Heating Controller for 2 heating circuits, d.h.w. and boiler, communicating

Similar documents
RVP331. Heating Controller for 2 heating circuits, d.h.w. and boiler. Building Technologies HVAC Products

RVP310. Heating Controller. Building Technologies HVAC Products

RVL470. Heating Controller. Use. Functions. Series B

RVL472. Heating Controller. Building Technologies HVAC Products. Series C. including d.h.w. heating

RVL481. Heating Controller. including d.h.w. heating

RVL480. Heating Controller

RVL479. Heating Controller. for use with a partner unit

Use. Functions. Key function. Other functions

RVL471 Heating and Domestic Hot Water Controller Basic Documentation

Heating and D.h.w. Controller RVL482 Basic Documentation

G a

RVP360 and RVP361 Heating controllers for 2 heating circuits and d.h.w. Basic Documentation

RVP340 Heating controller for 1 heating circuit RVP350 and RVP351 Heating controllers for 1 heating circuit and d.h.w. Basic Documentation

PRELIMINARY EDITION

District heating controller

RVL471. Heating controller. G2524en. Installation Instructions. 1 Installation. 2 Commissioning

District heating controller

QAW70. Room Unit. Building Technologies. for use with heating controllers

District heating controller for two heating circuits and d.h.w. according to Siemens specifications:

Room Units and Sensors for Use in Heating Plants. Siemens Building Technologies HVAC Products SIGMAGYR. Type summary

QAW70. Room Unit. Siemens Building Technologies HVAC Products. for use with heating controllers

Room Unit. Building Technologies SYNERGYR

District Heating Controller

RVD120, RVD140 Controllers for district heating and d.h.w. Basic Documentation

RVL47. Heating Controller. Installations Instructions. Installation

Operating Instructions

Heating Controller. Building Technologies HVAC Products. Synco 700

RVA Heating Circuit or Primary Controller Basic Documentation. Siemens Building Technologies Landis & Staefa Division

Operating Instructions Heating Controllers RVL479, RVL480, RVL481, RVL482

RVA /109. Heating Circuit ZONE Controller. Instructions for the INSTALLER

Immersion Temperature Controller

QAA Room Unit for Boiler Control with OpenTherm Interface Basic Documentation. Siemens Building Technologies Landis & Staefa Division

RVA Cascade Controller for modulating gas-fired Boilers Basic Documentation

Boiler Sequence Controller

Heating Controller. Synco 700

ProCon 16, 31, 47 & 75. RVA 63 Boiler and Circuit Controller Commissioning Data.

Room Temperature Controller

Operating Instructions

Room Temperature Controller

REA22 Room Temperature Controller

G2484. Installation. - Control panel (in the panel front, on the inner wall, or on a DIN rail)

ECL Comfort 210 controller, Remote Control Units ECA 30 / 31 and Application keys Designed in Denmark

ECL Comfort V a.c. and 24 V a.c.

Self-learning Room Temperature Controller

The ECL Comfort 110 is a universal 1-circuit controller for use in district heating substations and district heating systems as well as boilerbased

Main Features. Functions. with automatic ignition and control functions for the heating and domestic hot water circuit

ECL Comfort 210 controller, Remote Control Units ECA 30 / 31 and Application keys

Self-learning Room Temperature Controller

ECL Comfort V a.c. and 24 V a.c.

QFM21... Siemens Building Technologies HVAC Products. Symaro Duct Sensors. for relative humidity and temperature

Room Temperature Controller with LCD

P20. ECL Comfort. User's Guide. Installer's Guide. ECL Comfort P20. User's Guide. Installer's Guide *VI7BD502* *087R8014* *087R8014* *VI7BD502*

Self-learning Room Temperature Controller

RVS46.. AVS75.. AVS37.. QAA75.. QAA78.. QAA55.. Albatros 2 Zone controller User Manual. Building Technologies HVAC Products

Room Temperature Controllers

Room Temperature Controller

Self-learning Room Temperature Controller

ECL Comfort 110, application 116

for relative humidity and temperature

Local Process Bus LPB

RVS43.. RVS63.. AVS75.. AVS37.. QAA75.. QAA78.. QAA55.. Albatros2 Boiler controllers User manual. Building Technologies HVAC Products

Heating Controller SDC. District Heating Controller DHC 43 OPERATING INSTRUCTIONS

Central apartment unit

QFM21... Duct Sensors. Building Technologies HVAC Products. Symaro. for relative humidity and temperature

UV Flame Supervision System

1 DOCUMENT REVISION CONTROL ELEMENTS... 9

BM Programming Module. For the heating engineer Installation instructions

Room Temperature Sensors

Semi flush-mount room thermostats

Control solutions Biofloor

Weather compensated flow temperature control of heating and boiler systems

QFM21... Duct Sensors. Siemens Building Technologies HVAC Products

ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys

ProCon 16, 31, 47, 75, 77 & HT. RVA 46. Zone Controller Commissioning Data.

