COMPARISON OF HEATING SYSTEMS IN A RESIDENTIAL BUILDING

Similar documents
Energy Savings Potential of Passive Chilled Beam System as a Retrofit Option for Commercial Buildings in Different Climates

Clemens Felsmann 1, Jean Lebrun 2, Vincent Lemort 2 and Aad Wijsman 3 ABSTRACT INTRODUCTION METHODOLOGY

VENTILATIVE COOLING CONTROL STRATEGIES APPLIED TO PASSIVE HOUSE IN ORDER TO AVOID INDOOR OVERHEATING

Figure 1: Low energy dwellings testsite

indirect evaporative cooling: interaction between thermal performance and room moisture balance

MODELLING AND SIMULATION OF A ROOM WITH A RADIANT COOLING CEILING. Technicka 4, Prague 6, Czech Republic

*Bioenergy GmbH Gewerbepark Haag 3, 3250 Wieselburg Land, Austria

Measurement and modelling of a multifunctional solar plus heatpump system from Nilan. Experiences from one year of test operation.

The Corbioli House is a single-family house situated

PCM-module to improve hot water heat stores with stratification: first tests in a complete solar system

Available online at ScienceDirect. Energy Procedia 78 (2015 )

Indoor Climate Control Effect of AAC Panel Heat Capacity Experimental rooms and simulations with three structural materials

Appendix 8: Generic System #15: Two Stratifiers in a Space Heating Storage Tank with an External Load-Side Heat Exchanger for DHW

Reducing the Carbon Footprint of Existing Domestic Heating: A Non-Disruptive Approach

K.F. Fong *, C.K. Lee, T.T. Chow

A Simulation Study on the Energy Efficiency of Gas-Burned Boilers in Heating Systems

EXHAUST AIR HEAT PUMPS EVALUATED FOR NORDIC CIRCUMSTANCES

Experimental Study on the Thermal Behavior of a Domestic Refrigeration Compressor during Transient Operation in a Small Capacity Cooling System

CASE STUDIES OF THERMALLY DRIVEN HEAT PUMP ASSISTED DRYING. Minh Cuong Tran, Jamy Logie, Bruno Vanslambrouck, Martijn van den Broek

Adelaide Homes Design Guide 4 - Winter warming

STACK EFFECT IN LIGHT WELL OF HIGH RISE APARTMENT BUILDING

Aalborg Universitet. CLIMA proceedings of the 12th REHVA World Congress Heiselberg, Per Kvols. Publication date: 2016

Theoretical Performance Analysis of a Liquid Desiccant Air- Conditioning System for Air Heating and Cooling

- Data Brochure Universal Reset Module 423

Impact of Multi-Stage Liquid Desiccant Dehumidification in a Desiccant and Evaporative Cooling-Assisted Air Conditioning System

Performance evaluation of residential ventilation systems based on multi-zone ventilation models.

Analysis of freeze protection methods for recuperators used in energy recovery from exhaust air

Design Procedure for a Liquid Dessicant and Evaporative Cooling Assisted 100% Outdoor Air System

Thermal Comfort with Convective and Radiant Cooling Systems

Smart Green Roofs: Cooling with variable insulation

Optimized Finned Heat Sinks for Natural Convection Cooling of Outdoor Electronics

GROUND COOLING OF VENTILATION AIR FOR ENERGY EFFICIENT HOUSE IN MALAYSIA: A CASE STUDY OF THE COOLTEK HOUSE

- Data Brochure Universal Reset Module 422

Divacondens D Plus Atmospheric condensation wall-mounted boilers, with instant domestic hot water production

Jeremy Cockroft 1, David Kennedy 2, Martin O Hara 3, Aizaz Samuel 1, Paul Strachan 1, Paul Tuohy 1 ABSTRACT INTRODUCTION

