DC1136, DC1131-AA, DC1134-AA, DC1136-AA Input / Output modules

Similar documents
DC1154 / DC1154-AA / DC1156-AA / DC1157-AA Input / Output modules

DC1192 Input /Output module

FDCL221-M Multi line separator module

Input module, input/output modules

Output module (230 V)

Input module, input/output module

Multi line separator module

FDCIO223 (ES 45) Transponder

FDS229-R / FDS229-A Alarm sounder with supplementary optical indication

DM1131 / DM1133 / DM1134 Manual call points

Manual call points. Sinteso / Cerberus PRO FDM225, FDM226

DB110xA, DB1131A, SO620A, DB1151A Detector bases and accessories

DOW1171 / DCW1151 Radio fire detection system

DBS721, DBS729 Sounder interbase, Sounder beacon interbase

DM1153H-Ex / DM1154H-Ex Manual call point 'Heavy Duty'-Ex

Manual call point. Sinteso Cerberus PRO FDM223H, FDM224H. 'Heavy Duty' manual call point addressed (FDnet/C-NET)

FDBZ290 Air sampling smoke detection kit

Fire control panels FC360

DM1101 / DM1103 / DM1104 DM1103-L / DM1103-S Manual call points Manual release button and emergency stop button

OOH740, OOHC740 Automatic fire detectors

Fire control panels FC726 FC726-XA

FC722 Fire control panel

DF1101-Ex Infrared flame detector

FDBZ290 Air sampling smoke detection kit

FC330A-ECO1 Auto-addressing analogue 1-Loop fire detection panel

FDCL221 Line separator

FDCL221-Ex Line adapter (Ex)

FC724 Fire control panel

FC330A-ECO Auto-addressing analogue 1-Loop fire detection panel

FC722 Fire control panel

OH720, OP720, HI720, HI722

FC2020 Fire control panel

FC723 Fire control panel

FC724 Fire control panel

ASA linear smoke detector

OOH740, OOHC740. Cerberus PRO. Automatic fire detectors

DF1151-Ex Infrared flame detector

FDF Sinteso Cerberus PRO Cerberus FIT. Flame detector. Flame detector addressed or collective, ASAtechnology TM

FDOOT241-9, FDOOT241-A, FDO241, FDT241

Synova TM product catalog.

Mimic display driver, LED ribbon cable

FS20 Fire detection system

FDOOT221, FDO221, FDT221

FC700A Fire detection control unit

Fire control panel for modernization

FP120-Z1 Power supply kit A (70 W) Technical Manual

Sinteso TM product catalog.

FDOOT241-A3, FDOOT241-A4, FDOOT241-A5, FDOOT241-A9, FDOOT241-8

FDCI221, FDCIO221 Input module, input/output module Technical Manual

DT1101A / DT1102A / DO110xA Automatic fire detectors

XC10 Extinguishing control panels

Siemens aspirating smoke detector (ASD) for the addressed FDnet/C-NET detector line or for standalone operation

13 tones to choose from, 2 programmable alarm levels Adjustable sound levels up to 93 dba

FDCW221 / DOW1171 / SMF121 SMF6120 (repair/replacement) Radio fire detection system

FC2040. Fire control panel. Sinteso. FS20 series, MP6

FDCW241 Radio gateway Mounting

Interbases. Sinteso FDSB221, FDSB228, FDSB229

INPUT / OUTPUT MINI MODULES

Pakton Technologies Pty Ltd ABN Ferrier Road, Narangba Qld 4504

FDA241, FDA221 Siemens ASD

MINERVA MX. 800 Series Ancillary Equipment

QXA2100. Condensation monitor QXA2101. Monitor to prevent damage caused by condensation on chilled ceilings and HVAC plants with AC/DC 24 V power.