RVS13... RVS53... AVS75... AVS37... QAA75... QAA78... QAA55... Albatros2 Boiler controllers User Manual. Building Technologies HVAC Products

RVS43.. RVS63.. AVS75.. AVS37.. QAA75.. QAA78.. QAA55.. Albatros2 Boiler controller User Manual. Building Technologies HVAC Products

Duct Temperature Sensors

Type summary Albatros 2

Self-learning Room Temperature Controller

1 DOCUMENT REVISION SOFTWARE VERSION BASIC DESCRIPTION BASIC OVERVIEW OF HYDRAULIC DIAGRAMS HYDRAULIC DIAGRAMS...

Quickheat 30 weather compensated boiler control

for relative humidity and temperature with calibration certificates

- Data Brochure Universal Reset Module 422

M116 / M450 USER AND MAINTENANCE MANUAL FOR MODULATING-CONTROL BOILER WITH GAS BURNER EQUIPPED FOR NATURAL GAS. Type : B23 ATLANTIC 2000

Digital Room Thermostat for Heating Applications with 7-Day Time Program

ECL Comfort 110, application 130

Preliminary Release. Room Temperature

Installation Guide. ECL Comfort 210, application A Table of Contents

C37. ECL Comfort. User's Guide. Installer's Guide. ECL Comfort C37. User's Guide. Installer's Guide *VI7CE602* *087R8070* *087R8070* *VI7CE602*

C62. ECL Comfort. User's Guide. Installer's Guide. ECL Comfort C62. User's Guide. Installer's Guide *VIKME102* *087R8091* *087R8091* *VIKME102*

Operating Guide. ECL Comfort 210 / 296 / 310, application A247 / A Table of Contents

for relative humidity and temperature

C66. ECL Comfort. User's Guide. Installer's Guide. ECL Comfort C66. User's Guide. Installer's Guide. *vi7cc502* *087R8069* *087R8069* *vi7cc502*

Safety. DANGER Indicates potentially fatal situations. WARNING Indicates possible danger to life and limb.

Synco 900 Operating Instructions. Edition 1.0 Controller series 1 CE1B2707en Building Technologies HVAC Products

Room thermostat with Auto Timer, Option External Input

Appliance and Controller Electrical Installation Guide.

Synco 900 Operating instructions

Room Air Quality Sensors

Modulating clock thermostat

Transcription:

2 477 Heating Controller for 2 heating circuits, dhw and boiler, communicating RVP330 Multi-functional heating controller for use in residential and non-residential buildings Suitable for weather-compensated flow temperature control of 2 heating zones with or without room temperature influence and, at the same time, demandcompensated boiler temperature control Control of dhw heating With communication capability 6 preprogrammed plant types with automatic assignment of the functions required for each type of plant Digital setting of the heating curve, analog room temperature readjustment, operating line principle for all other parameters Multi-functional relay Operating voltage AC 230 V, CE conformity Use Types of buildings: Multi-family houses Single-family houses Smaller non-residential buildings Types of plants: Heating zones and dhw heating plants Interconnected plants consisting of heat generating equipment, several heating zones and central or decentral dhw heating plant Types of heating systems: Radiator, convector, underfloor and ceiling heating systems, radiant panels CE1N2477en 15032006 Building Technologies HVAC Products

