ICM 275. Replacement Description

Similar documents
Interrupted Ignition Series Oil Primary Control

SC Installation, Operation & Application Guide

SC Installation, Operation & Application Guide

SC Installation, Operation & Application Guide

ICM Simple Systems. CC750 Comfort Control Center CC and CC Application Guide

SC Installation, Operation & Application Guide

SC Installation, Operation & Application Guide

SC Installation, Operation & Application Guide

2. All connections are 24 volt AC. Verify all planned connections at TT thermostat connections, before turning on power

Programmable Thermostat

SC Installation, Operation & Application Guide

Installation and Operating Instructions

Isolation Relay: If Needed. # 9. NO relay for TT To Thermostat NO relay. MZ308 Exquisite Heat Controller

Installation Instructions

WARNING Important Safety Information

Service and Maintenance Instructions

Installation, Operation & Service Manual

service and maintenance procedures GAS-FIRED INDUCED-COMBUSTION FURNACE

Installation Instructions

READ AND SAVE THESE INSTALLATION INSTRUCTIONS

WARNING Important Safety Information

Installation and Venting Instructions

E1 Electrical Fundamentals. # 4 - Symbols and Wiring Diagrams

WARNING Important Safety Information

Quest Power Electric Heat EHS 62 Pro

Premier 2-Zone Controller model Installer Guide

Quest Power Electric Heat EHS 31 Pro

Superdryer Dehumidifiers

Installation Instructions

Air Cleaning Equipment, Inc. 303 N. Main St. Broadway, NC iers.com

59MN7A Series 100 TROUBLESHOOTING GUIDE

ion Genesis Pump Controller

Service and Maintenance Instructions For Sizes , Series B & C

Installation Instructions

IW-25-2 Dehumidifier Installation & Operations. Manual

Wiring Diagrams. 9AB4-12 Air-Cooled Remote Condenser INDEX OPERATING SEQUENCE ACCESSORIES LEGEND AND NOTES FOR FIG. 1-6

INSTALLATION & OPERATION MANUAL

MaxLite LED Vapor Tight Linear Fixture

USER MANUAL WARNING! CONTENTS MODEL SPECIFICATIONS READ ALL INSTRUCTIONS BEFORE PROCEEDING

*9MAC TROUBLESHOOTING GUIDE

MaxLite LED High Bay Fixtures

Owner s Manual Phoenix FireBird

WARNING Important Safety Information

OWNERS MANUAL YEAR LIMITED WARRANTY READ ALL INSTRUCTIONS BEFORE PROCEEDING. Store this booklet for future reference

MODEL HS115-3, HS115-4 & HS115-5 WIRING DIAGRAM ADDENDUM

Sentry LIQUID LEVEL CONTROLLER MODEL 120 OPERATING MANUAL.

CAUTION WARNING. 50T Integrated Furnace Control INSTALLATION INSTRUCTIONS DESCRIPTION PRECAUTIONS

B SERIES ELECTRIC FURNACE

Installation Instructions / User s Manual NAXA00101DB Communicating Daughter Board

Service Guide. 4-Way Multipoise Fixed-Capacity Condensing Gas Furnace. PG9MAB Series A

PAC-2750 ELECTRIC COOLING FAN CONTROLLER

EQUIPMENT Operation Manual

4-Way Multipoise Fixed-Capacity Dual-Vent Condensing Gas Furnace

LRP14HP/LRP14DF/LRP14AC/LRP14GE/LRP16GE/LRP16HP SERIES UNITS

50A Integrated Furnace Control

Installation Instructions

Installation instructions for Plenum-mounted add-on electric heaters

Automatic Humidity Controller. Model 512 (Revision C) Operating Manual

MICRO GROW GREENHOUSE SYSTEMS, INC ZEVO DR., SUITE B-1, TEMECULA, CA PHONE (951) FAX (951) Growmate Growmate Plus

Instruction Manual. 36 in. and 42 in. Popcorn Staging Cabinets

Installation, Start -Up, and Operating Instructions

Model Gas Alarm Panel APPLICABILITY & EFFECTIVITY. This manual provides instructions for the following Sierra Monitor products:

Installation Instructions

D-TEK O P E R A T I N G I N S T R U C T I O N S V E HI C L E L O O P DETECTOR Johnston Parkway, Cleveland, Ohio 44128

LZP-2 ZONE CONTROL PANEL

MANUAL 8/12/05. Model BKP TM 100 INSTALLATION, OPERATION & MAINTENANCE. Commercial High Efficiency Heat Pipe Dehumidifier

MODEL UC1 INSTALLATION INSTRUCTIONS

Installation Instructions

service and maintenance procedures

INSTRUCTION MANUAL TS21. 2 Heating and 1 Cooling

Operator: Save these instructions for future use!

