OWNER'S SERVICE MANUAL NO INSPECTION, MAINTENANCE AND RECHARGE

Similar documents
PURPLE K POWDER EXTINGUISHERS INSTALLATION, OPERATION, MAINTENANCE AND RECHARGE MANUAL

F-CLASS MODEL M6L WET CHEMICAL FIRE EXTINGUISHER Installation, Operation, Recharge and Maintenance Manual

WHEELED STORED PRESSURE

SERVICE MANUAL (v1) UL / ULC. WET CHEMICAL HAND PORTABLE RESTAURANT KITCHEN FIRE EXTINGUISHERS Model: SF-6LK / WBDL-6LK

HIGH PERFORMANCE HEAVY DUTY INDUSTRIAL STORED PRESSURE

OWNERS SERVICE MANUAL

FIre Extinguishers. K-GUARD Wet Chemical Fire Extinguishers Manual INSTALLATION 2014-DEC-29 REV. 03 PAGE 1 EXTINGUISHERS

OWNERS SERVICE MANUAL NO INSTALLATION, OPERATING & SERVICING INSTRUCTIONS

OWNERS SERVICE MANUAL NO

COMPONENT MAINTENANCE MANUAL WITH ILLUSTRATED PARTS LIST

FIRE EXTINGUSIHER INSPECTION, MAINTENANCE, AND TESTING PROCEDURES

TRAINING BULLETIN TOOLS 1 May 27, 2011 PRESSURIZED WATER EXTINGUISHER

DRY CHEMICAL AND CLEAN AGENT HAND PORTABLE FIRE EXTINGUISHERS

OWNER'S OPERATION AND MAINTENANCE MANUAL

TECHNICAL DATA. Wet 26a. February 22, 2009

DEPARTMENT OF LICENSING AND REGULATORY AFFAIRS DIRECTOR S OFFICE GENERAL INDUSTRY SAFETY STANDARDS PART 8. PORTABLE FIRE EXTINGUISHERS

HYDROSTATIC TEST INSTRUCTIONS

OPTIONAL INFORMATION PORTABLE FIRE EXTINGUISHERS SELF INSPECTION CHECKLIST

COMDTPUB P NVIC JUNE 1995

STORED PRESSURE YES TEST STANDARDS: CAN/ULC S504 & ANSI/UL 229 CAN/ULC S508 & ANSI/UL 711. Available Options: Stationary Design Tow Loop

Types of Detection. Fusible Link Detection - Most Common

*** Inspection *** Please identify yourself as a Cintas representative when arriving onsite.

Technical Data Sheet No. JS-SM-40 DOCUMENT TITLE 2.0 LITRE STORED PRESSURE WET CHEMICAL FIRE EXTINGUISHER

Technical Data Sheet No. JS-SM-33 DOCUMENT TITLE. 2.0kg ABE TYPE STORED PRESSURE DRY POWDER PORTABLE FIRE EXTINGUISHER MODEL: R2.

SECTION air supply system + WARNING: + NOTE: GENERAL DESCRIPTION COMPRESSED AIR RESERVOIRS / 1.

Technical Data Sheet No. JS-SM-38 DOCUMENT TITLE 3.5KG CARBON DIOXIDE FIRE EXTINGUISHERS

ANSUL. Twin-Agent Fire Fighting/Securing Systems Specifications. Models 450/50-B, 450/100-B, 900/100-B INDEX SPECIFICATIONS

2-SUPPRESSION REQUIREMENTS - CODE REQUIRED INSPECTIONS TEST Page 1 of 7

June 2018 Safety Meeting Fire Extinguishers Part I

COMPONENT MAINTENANCE MANUAL

Service Requirements SEMI- ANNUAL ANNUALLY OTHER REF. REQUIREMENT

Installation, Operation and Maintenance LOK-FLANGE Multitube Heat Exchangers

USER MANUAL SPRAY GUN CLEANER - WATER BASED PAINTS UA400W CAUTION FOR WATER BORNE PAINTS ONLY

Twin-Agent Fire Fighting/Securing Systems Specifications

Fire Extinguisher Use. Fire Extinguisher Review. and Fire Safety

GETZ EQUIPMENT INNOVATORS PART NO.: 9G58619 MODEL: SV1 150 PR VACUFILL SYSTEM (Revised 2/25/14)