GUIDANCE AND TOOLS FOR CHILLED CEILINGS COMBINED WITH A WET COOLING TOWER

Jülich Solar Power Tower System Behavior During Downtime

Reduced Order WECC Modeling for Frequency Response and Energy Storage Integration

PERFORMANCE MONITORING OF A HIGH-TEMPERATURE AIR-TO-WATER HEAT PUMP WITH INJECTION CYCLE INSTALLED IN A LOW-INSULATED SINGLE-FAMILY HOUSE IN BELGIUM

SOLAR COMBISYSTEMS IN DENMARK - THE MOST COMMON SYSTEM DESIGNS

Experimental Study on Crawl-Space Heating with Thermal Storage using Heat Pump

ENERGY ANALYSIS OF HEAT PUMP WITH SUBCOOLER

PERFORMANCES OF DAHT CONNECTED TO BUILDING AIRTIGHTNESS AND INDOOR HYGRO- THERMAL CLIMATE

INDOOR CLIMATE IN HEATING CONDITION OF A LARGE GYMNASIUM WITH UNDER-FLOOR SUPPLY/RETURN SYSTEM

CLIMA I Thermostat ZENNIO

Heat Exchanger. The purpose may be either to remove heat from a fluid or to add heat to a fluid.

Experimental Study to Evaluate Smoke Stratification and Layer Height in Highly Ventilated Compartments

Connect North and South Korean Separated Families Higher Comfort Lower Energy

THE EFFECT OF HEAT LOAD ARRANGEMENT ON THE PERFORMANCE OF RADIANT PANELS

New Steps towards Compact Solar Combisystems in Scandinavia

Feasibility of a Liquid Desiccant Application in an Evaporative. Cooling Assisted 100% Outdoor Air System

Winter heating This winter heating guide includes ways to reduce heating costs and provides advice on choosing the right heater to suit your needs.

Heat Transfer in Evacuated Tubular Solar Collectors

EXCELSIOR SINHGAD COLLEGE OF ENGINEERING, PUNE PAPER PRESENTATION

The Research of Performance Comparison of Displacement and Mixing Ventilation System in Catering Kitchen *

Radiant Heating. Systems

FAST AND ROBUST BUILDING SIMULATION SOFTWARE. Chilled Beam Performance: 1 Shelly Street, Sydney

THE RISK OF LEGIONELLA DEVELOPMENT IN SANITARY INSTALLATIONS

Itaru TAKAHASHI Ph.D 1 Akihiko KUROIWA 2

Appendix C House models for Dymola to be used in connection with the OPSYS test rig and annual simulations of the performance of heat pumps

A WET-VAPOUR INJECTION AND VARIABLE SPEED SCROLL COMPRESSOR AIR TO WATER HEAT PUMP MODEL AND ITS FIELD TEST VALIDATION

for family composition, time allocation of people, ownership and specification of home appliances. This paper first presents the simulation procedure

HSPF Calculation of a System Allowing Switching Between a Single-Stage to a Two-Stage Compression System

Mathematical Simulation of Longan Fruit Drying

Adsorption refrigeration system using waste heat

Analysis and Evaluation of a Passive Evaporative Cool Tower in conjunction with a Solar Chimney

A TRNSYS Simulation Case Study on Utilization of Heat Pump For both Heating and Cooling

Everything you need to know about Radiant Heating but didn t dare ask

When both switches are on, the heater works at the high power setting. What is the power of the heater when it is switched to the high power setting?

COMPARISON OF THE USE TRICKLE VENTILATORS IN EUROPEAN RESIDENTIAL VENTILATION STANDARDS

To describe human body heat transfer, the concept. Thermal comfort with radiant and convective cooling systems. Articles. REHVA Journal June

Open Access Operation Modes and Energy Analysis of a New Ice-Storage Air- Conditioning System

A study of radiant cooling for a room with daytime application in tropical climate

C66. ECL Comfort. User's Guide. Installer's Guide. ECL Comfort C66. User's Guide. Installer's Guide. *vi7cc502* *087R8069* *087R8069* *vi7cc502*

Implementation and testing of a model for the calculation of equilibrium between components of a refrigeration installation

NEBRASKA MODIFIED ROOF POND: 1985 SUMMER PERFORMANCE RESULTS

The complete energy-saving range.