Functions Heating zone controls Dhw control Weather-compensated flow temperature control through control of the seat or slipper valve and demand-compensated control of the boiler temperature through control of the burner Dhw heating through control of the charging pump Control of a circulating pump or of an electric immersion heater Operating modes Other functions Automatic mode Automatic changeover from normal to reduced temperature, and vice versa, according to the 7-day program, automatic changeover to holiday mode, demand-dependent control of the heating system (ECO function) Setback mode Continuous heating to the reduced temperature, with ECO function Comfort mode Continuous heating to the normal temperature, no ECO function Standby Automatic dhw heating Frost protection is ensured in all operating modes The controller can be switched to manual operation Optimization functions Protective functions Remote control Commissioning aids Communication functions Room temperature acquisition (averaging, automatic selection room unit / room sensor) Ordering When ordering, please give type reference RVP330 and the language code letter (-A, -B or -C) for the Operating Instructions and the Installation Instructions in the requested language: -A for English, French, Italian, German (eg RVP330-A for English) -B for French, Dutch, Spanish (eg RVP330-B for French) -C for Greek (RVP330-C) Sensors, room unit, actuators and valves must be ordered as separate items Equipment combinations Suitable sensors and room units Flow, return and dhw temperature: all sensors with LG-Ni 1000 Ω at 0 C, for example: Strap-on temperature sensor QAD22 Immersion temperature sensors QAE212 or QAP213 Room temperature: Room unit QAW50 for heating circuit 1, QAW5003 for heating circuits 1 and 2 Room unit QAW70 for heating circuits 1 and 2 Room temperature sensor QAA24 (Ni sensing element) Outside temperature: Outside sensor QAC22 (Ni sensing element) Outside sensor QAC32 (NTC sensing element) 2/8 HVAC Products 15032006

Suitable actuators Communication The following actuators made by SBT HVAC Products can be used: For 3-position control, running time 05 145 minutes For 2-position control Operating voltage AC 24 V 230 V The controller is capable of communicating with All units with LPB capability made by SBT HVAC Products SYNERGYR OZW30 central unit (software version 30 or higher) Technical design Plant types 4 2 space heating systems with mixing zones, 3-position or 2- position control acting on mixing valve Plant types "Space heating" Y1 M2 B7 LPB M5 B9 B1 E1 B12 E2 B5 A6 B52 A6 2477S01 Plant types "Dhw heating" 0 No dhw heating 5 2 space heating systems with mixing zones, 3-position or 2- position control acting on mixing valve Pre-control with boiler B2 E3 M1 B7 LPB B9 Y1 M2 B1 B5 A6 E1 B12 B52 A6 M5 E2 2477S02 1 Dhw heating M3 through control of the charging pump B31 K6 K6 2477S04 6 1 space heating system with pump circuit, 2-position control with direct burner control 1 space heating with mixing zone, 3- position or 2-position control acting on mixing valve Pre-control with boiler B2 E3 M1 B7 LPB B9 M2 M5 E1 B12 E2 B5 A6 B52 A6 2477S03 The RVP330 provides the following plant types: 4 0, 4 1 5 0, 5 1 6 0, 6 1 A6 Room unit QAW50 or QAW70 E3 Heat source (boiler) B1 Flow sensor, heating circuit 1 K6 Electric immersion heater / circulating pump B12 Flow sensor, heating circuit 2 LPB Data bus B2 Boiler sensor M1 Circulating pump B31 Dhw storage tank sensor / control thermostat M2 Heating circuit pump, heating circuit 1 B5 Room sensor, heating circuit 1 M3 Charging pump B52 Room sensor, heating circuit 2 M5 Heating circuit pump, heating circuit 2 B7 Return sensor Controller RVP330 B9 Outside sensor Y1 Seat or slipper valve, heating circuit 1 E1 Load (room 1) Seat or slipper valve, heating circuit 2 E2 Load (room 2) HVAC Products 15032006 3/8

Working principle End-user settings Temperature acquisition Space heating Control Heating zone with regulating unit The RVP330 offers 6 different plant types that are ready programmed in the controller When commissioning the system, the respective plant type must be entered This activates all functions that are required for the selected plant type The standard settings are practice-oriented All functions not required for the selected plant type will not be shown and are disabled With weather-compensated control, the flow temperature is controlled as a function of the prevailing outside temperature via the heating curve Its basic setting is made on 2 operating lines The room temperature can be readjusted with the knob Heating circuit-independent entries by the end-user: Operating mode dhw heating Dhw temperature setpoint 7-day switching program for dhw heating Time of day and date Entries the end-user can make for each heating circuit: Operating mode heating circuit Room temperature setpoints for normal heating, reduced heating and frost protection/holidays One 7-day switching program and one holiday period per year Room temperature readjustment (knob) Outside temperature: with Ni or NTC sensor; the RVP330 identifies the type of sensor used With interconnected controllers, it is also possible to define the outside temperature source Room temperature: with a room temperature sensor or a room unit or both (averaging) The selection of room unit/room temperature sensor is made automatically The room temperature is included in the control It can be acquired with a sensor or simulated by a room model with an adjustable building time constant When using a sensor, the effect on the control can be adjusted It is also possible to limit the maximum room temperature The heating is switched on and off depending on demand (ECO function) It is switched off when the amount of heat stored by the building mass is sufficient to maintain the required room temperature In that case, the controller takes into account the development of the room temperature and the building's heat storage capacity It is possible to set 2 heating limits, one for normal heating and one for reduced heating The control is optimized Switching on, heating up and shutting down are controlled such that, during occupancy times, the required room temperature is always maintained At the end of each occupancy period, the heating will be shut down (circulating pump) until the room temperature setpoint for the non-occupancy time is reached (quick setback, can be disabled) During heating up, the room temperature setpoint can be boosted (boost heating) It is possible to set maximum limits for the heating up time and for early shutdown The heating zone control operates as weather-compensated flow temperature control with 3-position or 2-position control The flow temperature is controlled via the regulating unit (seat or slipper valve) Minimum and maximum limitation of the flow temperature as well as maximum limitation of the rate of setpoint increase are adjustable 4/8 HVAC Products 15032006

