FPX103C Auto DUAL LOOP AUTO/MANUAL FIRE CONTROL PANEL Iss 1.0

Similar documents
FPX103C. Dual Loop Auto/Manual Fire Control Panel. Technical Manual

Application, Installation, Operation & Maintenance Manual

Installation, Operating and Maintenance Manual

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel

OPERATION AND INSTALLATION MANUAL

Intelligent Security & Fire Ltd

HOKKIM INTEGRATED AMF CONTROL BOARD MANUAL FOR MODELS: HAMF-8 AND HAMF-4

Control Panel Engineering and Commissioning Instructions

M2500 Engine Controller Installation Manual

GAS SUPRESSION CONTROL PANEL:

OPERATION & INSTALLATION MANUAL FOR ALARM PANEL M2AP01

DUAL MONITORED INPUT/OUTPUT UNIT BN-305

PSN-1000 & PSN 1000(E) Installation Manual

1200-HCM DIN RAIL MOUNTING FIRE SYSTEM MODULE Fire Detection & Extinguishant Control A R T PATOL LIMITED SUPPLY FAULT SOUNDER

Installation Guide for AL800UL-ADA. NAC Power Extender. Rev

EX8. Instruction Manual: COMBINED FIRE & EXTINGUISHING CONTROL PANEL COMPLIES WITH BS EN PART 1 AND EN54 PARTS 2 & 4

Sigma. K1000 Series 1, 2, 4 & 6 Zone Fire Control Panels. Operation and Maintenance Manual. Man-1048 Issue 05 October 2009

Control/Communicator Installation Manual

HA-263K HA-263D. OWNER'S MANUAL Installation And Operation 8-ZONE ALARM CONTROL PANEL FOR HOME AND OFFICE PROTECTIONS OPEN THE CABINET FOR SERVICE

MODEL 5100 VOTING LOGIC MODULE

Installation and user manual for the CF5000, MF5000 and FXP5000 range of fire panels

Heat Pump Defrost Board Replacement Kit

M2000 Engine Controller

FEC400 Series. Installation Manual

Conventional Fire Alarm System 2014 V1.2

Premier Hazard STC Instructions

DUAL MONITORED INPUT/OUTPUT UNIT BN-305-2

Reflective Optical Beam Smoke Detector User Guide

EXTINGUISHING AGENT RELEASE MODULE

TECHNICAL DATA OBSOLETE

PRODUCT INSTRUCTIONS. Fire Door Control Panel (FDCP) Stock Code Description Doc No: PI-115. Ellard Fire Door Control Panel Ellard Slave Repeater Unit

AL800ULADA. NAC Power Extender. Installation Guide

30.45 Electric Release PDRP-2001

USER MANUAL COMBINED FIRE & EXTINGUISHING CONTROL PANEL COMPLIES WITH BS EN PART 1 & EN54 PARTS 2 & 4

ZIOU/230 - MAINS IO INSTRUCTION MANUAL

RANGER 8600 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL

Emerald 3000 MK3 GJD010 Lighting Controller

TABLE OF CONTENTS TABLE OF CONTENTS 1

TECHNICAL DATA. Humidity: 85% Relative Humidity (non-condensing) at 90 F (32 C) maximum.

AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev

Remote NAC Power Supply D7038

0$; Installation Instructions. Computerized Control Panel '(6&5,37,21 63(&,),&$7,216 DE5011 1

Flopurge TS. Operation Manual

EC Series Wall Unit Humidifier

Public Safety DAS Annunciator Panel

SYSTEM MANUAL FT1-SB. Single Zone Fire Alarm System

MINERVA MX. 800 Series Ancillary Equipment

ICS Regent. Fire Detector Input Modules PD-6032 (T3419)

FTEN1, FTEN2, & FTEN4 1, 2 & 4 ZONE FIRE DETECTION AND ALARM CONTROL PANELS

705 Emmett Street Bristol, CT DynaLock MODEL 3101C-TJ101 DELAY EGRESS SYSTEM WIRING INSTRUCTIONS

Installation Instructions

Intruder - Fire - Water Combined Alarm

Model 17A00 Expansion Enclosure

AL600ULADA. NAC Power Extender. Installation Guide

FIRE ALARM CONTROL PANEL. COMPLIES WITH EN54 part 2 & part 4 MEETS THE FUNCTIONAL REQUIREMENT OF BS:EN 5839 part 1 INSTALLATION MANUAL

This wiring diagram describes circuit connections for all models of the Series Quaestor-SZU Releasing Fire Control

