Simulation of energy use in UK supermarkets using EnergyPlus

Similar documents
MODELING OF THE SINGLE COIL, TWIN FAN AIR-CONDITIONING SYSTEM IN ENERGYPLUS

VARIABLE HEAT RECOVERY IN DOUBLE BUNDLE ELECTRIC CHILLERS. Richard J Liesen 1, Rahul J Chillar 2 1 University of Illinois at Urbana Champaign

MODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING

Energy Savings Potential of Passive Chilled Beam System as a Retrofit Option for Commercial Buildings in Different Climates

SIMULATION ANALYSIS OF BUILDING HUMIDITY CONTROL AND ENERGY CONSUMPTION FOR DIFFERENT SYSTEM CONFIGURATIONS USA

seasons in regions with hot, humid climates. For this reason, a dehumidification system with a radiant panel system needs to be developed. In a former

CARRIER edesign SUITE NEWS. Interpreting High (Low) Peak Design Airflow Sizing Results for HVAC. Equipment Selection.

Clemens Felsmann 1, Jean Lebrun 2, Vincent Lemort 2 and Aad Wijsman 3 ABSTRACT INTRODUCTION METHODOLOGY

ENERGY SAVINGS THROUGH LIQUID PRESSURE AMPLIFICATION IN A DAIRY PLANT REFRIGERATION SYSTEM. A. Hadawey, Y. T. Ge, S. A. Tassou

The Energy Consumption Investigation of the Hotel Central. Air-conditioning System and the Research of Energy Saving Measures

Optimisation of cooling coil performance during operation stage for improved humidity control

Feasibility study on an energy-saving desiccant wheel system with CO 2 heat pump

Available online at ScienceDirect. Energy Procedia 52 (2014 ) Vishal Vadabhat, Rangan Banerjee

Available online at Energy Procedia 6 (2011) MEDGREEN 2011-LB

Impact of Multi-Stage Liquid Desiccant Dehumidification in a Desiccant and Evaporative Cooling-Assisted Air Conditioning System

Next Generation Passivhaus Archives

Binoe E. ABUAN, Menandro S. BERANA, Ruben A. BONGAT. University of the Philippines Diliman, Quezon City, Philippines

Modelling and Evaluation of Supermarket Energy Use and Emissions

Open Access Operation Modes and Energy Analysis of a New Ice-Storage Air- Conditioning System

Design Procedure for a Liquid Dessicant and Evaporative Cooling Assisted 100% Outdoor Air System

CARRIER edesign SUITE NEWS. Modeling 100% OA Constant Volume Air Systems. Volume 6, Issue 1. Page 1 Modeling 100% OA Constant Volume Air Systems

Feasibility of Controlling Heat and Enthalpy Wheel Effectiveness to Achieve Optimal Closed DOAS Operation

Impacts of Optimized Cold & Hot Deck Reset Schedules on Dual Duct VAV Systems - Theory and Model Simulation

CFD Analysis of a 24 Hour Operating Solar Refrigeration Absorption Technology

Computerized Simulation of Automotive Air-Conditioning System: A Parametric Study

Dynamic performance of a novel dew point air conditioning for the UK buildings

A TRNSYS Simulation Case Study on Utilization of Heat Pump For both Heating and Cooling

The Corbioli House is a single-family house situated

The importance of hot water system design in the Passivhaus

Victoria & Albert Museum, London Medieval & Renaissance Galleries: A Passive Approach to Humidity Control

Analysis of freeze protection methods for recuperators used in energy recovery from exhaust air

Energy Efficiency Through Waste Heat Recovery. Heat Recovery Centrifugal Chillers and Templifier Water Heaters

Feasibility of a Liquid Desiccant Application in an Evaporative. Cooling Assisted 100% Outdoor Air System

Performance Evaluation and Design Optimization of Refrigerated Display Cabinets Through Fluid Dynamic Analysis

COMPARING AIR COOLER RATINGS PART 1: Not All Rating Methods are Created Equal

NOVEL COMPACT SORPTION GENERATORS FOR HEAT PUMP APPLICATIONS

Open and Closed Door Moisture Transport and Corresponding Energy Consumption in Household Refrigerator

A study of Transient Performance of A Cascade Heat Pump System

Effect of the Use Pattern on Performance of Heat Pump Water Heater

97.501B. Prepared by: (415) Sponsored By: Final Report. Author: Presented at: ASHRAE. Meeting SF Me!

