Installation, Operation and Maintenance Instructions for Thermax Semi-Storage Calorifier

Similar documents
Installation, Operation and Maintenance Instructions for Electric Storage Calorifier

Installation, Operation and Maintenance Instructions Electric Flow Heater OM009

Installation, Operation and Maintenance Instructions for PlantPac Steam Plate Heat Exchanger Package

Installation, Operation and Maintenance Instructions Thermaflow E Plate Heat Exchanger Package OM013

Rycroft Storage & Non-Storage Calorifiers. Installation, Operation & Maintenance Manual

BOILER HOUSE PRODUCTS GMS

Installation, Operation and Maintenance Instructions ThermaFlex Gasketed Plate Heat Exchanger OM010

Installation, Operation and Maintenance LOK-FLANGE Multitube Heat Exchangers

MAXIMISER Semi-Storage Calorifiers

SERVICE MANUAL. For Service & Parts please call APK THERMAL at or SAFETY INSTRUCTION

REG NO FM BS EN ISO HEADER TANK HEAT EXCHANGER. Installation, Operation & Maintenance Guide

HYDRAULIC OIL COOLER. Installation, Operation & Maintenance Guide

Installation, Operation and Maintenance Instructions for ThermaFlex Brazed Plate Heat Exchangers

Powerstock Storage Tank

4 route 147, C.P.33 Coaticook, Qc J1A 2S8

LONGONI ENGINEERING SRL

OPERATING AND MAINTENANCE MANUAL FOR PLATE HEAT EXCHANGER INDIRECT FIRED WATER HEATER. Electric Heater Company Base Model "BWXP"

HYDRAULIC OIL COOLER Installation, Operation & Maintenance Guide

INFINITY FLUIDS CORPORATION

BuildingName The Description of the Project P DOCUMENTS

Packaged Steam Fired Water Heater

HEAT TRANSFER STORAGE CALORIFIERS EC SERIES SC SERIES BT SERIES

PLEASE LEAVE THIS MANUAL WITH THE OSO UNIT AFTER INSTALLATION INSTALLATION MANUAL

VS SERIES NH3 STEAM VAPORIZERS OPERATION MANUAL

Unvented Calorifier Range. Operating and Maintenance Manual. For Models & 500

SEALED THERMAL STORE

Extreme Domestic Hot Water Loading System TECHNICAL DOCUMENTATION. Issue 11/09

Installation, Operation and Maintenance Instructions for ThermaFlex Gasketed Plate Heat Exchangers

Technical Data TYPE T14 & T14D TEMPERATURE PILOT SPENCE ENGINEERING COMPANY, INC. 150 COLDENHAM ROAD, WALDEN, NY SD 4511A T14 PILOT

Niles Steel Tank Hot Water Generator Installation and Operation Manual

CROWN WATER HEATERS CPU10 - CPU15 CPOS10 - CPOS15

Installation, Operating and Servicing Instructions

PLEASE LEAVE THIS MANUAL WITH THE OSO UNIT AFTER INSTALLATION INSTALLATION MANUAL

Hamworthy. Dorchester DR-SA & DR-SE Fully Automatic and Permanent Pilot Direct Gas-Fired Storage Water Heaters. Exceeds Minimum Requirements

Installation, operating and servicing instructions

POWERFLOW Series. Unvented Electric Storage Water Heaters. Installation & Operating Instructions Manual

STORAGE TANK INSTALLATION and OPERATION MANUAL

Installation instructions. RECOUP Retrofit+ Shower Waste Water Heat Recover unit

Assessment Schedule - TS.6

Instruction Manual. Pharma-line ESE02198-EN Original manual

Flo-Rite-Temp Instantaneous Steam/Water Heater

OPERATING AND MAINTENANCE MANUAL FOR VERTICAL IMMERSION HEATED STEAM BOILERS. Technical Control Systems Limited MODELS "VIHS"