Boiler Manager Technical Report

EVALUATION OF A LIQUID DESICCANT AIR CONDITIONING SYSTEM WITH SOLAR THERMAL REGENERATION

Measuring And Understanding Energy Efficiency

- Essay Control Functions and Benefits

The Effect of the Ventilation and the Control Mode on the Performance of a VRV System in Cooling and Heating Modes

Performance Comparison of Hydronic Secondary Loop Heat Pump and Conventional Air-Source Heat Pump ABSTRACT 1. INTRODUCTION

C62. ECL Comfort. User's Guide. Installer's Guide. ECL Comfort C62. User's Guide. Installer's Guide *VIKME102* *087R8091* *087R8091* *VIKME102*

Cooling load calculations of radiant and all-air systems for commercial buildings

CHANCES AND LIMITS OF THE TIME-EQUIVALENCE-METHOD IN STRUCTURAL FIRE DESIGN

ENERGY SAVING IN A DOMESTIC SPLIT-TYPE AIR CONDITIONER WITH EVAPORATIVE COOLING SYSTEMS

Experimental study of hybrid loop heat pipe using pump assistance for high heat flux system

Application of two hybrid control methods of expansion valves and vapor injected compression to heat pumps

A STUDY ON THE APPLICATION OF THE RADIANT FLOOR COOLING SYSTEM INTEGRATED WITH A DEHUMIDIFICATION SYSTEM

DEMONSTRATION OF A MICROCHANNEL HEAT EXCHANGER FOR OPERATION IN A REVERSIBLE HEAT PUMP SYSTEM

SURVEY ON THE OCCUPANT BEHAVIOR RELATING TO WINDOW AND AIR CONDITIONER OPERATION IN THE RESIDENTIAL BUILDINGS

C37. ECL Comfort. User's Guide. Installer's Guide. ECL Comfort C37. User's Guide. Installer's Guide *VI7CE602* *087R8070* *087R8070* *VI7CE602*

FIRE DYNAMICS IN FAÇADE FIRE TESTS: Measurement, modeling and repeatability

Storage and hot and cold water in a thermocline for Space heating/cooling and domestic hot water

CLASSIFICATION AND EXPERIMENTATION FOR THE DEVELOPMENT OF DAYLIGHTING SYSTEMS IN COLD AND SNOWY REGIONS

Thermal Modeling of Buildings II

Tank systems. Layered tank Solar layered tank Hygienic layered tank Modular layered tank Hot water tank NEW:

Emerging Technologies: VFDs for Condensers. Douglas T. Reindl Director, IRC University of Wisconsin-Madison. University of Wisconsin-Madison

HEAT LOAD AND SOLAR GAIN PREDICTION FOR SOLID WALL DWELLINGS RETROFITTED WITH TRIPLE VACUUM GLAZING FOR SELECTED WINDOW TO WALL AREA RATIOS

Transcription:

Ninth International IBPSA Conference Montréal, Canada August 15-18, 2005 COMPARISON OF HEATING SYSTEMS IN A RESIDENTIAL BUILDING Jeroen Van der Veken, Leen Peeters, and Hugo Hens Laboratory of Building Physics Laboratory of Applied Mechanics and Energy Conversion K.U.Leuven (Catholic University of Leuven), Belgium ABSTRACT This paper presents the results of a case study in which Low Temperature radiators, High Temperature radiators and floor heating systems are compared using a TRNSYS16-model of a typical terraced house. The influence of radiant heating on temperature control is investigated as is the introduction of an outside temperature sensor, insulation around piping, different boiler types and temperature profiles, such as night set back. INTRODUCTION As the thermal resistance of a building enclosure increases, the impact of any additional thermal insulation on energy economy decreases. This physical law forces countries with tough insulation requirements to turn to Energy Performance Regulation (EPR). EPR not only evaluates thermal insulation, but also takes into account the energy efficiency of ventilation, lighting, hot water production and heating systems and the benefits of passive and active solar energy. (Hens et al., 2001) A great unknown in such a vast corpus of possibilities is the heating system s efficiency. Floor heating is renowned for its high level of radiant heat and its low supply water temperature, which leads respectively to a lower air set point temperature and a possible coupling to high efficiency systems such as heat pumps, condensing boilers or other systems that supply low temperature heat. Furthermore, thermal mass integrated with a floor heating system is often cited as a solution to reduce peak heating loads, decrease temperature swings and increase the use of solar gains. (Arneodo et al., 1988) On the other hand, scant attention is paid to the control difficulties resulting from the inherent large thermal lag of these systems. When intermittent heating is applied, the control efficiency can be so low that all benefits are neutralized. In other words, the total efficiency at the building level, defined as the ratio of net heat demand and total heat consumption, is not higher. To assess overall efficiency between heating systems, four main types are compared. These include High Temperature radiators, Low Temperature radiators and two systems with floor heating in the day zone and Low Temperature radiators in the night zone. The latter two systems differ in their floor capacity. The influence of controlling the operative or air bulb temperature is investigated, as is the introduction of a condensing boiler possibly combined with a variable boiler exhaust temperature. The simulations are con-ducted with TRNSYS16 on a typical terraced house. Results show that floor heating systems do not outperform radiators. On the contrary, only when coupled to condensing boilers, they consume less energy than the HT-radiator system, and LT-radiators perform best in all cases. This difference in efficiency is reduced when constant set point temperatures are applied or when the operative temperature is controlled instead of the air temperature. Finally, increasing the thermal lag of the floor heating systems has the undesirable effect of increasing rather than reducing heat consumption. SIMULATION In this paper, the Dynamic Building Energy Simulation Program TRNSYS16v1.036 is used to simulate the building and its heating installations. Building The terraced house is quite compact with an outer volume of 446 m³ and an exterior surface of 226 m². Together with an average U-value of 0.8 W/m²K, this leads to the exact compliance with the Flemish insulation decree (BS, 1992) and a net energy demand of 10181 kwh. The day zone, which comprises the kitchen and the living room and has a floor surface of 48 m², can be equipped by radiators or a floor heating system, while the night zone of 83.5 m² only contains radiators. This is due to the highly intermittent set point temperature in the latter area. (See figure 1) The ventilation is modeled as non-forced natural ventilation with the minimal flows of the standard NBN D50-001 (BIN, 1992). The internal gains show a peak in the morning and the evening due to the activity of people in the room and the normal use of home appliances. - 1277 -