SOL-LX-W, SOL-LX-C, RoLP-LX, RoLP Sounder, beacon, and sounderbeacon

FDMM01S - FDMM02 - FDMM10- FDMM11S FDMM12 - Input / output mini modules

Dipl.-Ing. W. Bender GmbH & Co. KG Londorfer Str Grünberg Tel.: Fax:

Building Technologies. FDUL221 en Line tester operating instructions for electricians

OOH740-A9-Ex Multi-sensor fire detector

FDA241, FDA221 Siemens ASD

FDL241-9 Linear smoke detector Mounting Commissioning

OH720, OP720, HI720, HI722 Automatic fire detectors Technical Manual

Interface and EOL Modules 8

Sensepoint XCL Fixed Gas Detector

Call stations and extensions

Installation guide for J4 Junction Box for R4 AIS Transponder System

OOH740-A9-Ex Multisensor fire detector

DUAL MONITORED INPUT/OUTPUT UNIT BN-305

MK8000 OPC Server Interface Specification for CS1115 Building Technologies

BX-MDI8 Input module for SecuriLine extended

ISOMETER IR425. Insulation monitoring device for unearthed AC/DC control circuits (IT systems)

FLAME AMPLIFIER MODULE 3001D

FDOOT241-A9-Ex Multisensor fire detector

RTA421. Technical Information. Limit alarm switch Alarm switch and power supply for monitoring current or voltage signals

VIMPEX BS Evacuation. Fire Alarms EN Banshee. Beacons. FlashDome. Electronic Sounders. Audible Alarm

Heating and D.h.w. Controller RVL482 Basic Documentation

LINETRAXX VME420. Multi-functional relay for overvoltage, undervoltage and frequency monitoring in AC/DC systems with external supply voltage

ISOMETER IR425. Insulation monitoring device for unearthed AC/DC control circuits (IT systems)

Water Leak Detector - Four Zone with open/short-circuit detection. Product overview

PTE0705 Electric Fence Monitor

FT2080 Fire terminal (Touch) Mounting Installation

FT2080 Fire terminal (Touch) Mounting Installation

Building Technologies

DUAL MONITORED INPUT/OUTPUT UNIT BN-305-2

Room thermostat with 24-hour time switch and large LCD

LDM-519-DIM LHDC MONITOR Digital Line Heat Detector Interface

QAF63.2-J QAF63.6-J. Frost detectors. for use on the air side

Radio fire detection system

M15051) INSTRUCTION MANUAL

FLAME AMPLIFIER MODULE 3001

Application Sheet Chilled/heated ceiling (4 pipe) with 6-way valve on analog output

Touchpoint Plus. A whole new control experience

Transcription:

DC1136, DC1131-AA, DC1134-AA, DC1136-AA Input / Output modules AnalogPLUS AlgoRex DC1130 Series Thanks to its robust construction, the input/output modules can be used in both dry and dusty / wet areas Housing for surface mounting with M20 cable entries DC1130-AA Series For use in dry areas Can be mounted in a row with standard guides TS35 Two-wire installation No additional supply required Equipped with isolating function

Input module DC1131-AA Function The address is assigned during commissioning via the key integrated in the module and confirmed by the flashing of the red LED. The LED lights through the transparent cover. The contact connected to the input module is monitored and registered by the control unit by means of the individual address of the input module. The key is provided to release a danger signal during normal operation (performance check). Application Transmits danger signals from sprinkler contacts or non-cerberus manual call points via the AnalogPLUS detector bus. It can be used as a make or break contact. DC1131-AA loop or stub line or contact input switch potential-free Output module DC1134-AA Function The address is assigned during commissioning via the key integrated in the module and confirmed by the flashing of the red LED. The LED lights through the transparent cover. Application Output module with 1 potential-free provides decentralized activation of fire doors, ventilators, air conditioning etc. DC1134-AA loop or stub line 1 relay output 30 VAC / DC / 1 A fire control installation 2