GEM TRAP FITTING & MAINTENANCE INSTRUCTIONS

Installation, Operating and Servicing Instructions

Flo-Rite-Temp Instantaneous Steam/Water Heater

Inta City Concealed Shower Mixing Valve CT80010CP

ALLEGHENY BRADFORD CORPORATION

Powerflow Unvented water heater

INSTALLATION & MAINTENANCE MANUAL FOR QuickDraw

Installation, Operation and Maintenance Guide. Steam Coil Installation, Operation and Maintenance. steam coils

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: HVAC Standards

CRU 200 and 500 Series Condensate Recovery Unit Installation and Maintenance Instructions

TABLE OF CONTENTS TECHNICAL DOCUMENTATION 03. Technical Data Electrical Details Connection Details Dimensions Standing Losses

BoilerSupplies.Com. America's Choice For Boiler Room Supplies. Installation, Operation, & Maintenance Instructions For Shell & Tube Heat Exchangers

A complete, compact steam heat exchange solution for process and domestic water heating requirements.

ENERSTORE. Vented Hot Water Storage System INSTRUCTIONS PLEASE LEAVE WITH HOUSEHOLDER

USER INSTRUCTIONS FOR FLANGE IMMERSION HEATERS USED IN HAZARDOUS LOCATIONS

INSTALLATION MANUAL. Ecoline Geo RI HP PLEASE LEAVE THIS MANUAL WITH THE OSO UNIT AFTER INSTALLATION

Installation, Operating and Maintenance Manual for F Modul plus Calorifiers

SEH Series. Stainless Steel Instantaneous Packaged Steam Fired Water Heaters

Design and Construction Standards SECTION PLUMBING EQUIPMENT

Installation and operating instructions. DK energy storage and DK energy buffer

Link-Up. Solid Fuel Association Guide to Central Heating.

Heat Transfer. the new standard in. Heat Exchangers. Storage, Installation, Operation and Maintenance

Operation & Maintenance Manual

ADVANCE ELECTRIC THERMAL STORE

TEMPERATURE CONTROLLERS

Series 1140 and 1141 Temperature Regulators

REG NO FM BS EN ISO EXHAUST GAS HEAT EXCHANGERS. Installation, Operation & Maintenance Guide

Contents. Commissioning 6 Operation 6 Routine Preventative Maintenance 6 Fault Finding 7 Spares Parts 8 Technical Support 9

USER MANUAL INSTALLATION INSTRUCTIONS WARRANTY REGISTER

Installation, operating and. Comfort

C. ASSE 1013: Performance Requirements for Reduced Pressure Principle Backflow Preventers.

Method Statement. General Site preparation by others: Preparation for screed system by others: Preparation for plate system by others:

Copper-Fin GAS-FIRED WATER HEATERS

Furrows Business Park, Haybridge Road Wellington, Telford, Shropshire TF1 2FE

Pressure Boosting Solutions

ADVANCE ECB ELECTRIC COMBINATION BOILER

Inverted Bucket Steam Traps

INSTALLATION, OPERATING & MAINTENANCE INSTRUCTIONS FOR 350 SERIES CIRCULATION HEATERS

SATK wall-mounted Heat Interface Unit (HIU) Instantaneous domestic hot water production

INSTALLER: PLEASE LEAVE THIS MANUAL FOR THE OWNER S USE. Condensate Return Systems General Installation, Operation, & Service Instructions !

PROVIDES TEPID WATER FOR EMERGENCY SHOWER

REGISTRATION EXAMINATION, JUNE 2015 LICENSED PLUMBER QUESTION AND ANSWER BOOKLET. Time allowed THREE hours

OPERATING AND MAINTENANCE MANUAL FOR BOILER WATER OR HIGH TEMPERATURE HOT WATER (HTHW) POWERED WATER HEATER

smart line E SLE

Armstrong J Series Float, Thermostatic Steam Traps, Condensate Controllers & Liquid Drainers Installation and Maintenance Manual

CRU-S Series Stainless Steel Condensate Recovery Unit

Installation and Maintenance Manual Forbes Marshall Tracer Line Trap FMMST63

Carry Out Maintenance Procedures

Installation instructions. Pump Group. For wall hung gas-fired condensing boiler GB162-50/65/80/ TD UK/IE (2014/09)

Steam Ancillary Equipment. Primary Steam System, Water Treatment and Auxiliary Steam System Equipment

Please take time to carefully read through these guidelines before using your Kamco pump.