Set point temperature ( C) 24 22 20 18 16 14 12 10 day zone bed rooms bath room 0 2 4 6 8 10 12 14 16 18 20 22 24 time (h) the emission system itself. Furthermore, the flow also depends on the pressure drop of the flowing water over the valve and the history of the valve itself, i.e. hysteresis (Ast, 1988). To focus on the behavior of the emission system itself, it is assumed that the valves are adjusted for these deviations. The water flow through the distribution system is then determined by adding the flows to and from the radiators. Boilers The boiler is modeled in TRNSYS as a combination of an ideal heater and two water pipes (see Figure 2). Figure 1 Set point temperatures in the building Heating systems The heat demand of the zones was calculated using the pren 12831 and the national NBN B62-002. We did not take the indoor temperatures from the standard, but the highest level from the temperature profile. Otherwise the desired temperatures could not be reached in an intermittent regime. The radiators and floor heating are then dimensioned following the technical reports of the Belgian Building Research Institute (De Meulenaer et al., 2004). The floor heating is simulated using active elements available in TRNBuild (SEL, 2004) and extra floor insulation is applied to compensate for the extra losses due to a higher floor temperature. In one case the insulation is put in between two concrete layers, namely the thin layer around the heating tubes to ensure an equal distribution of heat in the floor and the structural floor slab. In the other case, the first layer is made thicker and the insulation is put under the structural floor slab. Thus, a highcapacitive floor is created. The floor heating system is controlled by a four-way valve and a proportional controller. The radiators used are based on Type 72 from IEA annex 17 and numerically optimized (Kummert, 2001). Each radiator is accompanied by a proportional controller that determines the incoming flow. These controllers can be regarded as perfect thermostatic valves. That is to say, they measure the exact air or operative temperature in the middle of the zone, they cause a perfect proportional relation between room temperature and water flow and they are not system pressure dependent. In reality, the thermostatic valve measures a temperature that is the weighted average of the temperatures of air, walls, the water in the pipe and Figure 2 Boiler model in TRNSYS The pipes represent the water that flows through the boiler. The capacity of the water in the pipes is set equal to that of a real boiler. If the heat demand of the system reaches the power that the (modulating) boiler can produce, the boiler is turned on and the water from the distribution system flowing through is heated by the ideal heater until the set temperature is reached. At the same time the pipes loose energy and with the correct loss factor they can represent the boiler losses to the environment. If the water temperature of the boiler reaches the minimum and the heat demand is too low, water is sent around the boiler and the boiler heats up. When the boiler water temperature is high enough and the necessary load still too low, the heater is turned off and heat can be added to the small distributed flow through the boiler or be lost to the environment; i.e. the boiler is cycling. (see hour 0 till hour 7 in figure 3) When the energy to the boiler flow is divided by the burner efficiency, the total consumption is calculated. A condensing and a non-condensing boiler are modeled in EES by Professor Lebrun from the University of Liège (ULG). Parameter analysis of these models gives us a function for the heat losses of the boiler through the chimney. These heat losses - 1278 -

90 temperature ( C) 80 70 60 50 Twexburner Twexboiler Twsupburner Twsupboiler 40 30 0 2 4 6 8 10 12 14 16 18 20 22 24 time (h) Figure 3 Boiler water supply and exhaust temperature and burner supply and exhaust temperature for a modulating boiler coupled to an outside temperature sensor and HT-radiators depend mostly on the temperature of the air which is burned, the temperature of the supply water and the water flow through the heat exchanger. For condensing boilers the load itself is also a variable, as shown in Figure 4. The efficiency of the heat exchanger increases when the flow speed of gases decreases. For a modulating boiler, this efficiency is assumed constant at changing loads. Indeed, state-ofthe-art modulating boilers can maintain their high efficiency over a wide range. Under the modulating range of 3 kw the burner efficiency drops due to inefficiencies during start up and stop. As can be seen in Figure 3, the boiler set point temperature can be varied in function of the outside temperature. A power function is chosen between 50 C en 25 C for the LT-systems and between 90 C and 40 C for the HT-systems. Finally, the system is turned off when the daily average temperature rises above 12 C. Burner Efficiency (-) 1 0.98 0.96 0.94 0.92 0.9 0.88 0.86 0.84 0.82 0.8 0 1 2 3 4 5 6 7 8 9 10 11 Power (kw) 40 60 80 mod40 mod60 mod80 Figure 4 Burner efficiency (at Higher Heating Value) of a condensing and modulating boiler at 4 boiler temperatures - 1279 -

