600mm (24in) x 300mm (12in) and 2200mm (86in x 800mm (32in) x 600mm (24in)} of dead front construction. Entry to any circuits is suitably restricted via a keyed lock. 2.5 Local Alphanumeric Annunciator - Visible on the front door of the control is the main human interface with separate areas for displaying common system indicators, LED's and operator keys. The large alphanumeric display provides additional information via plain text. Page 3 af 11

2.6 UPS Power Supply (AKKUTEC 2402, 2410 & 2420) - Are dual voltage 120/240VAC supplies rated at 2, 10 or 20A of filtered and regulated 24VDC power to the control console and connected peripherals. Contains internal connections and supervision circuitry for secondary power source consisting of; 24VDC battery array available in 7, 12, or 24 amp hour ratings. 2.7 Master Module - One required per system and acts as the main processor that operates the front display, monitors the internal power supply and maintains bus communication with up to 29 Line Modules. Common system Alarm and Trouble outputs via dry form C contacts are provided. 2.8 Line Module - Bach Line Module provides four separate connection points for GreCon FM 1/8 and 3/8 spark detectors and four releasing circuits for connection to the GreCon solenoid extinguishing set. In addition, four outputs extinguishing circuits, one for each zone are provided. 2.9 RestrictedlLimited Access - In addition to the key-iocked enclosure restricting the user from access to the internal wiring, keypad access is only granted after execution of a proper password further restricting access to the user definable option. 2.10 FM 1/8, FM 3/8 Spark Detectors - Both detectors utilize the electrical circuits and enclosure as tested previously. New surface mount electronics are contained on a single circuit board. The single element FM 1/8 detector and the triple element FM3/8 differ in mounting techniques and application, but otherwise utilize the same circuitry. The FM 3/8 has provisions for connection to high temperature fiber optic polyps allowing the detector to mount remotely from the high temp application. 2.11 KK 9/1 Junction Box - This new version termination (junction) box utilizes the identical enclosure as tested previously. It provides three separate input circuits for connection of drycontact input devices. III EXAMINATIONS AND TESTS 3.1 One sample each of the CC 7004, 7020, 7036 console as well as samples of the FM 1/8 and FM 3/8 detectors and KK 1/9 junction box has been and examined at FM Approvals in Norwood, MA. These samples, considered to be representative of the product line and included as a minimum, one sample of each plug-in module with additional optional modules used to complete the enclosure at its maximum capacity. The equipment as supplied and tested was compared to the manufacturer's documentation and drawings. All data is on file at FM Approvals along with other documents and correspondence applicable to this program. 3.2 Normal Operation - The Model CC7000 spark extinguishing alarm control was tested to verify proper operation under normal conditions. The system performed as described below and in the Installation, Operation and Instruction Manual. A normal condition is indicated by the illumination of the green "Operation" and "AC Mains" indicator lamps. 3.3 Trouble Signals - Trouble signals and their restoration to normal shall be indicated within 200 seconds. A switch for silencing the audible trouble signal is permitted only if it transfers the trouble indication to a lamp or other acceptable visible indicator adjacent to the switch. The visual indication shall persist until the trouble has been corrected. It was verified that the audible trouble signal sounds if the switch is placed in the "silence" position and no trouble exists. 3.3.1 Fault conditions (single open, single ground, and wire to wire shorts) were introduced on extemal circuits. The trouble signal was annunciated audibly at the control and visually by the Page 4 af 11