Installation Manual RINS1211-4

RANGER 7600 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL

Model 3300 Technical Support and Installation Manual

Models NFPA 1221-A, NFPA 1221-B Public Safety DAS Annunciator Panel. Revision E 61117

MODEL KP-200 VANDAL RESISTANT & WEATHERPROOF FLUSH MOUNT DIGITAL KEYPAD DESIGNED FOR ACCESS CONTROL APPLICATIONS

THANK YOU FOR VOTING TEXECOM INSTALLATION MANUAL. Security Control Panel with Communicator Interface

highline SVCS-1 INSTALLATION & USER MANUAL SMOKE VENT CONTROL SYSTEM * enclosure design may vary software version: SVCS1r6 SVCS1r7 SVCS1r10

BT1 SINGLE ZONE FIRE ALARM SYSTEM OPERATORS MANUAL

RELEASE DEVICES RELEASE DEVICE-WPS MODELS A/B INSTALLATION MANUAL U.L. LISTED CANADIAN LISTED CSFM: :100 GENERAL DESCRIPTION:

MULTIFUNCTION ALARM SYSTEM TYPE ED510 FIRE LEVEL GAS ZONE 1 ZONE 2 ZONE 1 ZONE 2 SENSOR 1 SENSOR 2 ALARM FAULT TEST ON TEST OFF

End To End Optical Beam Smoke Detector. Additional Information

MR-2602 Two Zone Fire Alarm Control Panel

SECURIT 700L PLUS ENGINEERING MANUAL

ESP TECHNOLOGIES LIMITED

FR-4000 & FR-8000 Fire Alarm Monitor Installation Manual

DS3MX-E-I. Installation Guide. 3 Zone Mini Control Panel

DEIF A/S. Technical Manual. Type EC-2 Engine Control Unit D. Technical Manual

Fire Burglary Instruments Inc. XL-2G Gold Control/Communicator Installation Training Seminar Rev. 5/96

RED1. Technical Support And Installation Manual. Models ST, E1, E2, E3, E4, and 420. Approved

INSTALLATION MANUAL & PROGRAM RECORD SHEET

Gas Safety Products. Installation, operating and maintenance 11/18/2015. Merlin 1000S+ Gas Utility & Electrical Isolation Controller

CPS-1 USER S MANUAL AIR INLET / CURTAIN CONTROL

TECHNICAL DATA. multi-hazard. model vfr400. Release Control Panel 290a. January 16, 2014

Intelligent Security & Fire Ltd

4 & 8-POINT ANNUNCIATORS Instruction Manual

Danfoss gas detection units

Flostop TS D7E and A8E. Operation Manual

Instructions R8471J Gas Controller for use with Model OPECL Open Path Eclipse IR Gas Detector 1.1 1/

Ammonia Leak Detector Manual

LEAKMONITOR MULTIZONE WATER LEAK DETECTION ALARM PANEL INSTALLATION AND USER OPERATION MANUAL

I/O ZONE 560/583 AND OPERATION MANUAL

50M Integrated Single or Two-Stage HSI Integrated Furnace Control Kit INSTALLATION INSTRUCTIONS

Carbon Monoxide Transmitter

WARNING Important Safety Information

HEXA PROGRAMMING: STREAMLINED SECTION PROGRAMMING

TO ARM/DISARM ALARM The alarm is activated by pressing BUTTON 1 on the remote control transmitter once. The blinkers will flash once, and the

SOLID STATE SECURITIES, INC. THE "SS90" SERIES RELEASE DEVICES MADE IN THE U.S.A. SS90-WPS MODEL A/B INSTALLATION MANUAL

5000 SERIES 8 ZONE INSTRUCTION MANUAL

USER MANUAL CEF AP28 CONTROL PANEL

Gas Safety Products. Installation, operating and maintenance. Merlin 1000S+i Gas & Electric Utility Controller. Rev: 03 Date:

Operator: Save these instructions for future use!