COLD STORAGE WAREHOUSE, USING DIRECT EXPANSION AMMONIA REFRIGERANT Ray Clarke ISECO Consulting Services Pty Ltd

Thermal comfort investigation on a naturally ventilated two- storey residential house in Malaysia

Copyright 2017 Integrated Environmental Solutions Limited. All rights reserved.

Appendix C House models for Dymola to be used in connection with the OPSYS test rig and annual simulations of the performance of heat pumps

AIR-CONDITIONING SYSTEMS AND APPLICATIONS. Abdullah Nuhait Ph D. King Saud University

2. CURRICULUM. Sl. No.

Reducing the Carbon Footprint of Existing Domestic Heating: A Non-Disruptive Approach

INTERNATIONAL JOURNAL OF APPLIED ENGINEERING RESEARCH, DINDIGUL Volume 1, No 4, 2011

Numerical study of heat pipe application in heat recovery systems

Measurement and modelling of a multifunctional solar plus heatpump system from Nilan. Experiences from one year of test operation.

Simscape Refrigerant Loop Product

Heat transfer and heating rate of food stuffs in commercial shop ovens

Capillary Tube and Thermostatic Expansion Valve Comparative Analysis in Water Chiller Air Conditioning

Improving Control of Dual-Duct Single-Fan Variable Air Volume Systems

Daikin VRV Systems Plugin VE2012 User Guide

Residential ventilation concepts based on the idea of displacement airflow distribution

DESIGN WITH HEAT LOAD SIMULATION OF COMBINED PASSIVE-ACTIVE SYSTEMS

K.F. Fong *, C.K. Lee, T.T. Chow

Dynamic Simulation of Liquid Chillers

Hot Water Making Potential Using of a Conventional Air- Conditioner as an Air-Water Heat Pump

Evaluation on Residential Energy Efficiency Programs Using the City-Scale End-Use Simulation Model

Continuous Commissioning: A Valuable Partner to Retrofit Projects

PERFORMANCE OF SOLID DESICCANT COOLING WITH SOLAR ENERGY IN HOT AND HUMID CLIMATE

INDOOR CLIMATE IN HEATING CONDITION OF A LARGE GYMNASIUM WITH UNDER-FLOOR SUPPLY/RETURN SYSTEM

A Simulation Study on the Energy Efficiency of Gas-Burned Boilers in Heating Systems

Figure 1: Low energy dwellings testsite

Summary Comparison of Simulation Program Features

for family composition, time allocation of people, ownership and specification of home appliances. This paper first presents the simulation procedure

ASHRAE JOURNAL ON REHEAT

CEE 243. Week 2 HVAC systems at Y2E2

Adsorption refrigeration system using waste heat

TRACE 700. Slide 1. Hello, my name is Nick Cavitt and I m a marketing engineer in the C.D.S. group at TRANE.

ZONE MODEL VERIFICATION BY ELECTRIC HEATER

The design and development of a sanitation hand washing dispenser: a South African case study

Thermal analysis of flat evacuated glass enclosure for building integrated solar applications

Shortcut Model for Predicting Refrigeration Cycle Performance

Radiant Cooling Nonresidential HVAC Stakeholder Meeting #2

Chilled beam technology overview John Woollett 1, Jonas Åkesson 2 Swegon AB 1,2

MODELLING AND SIMULATION OF A ROOM WITH A RADIANT COOLING CEILING. Technicka 4, Prague 6, Czech Republic

SPACE CONDITIONING IN COMMERCIAL BUILDINGS Overview

Experimental Research of Air Source Heat Pump Frosting and Defrosting in a. Double Stage-Coupling Heat Pump

Heat Exchanger Shelves For Better Temperature Control Of Food In Open-Type Display Cases

Integrated dehumidification and downdraft evaporative cooling system for a hot-humid climate

VENTILATIVE COOLING CONTROL STRATEGIES APPLIED TO PASSIVE HOUSE IN ORDER TO AVOID INDOOR OVERHEATING

Experimental investigation of Hybrid Nanofluid on wickless heat pipe heat exchanger thermal performance

Analysis of Constant Pressure and Constant Area Mixing Ejector Expansion Refrigeration System using R-1270 as Refrigerant

Shuzo Murakami, Shinsuke Kato, and Taeyeon Kim Institute of Industrial Science, University of Tokyo Tokyo, Japan