illumination of the yellow "Trouble" LED with the individual problem identified on the alphanumeric display. Both audible and visual indications remained until the trouble condition was corrected. 3.3.2 It was verified that the manual means for de-activating the "Trouble" signal resides behind a keylocked door. This is satisfactory. 3.4 Alarm Signals - Alarm signals and their restoration to normal shall be annunciated within 10 seconds and produce a distinctive signal. A switch for silencing the alarm signal sounding appliances shall be permitted only if it is key operated or located within a locked cabinet. Such a switch shall be permitted only if it transfers the alarm indication to a lamp or other acceptable visual indicator, and subsequent alarms in other zones will operate the alarm signal sounding devices. 3.4.1 Alarm conditions were introduced on the initiating device circuits. The alarm signal was annunciated audibly and visually indicated on the control by the flashing or intermittent illumination of the red "Alarm" LED. Additional text appeared on the alpha numeric display indicating the affected zone and type of device as well as the operation of output circuits as required. 3.4.2 It was verified that the manual means for de-activating the "Alarm" signaloperated properly silencing the local audible and notification appliance circuits, provided a visual indication land resided behind a key-iocked door. 3.4.3 It was verified that subsequent alarm signals from different zones were properly displayed and caused re-activation of the notification appliance circuits. 3.5 Environmental Tests - Samples of the BS 7000 system were conditioned at the foliowing temperature extremes as described below: 3.5.1 cc7004 Control Console - 16 hours at -10 C (14 F) and 40 C (104 F) and 24 hours at 38 C (100 F) with 90% relative humidity. 3.5.2 FM 1/8 and FM 3/8 Spark Detectors and KK 9/1 Junction Box - 16 hours at -40 C (-40 F) and 70 C (160 F) and 24 hours at 38 C (100 F) with 90% relative humidity. 3.5.3 Proper operation was observed both during and after eachof these environmental exposures. 3.6 Voltage Variation Tests - The input power was varied from 85% to 110% ofrated voltage (102 to 132Vac primary and 20.4 to 26.4Vdc secondary) to the control console. The control and connected peripherals operated as intended overthese entire voltage ranges. This is acceptable. 3.7 Circuit Performance - The initiating device circuits, the notification appliance circuits, and the releasing circuits were tested to verify that they met the intent of the appropriate performance requirements as described in ANSIINFPA 72-2002 National Fire Alarm Code. Open, ground, wire to wire short, combination open and ground faults were introduced through the appropriate circuit. 3.7.1 lnitiating Device Circuits - The 3-wire spark detector initiating device circuits of the cc70xx control console, KK1/8 and KK9/1 junction box were verified to meet the intent of Class B (Style A) operation as defined by Table 6.5 ofnfpa72-2002. Page 5 af 11

3.7.2 Notification Appliance Circuits - It was verified that the output circuits of the cc70xx are nonsupervised and therefore must be located within the same room of origin as the cc70xx console. This is satisfactory since the primary purpose of this control is process protection and not that of an evacuation unit. 3.7.3 Releasing Circuit - It was verified that the release circuits of the cc70xx were properly supervised for open, short and single ground fault conditions. 3.8 Secondary Power Supply Test - The secondary (standby) power supply shall automatically supply the energy to the system within 10 seconds, and without loss of signals, whenever the primary supply is incapable of providing the minimum voltage required for proper operation. 3.8.1 Transfer to the secondary power supply was accomplished automatically and in less than 10 seconds upon loss of primary power to the control. The loss of primary Ae power was indicated within 60 seconds by the illumination of the yellow "Trouble" LED and illumination of the "Mains" LED and the sounding of the local audible annunciator. 3.8.2 The transfer to secondary power was observed at 85V ac. The equipment continued to operate properly down to the transfer point and after transfer while on secondary power. 3.8.3 It was verified that secondary power is properly supervised from accidental disconnect (line break) and operationlfailure of the battery charger circuit protection fuse (FBat). 3.8.4 It was verified that return to primary power occurred at approximately 102V ac and the "Trouble" cleared automatically (non-latching) 3.9 Battery Discharge and Recharge Test - After a fully charged battery is subjected to a single discharge cycle (4 hours standby and 10 minutes in full alarm load), the charging current shall be such that after 48 hours, the battery is retumed to a fully charged condition. 3.9.1 The two 12 V dc 24AH batteries were charged for more than 48 hours and the battery voltage was observed to be 27.2 V dc, and the charging current was observed to be 0.010 A. 3.9.2 The power supply was configured to draw 2.9 A (the maximum standby load specified by the manufacturer), and the primary power supply was disconnected. The battery voltage decreased to 23 V dc after 4 hours of discharge. A 10 minute Alarm load of 6.0 A was then applied to the control. All output circuits remained above 20 V dc. 3.9.3 The primary power was then reconnected, and the initial charging current was <1.0 A. The batteries were allowed to charge for 48 hours. At the end of 48 hours, the trickle current was measured to be 0.020 A, and the float voltage of the batteries was measured at 27.2 V dc, which indicated a fully recharged battery. 3.10 Electrical Safety Tests 3.10.1 Protective Grounding - Accessibie conductive parts of the equipment that are likely to become energized in the event of a fault shall be properly grounded. A suitably sized and properly labeled ground connection is provided in the control panel. The resistance from all surfaces likely to be energized was measured to the ground connector. The maximum resistance was less than one ohm in all cases. Page 6 af 11