Audi-Larm Audible Alarm

WARNING. Flexible Hose AH2 With AB6 With AB6. AH2-CC With AB6 With AB6

Extinguishers. Commercial Industrial High rise buildings

COMPONENT MAINTENANCE MANUAL

Subchapter 7. General Industry Safety Orders Group 27. Fire Protection Article 157. Portable Fire Extinguishers. Return to index New query

Safety Policy and Procedure

Government of Bermuda Department of Maritime Administration BERMUDA SHIPPING NOTICE

4 route 147, C.P.33 Coaticook, Qc J1A 2S8

Model ESFR-17 Dry Type Pendent Sprinklers Early Suppression Fast Response 16.8 K-factor General Description

Page 1 of 18. Part# /5/2013

568X, 587X, 588X Series

Model Policy On Portable Fire Extinguishers (Ontario Version)

WARNING. Pro Pack Portable Spray Pack 3A1292C. Operation. Model 24F893 Maximum Working Pressure 12 psi (0.83 bar, MPa)

P/N CC-100. Coolant Circulator. Operation manual

ModulAir Air Dryer with External Purge Tank - Changeover from Bendix AD-IS for Peterbilt Installation. Air Dryer Mounting Bracket (Item 1)

K 2.97 M. Specifications Operating pressure, max PSI Water volume GPM Voltage V Amp draw AMPS

Models: FM FM WARNING

Model K 280 M Part No

FIRE EXTINGUISHER SERVICING & MAINTENANCE INSTRUCTIONS

Maintenance Manual WATER SLUG CONTROL SWITCH PART NUMBERS: F528 AND F528B

Model K 330 M Part No

TECHNICAL DATA. model c-2

I-VICFLEX.AB4. Victaulic VicFlex Style AB4 Sprinkler Fitting for Hat Furring Channel Ceiling Systems WARNING INSTALLATION INSTRUCTIONS

SuperKlean Washdown Products

Model K 520 M Part No

Fight or Flee? Extinguisher Basics Extinguisher Use Extinguisher Placement and Spacing Hydrostatic Testing OSHA Requirements Test Your Knowledge

UPP7500E2 AUTOMATIC PRESSURE POT CLEANER

AC6 & AC8 HORIZONTAL SERIES Sealed Metallic Centrifugal Pumps Installation and Maintenance Instructions

TECHNICAL DATA OBSOLETE

REF. NO Clamp Assembly 8 1 set Gasket (4 per set) S.S. Lock-washer 3/8 x 1/ Brass Impeller 3.

Portable Fire Extinguishers

OPERATING MANUAL SOLVENT SPRAY GUN CLEANERS UG5000E, UG5000DVM AND UG5500E UNI-RAM CORPORATION ONTARIO CANADA PATENTS

GETZ MANUFACTURING PART NO.: MODEL: SV1 100 PR VACUFILL SYSTEM (Revised 6/7/05)

IMO. Resolution A.951(23) Adopted on 5 December 2003 (Agenda item 17) IMPROVED GUIDELINES FOR MARINE PORTABLE FIRE EXTINGUISHERS

Norminal Sprinkler Temperature Rating

Model A Pipe Line Strainer 3, 4, 6, 8 & 10 Inch (DN80, DN100, DN150, DN200 & DN250) 175 psi (12,1 bar) General Description.

Installation and Operating Instructions ISH ELECTRIC STEAM SUPERHEATER

Viking Installation Guide

569, 570, 571, 572 Series

GUILFORD COUNTY SCHOOLS

OWNER S MANUAL. Models: Herkules Equipment Corporation 2760 Ridgeway Court Walled Lake, MI USA Fax

OPERATING MANUAL UG2000D SERIES SPRAY GUN CLEANERS UG2000D, UG2000DM UNI-RAM CORPORATION ONTARIO CANADA UG2000DM UG2000D REVISION

Patterson/AMT Inline Circulator Pump Refer to pump manual for General Operating and Safety Instructions.