Broag Pressurisation equipment

INSTALLATION INSTRUCTIONS OWNERS GUIDE & WARRANTY STATEMENT

MW & EW 10 & 15 Litre Unvented Water Heaters HANDBOOK. IMPORTANT: This booklet should be given to the customer after installation and demonstration.

Please take time to carefully read through these guidelines before using your Kamco pump.

TITAN FLOW CONTROL, INC.

Euron. Compact Wall Mounted Gas Fired Condensing Boilers and Combis with Outputs 24kW - 30kW BOILERS

Hoval Cosmo Combination boilers. High efficiency heating combined with economic DHW generation. Boiler outputs from 100 to 1450kW.

Transcription:

OM001 Installation, Operation and Maintenance Instructions for Thermax Semi-Storage Calorifier These operating and maintenance instructions are for standard semi-storage calorifiers (vessels fitted with a heat exchanger and circulation pipe work and pump). Please note that an electronic version of these instructions is available from our website and also on a CD. Please contact our sales office for further information. Rev Date By Details A 20/11/12 SR EU area note added etc. Revision Details

Contents 1.0 Standard Unit Information and Description 3 2.0 PED Information. 4 3.0 Installation 5 4.0 Commissioning and Operation. 6 5.0 Maintenance 7-8 6.0 Recommended Spares.. 9 [T:\gms\Word\GMSO&M\Word Format\OM001.doc] Page 2

1.0 Standard Unit Information & Description The THERMAX semi-storage Calorifier is a compact unit designed to meet wide variations of Domestic Hot Water (DHW) load without making excessive demands on the primary heat source. A heat exchanger with matched bronze pump continuously supplies hot water at the required temperature to a small storage vessel. The stored hot water provides the capacity to meet peak demands. The THERMAX minimum configuration is Calorifier Shell, Heat Exchanger, Integral Circulation Pump with Pipe-work and Pump Isolation / Flow Regulation Valves. Two types of heat exchanger are available:- 1) Integral U-Tube type: Primary medium in tubes, DHW over tubes. This type is usually fitted partially inside the Calorifier shell. 2) Compact Fixed Tube Plate type: Primary medium over tubes, Secondary medium through tubes. This type is always fitted externally to the Calorifier shell. Depending on the scope of the order the unit may be supplied complete with Ancillary Mountings (Thermometer, Altitude Gauge, Steam Pressure Gauge (if applicable), Safety Valve & Drain Valve). Temperature Control Valve, High Temperature Cut-out Valve, Steam Trap-set (if applicable) may also be included. Some or all of these items may be supplied loose with the unit to be fitted on site. Units with copper -lined steel vessels will always be fitted with an anti-vacuum valve. This is an essential safe-guard. Vacuum will damage the thin copper lining. The General Assembly drawing specific to each unit gives details. In any case some or all of the above items must be fitted to give safe and satisfactory operation. Shell Header Heater Tubes Tubeplate (Other materials on request) Standard Material Options Schedule Copper (CS) Copper-Lined Steel (CL) Galvanised Steel (GS) Stainless Steel (SS) Glass-Lined Steel (PL) Carbon Steel Copper low-fin Integron Plain Copper Stainless Steel Brass Stainless Steel Vessel Design Data Shell Side Tube Side Maximum Working Pressure Refer to Vessel Nameplate Refer to Vessel Nameplate Hydraulic Test Pressure Refer to Vessel Nameplate Refer to Vessel Nameplate Design Code Refer to Vessel Nameplate Please refer to our brochure for standard connection and dimensional data. [T:\gms\Word\GMSO&M\Word Format\OM001.doc] Page 3