3.10.2 Eleetrieal Shoek - Examination showed that accessibility to the 120 VI 240 V ac power supply was suitably restricted by the locked steel cabinet. 3.10.3 Nameplate Rating - With the maximum loading on the power supply, the input load drawn must not exceed 110% of the marked input load rating of loa at 120 Vac. Testing showed that the maximum input load was 5A at 132 Vac with a full 18 load on the power supply, which is acceptable. 3.10.4 Dieleetrie Test - A test voltage of 1,240 Vac was applied for one minute between the power terminals and system ground. There was no dielectric breakdown observed during this test. 3.10.5 Battery Cireuit Reverse Polarization - The battery system was observed as using polarized connectors would not allow for miss-connection during installation. As aresult, this test was waived with satisfactory results. 3.11 Vibration Test - ane sample of the AKKUTEC 2402 was mounted in it's normal position and subjected to a four-hour vibration test of 0.02 inches (0.5 mm) displacement at a frequency sweep of 10 to 30 Hz. The equipment operated properly during and after this vibration test, and there was no loosening of parts or permanent deformation as aresult of this test. 3.12 Radio Fregneney Interferenee (RFI) - Although not an Approval requirement, the foliowing test was performed on the Model cc7004 controls with the FM 1/8 and 3/8 detectors connected: The powered control was subjected to voice modulated and un-modulated radio signals having frequencies of 154 MHz, 467 MHz, and 854 MHz with radiation power levels equivalent to 5.0 Watts from a distance of 0.61 m (24 in.). The controls did not false alarm or display any signs of instability as aresult of this test. IV MARKING 4.1 The foliowing information appears on the equipment identified in Section 1.7 and meets Standard requirements: Manufacturer's name and manufacturing location. Serial number and date code (on separate adhesive label) Maximum electrical input and output ratings The FM Approval Mark 4.2 The software/frrmware version (1.4) and ~erial number are displayed on the Alpha-numeric display by accessing the "System Info" level via the password protected keypad. Refer to Installations Manual for more information. V REMARKS 5.1 Extreme care should be taken with the installation of this equipment. The latest edition of the manufacturer's instruction manual must be followed completely, and any problems should be resolved by consultation with the factory or the authorized representative. 5.2 All installation wiring shall be in accordance with the appropriate national electrical code. (ANSIINFPA 70). Page 7 af 11