Feasibility study of the passive solar room dehumidifying system using the sorption property of a wooden attic space through field measurement

March 2014 AHRI Presents Research Findings at Low-GWP AREP Conference

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

ApacheHVAC in VE 2012

Article Energy Saving Benefits of Adiabatic Humidification in the Air Conditioning Systems of Semiconductor Cleanrooms

The Creative and Performing Arts High School (CAPA) Pittsburgh, PA 11/11/2002 Andrew Tech Mechanical Option Prof. S. A. Mumma

Simplified Space-Heating Distribution using Radiators in Super-Insulated Apartment Buildings

HEFAT th International Conference on Heat Transfer, Fluid Mechanics and Thermodynamics Sun City, South Africa Paper number:pp1

Heat Transfer in Evacuated Tubular Solar Collectors

Radiant Exchange in Stratified Environments: Considerations and Challenges for Hourly Energy Simulation of UFAD, DV, and Radiant Cooling Systems

White Paper Dehumidification in Humid Climates - A Theoretical Case Study

Passive building in Hot and Humid Climates

How to ensure Thermal Comfort in buildings with CFD

Transcription:

Loughborough University Institutional Repository Simulation of energy use in UK supermarkets using EnergyPlus This item was submitted to Loughborough University's Institutional Repository by the/an author. Citation: WITT, H.... et al, 2015. Simulation of energy use in UK supermarkets using EnergyPlus. IN: Mathur, J. and Garg, V. (eds). Proceedings of the 14th International Conference of the International Building Performance Simulation Association (BS2015), 7th-9th December 2015, Hyderabad, India, pp.1095-1102. Additional Information: This is a conference paper. Metadata Record: https://dspace.lboro.ac.uk/2134/21174 Version: Published Publisher: c International Building Performance Simulation Association (IBPSA) Rights: This work is made available according to the conditions of the Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International (CC BY-NC-ND 4.0) licence. Full details of this licence are available at: https://creativecommons.org/licenses/by-nc-nd/4.0/ Please cite the published version.

SIMULATION OF ENERGY USE IN UK SUPERMARKETS USING ENERGYPLUS Henry Witt 1, Simon Taylor 1, Kevin Lomas 1, Rob Liddiard 2 1 London-Loughborough Centre for Doctoral Training in Energy Demand, School of Civil and Building Engineering, Loughborough University, Leicestershire LE11 3TU, UK 2 UCL Energy Institute, University College London, Central House, 14 Upper Woburn Place, London WC1H 0NN, UK ABSTRACT This paper investigates the interaction between supermarket heating, ventilation and air conditioning and refrigeration systems through simulation in EnergyPlus. This interaction has been studied by modelling a generic UK supermarket. The impact on the sum of HVAC and refrigeration energy consumption due to changes in a range of operating conditions was studied. These include the effect of altering HVAC temperature set-points, supply air temperatures and refrigeration case operating temperatures on their overall energy use. Optimum values of the supply air temperature, to minimise CO 2 emissions, delivered by the HVAC system were found to vary with UK location, with typical values around 14 o C to 16 o C. INTRODUCTION Context The UK government has a target to cut greenhouse gas (GHG) emissions by 80% below 1990 levels by 2050 (DECC, 2011). Food retail buildings are responsible for approximately 3% of total electricity consumption and 1% of total GHG emissions in the UK (Tassou et al., 2011; Wu et al., 2015a). Addressing the energy performance of supermarket buildings can contribute to achieving the GHG emissions reduction target. Supermarkets typically have some of the highest annual energy intensities (annual energy use per unit floor area) amongst non-domestic buildings of around 1,000 kwh/m 2 (Mavromatidis et al., 2013). Typical values for other non-domestic buildings are about 100 300 kwh/m 2 for hotels and 100 200 kwh/m 2 for offices (Galvez-Martos et al., 2013). Combined with the large average floor areas, these high values of energy intensity give supermarkets the highest total energy use of non-domestic buildings (Mei et al., 2002). Electricity for refrigeration and for heating, ventilation and air conditioning (HVAC) accounts for about 30% of the total energy demand in large supermarket buildings, and gas for about 20% (Spyrou et al., 2014). HVAC and refrigeration in supermarkets The HVAC system in a supermarket conditions the air in the store, heating it when the sales floor air temperature is below the heating set-point and cooling it when it is above the cooling set-point. Tesco supermarkets typically use a heating set-point of 18 C and a cooling set-point of 24 C, along with setback values of 17 C and 25 C at unoccupied times, usually at night (Reed, M., personal communication, November 25, 2014). Internal heat gains occur due to the operation of lighting and electrical appliances and the presence of customers and store staff. Heat is lost through the fabric of the building and because of air changes for ventilation. Thus far, the situation resembles that in other non-domestic buildings. What distinguishes supermarkets is the additional presence of refrigeration cases, typically in large numbers in a defined area of the store, that display chilled and frozen food and remove heat and moisture from the sales floor air. The interaction between the HVAC and refrigeration systems is the subject of the present paper. The work forms the initial stage of a project that will go on to study the potential for energy saving by the application of a range of HVAC control strategies. A typical variable air volume (VAV) HVAC system supplies conditioned air to the sales floor. It does this in two stages. First, the outside air is heated (if it is cold outside) or cooled (if it is warm) in an air handling unit or AHU (ASHRAE, 2008) as shown in Figure 1 to reach the fixed supply air temperature (SAT), often set by default to 14 C. Second, if the zone air temperature is below the heating set-point, the temperature of the incoming air is raised by heat supplied by the boilers to reheat coils. If the zone air temperature is above the cooling set-point, no further treatment is applied to the incoming air and it is supplied at the SAT. - 1095 -