In-/output modules DC1136, DC1136-AA Function The address is assigned during commissioning via the key integrated in the module and confirmed by the flashing of the red LED. DC1136: With closed housing, the key and the LED are not visible DC1136-AA: The LED lights through the transparent cover. With monitored signal input for confirmation messages with potential free NO or NC contact. Application DC1136/-AA with 1 potential free changeover contact provides decentralized activation of fire doors, ventilators, air conditioning etc. The signal input for status or alarm messages is configurable via the fire detection control unit. DC1136 or DC1136-AA signal input loop or 1 relay output DC1136: 240 VAC / 4 A stub line DC1136-AA: 30 VAC / DC / 1 A switch potential-free fire control installations Built-in line separator Any short circuit on the detector bus is located by the control unit and the defective component isolated. A loop line ensures optimal security. Installation DC1136 The housing with cover DCA1191 and the terminal base DCB1136A are required for installation The housing has six M20 threaded cable entries to feed in the cable It can be used in dry, dusty and wet areas The circuit unit is only inserted after the wiring check shortly before commissioning DC1131-AA, DC1134-AA, DC1136-AA Mount in series on standard rail TS35 with mounting plate DCZ1190-AA possible. Modules can be installed and connected with or without the electronics unit being inserted. It can be used in dry areas. For applications in humid areas, the module can be built into the housing DCA1191. 3

Components Mounting plate DCZ1190-AA U-rail TS35 Input / Output module DC1131-AA, DC1134-AA, DC1136-AA Housing with cover DCA1191 Circuit unit DCA1136A Terminal base DCB1136A Dimensions DC113x-AA and DCZ1190-AA 97 DCA1191 22 65 88 11,5 111 71,5 135 135 6xM20 4

Technical data DC1131-AA DC1134-AA DC1136-AA DC1136 Load factor APMK 1 2 2 2 Line resistance (detection line) max.50 Ω max.20 Ω max.10 Ω volt-free switchover contact 30 VAC / DC / 1 A volt-free switchover contact 240 VAC / 4 A or 125 VDC / 4 A (max. 150 W) 0.2 1.5 mm 2 0.2 1.5 mm 2 0.2 1.5 mm 2 0.2 2.5 mm 2 Relay output volt-free NO or NC contact max. 30 VAC / DC / 1 A Wire cross-sectional area per terminal Operating temperature 10 +60 C 10 +60 C 10 +60 C 25 +70 C Storage temperature 30 +75 C 30 +75 C 30 +75 C 30 +75 C Humidity without housing DCA1191 with housing DCA1191 Protection category IEC60529 without housing DCA1191 with housing DCA1191 Color Approvals VdS LPCB Relay 95 % rel. IP30 Mounting plate Cover transparent G299030 126p/01 95 % rel. IP30 Mounting plate Cover transparent G299030 126p/02 95 % rel. IP30 Mounting plate Cover transparent G299030 126p/03 Housing DCA1191 G298081 SEV/VDE 5

Details for ordering Type Part no Designation Weight DC1136 DCA1191 4588560001 Housing with cover 0.346 kg DCA1136A 5082720001 Circuit unit 0.139 kg DCB1136A 5082850001 Terminal base 0.121 kg DBZ1190-AA 4677080001 Micro terminal 0.28 0.5 mm 2 0.001 kg A5Q00004478 Metal screwed cable gland M20 x 1.5 0.039 kg DC113x-AA DC1131-AA 5225200001 Input module 0.096 kg DC1134-AA 5225750001 Output module 0.098 kg DC1136-AA 5225880001 In-/output module 0.095 kg DCZ1190-AA 5226270001 Mounting plate 0.020 kg 5644780001 U-rail TS35, L=122 mm 0.040 kg Siemens Switzerland Ltd Group International Headquarters Alte Landstr. 411 CH-8708 Männedorf Tel. +41 1-922 6111 Fax +41 1-922 6450 www.sbt.siemens.com 2005 Copyright by Siemens Switzerland Ltd Data and design subject to change without notice. Supply subject to availability. Document no. 001546_g_en_-- Manual S11 Edition 07.2005 Section 4