FREEDOM RESIDENTIAL CONCEALED PENDENT SPRINKLER VK468 (K4.9) TECHNICAL DATA

Similar documents
TECHNICAL DATA. The Viking Corporation s Web site at Overall Length (Sprinkler Body): 2-5/16 (59 mm)

TECHNICAL DATA. * Metric K-factor measurement shown is in Bar. When pressure is measured in kpa, divide the metric K-factor shown by 10.0.

freedom residential concealed pendent sprinkler VK488 (K3.0)

freedom residential concealed pendent Sprinkler vk458 (K7.4)

freedom residential concealed pendent sprinkler vk474 (K5.8)

FREEDOM RESIDENTIAL CONCEALED PENDENT SPRINKLER VK494 (K4.9) TECHNICAL DATA

FREEDOM RESIDENTIAL CONCEALED PENDENT LEAD FREE SPRINKLER VK4570 (K4.9) TECHNICAL DATA

freedom residential concealed pendent lead free sprinkler

TECHNICAL DATA. Refer to the Approval Chart and Design Criteria for C-UL-US-EU Listing requirements that must be followed.

FREEDOM RESIDENTIAL CONCEALED PENDENT SPRINKLER VK498 (K5.8) TECHNICAL DATA

freedom residential pendent sprinkler vk466 (K5.2)

TECHNICAL DATA. Viking Technical Data may be found on UNS-C84400 for Sprinkler VK202.

STANDARD/QUICK RESPONSE CONCEALED PENDENT SPRINKLER VK352-D (K8.0) TECHNICAL DATA

FREEDOM RESIDENTIAL PENDENT SPRINKLER VK470 (K3.0) TECHNICAL DATA

TECHNICAL DATA. Page 1 of 5

TECHNICAL DATA vk470 (K3.0)

TECHNICAL DATA. Cover Plate Assembly must be ordered separately:

TECHNICAL DATA. Refer to the Approval Chart and Design Criteria for C-UL-US-EU Listing requirements that must be followed.

standard response sprinklers (vk102 & vk202) 3. technical data Specifications: Minimum Operating Pressure: 7 psi (0.5 bar) Sprinkler 11j

FREEDOM RESIDENTIAL HORIZONTAL SIDEWALL SPRINKLER VK479 (K3.0) TECHNICAL DATA

TECHNICAL DATA OBSOLETE

FREEDOM RESIDENTIAL PENDENT LEAD FREE SPRINKLER VK4700 (K3.0) TECHNICAL DATA

FREEDOM RESIDENTIAL HORIZONTAL SIDEWALL SPRINKLER VK460 (K5.8) TECHNICAL DATA

QUICK RESPONSE EXTENDED COVERAGE CONCEALED HSW SPRINKLER VK630 (K8.0) TECHNICAL DATA

FREEDOM RESIDENTIAL HORIZONTAL SIDEWALL SPRINKLER VK486 (K4.0) TECHNICAL DATA

FREEDOM RESIDENTIAL CONCEALED PENDENT SPRINKLER VK457 (K4.9) TECHNICAL DATA

freedom residential horizontal sidewall lead free sprinkler VK4840 (k4.2)

STANDARD/quick. Sprinkler 42o. August 8, 2011

FREEDOM RESIDENTIAL CONCEALED HORIZONTAL SIDEWALL SPRINKLER VK480 TECHNICAL DATA

Page 1 of 7. Form No. F_ Rev Replaces Form No. F_ Rev 17.1 (added 205deg version)

freedom residential Upright sprinkler vk467 (k4.9)

mirage Quick response concealed pendent sprinkler vk464 (K8.0)

TECHNICAL DATA. Viking Technical Data may be found on Maximum Working Pressure: 175 psi (12 Bar).