AHU return fan heating and cooling coils supply fan reheat coil chilled and ambient zones Figure 1 Template of HVAC VAV system air loop with terminal reheat coils in each zone Typically, areas of a supermarket with different thermal requirements are supplied by their own AHU. In particular, areas containing large numbers of refrigeration cases are supplied by dedicated AHUs which are distinct from those supplying parts of the store where items that need no special treatment, such as clothes, are displayed. Two types of refrigeration cases are used in supermarkets. Those displaying chilled food (chilled cases), typically operate between 1 C and 5 C, while those displaying frozen food ( freezers ) operate between -22 C and -16 C. Both types are affected by the surrounding conditioned air, especially if the cases are open, as is the norm. The energy use of the refrigeration system, servicing the refrigerated cases in the store, depends on the type of the refrigeration cases and the interaction between the HVAC system and air inside the cases (Ge & Tassou 2000). The warm, moist air in the supermarket sales floor, treated by the HVAC system, enters inside the refrigeration cases mainly via infiltration and radiation (Ge & Tassou, 2011). This increases the sensible and latent cooling load and so the electricity use. Wu et al., (2015b) showed that an increase in the temperature of the supply air of the HVAC system increases the operational energy use of the refrigeration cases due to infiltration of warmer air into an open case. The split of electricity consumption attributable to different types of heat gain and other causes is shown in Figure 2 (Ge & Tassou 2011), demonstrating that infiltration has a major effect. Figure 2 Refrigeration case energy use proportion for meat, dairy and frozen cases (Ge & Tassou 2011) The operating temperature of a refrigeration case is the temperature at which the contained food products are stored. Safe maximum operating temperatures for chilled and frozen food ensure that products remain fresh for customer health. Lower temperatures may be used for higher product quality. Typical maximum safe operating temperatures are 5 C for chilled cases and -16 C for freezers. In this study, the interaction between HVAC and refrigeration systems was studied by modelling a generic supermarket environment. The refrigeration case operating temperatures, zone heating and cooling temperature set-points and SATs were varied subject to the typical values referred to above. The process was carried out for weather in three different UK locations, London, Belfast and Aberdeen. Research problem The effect of operational settings of HVAC systems and refrigeration cases on the overall energy use in UK supermarkets is not well understood. This is due to an interaction between the thermal characteristics of the building, the HVAC system and the refrigeration cases in supermarkets (Ge and Tassou, 2000; Mathews et al., 2000). The refrigeration system energy use is influenced by the sales floor air temperature and humidity, which is in turn controlled by the HVAC system. The energy use of the HVAC system depends on the fabric of the building, temperature set-points and the temperature of the refrigeration cases. There has been little work on simulating the energy use of supermarkets as distinct from other types of non-domestic building. Wu et al (2015b) stated that future work is required to take into account the effect of the HVAC system on the energy use of refrigeration cases in a supermarket scale building simulation. The aim of this work is to investigate the interaction between HVAC and refrigeration systems in UK supermarkets by modelling the impact on HVAC and refrigeration system energy use by modifying the HVAC system temperature set-points, SATs and refrigeration case operating temperatures. SIMULATION DesignBuilder (DesignBuilder, 2015) was used as a Graphical User Interface (GUI) to develop the building model (geometry, construction, lighting and occupancy schedules etc.) and the detailed HVAC model and its controls. Current limitations mean DesignBuilder cannot model refrigeration systems. The building and HVAC models saved in DesignBuilder were exported directly into EnergyPlus (Figure 3). Following this EnergyPlus (DOE, 2015) was used to model HVAC and refrigeration system energy use. - 1096 -