2.0 PED Information The standard range of semi-storage calorifiers are designed in accordance with the requirements of the Pressure Equipment Directive 97/23/EC. Units classed as SEP in the PED category are not supplied with a CE mark. Units in category I & above are CE marked. Appropriate markings and certification is supplied with each unit. It is the responsibility of the user and/or installer to ensure that the unit is installed and operated safely, in accordance with the instructions supplied within this manual. [T:\gms\Word\GMSO&M\Word Format\OM001.doc] Page 4

3.0 Installation Lifting & Handling: Use lifting eyes where fitted. Do not lift a calorifier using the insulation (if fitted). Straps may crush the insulation. The shell of the calorifier may be made of relatively light gauge metal and care should be exercised when handling and moving the unit not to damage the shell. Do not lift the calorifier using chains directly in contact with the shell. Do not allow operatives to stand on the calorifier Siting: Unless specifically ordered for outside siting the calorifier must be sited indoors. Foundations must be firm and level to prevent settling, pipe strain or distortion of the calorifier. Unless specifically ordered differently, the calorifier should be installed in a level position. For calorifiers with removable tube bundles, ensure enough room exists to withdraw the bundle from the shell. For calorifiers with inspection openings ensure enough room exists to gain access to the opening. Protective covers/plugs may be fitted to connections to protect them in transit. These must be removed prior to use. If a connection is not required seal it appropriately. Check for and remove any foreign material which may have got into the vessel. Pipe-work connected to the calorifier should be supported to prevent loads being transmitted to the calorifier. Provide for thermal expansion with bends and expansion joints. To avoid corrosion do not use copper pipework with galvanised steel calorifiers or vice-versa. Fit isolation valves prior to calorifier connections (NOT TO THE VENT) to facilitate servicing. For flanged connections tighten bolts in a diametrically opposite sequence to load the flanges evenly onto the gasket. For screwed connections use a thread sealant approved for use with potable water by the local water authority. Ensure that the tube bundle can be isolated and easily disconnected for removal during maintenance. The vent must not be blocked so, if the unit may need to be isolated from the vent, fit a 3 way vent valve. Ensure adequate venting for air removal during filling and operation ("sealed" systems should have an autoair-vent and a manual air vent valve for this). Pressure and temperature relief valves (and bursting discs if fitted) should have their outlets piped away to a safe disposal point, preferably via an air-break and tun-dish so that discharge is unrestricted and easily visible. Water expansion must be accommodated by separate expansion vessel on the cold feed side (on sealed systems) or via the vent pipe on vented systems. Allowing expanded water back into the cold feed tank on vented systems is not recommended as the resultant warm water will encourage bacterial growth. On steam heated units arrangements must be made for condensate removal, usually via float type trap with thermostatic vent to a condensate return line at a lower level. To avoid damage in transit the pipe-work and integral circulation pump of the THERMAX may be supplied loose for fitting on site. The pump should be installed to circulate water from the bottom of the cylinder to the top. The unit should be flushed thoroughly with clean water prior to operation. A suitable starter should be provided for the pump (pump starting and running currents will be advised on request) and connected to the electrical supply. The pump must not be run dry (see below). [T:\gms\Word\GMSO&M\Word Format\OM001.doc] Page 5