DIESEL ENGINE CONTROL UNIT DCU USER S MANUAL - N-2000 Lillestrøm, Norway Tel: (+47) Fax: (+47)

Interface and EOL Modules 8

FIREPRO INSTALLATION MANUAL FIRE ALARM CONTROL PANEL INSTALLATION MANUAL. Approved Document No. GLT Issue: 1. 8 Author: NRPJ Date: 7/ 3/201 4

Transcription:

FPX103C Auto DUAL LOOP AUTO/MANUAL FIRE CONTROL PANEL Iss 1.0 SUMMARY: Dual detection loops with full fault monitoring. Automatic extinguisher operation after shutdown. Double knock automatic activation logic. Automatic Engine/fuel/fan shutoff capability. Spindown delay ensures extinguishant is not vented. Extinguisher activation button with anti-tamper tag. Universal 12 or 24Vdc electrical power. Low power consumption in PARKED mode. Full fault monitoring on all detector and firex circuits. Supports up to 6 aerosol fire extinguisher/generators. Very low false activation potential, tamper seal on ManOp The unit is reverse polarity, transient and EMC protected. Custom behavior logic available on request. Shutdown and delayed firex activation improves effectiveness and saves cost of extra extinguishant. Most existing extinguishing systems release the agent into a high airflow environment which makes it almost completely ineffective. Given that a 7 Liter 4 stroke engine at 3000RPM (that s 50revs/sec) aspirates 175 Liters or 0.175m 3 of air per second, add to this ventilation fan flow and the necessity for a shutdown with engine/fan spindown delay before activation is obvious. The FPX103C has effectively eliminated spurious activation warranty costs which are regularly caused by the inherent characteristics of microprocessors, semiconductor power switches and inquisitive fingers. Our tamper evident tag technology and our strict electronic design rules has proven highly effective. To eliminate the inherent hazards of microprocessor control the FPX103C uses a fully parallel path programmable logic device, which is coded using a language called VHDL, commissioned by US DOD and used for high reliability and safety critical applications. FEATURES: 2-wire Smoke, thermal or Linear Heat Sensors up to 50M are continuously monitored for alarms, open circuit and chassis faults. LED flash codes indicate the location of an alarm or fault condition. An internal alarm sounder and relay to drive a loud external audible alarm unit up to 2Amps. Uncommitted relay change-over contacts are available for fuel shutoff, engine/fan shutdown. The delay option provides a selectable spin-down time so that the extinguishant is not wasted. PARKED MODE is entered when unit senses that ignition is turned off and provides automatic extinguisher operation should both loops alarm - switching off engine during a double alarm will also enter timed auto activation mode (aka driver legging it protection). There is an electrical input for an override keyswitch to circumvent shutdown circuits for restarting. FUNCTIONAL NOTES: Any loop alarm condition will operate audible and visual alarm indications as follows: Single loop alarm condition produces internal pulsed alarm (1 per sec) and fan shutdown. Dual loop alarm condition produces internal pulsed alarm (2 per sec) and automatic extinguisher and fuel solenoid operation after spindown delay (user set on dip switches), audible alarm goes continuous. Alarm LED flash code indicates which loop is in alarm (1=1blink, 2=2blinks, 1&2=3blinks). The spindown delay allows time for fan and engine to stop before extinguisher is activated. This is to save extinguishing agent that would otherwise be wasted through venting. The timer tracks the

spindown of engine/fan(s) as a result of ignition switch-off or shutdown by FPX103C as a result of an alarm (from either detectors or manual operate switch). With the ignition off the unit enters low power mode and the ON LED will flash to conserve power. Single flash shows the spindown timer is still counting (fans still turning), then adopts a double flash heartbeat indicating that parked mode is active and extinguisher operation will be immediate on double alarm or manual operate.in parked mode (ignition off for longer than spindown delay) then the fuel solenoid will operate on first alarm and extinguisher immediately on second alarm. Switching on the ignition even for a short time will restart the spindown timer and it is also active on initial power-on. Spindown timer is selectable: NoAUTO, IMMEDIATE, 5 to 30 seconds, 5 sec granularity. A fault in one detector loop will cause the auto mode to fail (because of the double knock logic) however a manufacturing option can allow PARKED mode to auto operate the extinguisher after single loop alarm if the other loop is faulty. Manual operate command must also wait for the engine/fan spindown before extinguisher activation. After 125ms filter time the unit will confirm activation request by flashing 2ALARM=AUTO LED and internal beeper, fan and fuel solenoid shutdown relays are activated immediately. After spindown timeout the extinguisher will operate and beeper will go continuous. PANEL LED INDICATIONS: The panel layout has two distinct areas for extinguisher and detector status with separate LED flash pattern indications for each detection loop (1 and 2). Power On (Green LED) Detector Alarm (Red LED) - inverse flash pattern indicating affected loop Detector Loop Fault (Red AMBER) - inverse flash pattern indicating affected loop 2 Alarms=Auto Active (Red LED) Extinguisher Fault (Red AMBER) Internal sounder will operate on anything that requires user attention (alarm or fault). CONTROLS: Extinguisher manual operate button (behind tamper evidence tag) Auto mode time delay selector DIP switch on panel rear (delay = binary_value * 5 seconds). SW1-3 off-off-off = immediate, on-on-on = AutoDisabled, on-off-off=5sec, off-on-off=10sec, etc. SW4 on = vfc operates on single alarm, off = vfc operates on double alarm CONNECTIONS: BLOCK 1 (6 way) External Alarm Output (Power via 2A N.O. relay contact) Ignition input (sets auto PARKED mode when off) Power (11-32vdc via 4A fuse) BLOCK 2 (6 way) Detector Loop1A Detector Loop1B Detector Loop2A Detector Loop2B Aux input BLOCK 3 (6 way) FirexA FirexB VFC (2Amps Max) NO VFC (2Amps Max) COM VFC (2Amps Max) NC