Figure 3 Stages of the simulation method, including building, HVAC and refrigeration system and refrigeration case models Figure 3 is unidirectional: once the Input Data File (IDF) has been exported into EnergyPlus, it cannot be re-opened in DesignBuilder and similarly once the IDF file has been exported into jeplus it cannot be re-opened in EnergyPlus to develop the model. jeplus was used for parametric analysis. It defines a range of values, inserts them sequentially within the IDF file and then runs EnergyPlus simulations with the different values in place. It can change an IDF file to vary a certain parameter, e.g. a SAT, with the defined range of values. A generic supermarket model was developed to explore the interaction between the HVAC system and refrigeration cases and variations in a range of operating conditions (Figure 4). N DesignBuilder Supermarket building model, detailed HVAC system, export simulation Input Data File (IDF) Simulation IDF file or textfile EnergyPlus Energy use of building, HVAC and refrigeration system and cases jeplus Change parameters e.g. SATs and refrigeration case operating temperatures HVAC AHU system return air ambient product zone virtual partition supply air cooled product zone refrigeration cases AHU Figure 4 Generic supermarket model Refrigeration system No windows were included to minimise solar heat gains. The building model was 40m wide, 70m long and 3.5m high. Walls were 0.2m thick aerated concrete slab with metal framing, the roof was a concrete slab of thickness 0.3675m and the internal ground floor was 0.1m insulated concrete. Two adjacent zones of equal size were defined, one ambient product zone (with product kept at room temperatures) and one cooled product zone (with chilled and frozen product, where the chilled cases and freezers were located). The zones were separated by a virtual partition, a permeable boundary definable in DesignBuilder, that allows heat and mass transfer but allows different air temperatures and relative humidity on either side. The air flow rate that defines the heat and mass transfer was kept at the default value of 0.1 m 3 s -1 per m 2 of partition for all simulations. In order to demonstrate the impact of the refrigeration equipment, exactly the same conditions, including schedules of occupancy, lighting and appliances were applied to the two zones. Occupants (customers and store staff) were present between 09:00 and 06:00 every day of the week including weekends. Lighting and electrical appliances were on continuously from 09:00 to 06:00. Lighting, electrical appliance and heating and cooling time schedules were taken from the retail sales DesignBuilder templates. Ventilation was provided mechanically by the HVAC system. There was no natural ventilation as is typical in supermarkets. An infiltration rate of 0.5 ac/h was assumed. Lighting energy levels of 750 lux and ventilation rates of 10 L/s/person for supermarkets were taken from CIBSE Guide A (CIBSE, 2015). An occupancy density of 8 people per 100 m 2 was taken from ASHRAE Standards 62.1 (ASHRAE 2013). In this work a VAV HVAC system with no economiser or heat recovery of the recirculated air was modelled. The use of a VAV HVAC system provides a suitable way of varying the HVAC system operation because the SAT can be set to a range of fixed values. This is unlike the alternative constant air volume (CAV) system, where the SAT is dynamic to meet the thermal loads of a space (ASHRAE, 2004). Generic freezer and chilled refrigeration case types were modelled from the EnergyPlus dataset in line with those in UK supermarkets including vertical open chilled cases and open and closed horizontal freezers. These cover the common food products available in UK supermarkets, typically meat, dairy, delicatessen and fish. Default settings were maintained, except for varying the operating temperatures to determine the energy performance of the refrigerated cases over time. The model determines the refrigerated case energy performance based on the surrounding air temperature and heat transfer from the supermarket store air. The refrigerated cases modelled in EnergyPlus work in combination with compressor racks that contain the compressors and condensers. In line with standard practice, they were modelled as being outside the building, making their heat rejection environment the outside air. Two types were - 1097 -