4.0 Commissioning and Operation Do not operate the equipment at pressures or temperatures in excess of those specified on the nameplate of the vessel marking. Do not subject the equipment to conditions of vacuum or partial vacuum. This is particularly vital for copper-lined steel calorifiers, which are supplied complete with anti-vacuum valve - which must not be removed. For example partial vacuum can be caused if the cold feed or the vent are restricted during draw off or drain down. 1) Open any cold feed and vent valves to the THERMAX and valves either side of integral circulation pump. Fill with cold water ensuring unit is vented fully, but do not open downstream DHW system valve. 2) For unvented systems ensure that the pre-charge pressure in the expansion vessel is correct and that the expansion vessel is open to the unit. 3) Ensure that the unit is full of water and that valves either side of the integral circulation pump are open. Turn integral circulation pump on and check that rotation of pump is correct. The pump must be left running constantly 4) Referring to the commissioning booklet of the primary medium control and high limit valve (if fitted), set these as required and GRADUALLY introduce primary medium to the unit. (Gradually open the primary isolation valve manually to do this). 5) After a short time period the water at the top of the THERMAX will reach the control temperature, as indicated by a gauge on the top of the vessel. When the THERMAX contents are fully heated (indicated by closure of the control valve) the unit is ready to operate at design load conditions and the downstream DHW system valve may be opened. NOTE - The site Health and Safety rules regarding hot water storage should be consulted - it may be necessary to leave the unit running isolated from the downstream DHW system until the entire contents of the vessel are fully heated and for some defined period after that before opening the valve to the downstream DHW system. Check that all gaskets are effective when the unit is operating - some bolt tightening may be necessary after the unit has been first heated and subsequently from time to time. Following installation and commissioning it is advisable to remove, clean and re-assemble any strainers. This completes the commissioning procedure. NOTE: All fluids must be drained when the unit is out of operation to prevent freezing or possible corrosion. [T:\gms\Word\GMSO&M\Word Format\OM001.doc] Page 6

5.0 Maintenance The THERMAX is designed to operate efficiently with a minimum of attention. A regular maintenance programme will ensure continued high operating efficiency and trouble-free operation. Annual maintenance should include cleaning debris from the base of the calorifier to comply with guidelines on prevention of legionella bacteria proliferation. Also the site insurers may require annual inspection of heat exchanger and calorifier shell condition. GENERAL POINTS: Do not blow steam through single tubes - this will cause the tube to expand and disrupt the tube joint. Do not blow air through tubes if they may contain inflammable fluids (explosion hazard) It is recommended that a set of gaskets be carried for use when the unit is stripped down for insurance inspection, or cleaning. Maintenance of the pump and other ancillary equipment should be carried out in accordance with the instructions supplied for these items by their respective manufacturers. Copies of these are included with these instructions. If a loss of performance or increase in primary pressure drop has been observed the following are possible causes:- a) Primary fluid restriction (blocked strainer, faulty control valve etc.) b) Air lock on primary side. c) Scale deposits on the heat exchanger surfaces (primary or secondary side). This can severely affect heat transfer rates. To drain the THERMAX calorifier down (secondary side) Obtain a complete set of replacement gaskets from GMS Thermal Products Ltd. It is assumed here that all isolation valves (except drain) are open at the start. Isolate the primary fluid inlet and outlet - switch off primary pump and boilers if necessary. Switch off secondary system return pump and isolate secondary return to calorifier. Switch off integral circulation pump power. Isolate the secondary flow Isolate the cold feed For sealed systems reduce the residual calorifier pressure by manually operating the safety valve - some hot water will come out For sealed systems open a manual vent valve to allow air in during drain-down For copper-lined steel calorifiers ensure that the anti-vacuum valve is not stuck shut - also ensure that a vent is available at the top of the calorifier of flow area at least one half the flow area of the drain connection. Remove one of the fittings on the top of the calorifier if necessary to achieve this. Partial vacuum, caused by inadequate venting of copper-lined calorifiers during drain-down, will cause damage to the thin copper lining. If the calorifier is open vented and shares a vent with other calorifiers, isolate it from the common vent using the 3 way valve (it will now vent to atmosphere). Pipe the drain to a drain point and open the drain valve. [T:\gms\Word\GMSO&M\Word Format\OM001.doc] Page 7