RESULTS Modulating high-efficiency boilers Table 1 (annex) summarizes the results for modulating high-efficiency boilers. The first three lines in the table are taken by the total heat consumption, the energy into system being the energy delivered to the distribution system, the energy in zones being the energy emitted by radiators or floor heating and the losses of the pipes in the zones that need heating, and finally the energy emitted only by the radiators or floor heating in the day zone. Further on, the total efficiency being the ratio of net heat demand and total energy consumption for heating calculated with respect to the Higher Heat Value of gas, the production efficiency being the ratio of heat to the distribution system and total heat consumption of the boiler and the burner efficiency being the ratio of heat to boiler water and total heat consumption, is given. The latter is a measure for the heat loss of the boiler through the chimney and the difference between burner and production efficiency suggests how much the boiler loses to the zone. Finally the yearly averaged temperature in the day zone and the whole building are presented. If we compare the heating systems for this type of boiler, it is obvious that the floor heating systems consume more energy than the radiator systems. The difference is caused by the heat emitted in the day zone; the floor heating panels give off about 5500 kwh per year, while the HT-radiators only need 2300 kwh/a and the LT-radiators 3300 kwh/a. This is caused by the large thermal lag of the floor heating systems, as can be seen on figure 5. The temperature at night set back hardly drops 1 C while this is 4 C for the LT-radiators (figure 6). Nevertheless, to reach the set point temperature of 21 C in the morning, the heating has to be turned on 4 or 4.25 hours beforehand, depending on the capacity of the floor. temperature ( C) 25 24 23 22 21 20 19 18 17 16 15 0 2 4 6 8 10 12 14 16 18 20 22 24 time (h) Tair living Tair bath Tair sleep Tset living Tset bath Tset sleep Figure 5 Set point and simulated temperatures for the living room with floor heating; bed room and bath room with LT-radiators temperature ( C) 25 24 23 22 21 20 19 18 17 16 15 0 2 4 6 8 10 12 14 16 18 20 22 24 time (h) Tair living Tair bath Tair sleep Tset living Tset bath Tset sleep Figure 6 Set point and simulated temperatures for the living room, bed room and bath room with LT-radiators - 1280 -

Furthermore, when discontinuous solar heating and free gains enter the zone; the heating systems can not react fast enough and the temperature rises above the set point. The radiators are easier to control, although they show oscillations when temperature rises sharply, or when free gains are emitted in the zone, but this is typical for a proportional control (Ast, 1988). Consequently, the yearly averaged temperature in the day zone is about 0.6 degrees higher when floor heating systems are used, as shown in table 1. LT-radiators need the same amount of energy in the distribution system as HT-radiators, although they enter more energy in the zones that are heated. This shows that the extra heat loss from the piping at high temperatures outside those zones is mostly recuperated. Nevertheless, the production efficiency of the HT-system is lower and not all the heat losses to the storeroom, where the boiler is placed, are recuperated. The extra losses at high temperatures are high for such a small zone and therefore, the average temperature is about 1.6 C higher, which leads to extra losses to the environment. When the results of the modulating boilers with and without outside temperature sensor control are compared, the first perform a little better, partly due to increasing production efficiencies as lower water temperatures cause lower losses to the environment, and partly due to a better control, which is realized in a lower yearly averaged temperature across the building in table 1. The burner efficiency is hardly influenced by the variable boiler temperature. Condensing boilers Comparing Table 2 and Table 1 reveals that the distribution system reacts the same, which is logical since the modulating properties of both boilers are equal. However, the burner efficiency of condensing boilers is much higher at low temperatures, as figure 4 showed above. Floor heating systems coupled to condensing boilers will therefore perform better than HT-radiators. The latter hardly improve when a condensing boiler is installed because the burned gases will not condensate at these high temperatures. Moreover, if extra electricity losses from the ventilator would be taken into account, the small profit is quasi neutralized. LT-radiators still outperform floor heating panels for the same reasons as with modulating boilers, but the introduction of an outside temperature sensor control has a higher influence since the burner is more temperature dependent. HTradiators perform even 5% better with such a control, because in the heat exchanger temperatures can be reached at which condensation appears. Air temperature versus operative temperature The floor heating system radiates roughly the same amount of energy than it gives off with convection, depending on the actual floor, wall and air temperatures. The modern convecto-radiators used in our simulations, however, are much more relying on convection. Consequently, the operative temperature, the weighted average of air temperature and surface temperatures, is higher than the air temperature for floor heating and viceversa for radiator heating. Floor heating will therefore benefit from being controlled based on the operative temperature, which is illustrated in Table 3. No night set back Table 4 shows that using night set back in the day zone has practically no influence on the energy consumption of a floor heating system. The floor with large thermal lag consumes 0.1% less, the lighter version still just 0.5%. This contrasts with the 5% and 8% difference of HT and LT-radiator heating respectively. The increase of the average temperature is also much higher in these cases. Insulation around piping The small differences of total consumption in table 5 and the higher heat emission in the zones in the case of insulated pipes, proves that the majority of losses in adjacent zones is recuperated. The slightly higher temperatures give an idea of the non recuperated losses. The on/off-boiler and the modulating boiler on high temperature seem to be equivalent. DISCUSSION The results of our case study show that LTradiators outperform the floor heating alternative. Only floor heating systems that run on a condensing boiler and are used to maintain a constant temperature, equal to the operative temperature that the LT-radiators produce, can rival these radiators. Problems arise when the desired temperature is not constant and solar and free gains create an intermittent heat load profile. Adaptive predictive control could improve the control of these systems with such a large thermal lag. Limiting the floor heating and just use it as base heating is another solution. The losses of the distribution system seem to be almost completely recuperated in other zones of the building, but this is highly building (insulation) dependent. Scrutinizing this relation will be our main future research. - 1281 -