modelled, medium temperature for the chilled cases and low temperature for the freezers, with the default coefficients of performance (COPs) of 1.5 and 1.7 respectively. The default condenser fan power of 1.025 kw was used for both types. External conditions will have an impact on building operational energy use. Therefore, energy use estimations were repeated for three UK locations: London, Belfast and Aberdeen. The International Weather for Energy Calculations (IWEC) weather files were from ASHRAE (2001) derived from up to 18 years of typical hourly weather data to match long term average trends. The focus was the interaction between refrigeration and HVAC systems on the sales floor. Other interactions, such as energy saving by recycling waste heat from the refrigeration to the HVAC system, were not modelled. An assumption of the heat balance model used in EnergyPlus is that the air in separate thermal zones is simulated as a well-mixed body of air with a mean air temperature (Crawley et al., 2001). In reality, some vertical stratification of air will occur between the refrigeration cases and ambient air on the sales floor. Phan and Lin (2014) studied the effect of the temperature of supply air on energy use in EnergyPlus. They highlight that a multi-zone EnergyPlus simulation, with airflow between zones similar to the method in this paper, can show very similar air temperature results to those of Computational Fluid Dynamics (CFD) and suggests that the more detailed representation of reality offered by CFD is unnecessary. Simulations were carried out to determine HVAC and refrigeration system energy use at a range of HVAC system temperature set-point temperatures, SATs and refrigeration case operating temperatures. The sales floor air temperatures were first determined for a summers day at fixed values of all operating temperatures of interest. Next, the separate impact on heating and cooling energy use of the presence of refrigeration equipment was determined. The SATs were fixed at 14 C and heating and cooling set-point temperatures were varied between 18 C and 21 C and 22 C and 25 C respectively, constrained by occpuant theraml comfort. Then HVAC SATs were fixed whilst refrigeration case operating temperatures were varied separately for freezers and chilled cases. Finally, refrigeration case operating temperatures were fixed at typical values whilst the SATs were varied from 12 C to 19 C. RESULTS AND DISCUSSION Energy use estimations included refrigeration system electricity use and HVAC system boiler gas and chiller, pump and fan electricity use. The first step was to understand how the HVAC and refrigeration systems operate and interact in the generic supermarket model (Figure 5, 6 and 7). Figure 5 Hourly zone mean air temperatures for summer (8th July) Figure 5 shows that the sales floor air was maintained at the setback temperature of 17 C until 07:00 when the heating set-points of 18 C operate for both zones. During the day, the zone mean air temperatures (T a ) increased due to internal gains from electrical appliances, occupants and lighting between 09:00 and 18:00. T a increased in the ambient zone until it reached the cooling set-point of 24 C when space cooling began. The temperature difference between the ambient and cooled product zones was sometimes up to 2 C, in line with initial measurements in a real supermarket carried out as part of this work. Occupancy schedules account for the peaks in Ta at 11am and 4pm, clearly seen for both zones. The effect on HVAC energy use by comparing the values of gas for space heating and electricity for space cooling was determined with and without the refrigeration cases present. Figure 6 shows that the presence of refrigeration cases in the cooled product zone did not change cooling energy use significantly. The impact on heating energy use was different, however. Figure 7 shows that the presence of refrigerators has a significant effect on gas use by the HVAC system. - 1098 -

Chiiler Electricity Use [MWh/year] Figure 6 Monthly electricity use for space cooling with and without refrigeration equipment in the cooled product zone Gas Energy Use [MWh/year] 18 16 14 12 10 8 6 4 2 0 140 120 100 80 60 40 20 0 January January With February February March March Without April April May May June July With June July August September Without August September October October November November Figure 7 Monthly gas energy use for space heating with and without refrigeration equipment in the cooled product zone December The effect of varying heating and cooling temperature set-points on the overall energy use of the refrigeration system and HVAC system was explored as shown in Figure 8. December Unsurprisingly, higher heating temperature set-points were associated with higher space heating energy use. However, space cooling energy use was relatively insensitive to higher cooling temperature set-points. This is because the heat gains in the daytime did not usually increase T a above the cooling set-point of 24 C except for a few weeks in summer. Figure 9 and 10 show a roughly linear relationship between freezer and chilled case operating temperatures and refrigeration and HVAC system energy use. The effect of refrigeration cases removing heat and moisture from the sales floor air decreases with higher operating temperatures, resulting in lower gas energy use required to maintain space-heating set-points. Additionally, higher refrigeration case operating temperatures lead to lower energy use by the refrigeration system. A 2% energy saving in the HVAC system and a 4% energy saving in the refrigeration system electricity use was estimated from increasing freezer operating temperatures from -22 o C to -16 o C (Figure 9). A 3% energy saving in the HVAC system and a 1% energy saving in the refrigeration system electricity use was estimated from increasing chilled case operating temperatures from 1 o C to 5 o C (Figure 10) (whilst holding freezer operating temperatures constant at any typical value). Energy Use [MWh/year] 1,750 1,700 1,650 1,600 1,550 1,500 Refrigeration system HVAC system -22-21 -20-19 -18-17 -16 Freezer Operating Temperature [ o C] Figure 9 Annual refrigeration and HVAC system energy use with varying freezer operating temperatures Figure 8 Variation of total energy use with heating and cooling set-point temperatures - 1099 -