SPRINKLER HEAD. Upright, Pendent & Recessed Pendent Sprinklers MODEL: SD1010, SD1015, SD1030, SD1032 DESCRIPTION TECHNICAL SPECIFICATION

Upholstery and Drapery Cleaner. Operator and Parts Manual. Model No.: gal Extractor. MNL32506 Rev. 00 (08-98)

CAUTION UM120W (RIGHT TANK) FOR WATER BORNE PAINTS ONLY UM120W (RIGHT TANK) SECTION IS NOT DESIGNED FOR USE WITH SOLVENT BASED PAINT

Norminal Sprinkler Temperature Rating

Portable Fire Extinguishers

K 2.90 M. Specifications Operating pressure, max PSI Water volume GPM Voltage V Amp draw AMPS

HEATING AND AIR CONDITIONING

Vacuum toilet system Instruction manual. Series. Series and Series. VacuFlush

Models: GW/R-T GW/R-2-T GW/R-3-T

WARRANTY TABLE OF CONTENTS TECHNICAL SPECIFICATIONS. Product Warranty Always keep your receipt as proof of purchase. Technical specifications...

K Specifications. Max. Water Volume

HT650 TM FAN DRIVE SERVICE INSTRUCTIONS

INSTALLATION & OPERATING INSTRUCTIONS

K Specifications. Max. Water Volume


SERVICE INSTRUCTION SI0035 Rev NC Page 1 of 3

Technical Data TYPE T14 & T14D TEMPERATURE PILOT SPENCE ENGINEERING COMPANY, INC. 150 COLDENHAM ROAD, WALDEN, NY SD 4511A T14 PILOT

Patterson/AMT Inline Circulator Pump Refer to pump manual for General Operating and Safety Instructions.

SELF-CONTAINED POWER MISTER

Safety, Operation and Maintenance Manual with Parts List

JUL 17 Rev C

Transcription:

FOAM FIRE EXTINGUISHERS MODEL 254-6 LITER AFFF FOAM WITH SPRAY NOZZLE Model 250 2 ½ GAL.LON AFFF FOAM WITH ASPIRATED NOZZLE MODEL 252 2 ½ GAL.LON FFFP (ALCOHOL RESISTANT) FOAM WITH ASPIRATED NOZZLE OWNER'S SERVICE MANUAL NO. 05607 INSPECTION, MAINTENANCE AND RECHARGE WARNING: DO NOT USE THESE EXTINGUISHERS ON FIRES INVOLVING ENERGIZED ELECTRICAL EQUIPMENT (CLASS C HAZARDS), FLAMMABLE METALS (CLASS D HAZARDS) OR ANY FLAMMABLE THAT WILL REACT WITH WATER. PROTECT FROM FREEZING! All fire extinguishers should be installed, inspected and maintained in accordance with the National Fire Protection Association standard titled "Portable Fire Extinguishers", NFPA-0 and the requirements of local authorities having jurisdiction. When maintenance is indicated it should be performed by trained persons having proper equipment. Fire extinguishers are pressure vessels and must be treated with respect and handled with care. They are mechanical devices and require periodic maintenance to be sure that they are ready to operate properly and safely. Amerex strongly recommends that the maintenance of portable fire extinguishers be done by a trained professional your local authorized Amerex Distributor. Amerex Corporation makes original factory parts available to insure proper maintenance use of substitute parts releases Amerex of its warranty obligations. Amerex parts have machined surfaces and threads that are manufactured to exacting tolerances. O-rings, hoses, nozzles, horns and all metal parts meet precise specifications and are subjected to multiple in-house inspections and tests for acceptability. There are substitute parts available that are incorrectly labeled as UL component parts, some are advertised as Amerex type. None of these meet UL requirements and all of them void the Amerex extinguisher warranty and UL listing. DO NOT SUBSTITUTE. RECHARGE FIRE EXTINGUISHERS IMMEDIATELY AFTER ANY USE REFERENCES IN THIS MANUAL NFPA-0 Portable Fire Extinguishers AVAILABLE FROM National Fire Protection Association P. O. Box 90 Quincy, MA 02269-90 CGA C- Methods for Hydrostatic Testing Compressed Gas Association of Compressed Gas Cylinders 235 Jefferson Davis Hwy, Suite 50 CGA C-6 Standard for Visual Inspection Arlington, VA 22202 of Compressed Gas Cylinders AMEREX CORPORATION P.O. BOX 8 TRUSSVILLE, ALABAMA 3573-008 Phone: 205/655-327 Fax: 800/654-5980 e-mail: sales@amerex-fire.com Web Page: http://www.amerex-fire.com Printed in U.S.A. 0M05607D Rev. 0/ 0