December 14, 2015 Page 1 of 7 TECHNICAL DATA

mirage Quick response concealed pendent sprinkler vk465 (K4.2)

Page 1 of 7. Replaces Form No. F_ Rev 16.3 (Added 16X22 and 18X20 coverage areas)

standard response/qr extended coverage concealed pendent sprinklers vk614 & vk616

MIRAGE STANDARD AND QR CONCEALED PENDENT SPRINKLER VK462 AND HP SPRINKLER VK463 (K5.6) TECHNICAL DATA

QUICK RESPONSE DRY CONCEALED PENDENT SPRINKLER VK194 TECHNICAL DATA

MIRAGE STANDARD AND QR CONCEALED PENDENT SPRINKLER VK462 AND HP SPRINKLER VK463 (K5.6) TECHNICAL DATA

quick response sprinkler vk194 Sprinkler 104j January 1, 2011

standard/quick response sprinklers (vk302 & vk352) 3. technical data Specifications: Available since Sprinkler 41g May 1, 2009

mirage Quick response extended coverage concealed pendent sprinklers (vk632 and vk634)

Form No. F_ Rev 14.1 Page 1 of 6 TECHNICAL DATA

mirage standard response concealed pendent sprinkler vk492 (K5.6)

MIRAGE EC/QREC OH-ELO CONCEALED PENDENT SPRINKLER VK538 (K11.2) TECHNICAL DATA

standard response large orifice dry

The Viking Corporation s Web site at Rated to 175 psi (12 bar) water working pressure

Standard Spray concealed horizontal sidewall sprinkler VK481

standard response/ quick response extended coverage

standard response dry horizontal sidewall sprinklers

TECHNICAL DATA. The Viking Corporation s Web site at Frame Casting: Brass UNS-C84400

microfast and microfasthp quick response horizontal sidewall sprinklers (vk305 & vk319)

quick response extra-large orifice upright sprinkler vk531 (storage-density/area)

HORIZON MIRAGE QUICK RESPONSE LARGE ORIFICE CONCEALED PENDENT SPRINKLER VK406 TECHNICAL DATA

STANDARD RESPONSE DRY HORIZONTAL SIDEWALL SPRINKLERS TECHNICAL DATA

TECHNICAL DATA. 2. LISTINGS AND APPROVALS culus Listed: Category VNIV FM Approved: Class 2009 NYC Approved: MEA E, Volume 3

TECHNICAL DATA. Page 1 of 6

quick response ordinary hazard dry hsw sprinklers (8.0K) (VK275, VK277, & VK279)

freedom residential horizontal sidewall sprinkler Vk450 (k4.2)

standard response dry horizontal sidewall sprinklers

TECHNICAL DATA. Viking Technical Data may be found on Minimum Operating Pressure: Refer to the Approval Chart.

standard response elo upright sprinkler

Quick response concealed horizontal sidewall sprinkler VK481

TECHNICAL DATA. Refer to Approval Chart 1 and UL Design Criteria for culus Listing requirements that must be followed.

QUICK RESPONSE EXTENDED COVERAGE HORIZONTAL SIDEWALL SPRINKLER VK630 (K8.0) TECHNICAL DATA

quick response extended coverage horizontal sidewall sprinkler vk630 (k8.0)

STANDARD/QUICK RESPONSE EXTENDED COVERAGE DRY HORIZONTAL SIDEWALL SPRINKLER TECHNICAL DATA

microfast quick response Pendent sprinkler VK302 (K5.6)

MICROFAST QUICK RESPONSE PENDENT SPRINKLER VK302 (K5.6) TECHNICAL DATA

sprinkler vk538 (K11.2)

micromatic standard response Upright sprinkler VK100 (K5.6)

HORIZON STANDARD RESPONSE FLUSH PENDENT SPRINKLER VK400 TECHNICAL DATA

QUICK RESPONSE ELO PENDENT SPRINKLER VK377 (STORAGE-DENSITY/AREA) TECHNICAL DATA 1. DESCRIPTION 2. LISTINGS AND APPROVALS 3.

micromatic Standard response Horizontal Sidewall sprinkler

EC/QREC ORDINARY HAZARD UPRIGHT SPRINKLER VK570 (K14.0) TECHNICAL DATA

STANDARD RESPONSE FUSIBLE LINK PENDENT SPRINKLER VK008 (K4.2) TECHNICAL DATA 1. DESCRIPTION 2. LISTINGS AND APPROVALS 3. TECHNICAL DATA.