Energy Use [MWh/year] 1,750 1,700 1,650 1,600 1,550 1,500 Refrigeration system HVAC system 1 2 3 4 5 Chilled Case Operating Temperature [ o C] Figure 10 Refrigeration and HVAC system energy use at different chilled case operating temperatures Figure 11 shows that an increase in SAT decreases (and almost eliminates the need for) space cooling energy. Space heating energy use decreases initially between 12 C and 14 C mainly due to a decrease in the significant gas energy use requirements of the terminal unit reheat coils. However, a higher SAT above 14 o C requires higher AHU heating coil energy use and this starts to increase HVAC system energy use. Additionally, at a higher SAT value the difference in temperature between zone T a and SAT becomes lower and as a result higher HVAC system air flow rates are required to meet cooling loads and this was found to slightly increase fan electricity use. Higher SATs increase refrigeration case and total refrigeration system energy use. As the air temperature increases from higher SATs this increases the refrigeration case sensible and latent heat energy and therefore the electricity use of the refrigeration cases. Comparing the results from this work with supermarket benchmarks (CIBSE, 2008), total electricity use is higher than the annual electricity typical benchmark of 400 kwh/m 2 (Figure 10). Additionally, gas energy use is significantly higher than the annual fossil-thermal typical energy use benchmark of 105 kwh/m 2. A reason for this difference could include a set-back temperature of 17 o C, which will require significant gas energy use for space heating at night-time. The variation of the overall energy use by refrigeration and HVAC systems with SAT is shown in Figure 12 for the three UK locations studied. Clear minima around 14-16 C are visible. The same results are plotted again in Figure 13 but this time in terms of CO 2 emissions rather than energy, to highlight the importance of electricity having a higher CO 2 emissions conversion factor than natural gas. It was found that overall HVAC and refrigeration system CO 2 emissions are lowest at a SAT of 16 C for London and 15 C for Aberdeen, with Belfast in-between. The lower optimum SAT for Aberdeen is mainly due to the higher space heating energy use requirements for Aberdeen than London with increasing SAT. Figure 12 Change in the sum of energy use from HVAC and refrigeration systems with increasing SAT Figure 11 HVAC and refrigeration system energy use with various SATs for London Wu et al., (2015b) found similar results, though that work was limited to cooling energy. They showed an increase in refrigeration case electricity use and a decrease in HVAC chiller electricity use when increasing the SAT from 16 C to 19 C. Figure 13 Change in total CO 2 emissions from HVAC and refrigeration systems with increasing SAT CONCLUSION The interactions between refrigeration and HVAC systems have been modelled for a generic UK supermarket. The research has contributed toward filling a research gap in the knowledge of - 1100 -