AMEREX CORPORATION DOES NOT SERVICE, MAINTAIN OR RECHARGE FIRE EXTINGUISHERS. THE MAINTENANCE AND RECHARGE PORTION OF THIS MANUAL IS PUBLISHED AS A GUIDE TO ASSIST SERVICE PERSONNEL IN THE INSPECTION, MAINTENANCE AND RECHARGE OF AMEREX FIRE EXTINGUISHERS ONLY. NO INSTRUCTION MANUAL CAN ANTICIPATE ALL POSSIBLE MALFUNCTIONS THAT MAY BE ENCOUNTERED IN THE SERVICE OF FIRE EXTINGUISHERS. AMEREX ASSUMES NO LIABILITY FOR SERVICE, MAINTENANCE OR RECHARGE OF FIRE EXTINGUISHERS BY PUBLISHING THIS MANUAL. INSPECTING THE EXTINGUISHER This extinguisher should be inspected at regular intervals (monthly or more often if circumstances require) to insure that it is ready for use. INSPECTION (NFPA-0) A quick check should be made of the extinguisher for the following:. Located in designated place. 2. No obstructions to access or visibility. 3. Operating instructions on nameplate (label) and facing outward. 4. Seals and tamper indicators not broken or missing. 5. Determine fullness by weighing or "hefting". 6. Examine for obvious physical damage, corrosion, leakage or clogged nozzle. 7. Pressure gauge reading in the operable area. MAINTENANCE SERVICE PROCEDURE MAINTENANCE (NFPA-0) At least once a year (or more frequently if indicated by an inspection), maintenance should be performed. Maintenance is a thorough check of the extinguisher. It is intended to give maximum assurance that an extinguisher will operate effectively and safely. It includes a thorough examination and any necessary repair or replacement. It will normally reveal the need for hydrostatic testing.. Clean extinguisher to remove dirt, grease or foreign material. Check to make sure that the instruction nameplate is securely fastened and legible. Inspect the cylinder for corrosion, abrasion, dents or weld damage. If any of these conditions are found and you doubt the integrity of the cylinder, hydrostatically test, using the proof pressure method and a suitable cage, in accordance with CGA Pamphlet C- and NFPA Pamphlet 0. NOTE: When cleaning avoid use of solvents around the pressure gauge. They could seriously damage the plastic gauge face. 2. Inspect the extinguisher for damaged, missing or substitute parts. Only factory replacement parts are approved for use on Amerex fire extinguishers. 3. Check the date when last recharged. The foam charge must be replaced every three years with the proper Amerex charge (model 502 AFFF charge for models 250 and 254, model 504 FFFP for model 252). If the extinguisher is to be hydrotested do not reuse the charge even if within a three year cycle (the foaming action will make it almost impossible to get complete charge back into the extinguisher). 4. Weigh extinguisher and compare with weight printed on the Maintenance section of the nameplate (label). Recharge extinguisher if weight is not within the indicated allowable tolerances.