Silicone Rubber Heating Tape with Adjustable Thermostat Control (HSTAT Series) Instruction Manual

SERIES VAC Microprocessor-Based Hot Surface Ignition Control FEATURES APPLICATIONS SPECIFICATIONS DESCRIPTION AGENCY CERTIFICATIONS

Quest PowerHeat HFC 100 Pro

Operation and Maintenance Manual for the SODRTEK ST 400 Radiant Pre-Heating System P/N

T-SERIES Air Conditioner. T62 Model INSTRUCTION MANUAL nvent Rev. F P/N

OWNERS MANUAL YEAR LIMITED WARRANTY READ ALL INSTRUCTIONS BEFORE PROCEEDING. Store this booklet for future reference

Operator: Save these instructions for future use!

Operator: Save these instructions for future use!

120 VAC SYSTEM CONTROL KIT Model: CK-63

FUME HOOD MONITOR ALNOR AIRGARD 200

MODEL RLY-DIM-D INSTALLATION INSTRUCTIONS

Instruction Manual. Bucket Oil Pump

DAY/TIME Button: Selects hour, minute and day setting.

PLL. Pump-Lead-Lag. Provides Pump Rotation, Auxiliary Pump Activation, and Pump Failure Alarm Control. Installation and Operation Manual

Operating Instructions. Temperature and Humidity EC Control. Model 35YV93

INSTALLATION INSTRUCTIONS and OPERATING MANUAL. *Aquastat is a registered trademark of Honeywell International, Inc.

Installation Instructions

USER MANUAL WARNING! CONTENTS MODEL 1 SPECIFICATIONS READ ALL INSTRUCTIONS BEFORE PROCEEDING 2 INSTALLATION. Premier Series

A-1106 ACCESSORY KIT INSTALLATION INSTRUCTIONS IGNITION CONTROL P/N S , S , S

Ion Genesis II Pump Controller Digital Level Control with Pump Alternation and High Water Alarm

INSTALLER S & OWNER S MANUAL

Miniature Thermoelectric Cooler Controller MTCC-01 user's guide

DAY/TIME Button: Selects hour, minute and day setting.

WARNING WARNING TROUBLESHOOTING GUIDE INTEGRATED FURNACE CONTROL MODULE

Operator: Save these instructions for future use!

INSTALLATION INSTRUCTIONS and OPERATING MANUAL. *Aquastat is a registered trademark of Honeywell International, Inc.

WARNING Important Safety Information

Service and Maintenance Instructions For Sizes , Series 100

(HSTAT Series) Instruction Manual

Transcription:

IM 275 Fan ontrol enter Replacement Description The IM275 Gas Furnace ontrol enter is a new generation control for the replacement market. The IM275 Gas Furnace ontrol enter is designed to function similarly to previous control center designs, while incorporating some of the latest features in furnace control center technology. It is a direct replacement for the following arrier control center part numbers: HH84AA021, HH84AA001, HH84AA003, HH84AA005, HH84AA009, HH84AA014, HH84AA015, or ESO110019. Installation, Operation & Application Guide For more information on our complete range of American-made products plus wiring diagrams, troubleshooting tips and more, visit us at www.icmcontrols.com

Table of ontents Specifications... 1 Introduction... 1 Safety onsiderations... 1 Operational Differences and Added Features... 2 Installation Instructions... 2 IM275 omponent Layout... 3 Wiring Diagram... 4 Troubleshooting... 5