supermarket energy use. In particular, it has highlighted the importance of different operating conditions of HVAC systems and refrigeration cases. Both HVAC and refrigeration system energy use was minimized by operating refrigerators at their safe maximum temperatures. Lower refrigerator operating temperatures led to greater energy use by both systems. The presence of refrigerators affected heating energy use more than cooling energy use. The optimum supply air temperature varies with local climate. The value of the optimum depends upon whether energy use or CO 2 emissions are to be minimized. For CO 2 emissions, the optimum value was about 16 C in London and 15 C in Aberdeen. ACKNOWLEDGEMENT This research was made possible by Engineering and Physical Sciences Research Council (EPSRC) support for the London-Loughborough Centre for Doctoral Training in Energy Demand (Grant EP/H009612/1). The support of Tesco plc is gratefully acknowledged. REFERENCES ASHRAE, 2001. International Weather for Energy Calculations (IWEC Weather Files). Atlanta, GA: ASHRAE American Society of Heating, Refrigerating and Air-Conditioning Engineers 2001. ASHRAE, 2004. Systems and Equipment volume of the ASHRAE Handbook. Atlanta, GA: ASHRAE American Society of Heating, Refrigerating and Air-Conditioning Engineers 2004. ASHRAE, 2008. ASHRAE Fundamental Handbook - Heating, ventilating, and air-conditioning systems and equipment (Inch, Pound eds.). Atlanta, GA: ASHRAE American Society of Heating, Refrigerating and Air-Conditioning Engineers 2008. ASHRAE, 2009. Thermal Comfort, ASHRAE Handbook, Fundamentals, 9(3), 2009. Atlanta, GA: American Society of Heating, Refrigerating and Air-Conditioning Engineers 2009. ASHRAE, 2013. Standards 62.1 Ventilation for Acceptable Indoor Air Quality. Atlanta, GA: ASHRAE American Society of Heating, Refrigerating and Air-Conditioning Engineers 2013. CIBSE, 2015. CIBSE Guide A: Environmental Design, The Chartered Institution of Building Services Engineers. Crawley, D.B.D., Lawrie, L.K., Winkelmann, F.C., Buhl, W.F., Huang, Y.J., Pedersen, C.O., Strand, R.K., Liesen, W.F., D.E. Fisher, Witte, M.J., Glazer., R.J.J. 2001. EnergyPlus: creating a newgeneration building energy simulation program. Energy and Buildings, 33, pp.319-331. DECC, 2011. The Carbon Plan: Delivering our Low Carbon Future, Department of Energy and Climate Change (DECC), UK, 2011. Department of Energy (DOE), 2015. EnergyPlus v8.1. DesignBuilder, 2015. DesignBuilder website, http://www.designbuilder.co.uk/ Galvez-Martos, J.L., Styles, D., Schoenberger, H. 2013. Identified best environmental management practices to improve the energy performance of the retail trade sector in Europe. Energy Policy, 63, pp.982 994. Ge, Y.T., Tassou, S.A. 2000. Mathematical modelling of supermarket refrigeration systems for design, energy prediction and control. Proceedings of the Institution of Mechanical Engineers, Part A: Journal of Power and Energy, 214(2), pp.101 114. Ge, Y.T., Tassou, S.A., 2011. Performance evaluation and optimal design of supermarket refrigeration systems with supermarket model SuperSim, Part I: Model description and validation. International Journal of Refrigeration, 34(2), pp. 527 539. Mathews, E.H., Arndt, D.C., Piani, C.B., Heerden, E. 2000. Developing cost efficient control strategies to ensure optimal energy use and sufficient indoor comfort, 66. Mavromatidis, G., Acha, S., Shah, N., 2013. Diagnostic tools of energy performance for supermarkets using Artificial Neural Network algorithms. Energy and Buildings, 62, pp.304 314. Mei, V.C., Domitrovic, R.E., Chen, F.C., Kilpatrick, J.K., 2002. A frost-less heat pump. ASHRAE Transactions, 452 459. Phan, L., Lin, C.X. 2014. A multi-zone building energy simulation of a data center model with hot and cold aisles. Energy and Buildings, 77, pp.364 376. Reed, M. (martin.reed@uk.tesco.com), 25 November 2014. Interview/meeting regarding HVAC Design Brief and Tesco s control strategy. E- mail to H.Witt (h.witt@lboro.ac.uk). Tassou, S.A., Ge, Y., Hadawey, A., Marriott, D. 2011. Energy consumption and conservation in food retailing. Applied Thermal Engineering, 31(2-3), pp.147 156. - 1101 -

Wu, X., Chang, Z., Zhao, X., Li., W., Lu, Y., Yuan, P. 2015a. A multi-scale approach for refrigerated display cabinet coupled with supermarket HVAC system Part I: Methodology and verification. International Journal of Heat and Mass Transfer. Wu, X., Chang, Z., Zhao, X., Li., W., Lu, Y., Yuan, P. 2015b. A multi-scale approach for refrigerated display cabinet coupled with supermarket HVAC system-part II: The performance of VORDC and energy consumption analysis. International Journal of Heat and Mass Transfer. - 1102 -