5. Check the date of manufacture on the extinguisher hanger loop or on the extinguisher nameplate. Cylinder must be hydrostatically tested every 5 years to the test pressure indicated on the label. 6. Visually inspect the pressure gauge: a. If bent, damaged or improper gauge, depressurize and replace b. If pressure is low, check for leaks c. If over pressurized (overcharged), depressurize (discharge) and follow recharging instructions. 7. Inspect the footstand (base). If cracked or broken replace with proper footstand. 8. Inspect ring pin for freedom of movement by breaking the seal and removing the pin. Replace the ring pin if bent or if removal is difficult. 9. Inspect discharge lever for dirt or corrosion that might impair freedom of movement. Inspect carrying handle for proper installation. If lever, handle or rivets are damaged or distorted, replace with proper Amerex part(s). 0. Remove hose assembly, inspect hose assembly for damage, replace as necessary. Blow air through hose assembly to insure passage is clear of foreign material.. Inspect the valve assembly for corrosion or damage to hose thread connections. Replace valve assembly or component parts as necessary following the proper depressurization and recharge procedures. 2. Install hose and nozzle assembly. 3. Install new tamper seal and record service data on the extinguisher inspection tag. 4. Rehang the extinguisher on the wall hanger bracket making sure that it fits the hanger bracket properly replace the bracket if necessary. RECHARGE RECHARGING is the replacement of the extinguishing agent and includes the expellant for this type of extinguisher. THE FIRE EXTINGUISHING AGENT IN THIS EXTINGUISHER MUST BE COMPLETELY REPLACED EVERY THREE YEARS. Use only the Amerex Model 502 AFFF or Model 504 FFFP concentrate charge to retain the UL approval and manufacturer s warranty. Substitute charges could make the extinguisher less effective. WARNING: a. Before attempting to recharge be sure this extinguisher is completely depressurized. b. Use a regulated nitrogen pressurizing source. Set the regulator no more than 25 psi (862 kpa) higher than the gauge operating pressure. c. Check and calibrate regulator gauge at frequent intervals. The regulator gauge should be used to determine when the intended charging pressure has been reached. Do not use the extinguisher gauge for this purpose. d. Never leave an extinguisher connected to a regulator of a high pressure source for an extended period of time. A defective regulator could cause the cylinder to rupture due to excessive pressure. 2

RECHARGING PROCEDURE. Complete the Maintenance-Service Procedure, items thru. 2. Discharge all remaining pressure and AFFF or FFFP solution. 3. Remove the valve assembly and disassemble by removing downtube assembly, spring and valve stem from the valve assembly. Remove the collar o-ring from the valve assembly. Remove collar o-ring from the valve and plastic fill tube from the cylinder. 4. Thoroughly rinse all parts with clean water and wipe dry with a soft cloth. Inspect the valve components and collar o-ring and valve stem. Lubricate the collar o-ring and small o-ring on the valve stem with Visilox V-7 (do not lubricate the valve stem seal). Inspect the downtube. If it is cracked or deformed replace with proper downtube (see Parts List). Inspect downtube o-ring, replace if necessary. 5. Rinse the cylinder with clean water and inspect the interior following CGA Visual Inspection Standard C-6. 6. Firmly replace the plastic fill tube. On an accurate scale: a. Model 250 2-/2 gal. AFFF Premix. Fill cylinder with 2.43 gals. (9.20 liters) (20.24 lbs. [9.8 kg]) of clean tap or distilled water. Continue with steps b2. And b3. b. Model 254 6 Liter AFFF Premix. Fill cylinder with.52 gals. (5.75 liters) (2.65 lbs. [5.74 kg]) of clean tap or distilled water. 2. Slowly add an Amerex 502 AFFF charge to the water. The liquid level should now be close to the bottom of the fill tube. 3. If necessary add water very slowly to bring the liquid to this level. c. Model 252 2-/2 gal. FFFP Premix. Fill cylinder with 2.2 gals. (8.33 liters) (8.32 lbs. [8.3 kg]) of clean tap water or distilled water. 2. Slowly add an Amerex Model 504 FFFP charge to the water. The liquid level should now be close to the bottom of the fill tube. 3. If necessary add water very slowly to bring the liquid to this level. 7. Install a Verification of Service collar around neck of cylinder. Install valve assembly to the cylinder and properly align. Shake the extinguisher to assure a thorough mix of the foam solution. CAUTION: HAND TIGHTEN THE VALVE COLLAR NUT 00-25 IN LBS. MAX. (.5-.44 KG/m). OVER-TIGHTENING WITH A WRENCH WILL DAMAGE THE VALVE. 8. Install a P/N 024 Fill (Pressurizing) Adapter on the valve outlet (where the hose assembly attaches) and pressurize with nitrogen to 00 psi (690 kpa). The pressure regulator should be set to no more than 25 psi (862 kpa). Remove Fill Adapter. 9. Check the collar, gauge, cylinder welds and valve orifice for leaks using a leak detection fluid or a solution of soapy water. Remove leak detection fluid from the valve assembly by blowing out with air and wipe exterior of the extinguisher to dry. 0. Install hose assembly into the operating valve. Torque swivel nut lightly with a 5/6 wrench. Install in hose clip. 3