Specifications Input Voltage - Terminals: PR-1, PR-2, L1, L2 and OM...120 VA - Terminals: SE-1 and SE-2... 18-30 VA Line Frequency... 60 Hz Operating Temperature... -40ºF to +176ºF Maximum Operating Humidity... 95% R.H. Non-condensing @ 50º Time Delays - Heat ON...60 Seconds - Heat OFF...60-240 Seconds - ool OFF (R18 ut)...90 Seconds Introduction This application guide covers the installation of the Gas Furnace ontrol enter, Part No. IM275, in an intermittent ignition, induced draft, or condensing gas furnace. Safety onsiderations Installing and servicing heating equipment can be hazardous due to gas and electrical components. Only trained personnel should install or service heating equipment. Untrained personnel can perform basic maintenance functions such as cleaning coils, or cleaning and replacing filters. All other operations should be performed by trained personnel only. When working on heating equipment, observe precautions in the literature, on tags, and on labels attached to the unit. Follow all safety codes. Wear safety glasses and work gloves. Have a fire extinguisher available. AUTION!: Before beginning the installation or modification, be sure the main electrical disconnect switch is in the OFF position. AUTION!: Failure to carefully read and follow these instructions before servicing or operating this control, could result in personal injury, death and/or property damage.

Operational Differences and Added Features The following is a description of the slight operational differences and added features. Refer to IM275 omponent Layout (Page 3) for location of control center components. Operation with new blower and humidifier relays: The previous design control centers used a SPST-N or DPST-N heating fan relay (HFR of E2) and a DPDT cooling fan relay (FR or 2F) for blower and humidifier terminal operation. This new control center uses a SPST-NO blower relay (BLWR) and a SPDT blower speed change relay (hi/lo) for blower operation, and a SPST-NO humidifier relay. 1. The low-speed blower will not operate on a transformer failure as on previous designs. 2. If JW1 jumper is cut between R and GH terminals, a constant low-speed blower will occur without any thermostat inputs to the control center. A G or Y signal to the control center will not bring on the hi-speed blower for cooling operation. JW1 jumper must not be cut on cooling applications. 3. The humidifier H terminal is energized with low-speed blower operation. In cooling operation, the humidistat and humidifier water supply should be turned off to ensure the humidifier does not operate. 24 volt circuit protection: An automotive type, 3 amp fuse is provided to protect the transformer and thermostat from shorts in the low-voltage circuitry. An open fuse will initiate a constant low-speed blower. Refer to the IM275 omponent Layout (Page 3) for location on control center. Low-speed continuous G blower and 90-second hi-speed blower OFF delay option: Resistor (R18) on the control center can be cut to achieve heating speed continuous blower with a thermostat (R-G) call and a hi-speed blower with a 90 second OFF delay with a thermostat (R-Y) call. AUTION!: Do not cut R18 on twinned furnace applications. Installation Instructions AUTION!: Verify power is removed from the control by removing fuse or turning off circuit breaker. 1. Disconnect wiring from blower control center. Tag each wire as it is disconnected from the old furnace control center. Disconnect all wiring hookups. 2. Remove existing blower control center. 3. Install the IM275 fan control center into the control center box. Be sure that the top edge of the IM275 is in the mounting slot, just like the original board. AUTION!: If the IM275 is not installed correctly (i.e.: behind the slot), an electrical short could occur. 4. Reconnect all of the wire(s) that were removed in Step 1 above, to the proper terminals. 5. Turn power to ON position and check unit sequence of operation per unit installation instructions. 6. These instructions must be placed with the original unit instruction packet, or with the unit for future reference.

Input From Thermostat Blower Operating Modes Resistor (R18) Uncut Resistor (R18) ut W Lo-speed heating blower* Lo-speed heating blower* G Hi-speed cooling blower Lo-speed heating blower Y No blower Hi-speed cooling blower** * 60-second ON delay and 60-240 second adjustable OFF delay ** 90-second OFF delay omponent Layout HI LO PR1 L1 PR2 L2 OM T6 T5 T3 T4 T8 T7 T9 K2 K1 SPB-1 PB503-1 N FORM- NO NO JW8 OIL OIL P4 JW4 R9 R22 LED1 1 JW5 JW2 1 9 STATUS TS3 M1 2 R1 R14 R2 R5 R6 U2 SE-2 T1 R3 R1 JW4 R3 U1 10 R5 31 SE-1 T2 11 R4 R2 41 12 D2 R16 JW6 R17 R19 Z1 D1 IN 60 R4 TS1 TS2 R20 240 R15 R21 R18 TEST R8 PT1 G-BLOWER OPTION Blower Off Delay Pot Resistor (R18) S9 S8 R11 R13 R10 R12 NO N JW3 EA-2 S5 EA-1 R6 S1 R7 S4 ATO 3-amp Fuse 6 5 8 7 S7 Y S6 H S2 GH S3 G W R F1 3A ATO JW1 ATO 3-amp Fuse