The THERMAX calorifier shell internal condition can be inspected by removing the inspection cover to allow visual examination Re-fit new gaskets and re-fill the calorifier according to the commissioning instructions above. Constant circulation through the THERMAX heat exchanger minimises fouling. However, a clean heater gives maximum efficiency and capacity, and it is much easier to clean tubes with a light coat of scale, than it is to clean tubes which have been permitted to get excessively fouled. The THERMAX should be cleaned periodically to ensure maximum efficiency. Higher operating temperatures cause scale to accumulate in the heat exchanger more quickly than lower temperatures. Hard untreated water causes much faster scale accumulation than treated soft water. Cleaning frequency will be determined by experience. CLEANING THE HEAT EXCHANGER (SECONDARY SIDE) Because U-tube bundles are fairly tightly packed, chemical cleaning, e.g. using a suitable solution containing inhibitors to protect the metal, will generally give the best results. Take care that the chemicals used will not cause any adverse or hazardous reaction with the materials of the tube bundle or the deposits being cleaned. Drain as above. Allow primary pipe-work to cool to a safe temperature. a) Cleaning In Place (CIP) Disconnect and remove the integral circulation pump and the secondary pipework above the heat exchanger. Take care not to damage any control capillary tubes. Connect CIP hoses directly to the heat exchanger and circulate cleaning chemicals as necessary. Do not exceed normal heat exchanger flow-rate by more than 50%. Fully remove all traces of cleaning chemicals by flushing with fresh water after the CIP process. b) If the heat exchanger tube bundle is to be removed for chemical cleaning. Disconnect primary pipe-work and remove primary header. The tube bundle may be heavy. Ensure that adequate facilities are available to withdraw the bundle without distortion or damage. Avoid damaging surfaces of flanges. When lifting or working on the tube bundle support it by the tubeplates and the support plates - ideally on wooden blocks cut to fit the curvature of the tube bundle. The tube bundle must not be supported on the tubes. Do not bend or distort supports and baffles. Re-fit the tube bundle using new gaskets and re-fill the calorifier. Check all gaskets and joints for signs of leaks. Sacrificial Anodes Some vessels are fitted with sacrificial anodes to reduce corrosion. The anode corrodes instead of the vessel metal. The anodes need to be replaced periodically to ensure protection is continuous. Some enamel lined vessels have an anode condition meter on the top for easy checking. This should be checked by pressing the test button when the vessel is full of water. If the gauge shows goes to green then the anode is in good condition. When there is no test meter the anode should be checked after 6 months operation then periodically depending on rate of corrosion. It should be replaced when thickness has been reduced by 40% from the original. [T:\gms\Word\GMSO&M\Word Format\OM001.doc] Page 8

6.0 Recommended Spares Please contact our sales department for recommended spares prices and availability. The recommended quantities given are per unit supplied. Description Part Ref. 450-550 Litres 600-2000 Litres 2000-4500 Litres All Copper Lined Inspection Gasket TBA 1 Inspection Gasket TBA 1 Inspection Gasket TBA 1 1 Pump Seal Kit TBA 1 1 1 1 Please refer to the issued manufacturing drawing for the following sizes for the heater battery. The quantities shown are per battery, not per calorifier as some calorifiers can be supplied with more than one battery. Nominal Heater Size Description Part Ref. 80NB 125NB 150NB 200NB 250NB 300NB Chest Gasket NG075-P 1 Chest Gasket NG125-P 1 Chest Gasket NG150-P 1 Chest Gasket NG200-2P 1 Chest Gasket NG250-2P 1 Chest Gasket NG300-2P 1 Shell Gasket NG075-P 1 Shell Gasket NG125-P 1 Shell Gasket NG150-P 1 Shell Gasket NG200-P 1 Shell Gasket NG250-P 1 Shell Gasket NG300-P 1 [T:\gms\Word\GMSO&M\Word Format\OM001.doc] Page 9

OM001 Calorifiers Heat Exchangers Pressurisation Units Sales Tel: 01457 835700 Sales Fax: 01457 832700 E-mail: sales@gmsthermal.co.uk [T:\gms\Word\GMSO&M\Word Format\OM001.doc] Riverside Works, Egmont Street, Page Mossley 10 Ashton-Under-Lyne, OL5 9NE