ACKNOWLEDGMENT The work presented in this paper is part of the project Optimisation of Extreme Low Energy and Pollution Buildings (EL²EP) funded by the Flemish Institute for the Promotion of Industial Scientific and Technological Research. Their financial contribution is gratefully acknowledged. The author would also like to thank Jean Lebrun from the University of Liège and Michael Kummert from the Solar Energy Lab for the use of their simulation models. REFERENCES Arneodo P., Mazza A., Oliaro P., 1988. Annex 10 System Simulation, Floor heating panels, IEA, Politecnico di Torino, Italy Ast H., 1988. Annex 10 System Simulation, Thermostatic Valve, IEA, University of Stuttgart, Germany BS, 1992. Het Vlaamse isolatie- en ventilatiedecreet (Flemish decree on minimal insulation and ventilation). Belgisch Staatsblad, Brussels, Belgium BIN, 1992. NBN D 50-001. Ventilatievoorzieningen in woongebouwen (Ventilation facilities in residential buildings). Belgian National Institute for Standardization, Brussels, Belgium Demeulenaer V., Van der Veken J., 2004. Energiesimulatie van installatiecomponenten (Energy simulations of heating systems), Voortgangsverslag GBOU-project EL²EP, periode januari 2004- juni 2004, KUL LBF, KUL TME, KUL ELECTA and UG Architecture, Belgium Hens H., Verbeeck G., 2001, Heating efficiency, the great unknown, Clima 2000 proceedings, Napoli, Italy SEL. 2004. TRNSYS, A transient system simulation program, User Guide Version 16. Madison: Solar Energy Lab, University of Wisconsin-Madison Kummert M., 2001. Contribution to the application of modern control techniques to solar buildings. Simulation-based approach and experimental validation. Ph.D. Thesis. FUL (ULG), Arlon, Belgium Table 1 Modulating boilers with zone temperature control on dry air temperature and different boiler control systems HIGH CAP FLOOR FLOOR HT-RAD LT-RAD FIXED BOILER WATERTEMPERATURE SETPOINT 15024 11789 10487 5763 0.678 0.785 0.817 21.72 21.30 14844 11648 10355 5467 0.686 0.785 0.816 21.64 21.31 13639 10593 8784 2300 0.746 0.777 0.828 13062 10592 9747 3323 0.779 0.811 0.835 21.05 20.91 OUTSIDE TEMPERATURE BOILER CONTROL 14799 10729 4623 0.688 0.793 21.69 21.18 14504 11514 10506 5623 0.702 0.794 0.819 21.60 21.15 13548 10572 8931 2481 0.752 0.780 0.826 12943 10531 9799 3481 0.787 0.814 0.834 20.83-1282 -