ILK Wiring Diagram LINE 1 (PL1 or 10B1)-4 SEE NOTE 1 HI/LO BLWR (PL1 or 10B1)-7 MTR AP LO HI EA-1 EA-2 PR-1 115 VA PR-2 (PL1 or 10B1)-1 (PL1 or 10B1)-5 FU SE-1 TRAN 24 VA SE-2 SEE NOTE 1 BLWR HI/LO HUM R H HUM JW1 M GH (PL1 or 10B1)-3 (PL1 or 10B1)-2 W (PL1 or 10B1)-6 Y G SEE NOTE 1 LEGEND: AP Run apacitor Plug Receptacle TRAN Transformer JW1 Jumper Wire Junction MTR M Motor, Blower Microcontroller Unmarked Terminal FU Fuse (ATO 3-amp) Terminal PB HI/LO Blower Motor Speed hange Relay (DPST) HUM Humidifier Relay (SPST-NO) BLWR Blower Motor Relay (SPST-NO) ILK Switch, Blower Door Interlock (SPST-NO) Factory Wiring (115 VA) Factory Wiring (24 VA) onductor on PB Screw onnector Equipment Ground Note 1: PL1 and 10B1 indicates 7-PIN edge connector terminations that connect to control center. Refer to unit wiring diagram for specific unit wiring from control center edge connector.

Troubleshooting WARNING!: High voltage! Troubleshooting this fan control board involves working with high voltage which can result in personal injury, death and/or property damage. AUTION!: Always disconnect power by removing a fuse or opening a circuit breaker before doing continuity checks. Verify power is not present before troubleshooting. AUTION!: Troubleshooting tasks should only be performed by those trained to install or service HVA equipment. Symptom ontinuous low speed blower Blower speed not correct No fan for heating or cooling No fan delays No fan on heat call Status LED blinking Intermittent fan operation Remedy heck for open fuse heck for open limit heck for 24 VA at R and terminals heck if JW1 is cut heck edge connector slot 1 and slot 5; with no power applied and the edge connector removed, there should be continuity between edge connector slot 1 and slot 5 heck if R18 is cut heck wiring of LO and HI terminals heck for 24 VA at SE1 and SE2 Verify test pins are not shorted heck for 24 VA at R and terminals heck for 24 VA at SE1 and SE2 heck edge connector slot 3 and slot 6; with no power applied and the edge connector removed, there should be continuity between edge connector slot 3 and slot 6 Status LED blinks when 24 VA is applied to SE1 and SE2; there are no fault flash codes for this control heck for constant 24 VA at R and terminals Bypass thermostat and test operation of fan control; with no power applied, remove wires to thermostat; use a jumper wire to initiate a call for heat/cool blower; if operation is correct, thermostat or thermostat wire is faulty

ONE-YEAR LIMITED WARRANTY The Seller warrants its products against defects in material or workmanship for a period of one (1) year from the date of manufacture. The liability of the Seller is limited, at its option, to repair, replace or issue a non-case credit for the purchase prices of the goods which are provided to be defective. The warranty and remedies set forth herein do not apply to any goods or parts thereof which have been subjected to misuse including any use or application in violation of the Seller s instructions, neglect, tampering, improper storage, incorrect installation or servicing not performed by the Seller. In order to permit the Seller to properly administer the warranty, the Buyer shall: 1) Notify the Seller promptly of any claim, submitting date code information or any other pertinent data as requested by the Seller. 2) Permit the Seller to inspect and test the product claimed to be defective. Items claimed to be defective and are determined by Seller to be non-defective are subject to a $30.00 per hour inspection fee. This warranty constitutes the Seller s sole liability hereunder and is in lieu of any other warranty expressed, implied or statutory. Unless otherwise stated in writing, Seller makes no warranty that the goods depicted or described herein are fit for any particular purpose. 7313 William Barry Blvd., North Syracuse, NY 13212 (Toll Free) 800-365-5525 (Phone) 315-233-5266 (Fax) 315-233-5276 www.icmcontrols.com LIA13-2