5.3 An Approval examination of programmable equipment such as this can only evaluate typical configurations. Although those components identified in this report have been tested, it is beyond the scope of such an examination to test all possibie configurations. It is necessary, therefore, that those responsibie for the setup and acceptance of specific installations take special care to verify that the equipment, including programmable functions, is configured to operate properly for the required performance of that installation. 5.4 Because of the extreme sensitivity of the.spark detectors and their response to visible light, installation in a totally dark environment is required. 5.5 A weekly test procedure should be established, which includes an individual check of each detector using a portable light source (such as a flashlight) foliowing the manufacturers recommendation to verify proper operation. A complete maintenance schedule for testing and cleaning the lens of each detector should be foliowed. 5.6 The automatic test feature of the BS 7000 system should be employed, but by itself it can not be considered as a replacement for periodic visual inspections and cleaning as required. 5.7 The system is intended to protect a specific hazard: sparks or embers in the duct system. It should not be considered a substitute for general fire protection apparatus, including appropriate sprinkler protection. 5.8 Systems should not be used where an extreme change in temperature or humidity are anticipated which couldresult in condensation on the lens ofthe detector. 5.9 The adequacy of the water supply must be assured for effective operation of the system. Valves controiling the system supply should be adequately protected against improper closing and precautions should be taken to maintain the temperature of the water supply lines and valves above the freezing point. 5.10 This BS 7000 system is an alarm system designed to protect a particular hazard and can not be used as a protected premises fire alarm system intended for building evacuation unit as defined in NFPA 72, The National Fire Alarm Code. However, it does provide dry Form "C" Alarm and Trouble contacts that may interface with a variety of Approved local alarm signaling systems. 5.11 When disconnecting the extinguishing system discharge for testing and/or maintenance, the extinguishing system must be isolated mechanically and not solely by electrically disconnecting the equipment and not by the software programming. VI FACILITIES AND PROCEDURES AUDIT The manufacturing site in AlfeldIHannover Germany is currently included in the FM Approvals Facilities and Procedures Audit (F&PA) program. The facilities and quality control procedures in place have been found to be satisfactory to manufacture product identical to that examined and tested as described in this report. VII MANUFACTURERS RESPONSIBILITIES 7.1 The manufacturer shall provide instructions for installation, operation, and maintenance with each unit. Page 8 af 11

7.2 As part of the listing requirements, FM Approvals requires assurance that subsequent systems produced will present the same quality and reliability as the system examined. The manufacturer shall maintain a Quality Assurance Program, which includes as a minimum: incoming, inprocess, and final inspection and testing; equipment calibration, and drawing change control. The specific procedures used to control quality are best determined by the manufacturer. 7.3 Documentation considered critical to this Approval is on file at FM Approvals and listed in the Documentation File, Section VIII of this report. No changes of any nature shall be implemented unless notice of the proposed change has been given and written authorization obtained from FM Approvals. The Approved Product Revision Report, Form 797, shall be forwarded to FM Approvals as notice of proposed changes. 7.4 Since the power supply (UPS) is rated above 30 Vrms, it is required that the final assembly of all ARC-l controls be dielectric tested on 100% of production. The power input connections shall withstand, for one minute and with no insulation breakdown, the application of 1000 V ac (or 1400 V dc) with respect to the protective ground. Altematively, a test potential of 1200 V ac (or 1700 V dc) may be applied for at least one second. WARNING: The dielectric test required may present a hazard of injury to personnel and/or property and should only be performed under controlled conditions, and by persons knowledgeable of the potential hazards of such testing to minimize the likelihood of shock and/or fire. 7.5 Each fully assembled control console (cc70xx) shall be tested for continuity of the protective grounding system on 100% of all production. Page 9 af 11

IX CONCLUSION The system described in 107 meets FM Approvals requirementso Since a duly signed Master Agreement is on file for this manufacturer, Approval is effective the date of this report. EXAMINATION AND TESTING BY: Ro Wo Elliott PROJECT DATA RECORD: 3021347 ATTACHMENTS FM 1/8 Sensor (600279 12 O, 1pg) FM 3/8 Sensor (600284 12 O, 1 pg) BS-7000 Instruction Manual (Cover & Pgs 14 through 27, 15 pgs) (17 attachment pages total) REPORTBY: REPORT REVIEWED BY: ~6ittJ~ti Robert W. Elliott Senior Engineering Specialist Electrical Systems &/d/?z- Ed Laliberte Senior Engineer Electrical Systems Page 11 af 11