ELECTRICAL SPECIFICATION (at 24VDC supply unless otherwise stated): Power Supply Operating Voltage 11 to 32V DC Quescent Current Ign Off 8.5mA Typ (excluding external load currents) Ign On 16mA Typ (excluding external load currents) Maximum Alarm Current 100mA (excluding external load currents) Draw Max current draw 3A (including extinguisher operate current) Parked current draw 8.5mA Typ Suppressor Activation Discharge Current 1A to 4A depending on voltage and number of suppressors (1.6 3 Ohms nominal each unit) Up to 2 units on 12V, 4 units max on 24V Connect in series with bi-directional catch diodes across each element (see manual). Current/Time Limit Output is Vin via switch with 6 Ohms in series. Constant I2T limit = 9 Amp2*Seconds Monitoring current <4mA, Fault if loop R>300, 12Vmax o/c voltage AuxIn (Override key) Monitoring current 1.2mA Nominal Sense Logic Norm S/C, >1K active typ. Sensor Loop Inputs 1+2 Max Output voltage 12VDC regulated, filtered and transient protected Output current limit 25mA per loop Alarm condition threshold <700 Ohms Nominal Fault condition threshold Approximately 20K Ohms End Of Line Resistor 10K Ohms Fault monitoring Open circuit or ground fault = fault indication Alarm Output Relay Contacts 2A @ VinDC (Vin thru NO relay circuit) VFC Output Relay Contacts (volt free) 2A @ 24VDC (relay changeover circuit) Mechanical Dimensions H=82mm * W=83mm * D=25mm Mounting 75mm diameter round hole, retained by four #6*25 self tapping screws Connections Via 3 * 6 way terminal block accepting <1mm 2 wires with ferrules DIP SWITCH SETTINGS (Black = switch tab) DIP switches 1.2.3 set a delay time between shutdown (VFC) and subsequent extinguisher automatic activation. Delay can be set 0 to 30 seconds in 5 second steps. Manual only mode can be set with ON.ON.ON.OPT DIP switch 4 defines critical alarm OPTion. The default setting is OFF which requires 2 loops to be in alarm (OPT= double knock ) before shutdown and time delayed extinguisher activation. Moving to ON position requires only one loop to be in alarm (OPT= single knock ) before shutdown and time delayed extinguisher activation. Note that the unit dispenses activation delay following depowering of ignition input. The instant mode is indicated by flashing green PWR LED which gives double flash whilst moving through the delay and single flash on reaching zero delay instant mode.

Fan/Engine Spindown delay time before automatic release. Note: Spindown delay only when ignition is ON OFF.OFF.OFF.OPT ON.OFF.OFF.OPT OFF.ON.OFF.OPT ON.ON.OFF.OPT OFF.OFF.ON.OPT ON.OFF.ON.OPT OFF.ON.ON.OPT ON.ON.ON.OPT 0 Sec = Immediate 5 Sec 10 Sec 15 Sec 20 Sec 25 Sec 30 Sec No Automatic Operation Installation Notes: Ensure that Linear Heat Detectors are suitably mounted for the vehicle vibration levels. Front of panel is splash proof but it must be located to prevent excessive moisture or water getting to the unit, especially the rear connections. Locate to avoid excessive direct solar exposure. WARNING! (And some common sense..) Refer to the installation manual. System installation must be verified by a competent technician familiar with regulations governing such installations. Do not install in Engine, bilge, fuel or gas storage compartments (see RCD and ISO9094). In the event of an alarm shutdown the engines and ventilation immediately. The cause of the activation must be found and corrected before restarting. DO NOT PROCEED TO OVERRIDE UNLESS IT HAS BEEN DETERMINED SAFE TO DO SO.

Outline & Mounting drawing:

Typical Application wiring (Linear Heat Detector sensors)