STANDARD RESPONSE DRY PENDENT STANDARD ORIFICE SPRINKLERS TECHNICAL DATA

quick response Sprinkler 105a October 25, 2010

MICROMATIC STANDARD RESPONSE CONVENTIONAL SPRINKLER VK120 (K8.0) TECHNICAL DATA

MICROFAST QUICK RESPONSE PENDENT SPRINKLER VK3311 (K4.2) TECHNICAL DATA

TECHNICAL DATA OBSOLETE

micromatic standard sprinkler VK003 (K2.8) 3. technical data Page 1 of 7

standard response Fusible Link Upright sprinkler VK204 (K8.0)

MicrofastHP QUICK RESPONSE HORIZONTAL SIDEWALL HIGH PRESSURE SPRINKLER VK319 (K5.6) TECHNICAL DATA

TECHNICAL DATA OBSOLETE

TECHNICAL DATA 2. LISTINGS AND APPROVALS 3. TECHNICAL DATA

Special Features: For Light Hazard Occupancies Only Designed for Corridor Applications 28 Maximum Width Spacing. 3. technical data

TECHNICAL DATA. The Web site may include a more recent Frame Casting: Brass UNS-C84400

TECHNICAL DATA OBSOLETE

qr fusible element sprinklers (part nos , 13959, 17535, and 17536) 3. technical data Sprinkler 42h March 14, 2013

standard response dry horizontal sidewall sprinklers

micromatic standard sprinkler VK004 (K4.2) 3. technical data Page 1 of 6

EC/QREC ORDINARY HAZARD PENDENT SPRINKLER VK572 (K14.0) TECHNICAL DATA

MICROMATIC STANDARD RESPONSE PENDENT SPRINKLER VK102 (K5.6) TECHNICAL DATA 1. DESCRIPTION 2. LISTINGS AND APPROVALS 3. TECHNICAL DATA.

MICROMATIC STANDARD RESPONSE CONVENTIONAL SPRINKLER VK118 (K5.6) TECHNICAL DATA

microfast and microfasthp quick response horizontal sidewall sprinklers (vk305 & vk319)

quick response horizontal sidewall sprinkler vk360 (K8.0)

TECHNICAL DATA STANDARD/QUICK RESPONSE EXTENDED COVERAGE LIGHT HAZARD ELO PENDENT SPRINKLER VK608

FREEDOM RESIDENTIAL PENDENT SPRINKLER VK468 (K4.9) TECHNICAL DATA

Transcription:

Page 1 of 1. DESCRIPTION Viking Freedom Residential Concealed Pendent Sprinkler VK is a small highsensitivity glass bulb residential sprinkler for use with a domed cover assembly. The orifice design, with a K-Factor of.9 (70. metric*), allows the sprinkler s efficient use of available water supplies for the hydraulically designed fire-protection system. The glass bulb operating element and special deflector characteristics meet the challenges of residential sprinkler standards. Concealed sprinkler VK is pre-assembled with a threaded adapter for installation with the domed cover that provides up to ½ (12.7 mm) of vertical adjustment. The cover plate is available with several decorative finishes to meet design requirements. The two-piece design allows installation and testing of the sprinkler prior to installation of the cover plate. The push-on, thread-off design of the concealed cover plate assembly allows easy installation of the cover plate after the system has been tested and the ceiling finish has been applied. The cover assembly can be removed and reinstalled, allowing temporary removal of ceiling panels without taking the sprinkler system out of service or removing the sprinkler. The Electroless Nickel PTFE (ENT) coating has been investigated for installation in corrosive atmospheres and is C-UL-US-EU Listed as corrosion resistant as indicated in the Approval Charts. The ENT finish is only available for the sprinkler assembly, the cover plate is not plated. 2. LISTINGS AND APPROVALS UL Listed (C-UL-US-EU): Category VKKW NYC Approval: MEA 9-92-E, Volume 35 UL Classified to: NSF/ANSI Standard 1, Drinking Water System Components (MH03). Refer to the Approval Charts and Design Criteria for C-UL-US-EU Listing requirements that must be followed. 3. Specifications: Available since 0. Minimum Operating Pressure: Refer to the Approval Charts. Maximum Working Pressure: 5 psi (12 bar). Factory tested hydrostatically to 500 psi (3.5 bar). Thread size: 1/2 (15 mm) NPT Nominal K-Factor:.9 U.S. (70. metric*) * Metric K-factor measurement shown is in Bar. When pressure is measured in kpa, divide the metric K-factor shown by 10.0. Glass-bulb fluid temperature rated to -5 F (-55 C) Overall Length (Sprinkler Body): 2-1/ (5 mm) Material Standards: Frame Casting: Brass UNS-C00 or QM Brass Deflector: Brass UNS-C23000, Phosphor Bronze UNS-C51000, or Brass UNS-C00 Bulb: Glass, nominal 3 mm diameter Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with PTFE Tape Compression Screw: Brass UNS-C3000 Pip Cap and Insert Assembly: Copper UNS-C11000 and Stainless Steel UNS-S3000 Cover Adapter: Cold Rolled Steel UNS-G1000, Finish: Clear Chromate over Zinc Plating Cover Assembly Materials: Cover Plate Assembly: Copper UNS-C11000 and Brass UNS-C200 Spring: Beryllium Nickel Solder: Eutectic Ordering Information: (Also refer to the current Viking price list.) Viking Residential Concealed Pendent Sprinkler VK and Cover Plate Assembly must be ordered separately: Sprinkler: Base Part Nos. 37A-X for Brass finish and 37JN-X for ENT finish (includes sprinkler and adapter pre-assembled, with a protective plastic cap covering the unit) Viking Technical Data may be found on The Viking Corporation s Web site at http://www.vikinggroupinc.com. The Web site may include a more recent edition of this Technical Data Page. (Added EU Listing)

Page 2 of Specify sprinkler temperature rating by adding the appropriate suffix for the temperature rating to the base part number: Temperature Rating: 155 F ( C) = B, 5 F (79 C) = D For example, concealed sprinkler VK with a 155 F ( C) temperature rating = Part No. 37ABX Note: When ordering this sprinkler using the SIN, add suffix -D. For example, concealed sprinkler VK = VK-D. Cover Plate Assembly: Base Part No. 127 Specify finish and temperature rating of the cover plate assembly by adding the appropriate suffixes for the finish and the cover temperature rating to the base part number: Finish Suffix: Polished Chrome = F, Brushed Chrome = F-/B, Bright Brass = B, Antique Brass = B-/A, Brushed Brass = B-/B, Brushed Copper = E-/B, Painted White = M-/W, Painted Ivory = M-/I, Painted Black = M-/B Temperature Suffix: 5 F (57 C) = A For example, cover 127 with a Polished Chrome finish and a 5 F (57 C) temperature rating = 127FA. Available Finishes And Temperature Ratings: Refer to Table 1. Accessories: (Also refer to the Sprinkler Accessories section of the Viking data book.) Sprinkler Wrench: Part No. 577W/B** (available since 0) **A ½ ratchet is required (not available from Viking). Sprinkler Cabinet: Part No. 031A (available since 1971). INSTALLATION Refer to appropriate NFPA Installation Standards. 5. OPERATION During fire conditions, when the temperature around the sprinkler approaches its operating temperature, the cover plate detaches. Continued heating of the exposed sprinkler causes the heat-sensitive liquid in the glass bulb to expand and the bulb to shatter, releasing the pip cap and sealing spring assembly. Water flowing through the sprinkler orifice strikes the sprinkler deflector, forming a uniform spray pattern to extinguish or control the fire.. INSPECTIONS, TESTS AND MAINTENANCE Refer to NFPA 25 for Inspection, Testing and Maintenance requirements. 7. AVAILABILITY The Viking Model VK Sprinkler is available through a network of domestic and international distributors. The Viking Corporation web site for the closest distributor or contact The Viking Corporation.. GUARANTEE For details of warranty, refer to Viking s current list price schedule or contact Viking directly. Sprinkler Temperature Classification TABLE 1: AVAILABLE SPRINKLER TEMPERATURE RATINGS AND FINISHES Sprinkler Nominal Temperature Rating 1 Maximum Ambient Ceiling Temperature 2 Temperature Rating of the Cover Assembly (Required) Cover Plate Base Part No. 3 Ordinary 155 F ( C) 100 F (3 C) 5 F (57 C) 127 Red Bulb Color Intermediate 5 F (79 C) 150 F (5 C) 5 F (57 C) 127 Yellow Sprinkler Finishes: Brass or ENT ( Ordering Information section) Cover Plate Finishes: Polished Chrome, Brushed Chrome, Bright Brass, Antique Brass, Brushed Brass, Brushed Copper, Painted White, Painted Ivory, or Painted Black Corrosion Resistant Coatings : ENT s 1 The sprinkler temperature rating is stamped on the deflector. 2 Based on NFPA-, NFPA R, and NPFA D. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having Jurisdiction. Refer to specific installation standards. 3 Part number shown is the base part number. For complete part number, refer to current Viking price list schedule. The corrosion resistant coatings have passed the standard corrosion test required by the approving agencies indicated in the Approval Charts. These tests cannot and do not represent all possible corrosive environments. Prior to installation, verify through the end-user that the coatings are compatible with or suitable for the proposed environment. For automatic sprinklers, the ENT coating is applied to all exposed exterior surfaces, including the waterway. For ENT coated sprinklers, the Belleville spring is exposed.