Heating zone without regulating unit Boiler control Minimum limitation of the return temperature Locking functions Time switch Dhw heating Remote control Communication Fault status signals Other functions The heating zone control operates as weather-compensated flow temperature control The flow temperature is controlled through direct boiler control Minimum and maximum limitation of the flow temperature as well as overtemperature protection are adjustable The boiler temperature control operates as demand-compensated 2-position control The boiler temperature is controlled through cycling of the single- or 2-stage burner (direct burner control) 2-stage operation is enabled when the release limit is reached, and disabled when the reset limit is reached The limits can be adjusted When there is no demand for heat, the boiler will either be shut down or maintained at the minimum temperature limit (selectable) Both minimum and maximum limitation of the boiler temperature are adjustable Minimum limitation of the return temperature helps prevent flue gas condensation On the software side, all settings can be locked to prevent unauthorized readjustments The RVP330 has 3 independent 7-day time switches Each 7-day time switch affords 3 24-hour on periods, which may differ from one weekday to the other For entering a holiday period per heating circuit, the RVP330 is equipped with a yearly time switch featuring automatic summer- / wintertime changeover Dhw heating is controlled independent of the heating circuits It can be enabled: According to its own 7-day program According to the switching program of both heating circuits (one hour before space heating starts) According to the switching programs of the zone controllers on the data bus Permanently (24 hours a day) Dhw heating features a legionella function which can be deactivated Legionella protection is provided once a week The dhw temperature is acquired with a sensor or a thermostat Dhw control also includes the control of a circulating pump and an electric immersion heater (control via the multi-functional relay) The dhw storage tank can be forcedly charged once a day Changeover of operating mode with the QAW50 room unit Overriding the major controller functions with the QAW70 room unit Communication with other devices is accomplished via the data bus and allows: Signaling of heat demand to the heat source Exchange of locking and enforced signals Exchange of measured values such as outside temperature and return temperature as well as clock signals Communication with other devices Reception of heat demand from the SYNERGYR OZW30 central unit (software version 30 or higher) Exchange of fault status signals Fault status signal in the event of sensor faults Fault status signal in the event of data bus or room unit faults Multi-functional relay Choice of functions: Alarm contact in the event of fault status signals On / off according to heat demand Control of the dhw circulating pump Control of the electric immersion heater Display of parameters, actual values, operational statuses and fault status signals Simulation of the outside temperature HVAC Products 15032006 5/8