Table 2 Condensing boilers with zone temperature control on dry air temperature and different boiler control systems HIGH CAP FLOOR FLOOR HT-RAD LT-RAD FIXED BOILER WATERTEMPERATURE SETPOINT 12994 11788 10487 5763 0.784 0.907 0.945 21.72 21.30 12826 11648 10355 5467 0.794 0.908 0.946 21.64 21.31 13648 10593 8784 2300 0.749 0.779 0.831 11571 10592 9747 3323 0.880 0.915 0.924 21.05 20.91 OUTSIDE TEMPERATURE BOILER CONTROL 12747 10729 5893 0.798 0.921 21.69 21.18 12537 11557 10546 5598 0.812 0.922 0.951 21.60 12928 10572 8931 2481 0.788 0.866 11366 10531 9799 3482 0.896 0.927 20.83 Table 3 Condensing boilers with boiler water set point controlled by an outside temperature sensor and different zone temperature control HIGH CAP FLOOR FLOOR HT-RAD LT-RAD ZONE TEMPERATURE CONTROLLED ON DRY AIR BULB TEMP 12747 10729 5893 0.798 0.921 21.69 21.18 12537 11557 10546 5598 0.812 0.922 0.951 21.60 12928 10572 8931 2481 0.788 0.866 11366 10531 9799 3482 0.896 0.927 20.83 ZONE TEMPERATURE CONTROLLED ON OPERATIVE TEMP Day zone Top ( C) Building Top ( C) 12647 10727 5386 0.805 0.921 21.70 21.26 12501 11558 10550 5164 0.815 0.922 0.951 21.62 21.23 13619 11190 9563 2870 0.748 0.866 21.20 21.25 12134 11244 10511 3933 0.839 0.927 0.949 21.16-1283 -

Table 4 Condensing boilers with boiler water set point controlled by an outside temperature sensor and different night set back schedules HIGH CAP FLOOR FLOOR HT-RAD LT-RAD WITH NIGHT SET BACK 12747 10729 5893 0.798 0.921 21.69 21.18 12537 11557 10546 5598 0.812 0.922 0.951 21.60 12928 10572 8931 2481 0.788 0.866 11366 10531 9799 3482 0.896 0.927 20.83 WITHOUT NIGHT SET BACK 12766 11800 10627 5943 0.797 0.924 0.957 21.76 21.22 12601 11639 10456 5692 0.808 0.923 0.957 21.70 21.22 13589 11124 9299 2820 0.749 0.819 0.863 21.5 21.23 12299 10706 10267 4034 0.828 0.931 0.952 21.48 20.95 Table 5 Different boiler types without outside temperature sensor but with different insulated distribution system ON OFF HT-RAD MOD HT-RAD MOD LT-RAD CONDENS LT-RAD WITHOUT INSULATION 13683 10406 8546 2252 0.744 0.761 0.833 21.1 21.28 13639 10593 8784 2300 0.746 0.777 0.828 13062 10592 9747 3323 0.779 0.811 0.835 21.05 20.91 11571 10592 9747 3323 0.880 0.915 0.942 21.05 20.91 WITH INSULATION 13621 10239 9465 3302 0.747 0.752 0.830 21.08 13532 10419 9682 3347 0.752 0.770 0.826 13023 10537 10211 3896 0.782 0.809 0.834 21.04 20.86 11541 10537 10267 4034 0.882 0.913 0.941 21.04 20.86-1284 -