Page 3 of Approval Chart 1 Viking VK,.9 K-Factor Residential Concealed Pendent Sprinkler For systems designed to NFPA D or NFPA R. For systems designed to NFPA, refer to the design criteria. For Ceiling types refer to NFPA, R or D Editions Sprinkler Base Part Number 1 SIN NPT Thread Size Nominal K-Factor Maximum Water Overall Length Inches mm U.S. metric 2 Working Pressure Inches mm 37A-X VK 1/2 15.9 70. 5 psi (12 bar) 2-1/ 5 Max. Coverage Area Ft.X Ft. (m X m) Ordinary Temp Rating (155 F/ C) Flow Pressure Intermediate Temp Rating (5 F/79 C) Flow Pressure Deflector to Ceiling Installation Type Listings and Approvals 3 NYC 5 NSF 7 Minimum Spacing Ft. (m) 12 X 12 (3.7 X 3.7) 1 X 1 (.3 X.3) 1 X 1 (.9 X.9) 1 X 1 (5.5 X 5.5) (.) (.) 3/ to 7/ inch Concealed with Cover Plate Assembly. and 9. and 9. and 9. (2.) X (.1 X.1) 1.7 1.7 s 1 Part number shown is the base part number. For complete part number, refer to Viking s current price schedule. 2 Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kpa, divide the metric K-factor shown by 10.0. 3 This chart shows the listings and approvals available at the time of printing. Other approvals may be in process. Check with the manufacturer for any additional approvals. Refer also to Design Criteria. Listed by Underwriter s Laboratories, Inc. for use in the U.S., Canada, and European Union. 5 Accepted for use, City of New York Department of Buildings, MEA Number 9-92-E, Vol. 35. Cover Temperature Rating is 5 F (57 C). 7 UL Classified to: NSF/ANSI Standard 1, Drinking Water System Components (MH03). For areas of coverage smaller than shown, use the Flow and Pressure for the next larger area listed. Flows and pressures listed are per sprinkler. The distance from sprinklers to walls shall not exceed one-half the sprinkler spacing indicated for the minimum Flow and Pressure used. 9 Accepted Cover Plate Finishes are: Polished Chrome, Brushed Chrome, Bright Brass, Antique Brass, Brushed Brass, Brushed Copper, Painted White, Painted Ivory, or Painted Black 10. 10 Other paint colors are available on request with the same listings as the standard finish colors. Listings and approvals apply for any paint manufacturer. Contact Viking for additional information. Custom colors are indicated on a label inside the cover assembly. Refer to Figure 2.