. Install ring pin with ring facing front of the extinguisher. Install new tamper seal. Record recharge date and attach new recharge tag. 2. Weigh assembled extinguisher and confirm that the total weight is within the allowable tolerances indicated in the Maintenance section on the extinguisher nameplate (label). TROUBLESHOOTING GUIDE WARNING: Determine the source of a leak before the extinguisher is depressurized. THE EXTINGUISHER MUST BE COMPLETELY DEPRESSURIZED BEFORE ANY ATTEMPT IS MADE TO DEVALVE IT AND CORRECT ANY LEAKAGE PROBLEM. To depressurize hold the extinguisher in an inverted position and slowly squeeze the discharge handle. Some liquid remaining in the downtube will be discharged so care should be taken in the area used for depressurization. Thoroughly clean all valve parts after depressurization and valve removal. PROBLEM. Leak at collar o-ring 2. Leak through valve 3. Leak around gauge threads 4. Defective gauge 5. Leak in the cylinder CORRECTIVE ACTION Remove valve assembly, clean collar (knurled) nut thoroughly and install new o-ring. Lubricate the o-ring with Visilox V-7 (P/N 06247). Install new valve stem assembly. Check valve seat for scratches or foreign matter. Remove gauge* and reinstall using Teflon tape on the gauge threads. Remove defective gauge* and install a new gauge using Teflon tape on the gauge threads. Contact Amerex if under warranty, otherwise mark "Rejected" and return to owner. 6. Broken footstand Install new footstand (see parts list) * Pressure gauge threads are coated with a special epoxy at the factory. For easy removal soak the valve assembly (minus the downtube assembly) in hot water (80 F/82 C) for two to four minutes. Remove gauge with a 7/6 open end wrench. 4

PARTS LIST For Model 254 6 Liter AFFF Foam Extinguisher Model 250 2½ Gallon AFFF Foam Extinguisher Model 252 2½ Gallon FFFP Foam Extinguisher ITEM PART STD NO. NO. DESCRIPTION PKG 4345 Valve Assembly 2 06978 Hose Gasket (O-ring) 24 3 362 Hose & Spray Nozzle Asy 254 3A 07000 06982 Hose & Aspirated Noz. Asy 250 Hose & Aspirated Noz. Asy 252 4 0007 Wall Bracket 6 5 0060 Ring Pin, Stainless Steel 24 5A 00532 Chain (Nylon) for ring Pin 24 6 0387 Lock Wire Seal (Yellow) 500 7 07762 Lever & Rivet 7A 0563 Rivet Only for Handle (2 required) 24 8 09020 Handle & Rivets 8A 0564 Rivet Only for Handle (2 required) 24 9 06479 Valve Stem Asy 6 0 05240 Collar O-Ring 24 06093 Valve Stem Assembly Valve Stem Assembly (bulk bag) 2 05243 Valve Stem O-Ring 24 3 00383 Spring 6 4 02595 Fill tube 6 96 5 05690 Downtube O-Ring 2 6 0258 Downtube/Retainer Asy 254 02209 Downtube/Retainer Asy 250, 252 7 03376 Footstand w/post (Black) 250, 252 0309 Footstand (Black) 254 8 024 Pressurizing Adapter 9 038 Hydrotest Adapter 20 4776 Strap & Clip 254 027 Model 502 AFFF Premix Charge 250, 254 2 0698 Model 504 FFFP Premix Charge 252 2 04488 Adhesive (Footstand) 3 oz. tube 06247 Visilox Lubricant 5 oz. tube NOTE: All Valve Assemblies include new Valve Body, Pressure Gauge, Wing Nut Lever & Handle PARTS NOT PICTURED 5