Relay test; all relays can be controlled manually Sensor test; all measured values of the sensors can be displayed Outside temperature-dependent frost protection for the plant; a minimum flow temperature is maintained, its setpoint and the response threshold can be adjusted Pump overrun time to prevent the buildup of heat Periodic pump run (pump kick) to prevent seizing of the pump in the summer Controller hours run meter For more detailed information about technical features, functions and communication with LPB, please refer to the following pieces of documentation: Basic Documentation RVP330: P2477 Data sheet Basic System Data LPB : N2030 Data sheet LPB : N2032 Mechanical design The RVP330 is comprised of controller insert, which accommodates the electronics, the power section, the output relays and on the front all operating elements, and the base, which carries the connection terminals The operating elements are located behind a cover The operating instructions are inserted in the cover The controller insert is secured to the base with 2 screws The RVP330 can be fitted in 3 different ways: Wall mounting (on a wall, in the control panel, etc) Rail mounting (on a standard DIN mounting rail) Flush panel mounting (control panel door, etc) Analog operating elements Digital operating elements Buttons for selecting the required operating mode Button for selecting the heating circuit Button for dhw heating on / off Knobs for manual readjustment of the room temperature per heating circuit 3 buttons for manual operation and manual positioning commands The entry or readjustment of all setting parameters, activation of optional functions and reading of actual values and statuses is made according to the operating line principle An operating line with an associated number is assigned to each parameter, each actual value and each function that can be selected One pair of buttons is used to select an operating line and one pair to readjust the display 1 8 9 2 10 BUS 11 3 4 12 5 6 Landis & Staefa RVP330 1 Operating mode buttons 6 LED for manual operation (selected button is lit) 7 Buttons for «Open / Close valve» in manual operation 2 Service plug 8 Button for dhw heating on / off 3 Buttons for operating the display: 9 State display (outputs, temperature levels, holiday) Prog = selection of operating line 10 Display (LCD) + = readjustment of displayed value 11 Knob for room temperature readjustments, heating circuit 1 4 Operating instructions 12 Button for changeover of heating circuits 5 Button for manual operation 13 Knob for room temperature readjustments, heating circuit 2 2477Z01 13 6/8 HVAC Products 15032006

Notes Engineering Commissioning The wires of the measuring circuits carry extra low voltage The wires to the actuator and the pump carry AC 24 230 V The local regulations for electrical installations must be complied with Sensor cables should not be run parallel to mains carrying cables for loads such as actuator, pump, burner, etc On the room unit for heating circuit 2, the address to be set is 2 Every controller is supplied complete with installation and commissioning instructions Technical data General unit data Operating voltage AC 230 V +10/ 15 % Frequency 50 Hz Power consumption 9 VA Perm ambient temperature Transport and storage Operation 25 +65 C 0 50 C Bus loading characteristic E (LPB) 10 Backup of controller clock min 12 h Weight (net) 068 kg Standards Product safety Automatic electrical controls for household and similar use Particular requirements for temperature sensing controls Degree of protection Safety class (if correctly installed) conformity to EMC directive Low voltage directive EMC directive Electromagnetic immunity Electromagnetic emissions EN 60730-1 EN 60730-2-9 IP 40 to EN 60529 II to EN 60730 89/336/EWG 73/23/EWG EN 50082-2 EN 50081-1 Output relays Rated voltage AC 230 V Rated current 2 (2) A Contact current at AC 24 90 V 01 2 A, cos ϕ >06 Contact current at AC 90 250 V 002 2 A, cos ϕ >06 Rated current of ignition transformer 1 A max (30 s max) Switch-on current of ignition transformer 10 A max (10 ms max) Max switch-on current (fuse) max 10 A Perm cable lengths To the sensors and external contacts Copper cable 06 mm dia Copper cable 10 mm 2 Copper cable 15 mm 2 To the room unit Copper cable 025 mm 2 Copper cable from 05 mm 2 20 m 80 m 120 m 25 m 50 m HVAC Products 15032006 7/8

Connection diagrams Low voltage side LPB A6 D1 D2 A6 D1 D2 B9 B1 B12 B2 B31 B7 B5 B52 B M B M B M B M B M B M B M B M 2477A01 DB MB A6 MD B9 B1 M B12 B2 B31 B7 B5 M B52 M L N Mains voltage side AC 230 V F1 F2 1 2 E3 Q1 M1 F1/F2 F7 Q3 Y1 Y2 Q2 Q5 K6 1 ) M3 Y1 M2 M5 Y1 F6 Y2 Y8 2477A02 A6 Room units for heating circuits 1 and 2 F2 Manual reset safety limit thermostat B1 Flow sensor, heating circuit 1 LPB Data bus B12 Flow sensor, heating circuit 2 M1 Circulating pump B2 Boiler sensor M2 Heating circuit pump, heating circuit 1 B31 Dhw storage tank sensor / control thermostat M3 Charging pump B5 Room sensor, heating circuit 1 M5 Heating circuit pump, heating circuit 2 B52 Room sensor, heating circuit 2 Controller RVP330 B7 Return sensor Y1 Actuator heating circuit 1 B9 Outside sensor Actuator heating circuit 2 E3 2-stage burner 1 ) Multi-functional output F1 Limit thermostat Dimensions 93 19 max 3 96 26 26 26 26 15 144 106,8 12 14 138 +1 0 60,4 4,5 92 +1 0 56 112 2477M01 Dimensions in mm 8/8 2000 Siemens Building Technologies Subject to alteration HVAC Products 15032006