Page of Approval Chart 2 Viking VK,.9 K-Factor Residential Concealed Pendent Sprinkler For systems designed to NFPA D or NFPA R. For systems designed to NFPA, refer to the design criteria. For Ceiling types refer to NFPA, R or D Editions Sprinkler Base Part Number 1 SIN NPT Thread Size Nominal K-Factor Maximum Water Overall Length Inches mm U.S. metric 2 Working Pressure Inches mm 37JN-X 9 VK 1/2 15.9 70. 5 psi (12 bar) 2-1/ 5 Max. Coverage Area Ft.X Ft. (m X m) Ordinary Temp Rating (155 F/ C) Flow Pressure Intermediate Temp Rating (5 F/79 C) Flow Pressure Deflector to Ceiling Installation Type Listings and Approvals 3 C-UL- US- NYC NSF EU Minimum Spacing Ft. (m) 12 X 12 (3.7 X 3.7) 1 X 1 (.3 X.3) 1 X 1 (.9 X.9) 1 X 1 (5.5 X 5.5) (.) (.) 3/ to 7/ inch Concealed with Cover Plate Assembly. 5 and 7. -- -- (2.) X (.1 X.1) 1.7 1.7 s 1 Part number shown is the base part number. For complete part number, refer to Viking s current price schedule. 2 Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kpa, divide the metric K-factor shown by 10.0. 3 This chart shows the listings and approvals available at the time of printing. Other approvals may be in process. Check with the manufacturer for any additional approvals. Refer also to Design Criteria. Listed by Underwriter s Laboratories, Inc. for use in the U.S. and Canada. 5 Cover Temperature Rating is 5 F (57 C). For areas of coverage smaller than shown, use the Flow and Pressure for the next larger area listed. Flows and pressures listed are per sprinkler. The distance from sprinklers to walls shall not exceed one-half the sprinkler spacing indicated for the minimum Flow and Pressure used. 7 Accepted Cover Plate Finishes are: Polished Chrome, Brushed Chrome, Bright Brass, Antique Brass, Brushed Brass, Brushed Copper, Painted White, Painted Ivory, or Painted Black. Other paint colors are available on request with the same listings as the standard finish colors. Listings and approvals apply for any paint manufacturer. Contact Viking for additional information. Custom colors are indicated on a label inside the cover assembly. Refer to Figure 2. 9 C-UL-US-EU Listed as corrosion resistant.

Page 5 of UL Listing Requirements (C-UL-US-EU): DESIGN CRITERIA (Also refer to the Approval Charts.) When using Viking Residential Concealed Pendent Sprinkler VK for systems designed to NFPA D or NFPA R, apply the listed areas of coverage and minimum water supply requirements shown in the Approval Charts. For systems designed to NFPA : The number of design sprinklers is to be the four contiguous most hydraulically demanding sprinklers. The minimum required discharge from each of the four sprinklers is to be the greater of the following: The flow rates given in the Approval Charts for NFPA D and NFPA R applications for each listed area of coverage, or Calculated based on a minimum discharge of 0.1 gpm/sq. ft. over the design area in accordance with sections.5.2.1 or..2.1.2 of NFPA. Minimum distance between residential sprinklers: ft. (2. m). DEFLECTOR POSITION: Install Residential Concealed Pendent Sprinkler VK with the deflector 3/ (9.5 mm) to 7/ (22.2 mm) below the ceiling. Refer to Figure 3. NOTE: Concealed sprinklers must be installed in neutral or negative pressure plenums only. IMPORTANT: Always refer to Bulletin Form No. F_09199 - Care and Handling of Sprinklers. Also refer to pages RES1- for general care, installation, and maintenance information. Viking sprinklers are to be installed in accordance with the latest edition of Viking technical data, the appropriate standards of NFPA and any other similar Authorities Having Jurisdiction, and also with the provisions of governmental codes, ordinances, and standards, whenever applicable. Final approval and acceptance of all residential sprinkler installations must be obtained from the Authorities Having Jurisdiction. Figure 1: Concealed Sprinkler VK with Protective Shell Figure 2: Identification of Custom Paint Color for Concealed Covers

Page of Figure 3: Sprinkler Dimensions and Cover Installation Figure : Sprinkler Installation and Correct Use of Sprinkler Wrench (Added EU Listing)